Transient and Steady State Response Analysis: Module - 3
Transient and Steady State Response Analysis: Module - 3
MODULE - 3
LESSON STRUCTURE:
3.1. Introduction
3.2. Time Response
3.3. Steady State Response
3.4. Routh’s-Hurwitz Criterion
3.5. Definition of root loci
3.6. Analysis using root locus plots
3.7. General rules for constructing root loci
OBJECTIVES:
To analyse stability in complex domain and frequency domain systems.
To educate static and transient behavior of a system.
To demonstrate stability of the various control systems by applying Routh’s stability criterion.
To study stability by using Root locus plots.
3.1. Introduction:
Time is used as an independent variable in most of the control systems. It is important to
analyse the response given by the system for the applied excitation, which is function of time.
Analysis of response means to see the variation of output with respect to time. The output behavior
with respect to time should be within these specified limits to have satisfactory performance of the
systems. The stability analysis lies in the time response analysis that is when the system is stable
output is finite
The system stability, system accuracy and complete evaluation is based on the time response
analysis on corresponding results.
Classification:
The time response of a control system is divided into two parts.
19
Control Engineering -15ME73 2018
. . . c(t)=ct(t) +cSS(t)
Where c(t)= Time Response
Total Response=Zero State Response +Zero Input Response.
The time domain analysis essentially involves the evaluation of the transient and
Steady state response of the control system.
For the analysis point of view, the signals, which are most commonly used as
reference inputs, are defined as standard test inputs.
The performance of a system can be evaluated with respect to these test signals.
Based on the information obtained the design of control system is carried out. The
commonly used test signals are
1. Step Input signals.
2. Ramp Input Signals.
3. Parabolic Input Signals.
4. Impulse input signal.
The step is a signal who‘s value changes from 1 value (usually 0) to another level A in Zero
time.
In the Laplace Transform form R(s) = A / S
Mathematically r(t) = u(t)
= 1 for t > 0
= 0 for t < 0
2. Ramp Input Signal (Velocity Functions):
It is constant rate of change in input that is gradual application of input as shown in fig (2 b).
r(t)
20
Control Engineering -15ME73 2018
The ramp is a signal, which starts at a value of zero and increases linearly with time.
Mathematically r (t) = At for t ≥ 0
= 0 for t≤ 0.
In LT form R(S) = A
S2
If A=1, it is called Unit Ramp Input
It is the input applied instantaneously (for short duration of time ) of very high amplitude as
shown in fig 2(d)
Eg: Sudden shocks i e, HV due lightening or short circuit.
It is the pulse whose magnitude is infinite while its width tends to zero.
21
Control Engineering -15ME73 2018
= 0 for t ≠ 0
In LT form R(S) = 1 if A = 1
i. If all the roots of the characteristic equation have –ve real parts the system is
STABLE.
ii. If any root of the characteristic equation has a +ve real part or if there is a repeated root on
the j -axis, the system is unstable.
iii. If condition (i) is satisfied except for the presence of one or more non repeated roots on the j -
axis the system is limitedly STABLE
In this instance the impulse response does not decay to zero although it is bounded.
Additionally certain inputs will produce outputs. Therefore marginally stable systems are
UNSTABLE.
The Routh Stability criterion is a method for determining system stability that can be applied
to an nth order characteristic equation of the form
sn + an-1 sn-1 + an-2 sn-2 + an-3 sn-3 +…………. a1 s1 + a0 = 0
The criterion is applied through the use of a Routh Array (Routh table) Defined as follows:
22
Control Engineering -15ME73 2018
Example : find the stability of the system using Routh’s criteria. For the equation
3S4+10S3+5S2+5S+2=0
Here two roots are +ve (2 changes of sign) and hence the system is unstable.
23
Control Engineering -15ME73 2018
A designer can determine whether his design for a control system meets the specifications if
he knows the desired time response of the controlled variable. By deriving the differential
equations for the control system and solving them, an accurate solution of the system's
performance can be obtained, but this approach is not feasible for other than simple systems.
It is not easy to determine from this solution just what parameters in the system should be
changed to improve the response. A designer wishes to be able to predict the performance by
an analysis that does not require the actual solution of the differential equations.
The first thing that a designer wants to know about a given system is whether or not it is
stable. This can be determined by examining the roots obtained from the characteristic
equation
(3.1)
of the closed loop. The work involved in determining the roots of this equation can be
avoided by applying the Hurwitz or Routh criterion. Determining in this way whether the
system is stable or unstable does not satisfy the designer, because it does not indicate the
degree of stability of the system, i.e., the amount of overshoot and the settling time of the
controlled variable for a step input. Not only must the system be stable, but the overshoot
must be maintained within prescribed bounds and transients must die out in a sufficiently
short time.
