Diff6T Stabilized Three-Phase Differential Protection For Transformers
Diff6T Stabilized Three-Phase Differential Protection For Transformers
Stabilized three-phase
Issued: 1/2005
Version: C/10.8.2005
differential protection for
transformers
Data subject to change without notice
Contents
1. Introduction ................................................................................................ 3
1.1 Features................................................................................................ 3
1.2 Application ............................................................................................ 4
1.3 Input description ................................................................................... 5
1.4 Output description................................................................................. 5
2. Description of operation............................................................................ 6
2.1 Configuration ........................................................................................ 6
2.2 Setting the rated frequency of the protected unit .................................. 7
2.3 General ................................................................................................. 7
2.3.1 Description of the setting group settings ..................................... 7
2.3.2 Description of the Control settings............................................... 9
2.4 Operation criteria ................................................................................ 13
2.4.1 Stabilized differential current stage (3∆I>)................................. 13
2.4.2 The positive direction of the currents......................................... 14
2.4.3 The differential current............................................................... 14
2.4.4 The stabilizing current ............................................................... 15
2.4.5 The operating characteristic ...................................................... 15
2.4.6 Instantaneous differential current stage (3∆I>>)........................ 16
2.4.7 Error checking in the initialization phase ................................... 17
2.4.8 Compensation of the tap changer position ................................ 17
2.5 Blocking principles .............................................................................. 17
2.5.1 Blocking based on the second harmonic................................... 17
2.5.2 The 2. harmonic deblocking in the case of switch on to a fault . 19
2.5.3 The waveform based blocking................................................... 19
2.5.4 Blocking based on the fifth harmonic......................................... 19
2.5.5 Reset of the blocking signals (deblock) ..................................... 20
2.6 Connection principles ......................................................................... 20
2.6.1 Recommendations for current transformers .............................. 20
2.6.2 Connection of current transformers ........................................... 24
2.6.3 Transformer vector group matching .......................................... 25
Diff6T Distribution Automation
4. Technical Data...........................................................................................48
2
Distribution Automation Diff6T
1. Introduction
1.1 Features
3
Diff6T Distribution Automation
1.2 Application
3∆I>
3∆I>>
Figure 1. Protection diagram symbols of Diff6T
For IEC symbols used in single line diagrams, refer to the manual “Technical
Descriptions of Functions, Introduction”, 1MRS750528-MUM
Diff6T_1
Diff6T
IL1 TRIP
IL2 CBFP
IL3 STATUS
IL1b
IL2b
IL3b
BS_STAB
BS_INST
TRIGG
GROUP
Diff6T_FBsymb_a
TAP_POS
RESET
4
Distribution Automation Diff6T
5
Diff6T Distribution Automation
2. Description of operation
2.1 Configuration
When the analogue channels and binary inputs have been selected and
parameterized in the dialogue box, the inputs and outputs of the function block
can be configured on a graphic worksheet of the IEC configuration tool. The
phase currents IL1, IL2, IL3, IL1b, IL2b and IL3b are connected to the
corresponding IL1, IL2, IL3, IL1b, IL2b and IL3b inputs of the function block.
Note! It is not possible to connect the current channels to the current inputs in
any other way. E.g. connecting channel IL1 to input IL1b is not possible.
Note! When the function block Diff6T is used, the 2nd harmonic restraint must
be selected for the channels connected to the IL_ and IL_b inputs of the
function block from the special measurements dialogue box of the
configuration tool.
Binary inputs are connected to the Boolean inputs of the function block, and
the outputs of the function block are connected to the output signals in the
same way.
HV side
YNyn0 LV side
L1
L2
L3
Diff6T_HVLV_phasecurr_a
6
Distribution Automation Diff6T
The rated frequency of the relay or the feeder terminal is set via a dialogue
box in the configuration tool. The global control parameter Rated frequency of
the relay can also be used for reading the rated frequency.
2.3 General
Basic setting
The Basic setting defines the minimum differential current required for tripping
in any circumstances. The Basic setting basically allows for the no-load
current of the power transformer and small inaccuracies of the current
transformers, but it can also be used to influence the overall level of the
operation characteristic. At rated voltage the no-load losses of the power
transformer are about 0.2 percent. Should the supply voltage of the power
transformer suddenly increase due to operational disturbances, the
magnetizing current of the transformer increases as well. In general the
magnetic flux density of the transformer is rather high at rated voltage, and a
rise in voltage by a few percents will cause the magnetizing current to
increase by tens of percents. This should be considered in the Basic setting.
(Also see “The operating characteristic”.)
Starting ratio
Variations in the Starting ratio affect the slope of the characteristic, that is, how
big change in the differential current, in comparison with the change in the
load current, is required for tripping. The Starting ratio should consider CT
errors and variations in the transformer tap changer position (if not
compensated). Too high a starting ratio should be avoided, because the
sensitivity of the protection for detecting interturn faults depends basically on
the Starting ratio. Although the coverage area of the Starting ratio is mainly
between Turn-point 1 (fixed) and Turn-point 2, it also affects the overall level
(offset) of the last slope of the operating characteristic (see “The operating
characteristic”).
