Motstart Three-Phase Start-Up Supervision For Motors: 1Mrs752307-Mum
Motstart Three-Phase Start-Up Supervision For Motors: 1Mrs752307-Mum
Contents
1. Introduction ................................................................................................ 2
1.1 Features................................................................................................ 2
1.2 Application ............................................................................................ 2
1.3 Input description ................................................................................... 3
1.4 Output description................................................................................. 3
1. Introduction
1.1 Features
1.2 Application
This document specifies the function of the three-phase start-up supervision function
block MotStart used in products based on the RED 500 Platform.
For IEC symbols used in single line diagrams, refer to the manual “Technical
Descriptions of Functions, Introduction”, 1MRS750528-MUM.
2
Distribution Automation MotStart
3
MotStart Distribution Automation
2. Description of Operation
2.1 Configuration
When the analogue channels and digital inputs have been selected and configured in
the dialogue box, the inputs and outputs of the function block can be configured on a
graphic worksheet of the configuration tool. The phase currents IL1, IL2 and IL3 are
connected to the corresponding IL1, IL2 and IL3 inputs of the function block. Digital
inputs are connected to the boolean inputs of the function block, and the outputs of the
function block are connected to the output signals in the same way.
A separate scaling factor can be set for each analogue channel. The factors enable
differences between the ratings of the protected unit and those of the measuring device
(CTs, VTs, etc.). A setting of 1.00 means that the rated value of the protected unit is
exactly the same as that of the measuring device. For more information, refer to the
technical reference manual of the product in question.
The calculation of the thermal stress (I2 x t) for the motor is based on the TRUE RMS
measuring principle. The start-up situation for the motor is detected by the PEAK
measuring principle. Harmonics are not suppressed.
The setting parameter “Operation mode” is used for selecting one of the three
operation modes available. Mode 0 (Not in use) sets the function out of use, whereas
in mode 1 (IIt) MotStart calculates the thermal stress for the motor and in mode 2 (IIt
& Stall) protects the motor against stalling during a motor start-up.
4
Distribution Automation MotStart
2.4.1 I2 * t mode
The thermal stress during any single start-up is monitored by the start-up supervision
MotStart, which calculates the product I2 x t, i.e. the thermal stress, during a normal
start-up of a motor.
The motor start-up situation is a sequence, where each of the initial three phase
currents is less than 0.05 x In for 60 ms, i.e. the motor is at standstill, and where at
least one phase current within the rising time (60 ms) rises from a value below 0.05 x
In to a value higher than the start value (1.5 x In). If a phase current sample exceeds the
current level within the rising time, the START signal is immediately set to TRUE, i.e.
the START output can be activated before the rising time has elapsed.
The START signal remains active until all the three phase currents fall below 0.9 x
Start current (0.9 x 1.5 x In = 1.35 x In) and remain below that level for 150 ms, i.e.
until the start-up situation is over.
During the motor start-up MotStart measures the start current, raises the value to a
power of 2 and multiplies it by the running time, i.e. calculates the product I2 x t. If the
calculated value exceeds the set value, the function block trips immediately.
Note! The set I2 x t comes from the value set for the “Start current” parameter raised to
a power of two and multiplied by the value set for the “Start time” parameter.
5
MotStart Distribution Automation
In this mode, stall protection operates in parallel to the I2 x t function. The function
stalls during the motor start-up (STALL active) if the stall indication input signal
(STALL_IND) remains active longer than set stall time. An active STALL signal is
indicated by a steady trip LED (red) on the MMI.
Note! The trip and stall functions will both continue protecting the motor even though
the other function has operated.
Every time the motor is started, the start-up time is added to a register. If the contents
of the register exceed the preset level, i.e. the value set for the “Time limit” parameter,
the signal “Output RESTART” is deactivated. When the start-up situation is over, the
value of the register decreases at a certain speed, which is set via the parameter
“Countdown rate”. When the value of the register falls below the set time limit, the
signal “Output RESTART” is activated again. Note that the RESTART output is
normally activated, i.e. a new start is possible, even though its default value is zero.
For example, the motor manufacturer may state that three starts at the maximum are
allowed within 8 hours and the start-up situation time is 20 s. By initiating three
successive starts we reach the situation illustrated below. As a result, the value of the
register adds up to a total of 60 seconds. Right after the third start has been initiated,
the RESTART output is deactivated and the fourth start will not be allowed, provided
the time limit has been set to 41 seconds.
Furthermore, the maximum of three starts in 8 hours means that the value of the
register should reach the set time limit within 8 hours to allow a new start.
Accordingly, the countdown rate should be 20 seconds in 8 hours and should thus be
set to 20 s / 8 h = 2.5 s / h.
6
Distribution Automation MotStart
The two different groups of setting values, group 1 and 2, are available for the
function block. Switching between the two groups can be done in the following three
ways:
The control parameter “Active group” indicates the setting group valid at a given time.
The digital outputs of the function block can be activated with separate control
parameters for each output either locally via the MMI or externally via the serial
communication. When an output is activated with the test parameter, an event
indicating the test is generated.
The protection functions operate normally while the outputs are tested.
7
MotStart Distribution Automation
The minimum pulse width of the corresponding output signal is set via a separate
parameter on MMI (control setting) or serial communication. If the start situation is
longer than the set pulse width, the START signal stays active until the start situation
is over. The output signal TRIP may have a non-latching or latching feature. When the
latching mode has been selected, the TRIP signal remains continuously active though
the operation criteria have reset, until the output is reset.
