C8 Generator and Generator-Transformer Protection
C8 Generator and Generator-Transformer Protection
Generator and
Generator-Transformer Protection
Network Protection & Automation Guide
Network Protection & Automation Guide
Chapter
Generator and
C8
Generator-Transformer Protection
1. Introduction 315
C8 1. Introduction
The core of an electric power system is the generation. With governed by economic considerations, taking into account
the exception of emerging fuel cell and solar-cell technology the value of the machine, and the value of its output to the
for power systems, the conversion of the fundamental energy plant owner.
into its electrical equivalent normally requires a ‘prime mover’
The following problems require consideration when applying
to develop mechanical power as an intermediate stage.
the protection system:
The nature of this machine depends upon the source of
a. stator electrical faults
energy and in turn this has some bearing on the design of
the generator. Generators based on steam, gas, water or wind b. overvoltage
turbines, and reciprocating combustion engines are all in use.
c. low power / reverse power
Electrical ratings extend from a few hundred kVA (or even
less) for reciprocating engine and renewable energy sets, up d. overload / unbalanced loading
to steam turbine sets exceeding 1200MVA. e. overfrequency / underfrequency
Small and medium sized sets may be directly connected to f. inadvertent energisation
a power distribution system. A larger set may be associated
with an individual transformer, through which it is coupled to g. rotor electrical faults
the EHV primary transmission system. h. overfluxing
Switchgear may or may not be provided between the generator i. loss of excitation
and transformer. In some cases, operational and economic
advantages can be attained by providing a generator circuit j. loss of synchronism
breaker in addition to a high voltage circuit breaker, but special
demands will be placed on the generator circuit breaker for
interruption of generator fault current waveforms that do not
have an early zero crossing. Generator Main transformer
A unit transformer may be tapped off the interconnection
between generator and transformer for the supply of power
to auxiliary plant, as shown in Figure C8.1. The unit transformer
could be of the order of 10% of the unit rating for a large
HV busbars
fossil-fuelled steam set with additional flue-gas desulphurisation
plant, but it may only be of the order of 1% of unit rating for Unit transformer
a hydro set.
A modern generating unit is a complex system comprising
the generator stator winding, associated transformer and unit Auxiliary
transformer (if present), the rotor with its field winding and supplies switchboard
excitation system, and the prime mover with its associated
auxiliaries. Faults of many kinds can occur within this system
for which diverse forms of electrical and mechanical protection
Figure C8.1:
are required. The amount of protection applied will be Generator-transformer unit
2. Generator earthing C8
Failure of the stator windings or connection insulation can saturation effect of the generator CTs, but the bias current
result in severe damage to the windings and stator core. The will increase the relay setting, such that the differential spill
extent of the damage will depend on the magnitude and current is insufficient to operate the relay.
duration of the fault current. To respond quickly to a phase
In normal conditions, there is very small differential current
fault, sensitive and high-speed differential protection is
caused by the unbalance current between two CTs. The
normally applied to generators rated in excess of 1MVA.
threshold of the differential current Is1 shall avoid the mal-
If CTs are connected as shown in Figure C8.3, it can be seen operation under this normal unbalance current. The threshold
that current flowing through the zone of protection will cause setting Is1 can be set as low as 5% of rated generator current
current to circulate around the secondary wiring. If the CTs to provide protection for as much of the winding as possible.
are of the same ratio and have identical magnetising The bias slope break-point threshold setting Is2 would typically
characteristics they will produce identical secondary currents be set to a value (such as 120%) above generator rated
and so zero current will flow through the relay. If a fault exists current, to achieve external fault stability in the event of
within the zone of protection there will be a difference between transient asymmetric CT saturation. Bias slope setting K1
the outputs from these two CTs. This difference flowing through would typically be set at 0 to ensure high sensitivity for internal
the relay causes it to operate. faults while K2 would typically be set at 150% to provide
stability for external faults.
Stator
A
B
C
Figure C8.3:
Stator differential protection
Operate
Heavy through current, arising from an external fault condition
can cause one CT to saturate more than the other, resulting
in a difference between the secondary current produced by
Restrain
each CT. It is essential to stabilise the protection for these
conditions. Two methods are commonly used. One is biasing
technique, where the relay setting is raised as the through
current increases. Another is a high impedance technique,
where the relay impedance is such that under maximum (b) Biased differential operating characteristic
through fault conditions, the current in the differential element
is insufficient for the relay to operate.
3.1 Biased differential protection Figure C8.4:
Typical generator biased differential protection
The relay connections for this form of protection are shown
in Figure C8.4(a) and a typical bias characteristic is shown
in Figure C8.4(b). The differential current is the vector sum 3.2 High impedance differential protection
of the terminal currents I1 and I2. The bias current is half of
The principle of the high-impedance protection application
the scalar sum of the terminal currents. Normally a dual slope
is illustrated in Figure C8.5, together with a summary of the
percentage bias characteristic is implemented. The lower
calculations required to determine the value of external
slope provides sensitivity for internal faults, whereas the higher
stabilising resistance.
slope provides stability under through-fault conditions, during
which there may be transient differential currents due to the
Ie = CT magnetising current at Vs
Healthy CT Saturated CT Is1 is typically set to 5% of generator rated secondary current.
Protected zone
It can be seen from the above that the calculations for the
application of high impedance differential protection are more
complex than for biased differential protection. However, the
protection scheme is actually quite simple and it offers a high
Rst level of stability for through-faults and external switching
events.
With the advent of multi-function numerical relays and with a
Voltage across relay circuit
desire to dispense with external components, high impedance
differential protection is not as popular as biased differential
Vs = KI f (RCT + 2RL) - where K = 1.5
protection in modern relaying practice.
Stabilising resistor, RST, limits spill current to I s (relay setting)
Vs
RST = -R
Is R
A common connection arrangement for large generators is Since a power transformer is included within the zone of
to operate the generator and associated step-up transformer protection, biased transformer differential protection, with
as a unit without any intervening circuit breaker. The unit magnetising inrush restraint should be applied, as discussed
transformer supplying the generator auxiliaries is tapped off in Chapter [C7: Transformer and Transformer-Feeder Protection,
the connection between generator and step-up transformer. Section 8.5]. Transient overfluxing of the generator transformer
Differential protection can be arranged as follows. may arise due to overvoltage following generator load rejection.
In some applications, this may threaten the stability of the
4.1 Generator/step-up transformer differential
differential protection. In such cases, consideration should
protection
be given to applying protection with transient overfluxing
The generator stator and step-up transformer can be protected restraint/blocking (e.g. based on a 5th harmonic differential
by a single zone of overall differential protection (Figure C8.7). current threshold). Protection against sustained overfluxing
This will be in addition to differential protection applied to the is covered in Section 14.
generator only.