7
Diff6T Distribution Automation
Turn-point 2
The parameter Turn-point 2 specifies the second turning point (knee point) in
the operating characteristic between the coverage areas of the Starting ratio
and the last slope with the fixed ratio (see “The operating characteristic”).
Ratio I2f/I1f>
The parameter Ratio I2f/I1f> sets the required percentage level (in comparison
to the fundamental component of the differential current) of the second
harmonic component of the differential current to activate the second
harmonic blocking in the case of a transformer inrush or CT saturation during
an external fault.
Ratio I5f/I1f>
The parameter Ratio I5f/I1f> sets the required percentage level (in comparison
to the fundamental component of the differential current) of the fifth harmonic
component of the differential current to activate the fifth harmonic blocking in
the case of transformer overexcitation.
Ratio I5f/I1f>>
The parameter Ratio I5f/I1f>> sets the required percentage level (in
comparison to the fundamental component of the differential current) of the
fifth harmonic component of the differential current to deactivate (remove) the
fifth harmonic blocking in the case of a severe transformer overexcitation,
which could damage the transformer.
2. harm. block
The parameter 2. harm. block specifies whether the second harmonic blocking
is in use or not. Furthermore, it can be specified whether it is allowed for the
internal deblocking logic to remove the second harmonic blocking when the
appropriate conditions are met (see “The 2. harmonic deblocking in the case
of switch on to a fault”). The possible values are therefore “Not in use” (0), “In
use” (1) and “With deblock” (2).
5. harm. block
The 5. harm. block specifies whether the fifth harmonic blocking is in use or
not. Furthermore, it can be selected whether it is allowed to remove the
blocking if the ratio of the fifth harmonic to fundamental further rises above the
limit Ratio I5f/I1f>> (see “Blocking based on the fifth harmonic”). The possible
values are therefore “Not in use” (0), “In use” (1) and “With deblock” (2).
8
Distribution Automation Diff6T
Operation mode
The parameter Operation mode can have the values “In use” and “Not in use”.
When the parameter is set to “In use”, the protection operates normally. When
the parameter is set to “Not in use”, no measured or other output values are
shown and no events are sent, although the algorithms of the protection
function are still executed normally. In addition to setting all outputs to zero
only, a few internal variables are reset. The protection algorithm is therefore
aware of the present situation when it is enabled again by setting the
parameter Operation mode to “In use”. This means that almost no time is
needed to adapt to the current situation and the function is fully functional (and
stable).
Group selection
The Group selection is used either to directly select the active setting group
(values “Group 1” and “Group 2”) or indirectly (value “GROUP input”). In the
case of an indirect setting (value “GROUP input”), the actual active group is
selected by the input “GROUP” of the protection function.
Active group
The Active group is actually not a setting. It just monitors the number of the
actual active group, which in case of parameter Group selection having value
“GROUP input”, would not otherwise be visible.
Trip signal
The Trip signal selects whether the output signal TRIP is latched or not when
it becomes activate (possible values “Non-latching” and “Latching”). This does
not have any effect on the phase segregated trip indications included in the
output STATUS.
Trip pulse
The Trip pulse sets the minimum length to the output signal TRIP in the case it
is not latched. This means that when output TRIP becomes active and resets
quickly after that (due to that operation criteria are not met anymore) the
resetting of the output TRIP is delayed until the time set in the Trip pulse has
elapsed.
This setting sets also the length of the output signal CBFP.
CBFP time
The CBFP time sets the delay time, after the TRIP output has become active,
to activate the CBFP output, which is used to trip an alternative circuit breaker
when the tripping of the first priority circuit breaker has failed.
9
Diff6T Distribution Automation
CT connection
The following assumes that the currents are connected to the relay as
specified in Figure 8 and Figure 9 in section “Connection of current
transformers”.
When the currents are measured so that the CT secondary currents are both
flowing from the phase terminal to the ground terminal, the value is to be set to
“Type II”. Furthermore, if the currents are measured so that the CT secondary
currents are both flowing from the ground terminal to the phase terminal, the
value is also “Type II”.
Only if the CT secondary current on one side of the transformer (HV or LV) is
flowing from the ground terminal to the phase terminal, and the current on the
other side is flowing from the phase terminal to the ground terminal the value
shall be set to “Type I”.
HV connection
This parameter specifies the connection of the HV side winding. The correct
value is directly available from the data of the protected transformer. Values
possible are “Y” (0);“YN” (1);“D” (2); “Z” (3); “ZN” (4).
If the protected object is not a transformer (i.e. it does not need vector group
matching) the value for HV connection shall be set to “Y”.
LV connection
This parameter specifies the connection of the LV side winding. The correct
value is directly available from the data of the protected transformer. Values
possible are “y” (0);“yn” (1);“d” (2); “z” (3); “zn” (4).