The root-locus method described in this section not only indicates whether a system is stable
or unstable but, for a stable system, also shows the degree of stability. The root locus is a plot
of the roots of the characteristic equation of the closed loop as a function of the gain. This
graphical approach yields a clear indication of the effect of gain adjustment with relatively
small effort.
With this method one determines the closed-loop poles in the plane - these are the roots of
Eq.(5.1) - by using the known distribution of the poles and zeros of the open-loop transfer
function . If for instance a parameter is varied, the roots of the characteristic equation
will move on certain curves in the plane as shown by the example in Figure 3.1. On these
curves lie all
24
Control Engineering -15ME73 2018
An open-loop transfer function with poles at the origin of the plane is often described by
(3.2)
where is the gain of the open loop. In order to represent this transfer function in terms of
the open-loop poles and zeros it is rewritten as
(3.3)
or
(3.4)
25
Control Engineering -15ME73 2018
with and . The relationship between the factor and the open-loop gain
is
(3.5)
(3.7)
All complex numbers , which fulfil this condition for , represent the
root locus.
From the above it can be concluded that the magnitude of must always be unity and its
phase angle must be an odd multiple of . Consequently, the following two conditions are
formalised for the root locus for all positive values of from zero to infinity:
a)
Magnitude condition:
(3.8)
b)
Angle condition
(3.9)
for
(3.10)
for
26
Control Engineering -15ME73 2018
Apparently the angle condition is independent of . All points of the plane that fulfil the
angle condition are the loci of the poles of the closed loop by varying . The calibration of
the curves by the values of is obtained by the magnitude condition according to Eq. 8(3.8).
Based upon this interpretation of the conditions the root locus can constructed in a
graphical/numerical way.
Once the open-loop transfer function has been determined and put into the proper form,
the poles and zeros of this function are plotted in the plane.
The plot of the locus of the closed loop poles as a function of the open loop gain K,
when K is varied from 0 to +00.
When system gain K is varied from 0 to +oo, the locus is called direct root locus.
When system gain K is varied from -oo to 0, the locus is called as inverse root locus.
The root locus is always symmetrical about the real axis i.e. x-axis.
The number of separate branches of the root locus equals either the number of open
loop poles are number of open-loop zeros whichever is greater.
A section of root locus lies on the real axis if the total number of open-loop poles and
zeros to the right of the section is odd.
If the root locus intersects the imaginary axis then the point of intersection are
conjugate. From the open loop complex pole the root locus departs making an angle
with the horizontal line.
The root locus starts from open-loop poles.
The root locus terminates either on open loop zero or infinity.
The number of branches of roots locus are:
N if P>Z
and M if P<Z
where N —> No. of poles ‗P‘
M —> No. of zeros ‗Z‘
27
Control Engineering -15ME73 2018
Based on the pole and zero distributions of an open-loop system the stability of the closed-
loop system can be discussed as a function of one scalar parameter. The root-locus method
shown in this module is a technique that can be used as a tool to design control systems. The
basic ideas and its relevancy to control system design are introduced and illustrated. Ten
general rules for constructing root loci for positive and negative gain are shortly presented
such that they can be easily applied. This is demonstrated by some discussed examples, by a
table with sixteen examples and by a comprehensive design of a closed-loop system of higher
order.
28
Control Engineering -15ME73 2018
Example Problems:
As and it can be seen that for the poles of the closed loop
transfer function are identical with those of the open-loop transfer function . For other
: Both roots and are real and lie on the real axis in the range of
and ;
b)
: The roots and are conjugate complex with the real part ,
24
Control Engineering -15ME73 2018
must be valid. The complex numbers and have the angles and and the
one obtains the value on the root locus. E.g. for the gain of the open loop is
Table 5.1 shows further examples of some 1st- and 2nd-order systems.
Table 5.1: Root loci of 1st- and 2nd-order systems
25
Control Engineering -15ME73 2018
To facilitate the application of the root-locus method for systems of higher order than 2nd,
rules can be established. These rules are based upon the interpretation of the angle condition
and the analysis of the characteristic equation. The rules presented aid in obtaining the root
locus by expediting the manual plotting of the locus. But for automatic plotting using a
computer these rules provide checkpoints to ensure that the solution is correct.
Though the angle and magnitude conditions can also be applied to systems having dead time,
in the following we restrict to the case of the open-loop rational transfer functions according
to Eq. (3.3)
(3.11)
or
(3.12)
As this transfer function can be written in terms of poles and zeros and ( ;
or
(3.13)
(3.14)
(3.15)
for
26
Control Engineering -15ME73 2018
follows. Here and denote the angles of the complex values and ,
respectively. All angles are considered positive, measured in the counterclockwise sense. If
for each point the sum of these angles in the plane is calculated, just those particular points
that fulfil the condition in Eq. (3.15) are points on the root locus. This principle of
constructing a root-locus curve - as shown in Figure 3.3 - is mostly used for automatic root-
locus plotting.