4.2 Unit transformer differential protection
The current transformers should be located in the generator
The current taken by the unit transformer must be allowed by
neutral connections and in the transformer HV connections.
arranging the generator differential protection as a three-
Alternatively, CTs within the HV switchyard may be employed
ended scheme as shown in Figure C8.1. Unit transformer
if the distance is not technically prohibitive. Even where there
current transformers are usually applied to balance the
is a generator circuit breaker, overall differential protection
generator differential protection and prevent the unit
can still be provided if desired.
transformer through current being seen as differential current.
An exception might be where the unit transformer rating is
extremely low in relation to the generator rating, e.g. for some
Main hydro applications. The location of the third set of current
Generator transformer
transformers is normally on the primary side of the unit
transformer. One advantage is that unit transformer faults
Protected zone
would be within the zone of protection of the generator.
HV However, the sensitivity of the generator protection to unit
busbars
transformer phase faults would be considered inadequate,
due to the relatively low rating of the transformer in relation
to that of the generator. Thus, the unit transformer should have
its own differential protection scheme. Protection for the unit
transformer is covered in Chapter [C7: Transformer and
Transformer-Feeder Protection], including methods for
stabilising the protection against magnetising inrush conditions.
Figure C8.7:
Overall generator-transformer differential protection
5. Inter-turn protection
5.1 Inter-turn protection bars on each slot of the stator core so it is possible that two
stator bars of the same phase or even the same branch are
For the large generator, there are usually several parallel-
on the same slot of stator core. These two stator bars on the
connected branches of the stator winding for each phase. The
same slot are fully insulated under the normal conditions.
parallel-connected branches are good for the heat dissipation
However due to the complicated structure of the stator winding
and reduce the internal electromagnetic force. On large steam
and the stress damage during the operation, it is possible that
generators, the stator winding usually has two parallel-connected
inter-turn faults happen between two stator bars on the same
branches on each phase. The stator winding of a large hydro-
slot as shown in Figure C8.8. Furthermore, if the stator bar has
generator can have 4 branches, 6 branches, or more on each
multi turns, it has small insulation between each turn. A fault
phase.
between turns in a multi turn bar can be catastrophic. Inter-turn
The stator windings are normally formed into double-layer faults can happen between the branches of the same phase
structure except in very small generators. There are two stator or within the coils of the same branch, as shown in Figure C8.9.
5. Inter-turn protection C8
B2 X2
A B C
C2
Z1 26
27 28 29 30
24
25 C 31
32 U1 U5 V1 V5 W1 W5
(32) (33) 33
23 (31) 14 15
22 13 16 (34)
Y 34
Y2 F1 F2
(30) 12 17 (35) 35
21
A2 20
X (29) 11 18 (36) 36 U2 U6 V2 V6 W2 W6
19 (28) 10 1 (19) 1
18 (27) 9 2 (20)
A 2
A1
17 (26) 8 3 (21) 3
Y1 16 B (25) 7
6
4
5 (22)
4 Double Y connection
15 (24) (23) 5
14
13 Z 7
6
12
11 10 9 8 Z2
Figure C8.9
C1 Inter-turn faults indication
X1 B1
Inter-turn fault
Figure C8.8:
a1
Inter-turn fault in double-layer winding
i a1
The severity of the inter-turn fault is related with the turns in
the short circuit. Under the inter-turn fault, there are short i’ d id
circuit rings and additional circulation currents within the
winding, which could burn the winding and even stator core,
as shown in Figure C8.10. However the variations of the
currents on the generator terminal or the generator neutral
are slight, especially when the inter-turn fault is on the same
branch and involves only limited turns. The conventional Figure C8.10:
current differential protection compares the currents incoming Illustration of inter-turn fault on one branch
and outgoing, it cannot detect any inter-turn faults regardless
of the number of turns involved.
schemes, the parallel-connected branches in each phase of
For the large hydro-generator with several parallel-connected
the stator winding are split into two groups, as shown in Figure
branches, normally the line terminals of the parallel-connected
C8.11. If the numbers of the parallel-connected branches
branches are available on the generator neutral, so it can
are not the same in these two groups, a scale conversion is
apply the split-phase transverse current differential protection,
necessary before the calculation of the differential current.
or incomplete longitudinal differential protection or zero
The ratio of the CT should be selected carefully to ensure the
sequence current differential protection. These current based
unbalanced current is at the minimum when under normal
protections, described in later sections, can detect all the
conditions.
stator winding internal faults.
Except for the different CT connections, the implementation
For the large steam machine, normally there are only three
of transverse biased current differential protection is the same
line terminals on the generator neutral. Without enough line
as conventional biased current differential protection (refer
terminals, it is impossible to install the current based
to section 3). It can provide both better sensitivity and better
protections in the same way as for a hydro-generator. However,
stability but it requires one specific relay with two CT inputs,
it can apply the zero sequence overvoltage protection to
which is used only for inter-turn protection. An additional relay
detect the inter-turn faults and also internal phase-phase
is necessary for other protection purposes.
faults. This is described later in this section.
The philosophy of the setting calculation for transverse biased
5.2 Split phase transverse current differential protection
current differential protection is the same as conventional
In split phase transverse current differential protection biased current differential protection. The threshold of the
C8 5. Inter-turn protection
Inter-turn
fault
87G
Figure C8.12:
Incomplete longitudinal current differential protection
5. Inter-turn protection C8
51N
Figure C8.13:
Transverse zero-sequence current differential protection
C8 5. Inter-turn protection
of the NPS current is looking away from the machine, the inter-
turn protection can issue a trip signal. The directional NPS 15
overcurrent element shall be based on the CT at the generator
terminal side. A short time delay is usually used to ensure the
U/V
correct block from both directional NPS overcurrent and VTS. 0
The inter-turn protection by zero sequence overvoltage
protection avoids the maloperation due to the maximum
unbalanced voltage under normal conditions. Normally the -15
maximum unbalanced voltage can be measured during the 40 80 120
generator field test before normal operation. The default t/ms
setting is 2% of the generator rated voltage. A typical time
setting would be 0.1 s - 0.2 s. A long time delay increases
Figure C8.15: Zero sequence voltage across the generator
the risk of damage to the stator core. under external transformer HV earthfault
5.6 Summary
This section introduces four inter-turn protection solutions. Normally for the large hydro-generator inter-turn protection,
The split phase transverse current differential protection has two protection solutions are needed. Often, one solution is
high sensitivity and stability but more CTs and addition split phase transverse current differential protection and
protection relay are necessary. Transverse zero sequence another is transverse zero sequence current differential
current differential protection also has good sensitivity and protection. Longitudinal zero sequence overvoltage protection
application scheme is more simple. Incomplete longitudinal is normally for the inter-turn faults on a large steam generator.
current differential protection has a wider protection range It has high sensitivity but a short time delay is necessary for
including the generator terminal lines, but it may not detect good stability with direction NPS overcurrent blocking and
the inter-turn faults only on one branch and the current flowing VTS blocking.
in the faulted branch is not collected in this solution.
