0% found this document useful (0 votes)
342 views21 pages

NPS3 - Negative-Phase-Sequence Protection Low-Set Stage (NPS3Low) High-Set Stage (NPS3High)

This document provides information about negative-phase-sequence protection functions NPS3Low and NPS3High used in products based on the RED 500 automation platform. It contains 3 sections: 1. An introduction describing the features and applications of the functions for protecting power generators and motors from thermal stress due to negative-phase-sequence currents. 2. A description of the functions' operation including configuration, measurement modes, definite-time and inverse-time operation criteria, setting groups, and output signals. 3. Details on the functions' parameters, settings, measurement values, and event registration for monitoring performance and diagnosing issues.

Uploaded by

rajesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
342 views21 pages

NPS3 - Negative-Phase-Sequence Protection Low-Set Stage (NPS3Low) High-Set Stage (NPS3High)

This document provides information about negative-phase-sequence protection functions NPS3Low and NPS3High used in products based on the RED 500 automation platform. It contains 3 sections: 1. An introduction describing the features and applications of the functions for protecting power generators and motors from thermal stress due to negative-phase-sequence currents. 2. A description of the functions' operation including configuration, measurement modes, definite-time and inverse-time operation criteria, setting groups, and output signals. 3. Details on the functions' parameters, settings, measurement values, and event registration for monitoring performance and diagnosing issues.

Uploaded by

rajesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

1MRS752310-MUM NPS3_

Issued: 10/1998
Version: E/24.11.2003
Negative-Phase-Sequence Protection
Low-Set Stage (NPS3Low)
Data subject to change without notice High-Set Stage (NPS3High)

Contents
1. Introduction...............................................................................................2
1.1 Features ..............................................................................................2
1.2 Application ...........................................................................................2
1.3 Input description ..................................................................................4
1.4 Output description ...............................................................................4

2. Description of Operation ..........................................................................5


2.1 Configuration .......................................................................................5
2.2 Configuration error checking................................................................6
2.3 Measuring mode..................................................................................6
2.4 Operation criteria .................................................................................7
2.4.1 Definite-time operation ...............................................................7
2.4.2 Inverse-time operation ................................................................9
2.5 Setting groups ...................................................................................11
2.6 Test mode .........................................................................................11
2.7 START, TRIP and CBFP outputs.......................................................11
2.8 Resetting ...........................................................................................12
3. Parameters and Events ..........................................................................13
3.1 General..............................................................................................13
3.2 Setting values ....................................................................................14
3.2.1 Actual settings ..........................................................................14
3.2.2 Setting group 1 .........................................................................14
3.2.3 Setting group 2 .........................................................................15
3.2.4 Control settings ........................................................................16
3.3 Measurement values .........................................................................17
3.3.1 Input data .................................................................................17
3.3.2 Output data...............................................................................17
3.3.3 Recorded data ..........................................................................17
3.3.4 Events ......................................................................................20

4. Technical Data.........................................................................................21
NPS3 _ Substation Automation

1. Introduction

1.1 Features

• Negative-phase-sequence protection
• Definite-time (DT) or inverse-time (IDMT) operation
• Definite minimum time for high-level negative-sequence currents in inverse-time
operation
• Limited maximum operate time for long-time low-level negative-sequence currents
in inverse-time operation
• Adjustable start delay in inverse-time operation
• Backwards counting when overload disappears in inverse-time mode
• Current measurement with conventional current transformers or Rogowski coils
• Two- or three-phase negative-sequence current measurement
• Input signal for selecting the direction of rotation
• Delayed trip output for the circuit-breaker failure protection (CBFP) function
• Output for blocking the reconnection of an overheated machine
• Wide setting ranges

1.2 Application

This document specifies the functions of the negative-phase-sequence function blocks


NPS3Low and NPS3High used in products based on the RED 500 Platform. The low-
set stage and the high-set stage are identical in operation.

The function blocks NPS3Low and NPS3High are designed for negative-phase-
sequence protection whenever the operating characteristic is appropriate. They are
applied for the protection of power generators or synchronous motors against thermal
stress and damage.
(See Figure 5).

