LED Multifunctional Power Instrument
LED Multifunctional Power Instrument
Power Instrument
( LED )
K M
V A W Wh
V A Var Varh
V A Hz
MENU
K M
K M
V A W DI
V A W Wh
V A Var DO
V A Var Varh
V A Hz
V A Hz
MENU MEMU
-1-
Chapter 2. Product Function
Ordinary function Extended function
●Phase voltage : UA , UB , UC ●4 channels analog quantity output
●Line voltage : UAB , UBC , UCA ●4 channels switch value output
●Current : IA , IB , IC ●4 channels switch value input
●Active power
●Reactive power
●Apparent power
●Power factor
●Frequency
●Active electric energy
●Reactive electric energy
●2 channels electric pluse output
●Communication output : RS485
Active 3200imp/kwh
Pl u se constant Reactive 3200imp/kvarh
-2-
Output mode RS485
Frequency ±0.1Hz
Measuring
accuracy Power factor ±0.01PF
Scope AC 220V,50/60Hz
Sourse
Consumption <5VA
Operation : -10~50°C
Temperature
Storage : -25~70°C
Environment
Humidity ≤85%RH,free of wet and corrosive gas
Elevation ≤3000m
-3-
Chapter 4. Program and usage
3.1 Panel description
K M
V A W DI
Display screen
V A Var DO
V A Hz
V A W DI
The left picture shows:
V A Var DO UA-phase voltage is 220.1V
UB-phase voltage is 220.0V
V A Hz UC-phase voltage is 220.3V
MENU
The line voltage can be looked over
by pressing Enter key when 3P4W
K M
V A W DI
Fixed display three-phase current
The left picture shows:
V A Var DO
A-phase current is 5.200A
V A Hz
B-phase current is 5.197A
C-phase current is 5.198A
MENU
K M
K M
V A W DI
Fixed display switching value and frequency
The left picture shows:
V A Var DO
The first screen : output(0 : off 1 : on)
V A Hz
The second screen : input(0 : off 1 : on)
The third screen is frequency:50.00Hz
MENU
K M
V A W DI
MENU
K M
V A W DI
MENU
-5-
4.4 Menu framework
MENU
( DiSP mode:0~6 )
Press
MENU
( Voltage range )
( Current range )
-6-
Press
( RS485 communication address:1~247 )
MENU
( Baud rate )
MENU
-7-
4.5 Menu significations
Under the programmable mode, four menu setting items including of setting
(SEt), input(inPt), communication(Conn), switching value output(do1-4) , annlog
quantity(Ao1-4) , modify password(CodE) and LED display hierarchical menu
framework management are provided in this instrument. Row 1 displays the first-
tier menu; row 2 displays the second-tier menus; row 3 displays the parameter value.
Protocol
form
-8-
4.6 Programming operation examples
The measuring range of instruments has been set as the same parameters
provided by users at the factory. Users should check if the input network, voltage/
current measuring range and transformer multiplying power are consistent with
the actual input again before use..
4.6.1 Set display mode, change the display mode from three-phase voltage
(diSP=1) to frequency(diSP=4) , clear electrical energy.