6. Overcurrent protection
Overcurrent protection of generators may take two forms. Plain energise the overcurrent protection, to allow a response to winding
overcurrent protection may be used as the principle form of fault conditions. Relay characteristics should be selected to take
protection for small generators, and back-up protection for larger into account the fault current decrement behaviour of the generator,
ones where differential protection is used as the primary method with allowance for the performance of the excitation system and
of generator stator winding protection. Voltage dependent its field-forcing capability. Without the provision of fault current
overcurrent protection may be applied where differential protection compounding from generator CTs, an excitation system that is
is not justified on larger generators, or where problems are met in powered from an excitation transformer at the generator terminals
applying plain overcurrent protection. will exhibit a pronounced fault current decrement for a terminal
fault. With failure to consider this effect, the potential exists for the
6.1 Plain overcurrent protection
initial high fault current to decay to a value below the overcurrent
It is usual to apply time-delayed plain overcurrent protection to protection pick-up setting before a relay element can operate,
generators. For generators rated less than 1 MVA, this will form unless a low current setting and/or time setting is applied. The
the principal stator winding protection for phase faults. For larger protection would then fail to trip the generator. The settings chosen
generators, overcurrent protection can be applied as remote must be the best compromise between assured operation in the
back-up protection, to disconnect the unit from any uncleared foregoing circumstances and discrimination with the system
external fault. Where there is only one set of differential main protection and passage of normal load current, but this can be
protection, for a smaller generator, the overcurrent protection will impossible with plain overcurrent protection.
also provide local back-up protection for the protected plant, in
In the more usual case of a generator that operates in parallel with
the event that the main protection fails to operate. The general
others and which forms part of an extensive interconnected system,
principles of setting overcurrent relays are given in Chapter [C1:
back-up phase fault protection for a generator and its transformer
Overcurrent Protection for Phase and Earthfaults].
will be provided by HV overcurrent protection. This will respond
In the case of a single generator feeding an isolated system, to the higher-level backfeed from the power system to a unit fault.
current transformers at the neutral end of the machine should Other generators in parallel would supply this current and, being
6. Overcurrent protection C8
The most probable mode of insulation failure is phase to earth. characteristic or a wattmetric technique (Chapter [C1:
An earthfault involving the stator core results in damage to Overcurrent Protection for Phase and Earthfaults, Section 19])
the iron at the point of fault and welds laminations together. can also be used.
The damaged area can sometimes be repaired, but if severe
For direct-connected generators operating in parallel,
damage has occurred, a partial core rebuild will be necessary.
directional sensitive earthfault protection may be necessary.
Earthfault protection must be applied where impedance
This is to ensure that a faulted generator will be tripped before
earthing is employed that limits the earthfault current to less
there is any possibility of the neutral overcurrent protection
than the pick-up threshold of the overcurrent and/or differential
tripping a parallel healthy generator. When being driven by
protection for a fault located down to the bottom 5% of the
residually-connected phase CTs, the protection must be
stator winding from the star-point. The type of protection
stabilised against incorrect tripping with transient spill current
required will depend on the method of earthing and connection
in the event of asymmetric CT saturation when phase fault or
of the generator to the power system.
magnetising inrush current is being passed. Stabilising
7.1 Direct-connected generators techniques include the addition of relay circuit impedance
and/or the application of a time delay. Where the required
A single direct-connected generator operating on an isolated
setting of the protection is very low in comparison to the rated
system will normally be directly earthed. However, if several
current of the phase CTs, it would be necessary to employ a
direct-connected generators are operated in parallel, only
single Core Balance CT for the earthfault protection to ensure
one generator is normally earthed at a time. For the unearthed
transient stability.
generators, a simple measurement of the neutral current is
not possible, and other methods of protection must be used. Since any generator in the paralleled group may be earthed,
The following sections describe the methods available. all generators will require to be fitted with both neutral
overcurrent protection and sensitive directional earthfault
7.1.1 Neutral overcurrent protection
protection.
With this form of protection, a current transformer in the
The setting of the sensitive directional earthfault protection
neutral- earth connection energises an overcurrent relay
is chosen to co-ordinate with generator differential protection
element. This provides unrestricted earth-fault protection and
and/or neutral voltage displacement protection to ensure that
so it must be graded with feeder protection. The relay element
95% of the stator winding is protected. Figure C8.18 illustrates
will therefore have a time-delayed operating characteristic.
the complete scheme, including optional blocking signals
Grading must be carried out in accordance with the principles
where difficulties in co-ordinating the generator and
detailed in Chapter [C1: Overcurrent Protection for Phase
downstream feeder earthfault protection occur.
and Earthfaults]. The setting should not be more than 33%
of the maximum earthfault current of the generator, and a
lower setting would be preferable, depending on grading
considerations. Feeder
* Optional interlocked
earthfault protection
7.1.2 Sensitive earthfault protection > >> if grading problems exist
Loading
resistor
Generator stator winding using a current element
Figure C8.20:
Earthfault protection of high-resistance earthed generator
stator winding using a current element
(a) Protection using a current element
Application of both voltage and current operated elements 7.3 Restricted earthfault protection
to a generator with distribution transformer earthing provides This technique can be used on small generators not fitted
some advantages. The current operated function will continue with differential protection to provide fast acting earthfault
to operate in the event of a short-circuited loading resistor protection within a defined zone that encompasses the
generator. It is cheaper than full differential protection but The initial bias slope is commonly set to 0% to provide
only provides protection against earthfaults. The principle is maximum sensitivity, and applied up to the rated current of
that used for transformer REF protection, as detailed in Chapter the generator. It may be increased to counter the effects of
[C7: Transformer and Transformer-Feeder Protection, Section CT mismatch. The bias slope above generator rated current
7]. However, in contrast to transformer REF protection, both is typically set to 150% of rated value. The initial current setting
biased low-impedance and high-impedance techniques can is typically 5% of the minimum earthfault current for a fault at
be used. the machine terminals.
7.3.1 Low-impedance biased REF protection 7.3.2 High impedance REF protection
This is shown in Figure C8.22. The main advantage is that the The principle of high impedance differential protection is
neutral CT can also be used in a modern relay to provide given in Chapter [C2: Line Differential Protection] and also
conventional earthfault protection and no external resistors described further in Section 3.2. The same technique can be
are used. Relay bias is required, as described in Chapter used for earthfault protection of a generator, using three
[C2: Line Differential Protection, Section 4.2], but the formula residually connected phase CTs balanced against a similar
for calculating the bias is slightly different and also shown in single CT in the neutral connection, as shown in Figure C8.23.
Figure C8.22. Settings of the order of 5% of maximum earthfault current at
the generator terminals are typical. The usual requirements
in respect of stabilising resistor and non-linear resistance to
guard against excessive voltage across the relay must be
Phase CT ratio 1000/1
Phase A taken, where necessary.