I2>

I2>>

Figure 1. Protection diagram symbols of NPS3Low and NPS3High (For IEC


symbols used in single line diagrams, refer to the manual “Technical
Descriptions of Functions, Introduction”, 1MRS750528-MUM)

2
Substation Automation NPS3 _

Figure 2. Function block symbols of NPS3Low and NPS3High

3
NPS3 _ Substation Automation

1.3 Input description

Name Type Description


IL1 Analogue signal (SINT) Input for measuring phase current IL1
IL2 Analogue signal (SINT) Input for measuring phase current IL2
IL3 Analogue signal (SINT) Input for measuring phase current IL3
ROT_DIR Digital signal (BOOL, active Input signal for selecting rotation
high) direction of the machine
GROUP Digital signal (BOOL, active Control input for switching between the
high) setting groups 1 and 2
BLOCK Digital signal (BOOL, active Input for blocking the function
high)
RESET Reset signal (BOOL, pos. Input signal for resetting the trip signal
edge) and registers of NPS3Low or NPS3High

1.4 Output description

Name Type Description


START Digital signal (BOOL, active high) Start signal
TRIP Digital signal (BOOL, active high) Trip signal
CBFP Digital signal (BOOL, active high) Delayed trip signal for circuit-
breaker failure protection
(CBFP)
BLOCK_OUT Digital signal (BOOL, active high) Signal for blocking the
reconnection of an overheated
machine
ERR Digital signal (BOOL, active high) Signal for indicating a
configuration error

4
Substation Automation NPS3 _

2. Description of Operation

2.1 Configuration

Phase currents can be measured via conventional current transformers or Rogowski


coils. The measuring devices and signal types for the analogue channels are selected
and configured in a special dialogue box of the Relay Configuration Tool included in
the CAP 505 Tool Box. Digital inputs are configured in the same programming
environment (the number of selectable analogue inputs, digital inputs and digital
outputs depends on the hardware used).

When the analogue channels and digital inputs have been selected and configured in
the dialogue box, the inputs and outputs of the function block can be configured on a
graphic worksheet of the configuration tool.

In case of three phase currents (Figure 3), the phase currents IL1, IL2 and IL3 are
connected to the corresponding IL1, IL2 and IL3 inputs of the function block, whereas
in case of two phase currents (Figure 4), the phase currents are connected to the first
two phase current inputs and the third analogue input is left unconnected.

Digital inputs are connected to the boolean inputs of the function block and in the
same way, the outputs of the function block are connected to the output signals.

Figure 3. Configuration example in case of three phase currents

Figure 4. Analogue channel connections in case of two phase currents

5
NPS3 _ Substation Automation

In the input data and recorded data fields, the monitored phase currents are those
actually connected to the corresponding inputs. For example, if the analogue channel
IL3 is connected to the input IL1, the value of the “Current IL1” parameter is actually
the value of phase current IL3.

The ROT_DIR input is used for motor protection. If status information about the
motor rotation direction is available, it can be connected to the ROT_DIR input of the
function block. In this case the control setting parameter “Dir. selection” must be set
to value “Input rot.dir.”, which means the measured negative-sequence current and the
operation of the function block are independent of the motor rotation direction.

2.2 Configuration error checking

When the relay is started, the function block checks that at least two phase currents
are connected to the first two analogue inputs. If two currents are not connected, the
ERR output is activated and the error event E13 is sent.

If the phase currents are connected in a different order compared to the configuration
examples, the error event is not sent and the ERR output is not activated. In these
cases, however, the control setting parameter “Dir. selection” must be set to
“Reverse” value to achieve correct operation.

2.3 Measuring mode

Negative phase-sequence current can be calculated from two- or three-phase currents.


The number of phase currents is set via the control setting parameter ”Num. of
phases”. If only two phase currents are connected, the value of “Num. of phases”
parameter is always two and cannot be changed. The negative-sequence current
calculation is based on fundamental-frequency phase currents.

When three-phase currents are used, the negative-sequence current is calculated as


follows:

I2 = 1
3 I R + I S ∠240° + I T ∠120°

where IR, IS and IT are phase currents.

In case of two-phase currents, the value of the neutral current is assumed to be 0, that
is, IR+IS+IT=0. Thus, the negative-sequence current is calculated as follows:

3
I2 = I R + I T ∠ 60 °
3
where IR and IT are phase currents.

6
Substation Automation NPS3 _

2.4 Operation criteria

The function block has the two operation modes “Definite time” and “Inverse time”.
The type of operation is selected via the setting parameter ”Operation mode”.

