Temperature Transducers With Honeywell Logo Models HTE500/HTE511/HTE512
Temperature Transducers With Honeywell Logo Models HTE500/HTE511/HTE512
HTE500-AD12AC1A2
TEMPERATURE TRANSDUCERS
With Honeywell Logo
Models HTE500/HTE511/HTE512
Precision temperature
control/sensing
FEATURES:
• Precision RTD
• High accuracy transmitter for any application
• Several mounting configurations, i.e.: room, duct, duct averaging, immersion, etc.
• Room Sensor options – Setpoint Adjustment, Override, etc.
Peace of mind
through reliable
temperature monitoring
HTE500/511/512 – TEMPERATURE TRANSDUCER CONFIGURATIONS
FEATURES AND SPECIFICATIONS:
The HTE500/511/512 is a precision current loop temperature transmitter. It utilizes the platinum RTD and is available in various configurations. The transmitter
provides a high accuracy signal with excellent long term stability, low hysteresis and fast response while being virtually immune to power supply noise and input
voltage fluctuations. All models operate on a wide range of AC or DC power supplies. The HTE511/512 incorporates a LCD which is factory configured to display
readings in either °C or °F.
4-20mA Loop Power Supply……….... 15-35 Vdc or 22 to 32 Vac (No LCD) Output Signal ……………………….. 4-20mA current loop, 0-5 Vdc
22 to 35 Vdc or 22 to 32 Vac or 0-10 Vdc (factory configured)
(with 250 ohm load) withLCD Transmitter Accuracy ….. …………. ±0.1% of span, including
Minimum Loop Current ……………… 2 mA nominal, (occurs with linearity
shorted sensor) Temperature Calibration ..……...…… Three point with precision
Maximum Loop Current ……………... 22.5 mA nominal, (occurs with calibration standards
open sensor) Display Units …………………………. ºC or ºF (Factory set)
Maximum Loop Load ………………… > 600 ohms no LCD or > 325 ohms Display Range ……………………….. 0 – 100ºC typical range for
with LCD transmitter (other ranges
0-5 Vdc Power Supply ………………. 10 to 35 Vdc or 10 to 32 Vac available)
0-10 Vdc Power Supply …………….. 15 to 35 Vdc or 15 to 32 Vac Display Resolution …………………… 0.1ºC or 0.1ºF for display of
Voltage Mode Maximum Current ….. 15 mA nominal 00.0 to 99.9
Voltage Mode Maximum Output …… Limited to < 5.5 Vdc for 0-5 Display Accuracy …………………….. ±0.2ºC or ±0.2ºF over full range
model and < 10.5 Vdc for 0-10 with respect to the output signal
model Display Update Rate ……………..… 3 times per second
Input Voltage Effect ..………..……… Negligible over specified Display Size ……………………..….. 24 mm W x 11 mm H
operating range (0.95“ x 0.45“) three digit
RFI Rejection …………………….….. Good RFI rejection of normal PCB Operating Temperature …….... 0 to 70°C (32 to 158°F)
frequencies with standard PCB Operating Humidity …………… 0 to 95% RH (non-condensing)
installation Wiring Connections ……………..….. Two or three wires,screw
Protection Circuitry …………………. Reverse voltage protected and terminal block,(14 to 22 AWG)
output limited Manufacturing Process …………...… ISO 9001 Certified
Internal Adjustments ………...….….. Clearly marked ZERO and
SPAN pots
AE) Executive – Features include a universal AD) Designer – Features include a two-piece AS) Surface - A stainless steel plate which
back plate to mount to any wall box or may be enclosure that mounts directly to a wall box or can be mounted to a wall box used where
flush mounted. Available with various options, on any wall. tamper-proof or protection is required.
including setpoint adjustments, push button Available with various options, including push
overrides, LCD’s, etc. button overrides.
B) Duct Sensor – For single point monitoring. C) Immersion Sensor – Comes in two configura- E) & ES) Strap-on Sensor – Comes in a stain-
It is available with various probe lengths and tions. It has either spring loaded or non-spring less steel probe option or with 10” clamp assem-
enclosures to fit any application. loaded probes and has a ½” NPT fitting to be bly and is used in remote applications where an
mounted into a thermowell. It is available in various immersion sensor can not be installed.
lengths and enclosures styles.
D) Duct Average Sensor – Incorporates nu- FD) Flex-Duct Sensor – Is made of flexible plenum F) OSA Sensor – Comes in a hinged ABS
merous sensors inside a copper tube. It acts rated cable which incorporates numerous sensors enclosure. It incorporates a ½” NPT knockout
as a single sensor, averaging any tempera- along the assembly. It acts as a single sensor av- for connection to conduit and a sun/wind shield
ture change across the sensors eraging any temperature change across the sen- to protect the sensor.
sors.
NOTE:
Standard probe assemblies are rated at –20°C – 105°C (-4°F - 221°F).
For higher or lower temperature applications, please contact Greystone.
HTE500 – SPACE TEMPERATURE TRANSDUCERS:
PRODUCT ORDERING INFORMATION
MODEL Product Description
CODE Enclosure
AD Designer
AE Executive
AS S/S plate
AP 20-30K linear slide pot for setpoint control (call for other values)
BS Exposed push button momentary switch (NO)
AM Alcohol thermometer °C/°F
BC Bimetal thermometer °C
BF Bimetal thermometer °F
3-digit LCD temperature indicator °C
AC
3-digit LCD temperature indicator °F
AF
1A Current 4 – 20mA
1D Voltage 0 – 5 VDC
1E Voltage 0 – 10 VDC
HTE500 AE 12 AC 1A 2
NOTE:
Due to the many possible configurations, special part numbers may be required, please contact Greystone for more information.
ENCLOSURE DIMENSIONS
118.9 mm
(4.68”)
115 mm 114.3 mm
(4.53”) (4.5”)
69.9 mm
(2.75”)
70.55 mm 69.9 mm
(2.76”) (2.75”)
HTE500 – PROBE TEMPERATURE TRANSDUCERS
PRODUCT ORDERING INFORMATION
MODEL Product Description
HTE500 Sensor assembly c/w transmitter
CODE Style
B Duct mount
C Immersion
D Duct average (copper)
DC Duct average continuous (copper) Available with type 12, 1000 ohm RTD only
E Strap-on – 50 mm (2”) probe assembly
ES Strap-on – Assembly clamps around pipe with copper plate c/w 254 mm (10”) stainless clamp
F O.S.A. (ABS Hinged enclosure)
FD Duct average (flexible plenum rated cable)
FL Flying lead
G Glass
H Stack
CODE Probe Length CODE Copper Avg. CODE Flex Duct Only
(D & DC) (FD)
A 50 mm (2”) G 1800 mm (6’)* A 1800 mm (6’)
B 100 mm (4”) H 3600 mm (12’) B 3600 mm (12’)
C 150 mm (6”) I 6100 mm (20’)* C 6100 mm (20’)
D 200 mm (8”) J 7300 mm (24’) D 7300 mm (24’)
E 300 mm (12”) * - not available
F 450 mm (18”) in DC
HTE500 B - 12 E 2 - 1A 2
EXAMPLE: Duct temperature transmitter, c/w 1000Ω RTD , 12” S/S Probe, ABS Enclosure, 4–
20mA output with a 0°C – 50°C (32°F – 122°F) range.