Phase B
Phase C
Neutral CT ratio
200/1
NLR
RST
Relay
(highest of )+( x scaling factor)
2 ISEF
+ (scaling factor x )
Figure C8.23:
High impedance REF protection
Figure C8.22:
Low impedance biased REF protection of a generator
All of the methods for earthfault protection detailed in Section A problem encountered is that the level of third harmonic
7 leave part of the winding unprotected. In most cases, this voltage generated is related to the output of the generator.
is of no consequence as the probability of a fault occurring The voltage is low when generator output is low. In order to
in the 5% of the winding nearest the neutral connection is avoid maloperation when operating at low power output, the
very low, due to the reduced phase to earth voltage. However, third harmonic neutral undervoltage element can be inhibited
a fault can occur anywhere along the stator windings in the by a power element (kW, kVar or kVA). It can also be inhibited
event of insulation failure due to localised heating from a core when all the phase-phase voltages at the generator terminal
fault. In cases where protection for the entire winding is are below the threshold.
required, perhaps for alarm only, there are various methods
For effective application of this form of protection, there should
available.
be at least 1% Vn third harmonic voltage across the generator
8.1 Protection based on third harmonic voltage neutral earthing impedance under all normal operating
conditions. The third harmonic undervoltage threshold must
Most generators will produce third harmonic voltages to some
be set below the level of third harmonic voltage present under
degree due to non-linearity in the magnetic circuits of the
normal conditions. A typical value for this threshold could be
generator design. Under normal operating conditions the
0.5% Vn. The third harmonic overvoltage threshold must be
distribution of the third harmonic voltage along the stator
set above the level of third harmonic voltage present under
windings corresponds to Figure C8.24(a). The maxima occur
normal conditions. A typical value for this threshold could be
at the star point N and the terminal T. The values increase
1% Vn. A time delay for these elements can be set to ensure
with generator load, as shown in Figure C8.24(a). U’TE is the
the stability.
third harmonic voltage when the generator is off load and
U’’TE is the third harmonic voltage when the generator is fully As the fault location moves progressively away from the neutral
loaded. When a fault occurs in the part of the stator winding end, the drop in third harmonic voltage becomes less, so that
nearest the neutral end, the third harmonic voltage at the star at around 20-30% of the winding distance, it no longer
point N drops to near zero but the third harmonic voltage at becomes possible to discriminate between a healthy and a
the terminal T increases significantly, as shown in Figure faulty winding. Hence, a conventional earthfault scheme should
C8.24(b). Hence a relay element that responds to third be used in conjunction with a third harmonic scheme, to
harmonic voltage can be used to detect the fault near the provide overlapping cover of the entire stator winding. The
neutral end. If the third harmonic voltage is measured at the 3rd harmonic technique has to be blocked or is not operational
generator star point, an undervoltage characteristic is used. when the machine is stopped and when the machine is running
An overvoltage characteristic is used if the measurement is up and down. Also, some machines only produce a low level
taken from the generator line VT. The measurement of third of 3rd harmonic voltage (<1% Vn) and for these machines
harmonic voltage can be taken either from a star-point VT or the 3rd harmonic method of 100% stator earthfault protection
the generator line VT. In the latter case, the VT must be capable cannot be used.
of carrying residual flux, and this prevents the use of 3-limb
One alternative is to compare the third harmonic voltage at
types.
the neutral end UNE with the third harmonic voltage at the
terminal UTE. The operation setting is the ratio between these
two third harmonic voltages (UNE/UTE). When there is earthfault
U”TE near the neutral end, the third harmonic voltage at the neutral
G U’TE end decreases while the third harmonic voltage at the terminal
N 0 increases. So the ratio will be less than the setting. For this
N T T
solution there is no need to inhibit the operation when the
50% 100%
power output is low. The setting shall be greater than the
U’NE m
maximum ratio UNE/UTE under normal conditions.
U”NE
8.2 Protection based on low frequency injection
a) normal operation
G U” TE Another method for protecting the entire stator winding of a
U’TE generator is to deploy signal injection equipment to inject a
N T low frequency voltage into the star point or the terminals of
N0 T
the machine as shown in Figure C8.25. Typical injection
50% 100%
frequencies are 12.5 Hz or 20 Hz with 20 Hz being the most
m
b) stator earth fault at the star point popular. Under normal healthy conditions only a very small
m = relative number of turns
current flows via the stator earth capacitance due to the high
impedance of this path at low frequencies (Xc=1/2πfc, where
f is the low frequency injected signal and c is earth
Figure C8.24 Distribution of the 3rd harmonic component capacitance). In the event of an earthfault the measured
along the stator winding of a large generator
current increases due to the smaller impedance of the The voltage to be injected into the generator neutral depends
earthfault path. From the injected voltage and the fault current on the driving low frequency voltage (voltage divider, load
the relay can determine the fault resistance. The protection resistor and bandpass filter) and on the transformation ratio
can also detect earthfaults at the generator terminals including of the neutral or earthing transformer. To prevent the secondary
connected components such as voltage transformers. This load resistance from becoming too small and ensure better
form of protection can provide earthfault protection when the measurement accuracy, a high secondary voltage, such as
generator is at standstill, prior to run-up. It is also an appropriate 500 V, should be chosen for the neutral or earthing transformer.
method to apply to variable speed synchronous machines. The low frequency voltage is fed to the relay via a voltage
Such machines may be employed for variable speed motoring divider which is applied when the secondary rated voltage
in pumped-storage generation schemes or for starting a large of the distribution transformer is higher than relay maximum
gas turbine prime mover. voltage input. The low frequency measuring current is fed via
a miniature current transformer. All interference deviating from
the nominal low frequency signal is filtered out. The fault
resistance can be derived by the low frequency voltage and
current fed to the relay.
Normally two stages of under-resistance element with definite
time delay are applied. The higher setting stage is to issue
Residually
connected the alarm signal. Typically the value for the primary fault
3-phase 20 Hz frequency generator resistance alarm setting is 3-8 k Ohms with typically 1-5 s
transformer
delay. The lower setting stage is to issue the trip signal.
Typically the value for the primary fault resistance trip setting
is 1-2 k Ohms with typically 0.3-1 s delay.