In both operation modes the function block starts if the calculated negative phase-
sequence exceeds the set start current, which is set via the “Start value” parameter.
The parameter is common to the two operation modes.

Note! The default value of the “Start value” parameter is 20% of nominal, which is
usual for motor protection. Generators are more sensitive to current unbalance and the
negative sequence current value that a generator can stand continuously is usually
between 5% and 10%. Therefore in case of generator protection a safer value for the
“Start value” parameter is 5%.

2.4.1 Definite-time operation

The function block trips when the measured negative phase-sequence has remained
over the set limit for the time set via the “Operate time” parameter. The “Operate
time” parameter is used only in the definite-time operation.

When the function block trips, the BLOCK_OUT output is activated and will remain
active for the set time. The cooling time is set via the “Cooling time” parameter. The
same parameter is also used in the inverse-time operation. The BLOCK_OUT signal
is used to prevent the auto-reclosing of an overheated generator.

TRIP

Cooling time

BLOCK_OUT

Figure 5. Use of the “Cooling time” parameter


For intermittent faults, the definite-time operation includes the delayed reset function.
Without the delayed reset function the DT timer would reset once the negative-
sequence current drops off.

When the DT timer has started, it goes on running normally even if the current drops
off, provided the drop-off period is shorter than the set drop-off time. If the drop-off
period is longer than the set drop-off time, the DT timer will reset when the drop-off
time elapses (Figure 6).

7
NPS3 _ Substation Automation

In Figures 6 and 7 the input signal IN of the DT timer is TRUE when the current is
above the set start value and FALSE when the current is below the set start value.

1
IN
0

START

TRIP

Drop-off time
Drop-off
timer

Dropoff1.fh7
Operate time
Operate
timer

Figure 6. The drop-off period is longer than the set drop-off time
If the drop-off period is shorter than the set drop-off time and the DT timer time has
elapsed during the drop-off period, the function block will trip once the current
exceeds the set value again (Figure 7).

1
IN
0

START

TRIP

Drop-off time
Drop-off
timer
Dropoff2.fh7

Operate time
Operate
timer

Figure 7. The drop-off period is shorter than the set drop-off time

8
Substation Automation NPS3 _

2.4.2 Inverse-time operation

The operate time of the function block in the inverse-time mode is expressed
mathematically as follows :

K
t= 2
æ I2 ö
ç ÷ − StartValue 2
è IN ø

where
t relay operate time in seconds
I2 negative-sequence current
IN rated current of the machine
Start value Setting parameter that corresponds to the continuous negative-
sequence current withstand of the machine, the I2 current
expressed in xIN (rated current of the machine)
K Setting parameter that corresponds to the machine constant,
equal to the I22t constant of the machine, as stated by the
machine manufacturer

1.5 K=5 K=20 K=40 K=100

0.5
I2 (xIn)

Start value=0.2

0.1

Start value=0.05

1 10 100 1000 10000


Operate time (s)

Figure 8. The time/negative sequence current characteristics of NPS3Low and


NPS3High
When the measured negative-sequence current exceeds the set start current I2, the
function block starts accumulating a sum, the accumulate rate being proportional to
the subtraction of the squared value of the actual negative-sequence current and the

9
NPS3 _ Substation Automation

squared value of the “Start value” parameter. When the sum exceeds the level
corresponding to the setting parameter K, the function block operates. The higher the
degree of current unbalance, the faster the sum increases, and as the operate level of
the sum is defined only by the constant K, the negative-sequence relay will have an
inverse-time operating characteristic which conforms to the thermal load
characteristic of a rotating machine. When the overload disappears, the subtraction
(I22 - StartValue2) becomes negative and the sum decreases. Thus, decrease of the sum
indicates cooling of the machine, and the cooling speed depends on the value of the I2
current. When the sum reaches 0, the accumulation is stopped.

The accumulation is also stopped and the sum is set to 0 if the negative-sequence
current remains below the set limit for the set cooling time. Another purpose of the
“Cooling time” parameter is to keep the BLOCK_OUT signal active after tripping for
the set time. The BLOCK_OUT signal is used to prevent the auto-reclosing of the
overheated generator.

In inverse-time operation, the delay of the START output can be set via the parameter
“Start delay”. The start delay can be used for definite-time alarming when the START
output is used as an alarm output. The set start delay does not affect the operate time
of the function block.