K M K M K M
K M
V A W DI V A W DI V A W DI
V A W DI
MENU
V A Var DO V A Var DO V A Var DO
V A Var DO
V A Hz V A Hz V A Hz
V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
V A Hz V A Hz V A Hz V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
MENU
V A Var DO V A Var DO V A Var DO V A Var DO
V A Hz V A Hz V A Hz V A Hz
MENU
K M K M
V A W DI V A W DI
V A Var DO V A Var DO
V A Hz V A Hz
MENU MENU
-9-
4.6.2 Set siganl input net, change the net from n.3.4(3P4W) to n.3.3(3P3W) ,
set multiplying power of current transformer is 60(CT 300A/5A)
K M K M K M
K M
V A W DI V A W DI V A W DI
V A W DI
MENU
V A Var DO V A Var DO V A Var DO
V A Var DO
V A Hz V A Hz V A Hz
V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
V A Hz V A Hz V A Hz V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
V A Hz V A Hz V A Hz V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
V A Hz V A Hz V A Hz V A Hz
MENU
K M K M K M
- 10 -
4.6.3 Modify the comminucation parameters : set RS485 communication
address " Sn ": 10 , select protocol form " DAtA ": E.8.1
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
MENU
V A Var DO V A Var DO V A Var DO V A Var DO
V A Hz V A Hz V A Hz V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
V A Hz V A Hz V A Hz V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
V A Hz V A Hz V A Hz V A Hz
K M K M K M K M
V A W DI V A W DI V A W DI V A W DI
MENU
V A Var DO V A Var DO V A Var DO V A Var DO
V A Hz V A Hz V A Hz V A Hz
MENU
K M K M
V A W DI V A W DI
V A Var DO V A Var DO
V A Hz V A Hz
MENU MENU
- 11 -
Chapter 5. Installment and wiring
5. 1 Shape and cutout hole dimension(unit : mm)
K M K M
V A W DI V A W DI
V A Var DO V A Var DO
V A Hz V A Hz
MENU MENU
A A
B B
C C
N
Voltage≤600V,input directly Voltage≤600V,input directly
Current≤5A,input directly Current≤5A,input directly
A A
B B
C C
N
Voltage≤600V,input directly Voltage≤600V,input directly
Current > 5A,input via CT Current > 5A,input via CT
A A
B B
C C
N
Voltage > 600V,input via PT Voltage > 600V,input via PT
Current > 5A,input via CT Current > 5A,input via CT
5.3.3 Energy signal output: P+ is the active energy pulse output + port, Q+ is the
reactive energy pulse output + port, P-Q- are the active/reactive electrical pulse
output port. Output mode: open-collector optical coupling output; open-collector
voltage VCC≤48V; current Iz≤50mA. The energy pulse output corresponds with
thesecondary data. When measuring the primary energy, it needs to multiply the
PT multiplying power and CT multiplying power to get the primary data.
5.3.4 RS485 communication connection
The instrument supplies a RS485 communication interface and applies
- 13 -
MODBUS_RTU communication protocol (see the appendix). Up to thirty-two
instrument can be connected in one communication line at one time. Each instrument
should have the only communication address in the circuitry. Communication
connection should use the shielded twisted paired with copper mesh, whose
diameter should be not less than 0.5mm. Communication line should be far away
from the high-voltage cables or other highfield environment and the maximum
transmission distance is 1200 m. The typical network connections are shown in
the following figure and users can choose other suitable connect mode under
specific conditions.
5.3.5 Switching value input(DI input):DI1~DI4 are 1~4 way dry contact input
port , inside of the instrument there is power supply of +5V .
5.3.6 Switching output and ananlog transmitting output: can support four-channel
switching value output and four - channel analog transmitting output .
Chapter 6. Communication protocol
6.1 This series instrument are provided with Rs485 communication interface and
apply MODBUS_RTU communication protocol.
Address Function Data
Start CRC code End
code code sector
Halt time more Halt time more
1byte 1byte Nbyte 2byte than three bytes
than three bytes
6.2 Communication message transmitting process
When communication instructions transmit from master device to slave device,
the slave device with corresponding address code receives communication orders
and reads the massage according to functional code and relational requirements.
After successful CRC verification without error, the corresponding operation will
be conducted and the result (data), including address code, function code, data
after execution and CRC verification code, is returned to the master device. In
case of CRC verification failure, no message would be returned.
6 . 2 . 1 Address code:
Address code is the first byte (8 bits) of each communication message frame,
from 1 to 247. Every slave device must have the only address code and only the
slave device conforming to the address code can respond and return the message.
When the slave device returns the message, all of the return data start with each
- 14 -
address code. The address code sent by master device shows the receiving
address of slave device, while the address code returned by slave device shows
the returning slave address. The responding address code shows where the
message comes from.
6 . 2 . 2 Function code
Function code is the second byte of each communication message frame.
The master device sends and tells that what operation the slave device should
carry out by means of function code. Then the slave device responds. The functional
code returned by slave device is the same as the one sent by master device, which
shows that slave device has responded the master device and carry out the
relational operation. The instrument supports three function codes as following:
- 16 -
Power sign information
47 SING Power sign bit
Data of switch value and electrical quantity
55 DI Switch value input Switch value input part
56 DO Switch value output Switch value output part
57 , 58 UA A-phase voltage
59 , 60 UB B-phase voltage
61 , 62 UC C-phase voltage
63 , 64 UAB AB-line voltage
65 , 66 UBC BC-line voltage
67 , 68 UCA CA-line voltage
69 , 70 IA A-phase current
71 , 72 IB B - phase current
73 , 74 IC C - phase current
75 , 76 PA A - phase active power
77 , 78 PB B - phase active power 2 bytes (4 bytes) floating-point
79 , 80 PC C - phase active power representation data, IEEE-754
data format standard.All data is
81 , 82 PS Total active power
primary data,then by the ratio of
83 , 84 QA A - phase reactive power the value. The unit of voltage V,
The unit of current A, active power
85 , 86 QB B - phase reactive power
unit KW,reactive power unit Kvar,
87 , 88 QC C - phase reactive power apparent power unit KVA, the unit
89 , 90 QS Total reactive power of frequency Hz.