Band pass
filter
Distribution
transformer
Miniature RL V 64 S
CT
I 64 S
C8 9. Overvoltage protection
Overvoltages on a generator may occur due to transient generator supplies little or no load. The terminal voltage will
surges on the network, or prolonged power frequency increase substantially, and in severe cases it would be limited
overvoltages may arise from a variety of conditions. Surge only by the saturation characteristic of the generator. A rise
arrestors may be required to protect against transient in speed simply compounds the problem. If load that is
overvoltages, but relay protection may be used to protect sensitive to overvoltages remains connected, the consequences
against power frequency overvoltages. in terms of equipment damage and lost revenue can be
severe. Prolonged overvoltages may also occur on isolated
A sustained overvoltage condition should not occur for a
networks, or ones with weak interconnections, due to the fault
machine with a healthy voltage regulator, but it may be caused
conditions listed earlier.
by the following contingencies:
For these reasons, it is prudent to provide power frequency
a. defective operation of the automatic voltage regulator
overvoltage protection, in the form of a time-delayed element,
when the machine is in isolated operation
either IDMT or definite time. The overvoltage threshold should
b. operation under manual control with the voltage regulator typically be set to 100% - 120% of the nominal phase-phase
out of service. A sudden variation of the load, in particular voltage seen by the relay. The time delay should be long
the reactive power component, will give rise to a substantial enough to prevent operation during normal regulator action,
change in voltage because of the large voltage regulation and therefore should take account of the type of AVR fitted
inherent in a typical alternator and its transient response. The typical delay to be applied
would be 1 s - 3 s, with a longer delay being applied for lower
c. sudden loss of load (due to tripping of outgoing feeders,
voltage threshold settings.
leaving the set isolated or feeding a very small load) may
cause a sudden rise in terminal voltage due to the trapped Sometimes a high-set element is provided as well, with a very
field flux and/ or overspeed short definite-time delay or instantaneous setting to provide
a rapid trip in extreme circumstances. The typical threshold
Sudden loss of load should only cause a transient overvoltage
setting to be applied would be 130 - 150% of the nominal
while the voltage regulator and governor act to correct the
phase-phase voltage, depending on generator manufacturers’
situation. A maladjusted voltage regulator may trip to manual,
advice.
maintaining excitation at the value prior to load loss while the
Undervoltage protection is rarely fitted to generators. It is overloading or failure of the AVR. In some cases, the
sometimes used as an interlock element for another protection performance of generator auxiliary plant fed via a unit
function or scheme, such as field failure protection or transformer from the generator terminals could be adversely
inadvertent energisation protection, where the abnormality affected by prolonged undervoltage.
to be detected leads directly or indirectly to an undervoltage
Where undervoltage protection is required, it should comprise
condition.
an undervoltage element and an associated time delay. Settings
A transmission system undervoltage condition may arise when must be chosen to avoid maloperation during the inevitable
there is insufficient reactive power generation to maintain the voltage dips during power system fault clearance or associated
system voltage profile and the condition must be addressed with motor starting. Transient reductions in voltage down to
to avoid the possible phenomenon of system voltage collapse. 80% or less may be encountered during motor starting. The
time delay should be set to coordinate with downstream
However, it should be addressed by the deployment of ’system
protection and the System Back-up protection of the relay. The
protection’ schemes. The generation should not be tripped.
time delay would typically be in excess of 3 s - 5 s.
The greatest case for undervoltage protection being required
would be for a generator supplying an isolated power system,
where undervoltage may occur for several reasons, typically
Low forward power or reverse power protection may be The power threshold setting of the reverse power protection
required for some generators to protect the prime mover. Parts shall be set according to Table C8.1 and depends on the
of the prime mover may not be designed to experience reverse application. A definite time delay on operation is necessary
torque or they may become damaged through continued to prevent spurious operation with transient power swings
rotation after the prime mover has suffered some form of that may arise following synchronization or in the event of a
failure. power transmission system disturbance.
11.1 Low forward power protection Reverse power protection may also be used to interlock the
opening of the generator set circuit breaker for ‘non-urgent’
Low forward power protection is often used as an interlocking
tripping, as discussed in the above section.
function to enable opening of the main circuit breaker for
non-urgent trips – e.g. for a stator earthfault on a high- As shown in Table C8.1, the motoring power of the generator
impedance earthed generator, or when a normal shutdown set would be as small as 0.2% rated power. For applications
of a set is taking place. This is to minimise the risk of plant where a protection sensitivity of better than 3% is required,
overspeeding when the electrical load is removed from a a metering class CT should be employed to avoid incorrect
high-speed cylindrical rotor generator. The rotor of this type protection behaviour due to CT phase angle errors when the
of generator is highly stressed mechanically and cannot generator supplies a significant level of reactive power at
tolerate much overspeed. While the governor should control close to zero power factor. Besides, the angle compensation
overspeed conditions, it is not good practice to open the main setting can compensate for the angle error introduced by the
circuit breaker simultaneously with tripping of the prime mover system CT and VT.
for non-urgent trips. For a steam turbine, for example, there
is a risk of overspeeding due to energy storage in the trapped
steam, after steam valve tripping, or in the event that the steam Motoring power
Prime mover Possible damage
valve(s) do not fully close for some reason. For urgent trip (% of rated)
conditions, such as stator differential protection operation, Fire/explosion due to
the risk involved in simultaneous prime mover and 0.5 - 6 unburnt fuel
Diesel engine 5% - 25%
generator breaker tripping must be accepted. Mechanical damage
to gearbox/shafts
When required for interlocking of non-urgent tripping applications,
Motoring level depends on compression ratio and cylinder bore
the threshold setting of the low forward power protection function
stiffness. Rapid disconnection is required to limit power loss and
should be less than 50% of the power level that could result in risk of damage.
a dangerous overspeed transient on loss of electrical loading. 10-15
Some delay is desirable to avoid maloperation in the event of (split shaft)
power fluctuations arising from sudden steam valve/throttle Gas turbine gearbox damage
> 50%
closure. A typical time delay is 2 s. (single shaft)
Another typical application of low forward power protection Compressor load on single shaft machines leads to a high
motoring power compared to split-shaft machines. Rapid
would be for pump storage generators operating in the
disconnection is required to limit power loss or damage.
motoring mode, where there is a need to prevent the machine
0.2%-2% (blades
becoming unprimed (loss of load protection) which can cause out of water) blade and runner
blade and runner cavitations. It is typically set to 80 - 90% of Hydro
> 2% cavitation
the minimum load. For loss of load applications the pickup (blades in water)
time delay is necessary to avoid the maloperation during
Power is low when blades are above tail-race water level. Hydraulic
machine starting or interlock logic is applied to inhibit low flow detection devices are often the main means of detecting loss
forward power protection for a required time. of drive. Automatic disconnection is recommended for unattended
operation.