The maximum operate time is limited for long-time low-level negative-sequence


currents. The maximum operate time can be set via the “Maximum time” parameter
and the minimum operate time via the “Minimum time” parameter. The meaning of
the minimum and maximum time settings is illustrated in the figure below.

I2 /IN

Operating curve

t= K
(I2/IN)2- Start value 2

Start value

t
Minimum time Maximum time

Figure 9. Operating characteristic


The setting parameters “K”, “Start delay”, “Minimum time” and “Maximum time” do
not affect the definite-time mode.

10
Substation Automation NPS3 _

2.5 Setting groups

Two different groups of setting values, group 1 and group 2, are available for each
function block. Switching between the two groups can be done in the following three
ways:

1 Locally via the control parameter “Group selection”1) of the MMI


2 Over the communication bus by writing the parameter V21)
3 By means of the input signal GROUP when allowed via the parameter “Group
selection” (i.e. when V2 = 21))
1)
Group selection (V2): 0 = Group 1; 1 = Group 2; 2 = GROUP input

The control parameter “Active group” indicates the setting group valid at a given
time.

2.6 Test mode

The digital outputs of the function block can be activated with separate control
parameters for each output either locally via the MMI or externally via the serial
communication. When an output is activated with the test parameter, an event
indicating the test is generated.

The protection functions operate normally while the outputs are tested.

2.7 START, TRIP and CBFP outputs

The output signal START is always pulse-shaped. The minimum pulse width of the
corresponding output signal is set via a separate parameter on the MMI or on serial
communication. If the start situation is longer than the set pulse width, the START
signal remains active until the start situation is over.

The output signal TRIP may have a non-latching or latching feature. When the
latching mode has been selected, the TRIP signal remains active until the output is
reset even if the operation criteria have reset.

Each function block provides a delayed trip signal CBFP after the TRIP signal unless
the fault has disappeared during the set CBFP time delay. In circuit-breaker failure
protection, the CBFP output can be used to operate a circuit breaker in front of the
circuit breaker of the machine. The control parameter “Trip pulse” also sets the width
of the CBFP output signal.

11
NPS3 _ Substation Automation

2.8 Resetting

The TRIP output signal and the registers can be reset either via the RESET input, or
over the serial bus or the local MMI.

The operation indicators, latched trip signal and recorded data can be reset as follows:

Operation Latched trip Recorded


indicators signal data
1)
RESET input of the function block X X
1)
Parameter F077V013 for NPS3Low X X
1)
Parameter F078V013 for NPS3High X X
2)
General parameter F001V011 X
2)
General parameter F001V012 X X
2)
General parameter F001V013 X X X
2)
Push-button C X
2)
Push-buttons C + E (2 s) X X
2)
Push-buttons C + E (5 s) X X X
1)
Resets the latched trip signal and recorded data of this particular function block.
2)
Affects all function blocks.

12
Substation Automation NPS3 _

3. Parameters and Events

3.1 General

• Each function block has a specific channel number for serial communication
parameters and events. The channel for NPS3Low is 77 and that for NPS3High 78.
• The data direction of the parameters defines the use of each parameter as follows:
Data direction Description
R, R/M Read only
W Write only
R/W Read and write

• The different event mask parameters (see section “Control settings”) affect the
visibility of events on the MMI or on serial communication (LON or SPA) as
follows:
Event mask 1 (FxxxV101/102) SPA / MMI (LON)
Event mask 2 (FxxxV103/104) LON
Event mask 3 (FxxxV105/106) LON
Event mask 4 (FxxxV107/108) LON

For example, if only the events E3, E4 and E5 are to be seen on the MMI of the
relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask
1” parameter (FxxxV101).
In case a function block includes more than 32 events, there are two parameters
instead of e.g. the “Event mask 1” parameter: the parameter “Event mask 1A”
(FxxxV101) covers the events 0...31 and “Event mask 1B”(FxxxV102) the events
32...63.