Note! The values set for the control parameters “Trip signal” (non-latching or
latching) and “Trip pulse” (minimum pulse width) apply to both the TRIP output and
the STALL output.
An active STALL signal is indicated by a steady trip LED (red) on the MMI. Active
TRIP and START signals are indicated as normally, i.e. TRIP with a steady trip LED
(red) and START with a steady start LED (yellow).
2.9 Resetting
The TRIP output signal and the registers can be reset either via the RESET input, over
the serial bus or via the local MMI.
The operation indicators, latched trip signal and recorded data can be reset as follows:
8
Distribution Automation MotStart
3.1 General
• Each function block has a specific channel number for serial communication
parameters and events. The channel for MotStart is 54.
• The data direction of the parameters defines the use of each parameter as follows:
Data direction Description
R, R/M Read only
W Write only
R/W Read and write
• The different event mask parameters (see section “Control settings”) affect the
visibility of events on the MMI or on serial communication (LON or SPA) as
follows:
Event mask 1 (FxxxV101/102) SPA / MMI (LON)
Event mask 2 (FxxxV103/104) LON
Event mask 3 (FxxxV105/106) LON
Event mask 4 (FxxxV107/108) LON
For example, if only the events E3, E4 and E5 are to be seen on the MMI of the
relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask
1” parameter (FxxxV101).
In case a function block includes more than 32 events, there are two parameters
instead of e.g. the “Event mask 1” parameter: the parameter “Event mask 1A”
(FxxxV101) covers the events 0...31 and “Event mask 1B”(FxxxV102) the events
32...63.
9
MotStart Distribution Automation
Countdown rate S5 2.0...250.0 s/h 60.0 R/M Countdown rate for the time counter
Stall time S6 2.0...120.0 s 10.0 R/M Permitted stalling time for rotor
1)
Operation mode 0 = Not in use; 1 = IIt; 2 = IIt & Stall
Start current S42 1.0...10.0 x In 2.0 R/W Starting current for motor
Start time S43 0.3...250.0 s 5.0 R/W Starting time for motor
Time limit S44 1.0...500.0 s 10.0 R/W Time-based restart inhibit limit
Countdown rate S45 2.0...250.0 s/h 60.0 R/W Countdown rate for the time counter
Stall time S46 2.0...120.0 s 10.0 R/W Permitted stalling time for rotor
1)
Operation mode 0 = Not in use; 1 = IIt; 2 = IIt & Stall
Start current S72 1.0...10.0 x In 2.0 R/W Starting current for motor
Start time S73 0.3...250.0 s 5.0 R/W Starting time for motor
Time limit S74 1.0...500.0 s 10.0 R/W Time-based restart inhibit limit
Countdown rate S75 2.0...250.0 s/h 60.0 R/W Countdown rate for the time counter
Stall time S76 2.0...120.0 s 10.0 R/W Permitted stalling time for rotor
1)
Operation mode 0 = Not in use; 1 = IIt; 2 = IIt & Stall
10
Distribution Automation MotStart
Event mask 1 V101 0...255 - 63 R/W Event mask 1 for event transmission
(E0 ... E7)
Event mask 2 V103 0...255 - 63 R/W Event mask 2 for event transmission
(E0 ... E7)
Event mask 3 V105 0...255 - 63 R/W Event mask 3 for event transmission
(E0 ... E7)
Event mask 4 V107 0...255 - 63 R/W Event mask 4 for event transmission
(E0 ... E7)
1)
Group selection 0 = Group 1; 1 = Group 2; 2 = GROUP input
2)
Active group 0 = Group 1; 1 = Group 2
3)
Trip signal 0 = Non-latching; 1 = Latching
4)
Testing 0 = Do not activate; 1 = Activate
11
MotStart Distribution Automation
3.3.3.1 General
The information required for later fault analysis is recorded at the rising and falling
edge of start or when the function block trips. Tripping can be caused by either the I2 x
t function or the stalling function. In case both the I2 x t function and the stalling
function operate, only the first one is recorded.
The data of the last three events are stored into Recorded data 1...3, beginning from
Recorded data 1. These registers are updated in a cyclical manner, where the values of
the most recent event overwrite the oldest recorded data. If recorded data has been
reset or the relay has been restarted, the first event is again stored to Recorded data 1.
12
Distribution Automation MotStart
The time stamp indicates the rising edge of the START signal and will be updated in
case the function block trips or stalls.
The duration of the start-up situation is recorded both in seconds and as a percentage
of the set operate time. The duration is updated for both IIT and STALL either at the
falling edge of the START signal i.e. when the motor start-up situation is over, or
when the TRIP or STALL output becomes active.
3.3.3.4 Currents
An average for each of the phase currents IL1, IL2 and IL3 is calculated during the start
situation, that is, the time from the rising edge of the START signal until its falling
edge or until the function block trips or stalls. The values of the phase currents IL1, IL2
and IL3 are recorded as multiples of the rated current In.
The status data of the “Active group” parameter, which indicates the setting group
valid for the recorded data, is recorded at the moment of triggering.
13
MotStart Distribution Automation
14
Distribution Automation MotStart
3.3.4 Events
15
MotStart Distribution Automation
4. Technical Data
Operation accuracies At the frequency range f/fn = 0.95...1.05:
F -
G -
16