If the protected object is not a transformer (i.e. it does not need vector group
matching), the value for LV connection shall be set to “y”.
Clock number
A correct value for the Clock number is directly available from the data of the
protected transformer. For example, if the transformer vector group is YNd11,
then the value for Clock number is “11” (also see Transformer vector group
matching”).
If the protected object is not a transformer (i.e. it does not need vector group
matching) the value for Clock number is always “0”.
10
Distribution Automation Diff6T
Io elimination
If the protected object is not a transformer, the value for Io elimination shall be
set to “Not in use”.
This parameter specifies the tap position number resulting in the minimum
effective number of winding turns on the side of the transformer where the tap
changer resides. With the aid of this parameter and the parameter Max. turns
tap, the tap position compensation algorithm knows in which direction the
compensation shall be made (see Figure 4).
This also ensures that if the current tap position information for some reason is
corrupted, the automatic tap changer position adaptation does not try to adapt
to any unrealistic position values.
This parameter specifies the tap position number resulting in the maximum
effective number of winding turns on the side of the transformer where the tap
changer resides. With the aid of this parameter and the parameter Min. turns
tap the tap position compensation algorithm knows in which direction the
compensation shall be made (see Figure 4).
This also ensures that if the current tap position information for some reason is
corrupted, the automatic tap changer position adaptation does not try to adapt
to any unrealistic position values.
Nominal tap
This parameter specifies the tap position number, resulting in nominal voltage
(and current).
When the current tap position deviates from this value, the input current
values (on the side where the tap changer resides) are scaled to match the
currents on the other side. The correct scaling is determined by the number of
steps and the direction of the deviation from the nominal tap as well as the
percentual change in voltage, which one tap step results in. The percentual
value is set in the Tap step % parameter.
11
Diff6T Distribution Automation
HV LV
Max. turns tap
Nominal tap
This parameter specifies whether the tap changer is connected in the high
voltage side winding or in the low voltage side winding. This parameter is also
used to enable and disable the automatic adaptation to the tap changer
position. The possible values are “Not in use” (0); “HV winding” (1); “LV
winding” (2).
Tap step %
The Tap step % specifies how much the voltage changes (in percents) when
the tap position changes one step. Also see “Compensation of the tap changer
position”.
Reset registers
This parameter is only visible in the setting tool and not on the local HMI.
Reset registers is actually a command (not setting) which resets all the values
in the views “Recorded data X” (where X is 1, 2 or 3).
Test TRIP
The Test TRIP setting is used to activate the test mode for the TRIP output
signal. In practice, the test mode means that the TRIP output is activated
when Test TRIP is set to “TRUE”. When the value is “FALSE” the test mode
for the TRIP output is disabled (also see “Test mode”).
Test CBFP
The Test CBFP setting is used to activate the test mode for the CBFP output
signal. In practice, the test mode means that the CBFP output is activated
when Test CBFP is set to “TRUE”. When the value is “FALSE” the test mode
for the CBFP output is disabled (also see “Test mode”).
12
Distribution Automation Diff6T
These parameters set the event masks for different clients in order to disable
the unwanted events so that they will not be visible to the corresponding
clients (see “Events ”).
• CT errors,
In the protection of generators the false differential current can be caused by:
• CT errors and
13
Diff6T Distribution Automation
The special algorithms are described later in the document (see “The
waveform based blocking”).
HV LV
I1 I2
curr_pos_dir_a
I d = I1 − I 2 EQ. (1)
14
Distribution Automation Diff6T
I1 + I 2
Ib = EQ. (2)
2
d
In
Maximum settings I b3
3 Default settings
OPERATION
I d3
2 I b2
15
Diff6T Distribution Automation
The second turning point Turn-point 2 can be set in the range 1.0...3.0.
• In part 1 (0.0 < Ib/In < Turn-point 1) the differential current required for
tripping is constant. The value of the differential current is the same as the
basic setting selected for the function. The basic setting basically allows
the no-load current of the power transformer and small inaccuracies of the
current transformers, but it can also be used to influence the overall level
of the operation characteristic. At rated current, the no-load losses of the
power transformer are about 0.2 percent. Should the supply voltage of the
power transformer suddenly increase due to operational disturbances, the
magnetizing current of the transformer will increase as well. In general, the
magnetic flux density of the transformer is rather high at rated voltage, and
the rise in voltage by a few percents will cause the magnetizing current to
increase by tens of percents. This should be considered in the basic
setting.
• Part 2, i.e. when Turn-point 1 < Ib/In < Turn-point 2, is called the influence
area of Starting ratio. In this part, variations in the starting ratio affect the
slope of the characteristic, that is, how big the change in the differential
current, in comparison with the change in the load current, is required for
tripping. The starting ratio should consider CT errors and variations in the
transformer tap changer position (if not compensated). A too high starting
ratio should be avoided, because the sensitivity of the protection for
detecting interturn faults basically depends on the starting ratio.