13
NPS3 _ Substation Automation

3.2 Setting values

3.2.1 Actual settings

Parameter Code Values Unit Default Data Explanation


direction
Operation mode S1 0...2 1) - 1 R Selection of operation mode
(definite- or inverse-time mode)

Start value S2 0.01...0.50 x In 0.20 R Start value of negative-sequence


current I2

Operate time S3 0.1...120.0 s 1.0 R Operate time in definite-time mode

K S4 5.0...100.0 - 5.0 R Operating characteristic constant

Start delay S5 0.1...60.0 s 1.0 R Definite start time in inverse-time


mode

Minimum time S6 0.1...120.0 s 0.1 R Definite minimum operate time

Maximum time S7 500...10000 s 1000 R Maximum operate time regardless of


the inverse characteristic

Cooling time S8 5...10000 s 50 R Time required to cool the machine


1)
Operation mode 0 = Not in use; 1 = Definite time; 2 = Inverse time

3.2.2 Setting group 1

Parameter Code Values Unit Default Data Explanation


direction
Operation mode S41 0...2 1) - 1 R/W Selection of operation mode
(definite- or inverse-time mode)

Start value S42 0.01...0.50 x In 0.20 R/W Start value of negative-sequence


current I2

Operate time S43 0.1...120.0 s 1.0 R/W Operate time in definite-time mode

K S44 5.0...100.0 - 5.0 R/W Operating characteristic constant

Start delay S45 0.1...60.0 s 1.0 R/W Definite start time in inverse-time
mode

Minimum time S46 0.1...120.0 s 0.1 R/W Definite minimum operate time

Maximum time S47 500...10000 s 1000 R/W Maximum operate time regardless
of the inverse characteristic

Cooling time S48 5...10000 s 50 R/W Time required to cool the machine
1)
Operation mode 0 = Not in use; 1 = Definite time; 2 = Inverse time

14
Substation Automation NPS3 _

3.2.3 Setting group 2

Parameter Code Values Unit Default Data Explanation


direction
Operation mode S71 0...2 1) - 1 R/W Selection of operation mode
(definite- or inverse-time mode)

Start value S72 0.01...0.50 x In 0.20 R/W Start value of negative-sequence


current I2

Operate time S73 0.1...120.0 s 1.0 R/W Operate time in definite-time


mode

K S74 5.0...100.0 - 5.0 R/W Operating characteristic constant

Start delay S75 0.1...60.0 s 1.0 R/W Definite start time in inverse-time
mode

Minimum time S76 0.1...120.0 s 0.1 R/W Definite minimum operate time

Maximum time S77 500...10000 s 1000 R/W Maximum operate time regardless
of the inverse characteristic

Cooling time S78 5...10000 s 50 R/W Time required to cool the machine
1)
Operation mode 0 = Not in use; 1 = Definite time; 2 = Inverse time

15
NPS3 _ Substation Automation

3.2.4 Control settings

Parameter Code Values Unit Default Data Explanation


direction
Num. of phases V1 2...3 - 3 R/W Selection of two-phase or three-
phase measurement

Group selection V2 0...2 1) - 0 R/W Selection of the active setting


group

Active group V3 0 or 1 2) - 0 R/M Active setting group

Dir. selection V4 0...2 3) - 0 R/W Selection of rotation direction


4)
Rotation dir. V5 0 or 1 - 0 R/M Rotation direction

Drop-off time V6 0...1000 ms 0 R/W Resetting time of the operate time


counter in DT mode

Start pulse V7 0...1000 ms 0 R/W Minimum pulse width of START


signal

Trip signal V8 0 or 1 5) - 0 R/W Selection of latching feature for


TRIP output

Trip pulse V9 40...1000 ms 40 R/W Minimum pulse width of TRIP and


CBFP

CBFP time V10 100...1000 ms 100 R/W Operate time of the delayed trip
CBFP

Reset registers V13 1=Reset - 0 W Resetting of latched trip signal


and registers

Test START V31 0 or 1 6) - - R/W Testing of START


6)
Test TRIP V32 0 or 1 - - R/W Testing of TRIP

Test CBFP V33 0 or 1 6) - - R/W Testing of CBFP

Event mask 1 V101 0...12287 - 8255 R/W Event mask 1 for event
transmission (E0... E13)

Event mask 2 V103 0... 12287 - 8255 R/W Event mask 2 for event
transmission (E0... E13)

Event mask 3 V105 0... 12287 - 8255 R/W Event mask 3 for event
transmission (E0... E13)

Event mask 4 V107 0... 12287 - 8255 R/W Event mask 4 for event
transmission (E0... E13)
1)
Group selection 0 = Group 1; 1 = Group 2; 2 = GROUP input
2)
Active group 0 = Group 1; 1 = Group 2
3)
Dir. selection 0 = Forward; 1 = Reverse; 2 = Input rot.dir.
4)
Rotation dir. 0 = Forward; 1 = Reverse
5)
Trip signal 0 = Non-latching; 1 = Latching
6)
Test 0 = Do not activate; 1 = Activate

