1. Scope
1.1. The purpose of this document is to list the voltage testers approved for “Test Before
Touch” purposes, and provide guidelines for approving testers not listed in this
document.
2. Background
2.1. In the past, injuries have occurred to personnel due to use of inadequate voltage
testers and improper use of voltage testers. In order to minimize risk to personnel
the following list of approved voltage testers, and tester criteria was developed.
These voltage testers possess extra measures of safety for personnel and
equipment protection.
i
2.2. Testing for de-energization is considered energized electrical work and the
requirements of EWP-30 apply. Only Electrically Instructed or Skilled Persons may
perform energized electrical work.
3. Definitions
3.1. “Test Before Touch” - Detecting the presence and level of voltage for electrical
clearing and troubleshooting. This meter shall only be used on circuitry whose
nominal operating voltage is within the manufacturer’s rating.
3.2. “Bipolar tester” – A tester that makes measurements with two probes connected to
the circuit under test.
3.3. “Unipolar tester”- A tester that makes measurements with a single probe only
Note: As of April, 2006, Fluke T5-1000 should not be purchased for test
before touch applications in Europe based on revised local regulations.
Purchase of Fluke T100 series of meters in Europe is acceptable. Continued
use of existing T5-1000 in Europe is acceptable.
4.2.1. Chance Phasing Tester with dual-range 5 kV and 15 kV tester kit. (AC only –
clearing procedures must address dissipating any DC charge)
5.1. To secure approval for voltage testers that are not listed in this document, any one of
the following may be done:
5.1.2. Written approval to use the tester may be secured from the site Electrical
Discipline Activity Specialist (DAS), based on DAS review of the tester vs. the
criteria listed in section 6 of this document. Site DAS approval can be in the
form of a documented list of acceptable testers for the site.
5.1.3. Where approved in writing by Dow, the employer of non-Dow personnel may
approve, in writing, testers in accordance with the criteria listed in section 6 of
this document. The site DAS shall be consulted as part of the Dow approval.
5.2. Global Electrical Safety and Maintenance Network may also be consulted for
guidance.
6. Guidelines for selection of voltage testers suitable for “Test Before Touch”.
6.2.3. Must be sensitive to at least AC. Meters that lack the ability to accurately
measure DC voltage can be approved for test before touch purposes on AC
circuits where clearing procedures address the dissipation of any DC charges
left on a de-energized circuit.
6.2.5. Bipolar testers must be capable of accurately measuring phase to phase plus
phase to ground.
7.1. This document is not meant to limit the use of equipment utilized in advanced trouble
shooting and other diagnostic purposes. Equipment such as oscilloscopes, storage
scopes, etc. is beyond the scope of this document. Technicians utilizing these types
of equipment are expected to understand their uses and limitations. Voltages must
be confirmed with an approved test-before-touch tester before applying diagnostic
equipment that is not rated for test-before-touch.
8. References
8.1. (None at this time)
i
04-DEC-2007; MOC2007_05602; By: Walt Selle; Supersedes Issue Date 18-APR-
2006; Added paragraph 2.2.
ii
02-DEC-2005, MOC 2005_02980, By: Peter Willhoeft, Supercedes Issue Date 07-
JAN-2004, Para 4.2.0 Deleted sub para 4.2.2 Metrawatt, Type HIT 26 S
iii
18-APR-2006; MOC 2006_03540; By: Jochen Beyer; Supercedes Issue Date 02-
DEC-2005; Revised para 4.1.1 concerning approved ‘test before touch’ meters.
iv
02-DEC-2005, MOC 2005_02980, By: Peter Willhoeft, Supercedes Issue Date 07-
JAN-2004, Para 6.1.4 added IEC 61243-3 required compliance.
v
04-DEC-2007; MOC2007_05602; By: Walt Selle; Supersedes Issue Date 18-APR-
2006; Changed the title of paragraph 7.
vi
04-DEC-2007; MOC2007_05602; By: Walt Selle; Supersedes Issue Date 18-APR-
2006; Added Note to paragraph 7.2.