• At high stabilizing currents, when Ib/In > Turn-point 2, the slope of the
characteristic is constant (Part 3). The slope is 100%, which means that
the increase in the differential current is equal to the corresponding
increase in the stabilizing current.
The operation of the differential protection is based on the fundamental
frequency components. Operation is accurate and stable: the DC component
and harmonics of the current do not cause unwanted operations.
16
Distribution Automation Diff6T
current stage. When required, the operate signal of the stage can be blocked
by the external control signal BS_INST.
Should the stabilizing current fall below 30% of the differential current, or the
phase angle between the HV side and LV side phase currents exceed 130
degrees after the automatic vector group matching has been made, a fault has
most certainly occurred in the area protected by the differential relay. Then the
operate value set for the instantaneous stage will be automatically halved and
the internal blocking signals of the stabilized stage will be inhibited.
• The signal types are IL1, IL2, IL3, IL1b, IL2b or IL3b.
• All the required system measurements are on for the connected channels.
• The measuring devices for all channels are CTs.
• The associated task is fast enough (<= 4 times in a fundamental cycle).
The position of the tap changer used for voltage control can be compensated
if the position information is provided for the protection function via the input
signal “TAP_POS”.
The position value of the tap changer can be brought to the relay as a
resistance value, a mA signal or as binary coded. For more information on
how the resistance value or the mA signal interface is implemented, refer to
the Technical Reference Manual of the relay. For the binary coded interface
via the function blocks BCD2INT, GRAY2INT and NAT2INT, refer to the
Generic Base Elements function block manual (1MRS752371-MUM).
17
Diff6T Distribution Automation
Because of the above some action needs to be taken in order to avoid false
tripping of the phase having too low ratio of the second harmonic to
fundamental component. One way could be to always block all phases when
the second harmonic blocking conditions are fulfilled at least in one phase.
The other way is to calculate weighted ratios of the second harmonic to
fundamental for each phase using the original ratios of the phases. The latter
option is used here.
Using separate blocking for the individual phases and weighted averages
calculated for the separate phases provides a blocking scheme that is stable
at connection inrush currents.
If the peak value of the differential current is very high (> 12 p.u.), the limit for
the second harmonic blocking is desensitized (in the phase in question) by
increasing it proportionally to the peak value of the differential current.
The connection of the power transformer against a fault inside the protected
area does not delay the operation of the tripping, because in such a situation
the blocking based on the second harmonic of the differential current is
prevented by a separate algorithm based on the different waveform and the
different rate of change of normal inrush current and inrush current containing
fault current. The algorithm does not eliminate the blocking at inrush currents,
unless there is a fault in the protected area. The special algorithms used are
18
Distribution Automation Diff6T
Normally there are low current periods in the differential current during inrush.
Also the rate of change of the differential current is very low during these
periods. If these features are not present in the differential current, it can be
suspected that there is a fault in the transformer.
This feature can also be enabled and disabled via the parameter 2. harm.
block.
This algorithm has two parts. Both parts are very similar compared to the
above (“The 2. harmonic deblocking in the case of switch on to a fault”), but in
this case the criteria for a low current period is different and only the
differential current (not derivative) is checked. The first part is intended for
external faults while the second is intended for inrush situations.
Both the fifth harmonic blocking and the fifth harmonic deblocking have a
hysteresis to avoid oscillation.
For further clarification of the limits Ratio l5f/l1f> and Ratio l5f/l1f>> and their
hysteresis, see Figure 7.
19
Diff6T Distribution Automation
Id5f/Id1f>>
hysteresis
Id5f/Id1f>
hysteresis
1 t
5th harmonic block
Figure 7. The fifth harmonic blocking limits and the operation when both blocking
and deblocking features are enabled via control parameter 5. harm. block
All the three blocking signals (Waveform, 2. and 5. harmonic) have a counter,
which holds the blocking on for a certain time after the blocking conditions
have ceased to be fulfilled. Deblocking takes place when those counters have
elapsed. This is a “normal” case of deblocking.
The blocking signals can be reset immediately if a very high differential current
is measured or if the phase difference (the angle between) of the compared
currents is over 130 degrees after the automatic vector group matching has
been made. This does not, however, reset the counters holding the blockings,
so the blocking signals may return once these conditions are not valid
anymore.
The more important the object to be protected, the more attention should be
paid to the current transformers. Normally, it is not possible to dimension the
current transformers so that they repeat currents with high DC components
without saturating when the residual flux of the current transformer is high.
The differential protection function block Diff6T operates reliably even though
the current transformers are partially saturated. The purpose of the following
current transformer recommendations is to secure the stability of the relay at
20
Distribution Automation Diff6T
high through currents and the quick and sensitive operation of the relay at
faults occurring in the protected area, where the fault currents may be high.