16
Substation Automation NPS3 _

3.3 Measurement values

3.3.1 Input data

Parameter Code Values Unit Default Data Explanation


direction
Neg. seq. cur. I1 0.00...60.00 x In 0.00 R/M Negative-sequence current I2

Current IL1 I2 0.00...60.00 x In 0.00 R/M Phase current IL1

Current IL2 I3 0.00...60.00 x In 0.00 R/M Phase current IL2

Current IL3 I4 0.00...60.00 x In 0.00 R/M Phase current IL3

Input Rot. dir. I5 0 or 1 1) - 0 R/M Input signal for selecting rotation


direction for the generator

Input BLOCK I6 0 or 1 2) - 0 R/M Input signal for blocking the


function block

Input GROUP I7 0 or 1 2) - 0 R/M Signal for switching between


groups 1 and 2

Input RESET I8 0 or 1 2) - 0 R/M Signal for resetting the output


signals and registers of
NPS3Low or NPS3High
1)
Rot. dir. 0 = forward; 1 = reverse
2)
Input 0 = Not active; 1 = Active

3.3.2 Output data

Parameter Code Values Unit Default Data Explanation


direction
Output START O1 0 or 1 1) - 0 R/M Status of start signal
1)
Output TRIP O2 0 or 1 - 0 R/M Status of trip signal

Output BLOCK O3 0 or 1 1) - 0 R/M Status of BLOCK_OUT signal


(signal for keeping the machine
separated from the power system)

Output ERR O4 0 or 1 1) - 0 R/M Status of error signal


1)
Output 0 = Not active; 1 = Active

3.3.3 Recorded data

3.3.3.1 General

The information required for later fault analysis is recorded when the function block
starts or trips.

The data of three last operations (operation 1...3) are recorded and the values of the
most recent operation always replace the data of the oldest operation. The registers

17
NPS3 _ Substation Automation

are updated in the following order: Operation 1, Operation 2, Operation 3, Operation


1, Operation 2,...

3.3.3.2 Date and time

The time stamp indicates the rising edge of the START or TRIP signal.

3.3.3.3 Duration

The duration of the start situation is recorded as a percentage of the calculated operate
time.

3.3.3.4 Currents

If the function block trips or starts, the negative-sequence current is updated at the
moment of tripping or starting i.e. on the rising edge of the TRIP or START signal.
The negative-sequence current is recorded as a multiple of the rated current In.

3.3.3.5 Status data

The status data of the input signal BLOCK (Active or Not active) and the parameters
“Rotation dir.” and “Active group” are recorded at the moment of triggering.The
“Rotation dir.” parameter indicates the rotation direction of the machine and the
“Active group” parameter the setting group valid for the recorded data.

3.3.3.6 Priority

The priority of the recording function is the following:

1 Tripping
2 Starting

18
Substation Automation NPS3 _

3.3.3.7 Recorded data 1

Parameter Code Values Unit Default Data Explanation


direction
Date V201 YYYY-MM-DD - - R/M Recording date

Time V202 hh:mm:ss.mss - - R/M Recording time

Duration V203 0.0...100.0 % 0.0 R/M Duration of start situation

Neg. seq. cur. V204 0.00...60.00 x In 0.00 R/M Negative-sequence current

Current IL1 V205 0.00...60.00 x In 0.00 R/M Filtered value of IL1

Current IL2 V206 0.00...60.00 x In 0.00 R/M Filtered value of IL2

Current IL3 V207 0.00...60.00 x In 0.00 R/M Filtered value of IL3

Rotation dir. V208 0 or 1 1) - 0 R/M Status of rotation direction


2)
BLOCK V209 0 or 1 - 0 R/M Status of BLOCK input

Active group V210 0 or 1 3) - 0 R/M Active setting group


1)
Rotation dir. 0 = Forward; 1 = Reverse
2)
BLOCK 0 = Not active; 1 = Active
3)
Active group 0 = Group 1; 1 = Group 2