To prevent unwanted relay alarms and flags, a low forward
0.5% - 3% Thermal stress
power protection element can be disabled when the circuit (Condensing sets) damage on
breaker is open. Steam turbine
3% - 6% (Non- low-pressure turbine
condensing sets) blades
11.2 Reverse power protection (motoring protection)
Damage may occur rapidly with non-condensing sets or when
Reverse power protection is applied to prevent damage to vacuum is lost with condensing sets. Reverse power protection
mechanical plant items in the event of failure of the prime may be used as a secondary method of detection and might only
mover. Table C8.1 gives details of the potential problems for be used to raise an alarm.
various prime mover types and the typical settings for reverse
power protection. Table C8.1:
Generator reverse power problems
A three-phase balanced load produces a reaction field that, Maximum I2/In for Maximum (I2/In )2t
to a first approximation, is constant and rotates synchronously Generator type continuous for operation
with the rotor field system. Any unbalanced condition can be operation under faults, Kg
resolved into positive, negative and zero sequence Salient-pole:
components. The positive sequence component is similar to Indirectly cooled 0.08 20
the normal balanced load. The zero sequence component Directly cooled (inner
produces no main armature reaction. cooled stator and/or 0.05 15
field
12.1 Effect of negative sequence current
Cylindrical rotor synchronous:
The negative sequence component is similar to the positive Indirectly cooled rotor
sequence system, except that the resulting reaction field
Air cooled rotor 0.1 15
rotates in the opposite direction to the d.c. field system. Hence,
Directly cooled (inner cooled) rotor
a flux is produced which cuts the rotor at twice the rotational
velocity, thereby inducing double frequency currents in the 350 MVA 0.08 8
350>
900 MVA * **
field system and in the rotor body. The resulting eddy-currents 900>
1250 MVA * 5
are very large and cause severe heating of the rotor. 1250
1600 MVA 0.05 5
So severe is this effect that a single-phase load equal to the ** For these generators, the value of I2/In is calculated as follows:
normal three-phase rated current can quickly heat the rotor
I2 Sn - 350
slot wedges to the softening point. They may then be extruded = 0.8 -
under centrifugal force until they stand above the rotor surface, In 3 x 10
4
K = constant proportional to the thermal capacity of the The limiting maximum continuous temperature (ӨMCR) would
2
generator rotor be in the form Ө MCR = I 2MCR , as follow:
t
For heating over a period of more than a few seconds, it is 2
Ө MCR = I 2MCR (1-e ,t=∞
τ)
necessary to allow for the heat dissipation, otherwise the
generator maybe cut off incorrectly while the rotor temperature
12.2 Negative phase sequence protection
still remains within the machine's design thermal limits. As
shown in Figure C8.26, the true thermal model is above the This protection is applied to prevent overheating due to
I22t model when the negative sequence current is lower. negative sequence currents. Small salient-pole generators
have a proportionately larger negative sequence capacity
To consider the heat dissipation, the temperature depends
and may not require protection. A true thermal replica
on both the negative sequence component and the thermal
approach which considers the heat dissipation is often applied
time constant, as follows:
in numerical relays.
Ө∧ 2 t
= I 2 (1-e τ)
Where:
10000 I2MCR = Generator per unit maximum continuous I2 rating
Kg = Generator thermal capacity constant(s)
1000
Iflc = Generator primary full-load current (A)
Ip = CT primary current rating (A)
The negative sequence protection element will respond to
100 system phase to earth and phase to phase faults. Therefore,
Indirectly cooled (air)
Indirectly cooled (H2)
the element must be set to grade with downstream earth and
350MW direct cooled phase fault protections. To aid grading with downstream
Time (sec)
10 660MW direct cooled devices a definite minimum operating time for the operating
1000MW direct cooled characteristic can be set, as the I2> tMIN setting shown in
Figure C8.27. This definite minimum time setting should be
1 Using I 22 t model set to provide an adequate margin between the operation of
Using true thermal the negative phase sequence thermal protection function and
model
external protection.
0.1 For levels of negative phase sequence current that are only
slightly in excess of the thermal element pick-up setting, there
will be a noticeable deviation between negative phase
sequence thermal protection current-time characteristic and
0.01
0.01 0.1 1 10 that of the simple I 22 t characteristic. For this reason, a
maximum negative phase sequence protection trip time setting
Negative sequence current (p.u.)
is provided, as the I2> tMAX setting shown in Figure C8.27.
This maximum time setting also limits the tripping time of the
negative phase sequence protection for levels of unbalance
Figure C8.26: where there maybe uncertainty about the machine’s thermal
Typical negative phase sequence current withstand of
withstand.
cylindrical rotor generators
From the above section 12.1, the time for which a level of
t
negative phase sequence current in excess of I2MCR can be
maintained is expressed as follows: I 2>
2 2 t MAX
K I 2MCR
t =- ×1n [1- ]
2
I 2MCR I2 ...Equation C8.1
Set K as I flc 2
( ) ×K g
Ip Figure C8.27:
Negative phase sequence thermal characteristic
I
Set I2set > as I 2MCR ×( flc )
Ip
Accidental energisation of a generator when it is not running undervoltage element when the generator is operating
may cause severe damage to it. With the generator at standstill, normally. The voltage setting should be low enough to ensure
closing the circuit breaker results in the generator acting as that operation cannot occur for transient faults. A setting of
an induction motor; the field winding (if closed) and the rotor about 50% of rated voltage is typical. VT failure can cause
solid iron/damper circuits acting as rotor circuits. Very high maloperation of the protection, so the element should be
currents are induced in these rotor components, and also inhibited under these conditions.
occur in the stator, with resultant rapid overheating and
The pick-up time delay is necessary. It is to prevent initialisation
damage. Protection against this condition is therefore
of the element during system faults. The typical pick-up time
desirable.
delay is 5 s or it is at least in excess of the protection clearance
A combination of stator undervoltage and overcurrent can time for a close up phase to phase fault. In addition the drop-
be used to detect this condition. An instantaneous overcurrent off time delay is also necessary to ensures that the element
element is used, and gated with a three-phase undervoltage remains initialised following accidental closure of the circuit
element (fed from a VT on the generator side of the circuit breaker when the undervoltage detector could reset. A drop-
breaker) to provide the protection. The overcurrent element off delay of 0.5 s - 1 s will ensure that the element can operate
can have a low setting, as operation is blocked by three-phase when required.
These conditions are grouped together because these In general, a generator or step-up transformer overfluxing
problems often occur due to a departure from synchronous condition will occur if the V/Hz ratio exceeds 1.05 p.u, such
speed. as a 5% overvoltage condition at rated frequency.
14.1 Overfluxing Besides, it is very important that the VT reference for overfluxing
protection is not the same as that used for the AVR. The
Overfluxing occurs when the ratio of voltage to frequency is
overfluxing protection based on V/Hz ratio shall reference the
too high. Either excessive voltage, or low frequency, or a
phase to phase voltage to avoid the maloperation under the
combination of both can produce high flux densities in the
earthfault condition which could cause the increase of phase
magnetic core of the generator or transformer. This could
voltage.
cause the core of the generator or transformer to saturate
and stray flux to be induced in un-laminated components that
have not been designed to carry flux. Overheating can then
occur, resulting in damage. 1.50
1.45
Both the generator and transformer shall have the capability
to tolerate the transient overfluxing, which may be caused by 1.40
the sudden loss of load. The typical overfluxing withstand 1.35
characteristics of the generator is shown in Figure C8.28. 1.30
n
The field circuit of a generator, comprising the field winding It will be seen from Figure C8.29 that the flux is concentrated
of the generator and the armature of the exciter, together with on one pole but widely dispersed over the other and intervening
any associated field circuit breaker if it exists, is an isolated surfaces. The attracting force is in consequence large on one
d.c. circuit which is not normally earthed. If an earthfault pole but very weak on the opposite one, while flux on the
occurs, there will be no steady-state fault current and the quadrature axis will produce a balancing force on this axis.
need for action will not be evident. The result is an unbalanced force that in a large machine may
be of the order of 50-100 tonnes.