The accuracy class recommended for current transformers to be used with the
differential function block Diff6T is 5P, in which the limit of the current error at
the rated primary current is 1% and the limit of the phase displacement is 60
minutes. The limit of the composite error at the rated accuracy limit primary
current is 5%.
Sin + S n
Fa = Fn × EQ. (5)
Sin + Sa
Example 1
In the example the rated burden Sn of the CTs 5P20 is 10 VA, the secondary
rated current 5A, the internal resistance Rin = 0.07 Ω and the accuracy limit
factor Fn (ALF) corresponding to the rated burden is 20 (5P20). Thus the
internal burden of the current transformer is Sin = (5A)2 × 0.07 Ω = 1.75 VA.
The input impedance of the relay at a rated current of 5A is < 20 mΩ. If the
measurement conductors have a resistance of 0.113 Ω, the actual burden of
the current transformer is Sa =(5A)2 × (0.113 + 0.020) Ω = 3.33 VA. Thus the
accuracy limit factor Fa corresponding to the actual burden will be about 46.
The CT burden may grow considerably at the rated current of 5A. At the rated
current of 1A the actual burden of the current transformer decreases, while the
repeatability simultaneously improves.
At faults occurring in the protected area, the fault currents may be very high
compared to the rated currents of the current transformers. Thanks to the
instantaneous stage of the differential function block, it is enough that the
current transformers are capable of repeating, during the first cycle, the
current required for instantaneous tripping.
The accuracy limit factors corresponding to the actual burden of the phase
current transformer to be used in differential protection shall fulfill the following
requirement:
21
Diff6T Distribution Automation
where
Ikmax is the maximum through-going fault current (in p.u.) at which the
protection is not allowed to operate,
The parameter r gives the maximum remanence flux density in the CT core.
The value of the parameter r depends on the magnetic material used and on
the construction of the CT. For example, the value r = 0.4 means that the
remanence flux density may be 40 % of the saturation flux density. The
manufacturer of the CT should be contacted when an accurate value for the
parameter r is needed. The value r = 0.4 is recommended to be used when an
accurate value is not available.
In the following, two typical cases are considered for the determination of the
sufficient accuracy limit factor (Fa):
Ikmax 10 (p.u.)
Tdc 100 (ms)
ω 100π (Hz)
Tm 10 (ms)
Kr 1
22
Distribution Automation Diff6T
On the other hand the fault current is now smaller and since the ratio of
the resistance and reactance is greater in this location, having a full DC
offset is not possible. Furthermore, the DC time constant (Tdc) of the
fault current is now smaller, let’s assume 50 ms.
Assuming a maximum fault current 30% lower than in the bus fault and
a DC offset 90% of the maximum, equation (6) will be written.
If the actual burden of the current transformer (Sa) in equation (5) cannot be
reduced low enough to provide a sufficient value for Fa, there are two
alternatives to deal with the situation:
2. a current transformer with a higher nominal primary current I1n (but the
same rated burden) can be chosen.
Example 2
Fa = (IrCT / IrTR) * Fn (actual accuracy limit factor due to oversizing the CT)
Fa = (1500/1000) * 30 = 45
23
Diff6T Distribution Automation
P2 P1 P1 P2
L1
S2 S1 S1 S2
L2
L3
P1 P2 P2 P1
L1
S1 S2 S2 S1
L2
L3
24
Distribution Automation Diff6T
P2 P1 P2 P1
L1
S2 S1 S2 S1
L2
L3
P1 P2 P1 P2
L1
S1 S2 S1 S2
L2
L3
The phase difference of the HV side and LV side currents caused by the
vector group of the power transformer is numerically compensated. The
matching of the phase difference is based on phase shifting and numerical
delta connection inside the relay. The LV connection parameter determines
the connections of the phase windings on the LV side (0="y", 1="yn", 2="d",
3="z", 4="zn"). In the same way, the HV connection parameter determines the
connection on the HV side (0="Y", 1="YN", 2="D", 3="Z", 4="ZN").
When the vector group matching is Yy0, the phase angle of the phase
currents connected to the relay does not change. When the vector group
matching is Yy6, the phase currents will be turned 180° in the relay.
25
Diff6T Distribution Automation
Example 1.
I L1 − I L 2
I L1mHV =
3
I L2 − I L3
I L 2 mHV =
3 EQ. (9)
I L3 − I L1
I L 3 mHV =
3
Example 2.
If the vector group is Yd11and the CT connection according to Type II, the
compensation is a little bit different.
If the Clock number is 4, 6, 8 or 10, the vector group matching is always done
both on the HV and on the LV side. The combination will result in the correct
compensation. In this case the zero-sequence component is always removed
26
Distribution Automation Diff6T
If the Clock number is 1, 5, 7 or 11, the vector group matching is done on one
side only. A possible zero-sequence component of the phase currents at earth
faults occurring out of the protection area will be eliminated in the numerically
implemented delta connection before the differential current and the stabilizing
current are calculated. That is why the vector group matching is almost always
made on the wye-connected side of YNd and Dyn connected transformers.