3.3.3.8 Recorded data 2

Parameter Code Values Unit Default Data Explanation


direction
Date V301 YYYY-MM-DD - - R/M Recording date

Time V302 hh:mm:ss.mss - - R/M Recording time

Duration V303 0.0...100.0 % 0.0 R/M Duration of start situation

Neg. seq. cur. V304 0.00...60.00 x In 0.00 R/M Negative-sequence current

Current IL1 V305 0.00...60.00 x In 0.00 R/M Filtered value of IL1

Current IL2 V306 0.00...60.00 x In 0.00 R/M Filtered value of IL2

Current IL3 V307 0.00...60.00 x In 0.00 R/M Filtered value of IL3

Rotation dir. V308 0 or 1 1) - 0 R/M Status of rotation direction


2)
BLOCK V309 0 or 1 - 0 R/M Status of BLOCK input

Active group V310 0 or 1 3) - 0 R/M Active setting group


1)
Rotation dir. 0 = Forward; 1 = Reverse
2)
BLOCK 0 = Not active; 1 = Active
3)
Active group 0 = Group 1; 1 = Group 2

19
NPS3 _ Substation Automation

3.3.3.9 Recorded data 3

Parameter Code Values Unit Default Data Explanation


direction
Date V401 YYYY-MM-DD - - R/M Recording date

Time V402 hh:mm:ss.mss - - R/M Recording time

Duration V403 0.0...100.0 % 0.0 R/M Duration of start situation

Neg. seq. cur. V404 0.00...60.00 x In 0.00 R/M Negative-sequence current

Current IL1 V405 0.00...60.00 x In 0.00 R/M Filtered value of IL1

Current IL2 V406 0.00...60.00 x In 0.00 R/M Filtered value of IL2

Current IL3 V407 0.00...60.00 x In 0.00 R/M Filtered value of IL3

Rotation dir. V408 0 or 1 1) - 0 R/M Status of rotation direction


2)
BLOCK V409 0 or 1 - 0 R/M Status of BLOCK input

Active group V410 0 or 1 3) - 0 R/M Active setting group


1)
Rotation dir. 0 = Forward; 1 = Reverse
2)
BLOCK 0 = Not active; 1 = Active
3)
Active group 0 = Group 1; 1 = Group 2

3.3.4 Events

Code Weighting Default Event reason Event state


coefficient mask
E0 1 1 START signal from I2> or I2>> stage Reset

E1 2 1 START signal from I2> or I2>> stage Activated

E2 4 1 TRIP signal from I2> or I2>> stage Reset

E3 8 1 TRIP signal from I2> or I2>> stage Activated

E4 16 1 CBFP signal from I2> or I2>> stage Reset

E5 32 1 CBFP signal from I2> or I2>> stage Activated

E6 64 0 BLOCK_OUT signal from I2> or I2>> stage Reset

E7 128 0 BLOCK_OUT signal from I2> or I2>> stage Activated

E8 256 0 BLOCK signal of I2> or I2>> stage Reset

E9 512 0 BLOCK signal of I2> or I2>> stage Activated

E10 1024 0 Test mode of I2> or I2>> stage Off

E11 2048 0 Test mode of I2> or I2>> stage On

E12 0 0 - -

E13 8192 1 Config. error of I2> stage Activated

20
Substation Automation NPS3 _

4. Technical Data
Operation accuracies Depends on the frequency of the current measured:

f/fn = 0.95...1.05: ± 2.5% of set value or ± 0.01 x In.

Start time Injected negative-seq. current = 2.00 x start value:

f/fn = 0.95...1.05 internal time < 32 ms


1)
total time < 40 ms

Reset time 40...1000 ms


(depends on the minimum pulse width set for the TRIP output)

Reset ratio Typ. 0.96 (range 0.95...0.98) in definite-time mode

Retardation time Total retardation time when the negative-


sequence current drops below the start value2) < 45 ms

Operate time accuracy Depends on the frequency of the current measured:


in definite-time mode
f/fn = 0.95...1.05: ± 2% of set value or ± 20 ms2)

Accuracy class index E Depends on the frequency of the current measured:


in inverse-time mode
f/fn = 0.95...1.05: ± 2% of the calculated ideal operate time or ± 20
ms2)

Configuration data Task execution interval (Relay Configuration Tool):10 ms


at the rated frequency fn = 50 Hz
1)
Includes the delay of the signal relay
2)
Includes the delay of the heavy-duty output relay

Technical revision history


Technical revision Change
E -

F -

21

You might also like