Danger arises if a second earthfault occurs at a separate
point in the field system, to cause the high field current to be A violent vibration is set up that may damage bearing surfaces
diverted, in part at least, from the intervening turns. Serious or even displace the rotor by an amount sufficient to cause it
damage to the conductors and possibly the rotor can occur to foul the stator.
very rapidly under these conditions.
15.1 Rotor earthfault protection
More damage may be caused mechanically. If a large portion
Two methods are available to detect this type of fault. The
of the winding is short-circuited, the flux may adopt a pattern
first method is suitable for generators that incorporate brushes
such as that shown in Figure C8.29. The attracting force at
in the main generator field winding. The second method
the surface of the rotor is given by:
requires at least a slip-ring connection to the field circuit:
B2A a. potentiometer method
F=
8π
b. a.c. injection method
where:
A = area
B = flux density
Generator
field Exciter
winding
Field
winding > Exciter
Injection
supply
<
Figure C8.30:
Earthfault protection of field circuit by potentiometer method
(b) Power frequency a.c. voltage injection -
impedance measurement
The low–frequency injection scheme is also advantageous in 15.3 Rotor shorted turn protection
that the current flow through the field winding shunt capacitance
As detailed in Section 15 a shorted section of field winding
will be lower than for a power frequency scheme. Such current
will result in an unsymmetrical rotor flux pattern and in
would flow through the machine bearings to cause erosion
potentially damaging rotor vibration. Detection of such an
of the bearing surface. For power frequency schemes, a
electrical fault is possible using a probe consisting of a coil
solution is to insulate the bearings and provide an earthing
placed in the airgap. The flux pattern of the positive and
brush for the shaft.
negative poles is measured and any significant difference in
15.2 Rotor earthfault protection for brushless flux pattern between the poles is indicative of a shorted turn
generators or turns. Automated waveform comparison techniques can
be used to provide a protection scheme, or the waveform can
A brushless generator has an excitation system consisting
be inspected visually at regular intervals. An immediate
of:
shutdown is not normally required unless the effects of the
a. a main exciter with rotating armature and stationary field fault are severe. The fault can be kept under observation until
windings a suitable shutdown for repair can be arranged. Repair will
take some time, since it means unthreading the rotor and
b. a rotating rectifier assembly, carried on the main shaft line
dismantling the winding.
out
Since short-circuited turns on the rotor may cause damaging
c. a controlled rectifier producing the d.c. field voltage for
vibration and the detection of field faults for all degrees of
the main exciter field from an a.c. source (often a small
abnormality is difficult, the provision of a vibration detection
‘pilot’ exciter)
scheme is desirable – this forms part of the mechanical
Hence, no brushes are required in the generator field circuit. protection of the generator.
All control is carried out in the field circuit of the main exciter.
Detection of a rotor circuit earthfault is still necessary, but
this must be based on a dedicated rotor-mounted system that
has a telemetry link to provide an alarm/data.
Loss of excitation may occur for a variety of reasons. If the 16.1 Protection against loss of excitation
generator was initially operating at only 20%-30% of rated
The protection used varies according to the size of generator
power, it may settle to run super-synchronously as an induction
being protected.
generator, at a low level of slip. In doing so, it will draw reactive
current from the power system for rotor excitation. This form 16.1.1 Small generators
of response is particularly true of salient pole generators. In
On the smaller machines, protection against asynchronous
these circumstances, the generator may be able to run for
running has tended to be optional, but it may now be available
several minutes without requiring to be tripped. There may
by default, where the functionality is available within a modern
be sufficient time for remedial action to restore the excitation,
numerical generator protection package. If fitted, it is arranged
but the reactive power demand of the machine during the
either to provide an alarm or to trip the generator. If the
failure may severely depress the power system voltage to an
generator field current can be measured, a relay element can
unacceptable level. For operation at high initial power output,
be arranged to operate when this drops below a preset value.
the rotor speed may rise to approximately 105% of rated
However, depending on the generator design and size relative
speed, where there would be low power output and where a
to the system, it may well be that the machine would be
high reactive current of up to 2.0p.u. may be drawn from the
required to operate synchronously with little or no excitation
supply. Rapid automatic disconnection is then required to
under certain system conditions.
protect the stator windings from excessive current and to
protect the rotor from damage caused by induced slip The field undercurrent relay must have a setting below the
frequency currents. minimum exciting current, which may be 8% of that
corresponding to the MCR of the machine. Time delay relays
XG XT ZS
EG ES 1.8
2.0
A
Load point
2.5
+jX
D
5.0 Loss of field
ZS XG+XT+ZS locus
D
EG
=1 XT
ES
q
ZR C
-R +R
A
XG
0.5
0.6
C 0.7
-jX
Figure C8.33:
Swing curves and loss of synchronism locus
Figure C8.32:
Basic interconnected system
ZR =
( X G + X T + Z S ) n (n - cosѲ - jsinѲ ) -X G
machine is increasing. The operating condition plotted on an
impedance diagram therefore travels along a locus that
(n-cosѲ ) 2 + sin 2Ѳ crosses the power swing circles. At the same time, it progresses
...Equation C8.2
in the direction of increasing rotor angle. After passing the corresponds to the maximum practicable rotor angle, taken
anti-phase position, the locus bends round as the internal to be at 120°. The locus of operation can be represented as
e.m.f. collapses, condensing on an impedance value equal a circle on the impedance plane, as shown in Figure C8.34,
to the machine reactance. The locus is illustrated in Figure stable operation conditions lying outside the circle.
C8.33.