With the Clock number 0 and 6, the zero-sequence component of the phase
currents is not eliminated automatically on either side. However, the
zero-sequence component on the wye-connected side, earthed at its star
point, has to be eliminated by using the Io elimination parameter.
1
I L1m = I L1 − x ( I L1 + I L 2 + I L 3 )
3
1
I L 2 m = I L 2 − x ( I L1 + I L 2 + I L 3 )
3
EQ. (11)
1
I L 3 m = I L 3 − x ( I L1 + I L 2 + I L 3 )
3
27
Diff6T Distribution Automation
28
Distribution Automation Diff6T
29
Diff6T Distribution Automation
30
Distribution Automation Diff6T
The correct settings for the connection group compensation (control settings
CT connection, HV connection, LV connection and Clock number) can be
verified by monitoring the angle values (Angle IL1-IL2, Angle IL2-IL3, Angle
IL3-IL1, Angle IL1b-IL2b, Angle IL2b-IL3b, Angle IL3b-IL1b, Angle IL1-IL1b,
Angle IL2-IL2b and Angle IL3-IL3b) while injecting current into the transformer.
These angle values are calculated from the compensated currents.
HV side
YNyn0 LV side
3 phase
low
voltage
source IL1 IL2 IL3 N N IL1b IL2b IL3b
Figure 10. Low voltage test arrangement. The three-phase low voltage source can for
example be the station service transformer.
To make sure that the monitored current values are not scaled by the
automatic adaptation to the tap changer position, the control setting parameter
Tapped winding should be set to value “Not in use”. When only interested on
the angle values this is not needed since angle values are not affected by the
tap changer position adaptation.
When injecting the currents into the HV winding as described above the angle
values Angle IL1-IL2, Angle IL2-IL3, Angle IL3-IL1, Angle IL1b-IL2b, Angle
IL2b-IL3b and Angle IL3b-IL1b should show +120.
If this is not the case the phase order may be wrong or the polarity of one
current transformer differs from the polarities of the other current transformers
on the same side. If the angle values Angle IL1-IL2, Angle IL2-IL3 and Angle
IL3-IL1 are shown -120, the phase order is wrong on HV side. If the angle
values Angle IL1b-IL2b, Angle IL2b-IL3b and Angle IL3b-IL1b show -120, the
phase order is wrong on LV side. If the angle values Angle IL1-IL2, Angle IL2-
IL3 and Angle IL3-IL1 do not show the same value (+120) the polarity of one
current transformer may be wrong. For example, if the polarity of the current
transformer measuring IL2 is wrong, the Angle IL1-IL2 show -60, Angle IL2-IL3
show -60 and Angle IL3-IL1 show +120.
31
Diff6T Distribution Automation
When the phase order is correct and the angle values mentioned above are
OK, the angle values Angle IL1-IL1b, Angle IL2-IL2b and Angle IL3-IL3b
should show 0. There can be several reasons if this is not the case. If the
angle values are +/-180 most probably the value given for CT connection is
wrong. If the angle values are something else the value for Clock number can
be wrong. Another possibility is that the combination of HV connection and LV
connection does not match Clock number. This means that the resulting
connection group is not supported.
Two different groups of setting values, group 1 and group 2, are available for
the function block. Switching between the two groups can be done in the
following three ways:
3. By means of the input signal GROUP when allowed via the parameter
Group selection (i.e. when V2 = 2).
The digital outputs of the function block can be activated with separate control
parameters for each output either locally via the HMI or externally via the
serial communication. When an output is activated with the test parameter, an
event indicating the test is generated.
The protective functions operate normally when the outputs are tested.
The information required for later fault analysis is recorded when the function
block trips or when the recording function is triggered via an external triggering
input.
32
Distribution Automation Diff6T
The data of the last three operations (Operation 1...3) are recorded, and the
values of the most recent operation always replace the data of the oldest
operation. The registers are updated in the following order: Operation 1,
Operation 2, Operation 3, Operation 1, Operation 2 and so on.
The time stamp indicates the rising edge of the TRIGG signal or the rising
edge of the TRIP signal.
The status data of the input signals BS_STAB and BS_INST (Active or Not
active) are recorded at the moment of tripping and triggering.
If the function block trips, the highest differential current value during 50 ms
after the rising edge of the TRIP signal is recorded. All the recorded current
and phase difference values will originate from that same moment determined
by the highest differential current. For external triggering, the current values
are recorded at the moment of triggering i.e. on the rising edge of the input
signal TRIGG. Consequently, the values of the phase currents IL1, IL2, IL3,
IL1b, IL2b, IL3b, the values of the differential currents Id1, Id2, Id3, the values
of the stabilizing currents Ib1, Ib2, Ib3 and the phase difference values always
originate from the same moment. The current values are recorded as multiples
of the rated current In and the phase difference values are recorded in
degrees.