In the following the most important rules for the construction of root loci for are listed:
Rule 1 Symmetry
As all roots are either real or complex conjugate pairs so that the root locus is
symmetrical to the real axis.
Rule 2 Number of branches
The number of branches of the root locus is equal to the number of poles of the
open-loop transfer function.
Rule 3 Locus start and end points
The locus starting points ( ) are at the open-loop poles and the locus ending
(3.16)
27
Control Engineering -15ME73 2018
(3.17)
(3.18)
(3.19)
(3.20)
28
Control Engineering -15ME73 2018
(3.21)
(3.22)
The rules shown above are for positive values of . According to the angle condition of
Eq. (5.10) for negative values of some rules have to be modified. In the following these
rules are numbered as above but labelled by a *.
(3.23)
29
Control Engineering -15ME73 2018
(3.24)
(3.25)
The root-locus method can also be applied for other cases than varying . This is possible as
long as can be rewritten such that the angle condition according to Eq. (3.15) and the
rules given above can be applied. This will be demonstrated in the following two examples.
the root locus for varying the parameter is required. The characteristic equation is therefore
rewritten as
30
Control Engineering -15ME73 2018
it is required to find the effect of the parameter on the position of the closed-loop poles. The
equation is rewritten into the desired form
Using the rules 1 to 10 one can easily predict the geometrical form of the root locus based on
the distribution of the open-loop poles and zeros. Table 3.2 shows some typical distributions
of open-loop poles and zeros and their root loci.
Table 3.2: Typical distributions of open-loop poles and zeros and the root loci
31
Control Engineering -15ME73 2018
For the qualitative assessment of the root locus one can use a physical analogy. If all open-
loop poles are substituted by a negative electrical charge and all zeros by a commensurate
positive one and if a massless negative charged particle is put onto a point of the root locus, a
movement is observed. The path that the particle takes because of the interplay between the
repulsion of the poles and the attraction of the zeros lies just on the root locus. Comparing the
root locus examples 3 and 9 of Table 3.2 the 'repulsive' effect of the additional pole can be
clearly seen.
The systematic application of the rules from section 3.2 for the construction of a root locus is
shown in the following non-trivial example for the open-loop transfer function
(3.26)
The degree of the numerator polynomial is . This means that the transfer function has
one zero ( ). The degree of the denominator polynomial is and we have the
32
Control Engineering -15ME73 2018
those points of the root locus where and the zeros where . We have
branches that go to infinity and the asymptotes of these three branches are lines
which intercept the real axis according to rule 6. From Eq. (3.17) the crossing is at
(3.27)
(3.28)
i.e.
The asymptotes are shown in Figure 3.5 as blue lines. Using Rule 4 it can be checked which
points on the real axis are points on the root locus. The points with and
belong to the root locus, because to the right of them the number of poles and zeros is
odd. According to rule 7 breakaway and break-in points can only occur pairwise on the real
axis to the left of -2. These points are real solutions of the Eq. (3.19). Here we have
(3.29)
or
The angle of departure of the root locus from the complex pole at can be
determined from Figure 3.6 according to Eq. (3.20):
(3.30)
33
Control Engineering -15ME73 2018
With this specifications the root locus can be sketched. Using rule 9 the value of can be
determined for some selected points. The value at the intersection with the imaginary axis is
OUTCOMES:
At the end of the module, the students are able to:
Obtain the time response and steady-state error of the system.
Knowledge about improvement of static and transient behaviour of a system.
Determine stability of the various control systems by applying Routh’s stability
criterion.
Construct root loci from open loop transfer functions of control systems and Analyze
the behaviour of roots with system gain.
Assess the stability of closed loop systems by means of the root location in s-plane and
their effects on system performance.
SELF-TEST QUESTIONS:
1. Obtain an expression for time response of the first order system subject to step input.
2. Define
1) Time response.
2) Transient response.
3) Steady state response.
4) Steady state error.
3. Determine the stability of the system whose characteristic equation is given by
S4+6S3+23S2+40S+50=0, Using Routh's criterion.
4. Sketch the root locus for G(S)H(S)= K show all details on it.
S(S+2)(S+4)
5. Sketch the root locus for G(S)H(S)= 10K show all details on it.
S(S+2)(S+6)
34
Control Engineering -15ME73 2018
6. Sketch the root locus for G(S)H(S)= K(S+1) show all details on it.
S(S+2)(S+4)
FURTHER READING:
1. Control engineering, Swarnakiran S, Sunstar publisher, 2018.
2. Feedback Control System, Schaum’s series. 2001.
35