- 17 -
electric energy information
129 , 130 WPP Primary positive active energy
2 bytes (4 bytes) floating-point
131 , 132 WPN Primary opposite active energy
representation data, IEEE-754
133 , 134 WQP Primary positive reactive energy data format standard.All data is
135 , 136 WQN Primary opposite reactive energy primary data,then by the ratio of
the value. The unit of voltage V,
137 , 138 EPP Secondary positive active energy The unit of current A, active power
139 , 140 EPN Secondary opposite active energy unit KW,reactive power unit Kvar,
apparent power unit KVA, the unit
141 , 142 EQP Secondary positive reactive energy
of frequency Hz.
143 , 144 EQN Secondary opposite reactive energy
Exponent part
Mantissa part
- 19 -
K M K M
V A W DI V A W DI
V A Var DO V A Var DO
V A Hz V A Hz
MENU MENU
8.1 Examples
8.1.1Switch value input function:
The switch module has the collecting function for 4 K M
- 21 -
interface closed.If input binary system 10110000,it means channel 1,2,4 switch
value output interface open,channel 3 closed.This function can not be used at
the same time with the another function off-limited alarm output.If using the remote
controlling function,the users need to set the parameter as 0,it means the close
the alarm output function.When the instrument is under the setting for the switch
value output function,the line 2 parameter is 0.The picture shows the channel
1 and 4 is closed;channel 2 and 3 is open.The another function of the switch value
output module is off-limited alarm output.Set the range for the parameters.When
the parameter is off-limited the range,the corresponding switch value output
interface is open,the screen will display 1.When the signal is in the range,the
screen will display 0.The internal DOSI(3 bytes) of the instrument is the switch
value settingregister.Input the parameter via the instrument's connecting interface,
the users can realize the alarm setting.Or the users can set the alarm target and
alarm data directly via the key-pressing on the plate.
Control word
Classification Alarm condition
BYTE2 BYTE1 BYTE0
Switch value output 1 UA>11KV 128+1=129 1100(04H4CH)
Switch value output 2 IA>400A 128+7=135 4000(0FHA0H)
Switch value output 3 PF<0.9 21 900(03H84H)
Switch value output 4 F>51.00Hz 128+26=154 5100(13HECH)
The instrument can offer the function of four-channel analog transmitting output.
Each channel can choose to set any of the 26 parameters,with the instrument's
function for analog transmitting output module, to reach the function of parameter 's
analog transmitting output(0-20mA/4-20mA).The corresponding relation can be
set at random.
9.1 Parameter:output 0-20mA,4-20mA,class:0.5
Overload:120% effective output,the maximum current:24mA,the maximum volt:16V
Load:Rmax=400Ω
9.2 Register:Each channel for the transmitting output parameter will use AOi-3
continuous address space to save.For example:Channel 1 will use address 22,
23,24(BYTE2,BYTE1,BYTE0),these three bytes to save.The lowest address byte
(address 22) save the parameters for the transmitting output's target,such as the
- 24 -
transmitting parameter for Ua 0-20mA is 1;the transmitting output for 4-20mA is
129.The another two bytes(address 23,24)is the parameters for 20mA transmitting
output.The other 3 channels is the same like this.The corresponding address can
have a reference at the address form.
The users can set the AOSI'S controlling word via computer or the instrument's
plate key-pressing,as well as the setting for reaching 4 channels analog transmitting
output.It includes the choice for item which need the transmitting,and the corresponding
parameter for 20mA output.
9 . 3 Application example
For 10KV/100V,400A/5A instrument settings: AO1-UA:0~10KV/4~20mA; AO2-IA:
0~400A/4~20mA;AO3-PS:0~12MW/0~20mA; AO4-QS:0~12MVar/0~20mA;
Note: when the transmission value errors, modify the corresponding set value.
- 25 -
If the instrument ' s parameters are 400V,800A/5A
Programming parameters
Setting Transmission Range Reference
requirements condition value value Electricity
parameters Set value