The output signal TRIP may have a non-latching or latching feature. When the
latching mode has been selected, the TRIP signal remains active until the
output is reset even if the operation criteria have reset. When the non-latching
mode has been selected, the TRIP signal remains active until the operation
criteria have reset and the time determined by the control parameter Trip
pulse has elapsed.
The additional separate indications for each phase included in the output
STATUS will always be non-latched (and is not affected by the parameter
Trip pulse).
33
Diff6T Distribution Automation
The stage provides a delayed trip signal CBFP after the TRIP signal unless
the fault has disappeared during the set CBFP time delay. In circuit breaker
failure protection the CBFP output can be used to operate a circuit breaker
upstream from the circuit breaker of the transformer. The control parameter
Trip pulse determines also the width of the CBFP output signal.
The function block has one coded output for a set of infrequently needed data.
The STATUS output collects phase-segregated indications of instantaneous
trip, stabilized trip, 2. harmonic blocking, 5. harmonic blocking and waveform
based blocking. The following figures explain the meaning of the bits.
34
Distribution Automation Diff6T
=> The second harmonic blocking is active in all phases 2, 3 and both stabilized and
instantaneous trip have occurred in phase 1.
INT2BOOL_1
INT2BOOL
STATUS IN B0 InstTripPh1
B1 InstTripPh2
B2 InstTripPh3
B3 StabTripPh1
B4 StabTripPh2
B5 StabTripPh3
B6 F2BlockPh1
B7 F2BlockPh2
B8 F2BlockPh3
B9 F5BlockPh1
B10 F5BlockPh2
B11 F5BlockPh3
B12 WaveBlockPh1
B13 WaveBlockPh2
B14 WaveBlockPh3
STATUS_bits
B15
Figure 11. Example of decoding the bits in the coded output STATUS
35
Diff6T Distribution Automation
2.13 Resetting
The TRIP output signal and the registers can be reset via the RESET input, or
over the serial bus or the local HMI.
The operation indicators, latched trip signal and recorded data can be reset as
follows:
36
Distribution Automation Diff6T
3.1 General
• The data direction of the parameters defines the use of each parameter as
follows:
• The different event mask parameters (see section “Control Settings”) affect
the visibility of events on the HMI or on the serial communication (LON or
SPA) as follows:
For example, if only the events E3, E4 and E5 are to be seen on the HMI of
the relay terminal, the event mask value 56 (8 + 16 + 32) is written to the
“Event mask 1” parameter (F106V101).
37
Diff6T Distribution Automation
38
Distribution Automation Diff6T
Starting ratio S42 10...50 % 30 R/W Slope of the second line of the operation
characteristics.
Turn-point 2 S43 1.0...3.0 x In 1.5 R/W Turn-point between the second and the
third line of the operation characteristics.
Inst. setting S44 5...30 x In 10 R/W Trip value of the instantaneous stage.
Ratio I2f/I1f> S45 7...20 % 15 R/W The ratio of the 2. harmonic component to
the fundamental component required for
blocking.
Ratio I5f/I1f> S46 10...50 % 35 R/W The ratio of the 5. harmonic component to
the fundamental component required for
blocking.
Ratio I5f/I1f>> S47 10...50 % 35 R/W The ratio of the 5. harmonic component to
the fundamental component required to
remove the 5. harmonic blocking.
1)
2. harm. block S48 0…2 - 2 R/W Selects if the 2. harmonic blocking is
allowed and if the deblocking is allowed in
case of switch on to a fault.
1)
5. harm. block S49 0…2 - 1 R/W Selects if the 5. harmonic blocking is
allowed and if the deblocking is allowed in
case of a severe overvoltage situation.
1)
Harm_blk 0 = Not in use; 1 = In use; 2 = With deblock
39
Diff6T Distribution Automation
Starting ratio S72 10...50 % 30 R/W Slope of the second line of the operation
characteristics.
Turn-point 2 S73 1.0...3.0 x In 1.5 R/W Turn-point between the second and the
third line of the operation characteristics.
Inst. setting S74 5...30 x In 10 R/W Trip value of the instantaneous stage.
Ratio I2f/I1f> S75 7...20 % 15 R/W The ratio of the 2. harmonic component to
the fundamental component required for
blocking.
Ratio I5f/I1f> S76 10...50 % 35 R/W The ratio of the 5. harmonic component to
the fundamental component required for
blocking.
Ratio I5f/I1f>> S77 10...50 % 35 R/W The ratio of the 5. harmonic component to
the fundamental component required to
remove the 5. harmonic blocking.
1)
2. harm. block S78 0…2 - 2 R/W Selects if the 2. harmonic blocking is
allowed and if the deblocking is allowed in
case of switch on to a fault.
1)
5. harm. block S79 0…2 - 1 R/W Selects if the 5. harmonic blocking is
allowed and if the deblocking is allowed in
case of a severe overvoltage situation.
1)
Harm_blk 0 = Not in use; 1 = In use; 2 = With deblock
40
Distribution Automation Diff6T
Trip pulse V5 40...1000 ms 40 R/W Minimum pulse length of TRIP and CBFP.
CBFP time V6 100...1000 ms 100 R/W Operate time of the delayed trip CBFP.
5)
CT connection V7 0…1 - 0 R/W CT connection type. Determined by the directions of the connected
current transformers.
6)
HV connection V8 0…4 - 0 R/W Connection of the HV side windings. Determined by the transformer
vector group (e.g. Dyn11 ->"D").
7)
LV connection V9 0…4 - 0 R/W Connection of the LV side windings. Determined by the transformer
vector group (e.g. Dyn11 ->"yn").
Clock number V10 0...11 - 0 R/W Setting the Clock number for vector group compensation
(e.g. Dyn11 -> 11).
8)
Io elimination V11 0…3 - 0 R/W Elimination of the zero-sequence current.
Min. turns tap V12 -36...36 - 36 R/W The tap position number results the minimum number of effective
winding turns on the transformer where the tap changer is.
Max. turns tap V14 -36...36 - 0 R/W The tap position number results the maximum number of effective
winding turns on the transformer where the tap changer is.
Nominal tap V15 -36...36 - 18 R/W The nominal position of the tap changer resulting in the default
transformation ratio of the transformer (as if with no tap changer).
9)
Tapped winding V16 0…2 - 0 R/W The winding where the tap changer is connected. Also used to
enable/disable the automatic compensation of the tap changer position.
Tap step % V17 0.60...9.00 % 1.50 R/W The percentage change in voltage corresponding one step of the tap
changer.
10)
Reset registers V13 0…1 - 0 W Resetting of latched trip signal and registers.
11)
Test TRIP V32 0…1 - 0 R/W Testing of TRIP.
11)
Test CBFP V33 0…1 - 0 R/W Testing of CBFP.
Event mask 1 V101 0...262143 - 63 R/W Event mask 1 for event transmission (E0...E17).
Event mask 2 V103 0...262143 - 63 R/W Event mask 2 for event transmission (E0...E17).
Event mask 3 V105 0...262143 - 63 R/W Event mask 3 for event transmission (E0...E17).
Event mask 4 V107 0...262143 - 63 R/W Event mask 4 for event transmission (E0...E17).
1)
Status 0 = Not in use; 1 = In use
2)
Group selection 0 = Group 1; 1 = Group 2; 2 = GROUP input
3)
Active group 0 = Group 1; 1 = Group 2
4)
Trip signal 0 = Non-latching; 1 = Latching
5)
Connection type 0 = Type I; 1 = Type II
6)
HV type 0 = Y; 1 = YN; 2 = D; 3 = Z; 4 = ZN
7)
LV type 0 = y; 1 = yn; 2 = d; 3 = z; 4 = zn
8)
IO elimination 0 = Not in use; 1 = HV side; 2 = LV side; 3 = HV&LV side
9)
Tapped winding 0 = Not in use; 1 = HV winding; 2 = LV winding
10)
Reset 0 = 0; 1 = Reset
11)
Test 0 = Do not activate; 1 = Activate
41
Diff6T Distribution Automation
Id2f/Id1f L1 I13 0.0...100.0 % 0.0 R/M The ratio of the second harmonic to fundamental in phase 1
Id2f/Id1f L2 I14 0.0...100.0 % 0.0 R/M The ratio of the second harmonic to fundamental in phase 2
Id2f/Id1f L3 I15 0.0...100.0 % 0.0 R/M The ratio of the second harmonic to fundamental in phase 3
Angle IL1-IL2 I16 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L1 and L2
Angle IL2-IL3 I17 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L2 and L3
Angle IL3-IL1 I18 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L3 and L1
Angle IL1b-IL2b I19 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L1b and L2b
Angle IL2b-IL3b I20 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L2b and L3b
Angle IL3b-IL1b I21 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L3b and L1b
Angle IL1-IL1b I22 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L1 and L1b
Angle IL2-IL2b I23 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L2 and L2b
Angle IL3-IL3b I24 -180.0...180.0 ° 0.0 R/M Phase difference of the currents L3 and L3b
1)
Input BS_STAB I25 0…1 - 0 R/M Status of BS_STAB signal
1)
Input BS_INST I26 0…1 - 0 R/M Status of BS_INST signal
1)
Input GROUP I27 0…1 - 0 R/M Status of signal for switching between group 1 and 2
42
Distribution Automation Diff6T
43
Diff6T Distribution Automation
44
Distribution Automation Diff6T
45
Diff6T Distribution Automation
46
Distribution Automation Diff6T
3.3.4 Events
47
Diff6T Distribution Automation
4. Technical Data
Operation accuracies At the frequency range f/fn = 0.95...1.05
± 4% of set value or ± 2% x In
± 4% of set value or ± 2% x In
48