On the same diagram the full load impedance locus for one
The relay location is displaced from point C by the generator per unit power can be drawn. Part of this circle represents a
reactance XG. One problem in determining the position of condition that is not feasible, but the point of intersection with
these loci relative to the relay location is that the value of the maximum rotor angle curve can be taken as a limiting
machine impedance varies with the rate of slip. At zero slip operating condition for setting impedance-based loss of
XG is equal to XD, the synchronous reactance, and at 100% excitation protection.
slip XG is equal to X"d, the sub-transient reactance. The
16.2 Impedance-based protection characteristics
impedance in a typical case has been shown to be equal to
X'd, the transient reactance, at 50% slip, and to 2X"d with a Figure C8.33 alludes to the possibility that a protection scheme
slip of 0.33%. The slip likely to be experienced with for loss of excitation could be based on impedance
asynchronous running is low, perhaps 1%, so that for the measurement. The impedance characteristic must be
purpose of assessing the power swing locus it is sufficient appropriately set or shaped to ensure decisive operation for
to take the value XG = 2X"d. loss of excitation whilst permitting stable generator operation
within allowable limits. One or two offset mho under impedance
This consideration has assumed a single value for XG. However,
elements (see Chapter [C3: Distance Protection] for the
the reactance Xq on the quadrature axis differs from the
principles of operation) are ideally suited for providing loss
direct-axis value, the ratio of Xd / Xg being known as the
of excitation protection as long as a generator operating at
saliency factor. This factor varies with the slip speed. The
low power output (20-30% Pn) does not settle down to operate
effect of this factor during asynchronous operation is to cause
as an induction generator. The characteristics of a typical
XG to vary at slip speed. In consequence, the loss of excitation
two-stage loss of excitation protection scheme are illustrated
impedance locus does not settle at a single point, but it
in Figure C8.35. The first stage, consisting of settings Xa1
continues to describe a small orbit about a mean point.
and Xb1 can be applied to provide detection of loss of
A protection scheme for loss of excitation must operate excitation even where a generator initially operating at low
decisively for this condition, but its characteristic must not power output (20-30% Pn) might settle down to operate as
inhibit stable operation of the generator. One limit of operation an induction generator.
XT Alarm
angle
0.75
Limiting
generation
point
Relay
characteristic Figure C8.35:
Locus of constant load angle
Diameter = Loss of excitation protection characteristics
Trip within circle
Pick-up and drop-off time delays td1 and tdo1 are associated
Figure C8.34: with this impedance element. Timer td1 is used to prevent
Locus of limiting operating conditions of synchronous machine operation during stable power swings that may cause the
impedance locus of the generator to transiently enter the If a fast excitation system is employed, allowing load angles
locus of operation set by Xb1. However, the value must short of up to 120° to be used, the impedance diameter must be
enough to prevent damage as a result of loss of excitation reduced to take account of the reduced generator impedance
occurring. If pole-slipping protection is not required (see seen under such conditions. The offset also needs revising.
Section 17.2), timer tdo1 can be set to give instantaneous In these circumstances, typical settings would be:
reset. The second field failure element, comprising settings
a. impedance element diameter Xb1 = 0.5Xd
Xa2, Xb2, and associated timers td2 and tdo2 can be used to
give instantaneous tripping following loss of excitation under b. impedance element offset Xa1 = -0.75X'd
full load conditions.
c. time delay on pick-up, td1 = 0.5s - 10s
16.3 Protection settings
d. time delay on drop-off, tdo1 = 0s
The typical setting values for the two elements vary according
The typical impedance settings for the second element, if
to the excitation system and operating regime of the generator
used, are:
concerned, since these affect the generator impedance seen
by the relay under normal and abnormal conditions. For a • impedance element diameter
generator that is never operated at leading power factor, or
kV 2
at load angles in excess of 90° the typical settings are: X b2 =
MVA
a. impedance element diameter Xb1 = Xd
X a2 = − 0.5X'd
b. impedance element offset Xa1 = -0.5X'd
The time delay settings td2 and tdo2 are set to zero to give
c. time delay on pick-up, td1 = 0.5s - 10s instantaneous operation and reset.
d. time delay on drop-off, tdo1 = 0s
A generator may pole-slip, or fall out of synchronism with the used for other purposes. However, since the reverse power
power system for a number of reasons. The principal causes conditions are cyclical, the element will reset during the forward
are prolonged clearance of a heavy fault on the power system, power part of the cycle unless either a very short pick-up
when the generator is operating at a high load angle close to time delay and/or a suitable drop-off time delay is used to
the stability limit, or partial or complete loss of excitation. eliminate resetting.
Weak transmission links between the generator and the bulk
The main advantage of this method is that a reverse power
of the power system aggravate the situation. It can also occur
element is often already present, so no additional relay
with embedded generators running in parallel with a strong
elements are required. The main disadvantages are the time
Utility network if the time for a fault clearance on the Utility
taken for tripping and the inability to control the system angle
network slow, perhaps because only IDMT relays are provided.
at which the generator breaker trip command would be issued,
Pole slipping is characterised by large and rapid oscillations
if it is a requirement to limit the breaker current interruption
in active and reactive power. Rapid disconnection of the
duty. There is also the difficulty of determining suitable settings.
generator from the network is required to ensure that damage
Determination of settings in the field, from a deliberate pole-
to the generator is avoided and that loads supplied by the
slipping test, is not possible and analytical studies may not
network are not affected for very long.
discover all conditions under which pole-slipping will occur.
Protection can be provided using several methods. The choice
17.2 Protection using an under impedance element
of method will depend on the probability of pole slipping
occurring and on the consequences should it occur. With reference to Figure C8.33, a loss of excitation under
impedance characteristic may also be capable of detecting
17.1 Protection using reverse power element
loss of synchronism, in applications where the electrical centre
During pole-slipping, there will be periods where the direction of the power system and the generator lies ‘behind’ the relaying
of active power flow will be in the reverse direction, so a point. This would typically be the case for a relatively small
reverse power relay element can be used to detect this, if not generator that is connected to a power transmission system
XG >> (XT + XS). With reference to Figure C8.35; if pole- traversed so that tripping will not be initiated. The security of
slipping protection response is required, the time delay on this type of protection scheme is normally enhanced by the
drop-off tdo1 of the large diameter impedance measuring addition of a plain underimpedance control element (circle
element should be set to prevent its reset in each slip cycle, about the origin of the impedance diagram) that is set to
until the trip time delay on pick-up td1 has expired. prevent tripping for impedance trajectories for remote power
system faults.
As with reverse power protection, this would be an elementary
form of pole-slipping protection. It may not be suitable for Setting of the ohm elements is such that they lie parallel to
large machines where rapid tripping is required during the the total system impedance vector, and enclose it, as shown
first slip cycle and where some control is required for the in Figure C8.36.
system angle at which the generator circuit breaker trip
command is given. Where protection against pole-slipping
must be guaranteed, a more sophisticated method of
protection should be used. A typical reset timer delay for
pole-slipping protection might be 0.6s. For generator
transformer units, the additional impedance in front of the
relaying point may take the system impedance outside the
Relaying point
under impedance relay characteristic required for loss of
excitation protection. Therefore, the acceptability of this pole-
slipping protection scheme will be dependent on the
application. Slip locus
X
Left-lens Right-lens
S M
a Ang
Pole slipping
characteristic
Blinder
Figure C8.38:
Definition of zones for lenticular characteristic
From the preceding sections, it is obvious that the protection d. overvoltage protection
scheme for a generator has to take account of many possible
e. undervoltage protection
faults and plant design variations. Determination of the types
of protection used for a particular generator will depend on f. overload/low forward power/ reverse power protection
the nature of the plant and upon economic considerations, (according to prime mover type)
which in turn is affected by set size. Fortunately, modern,
g. unbalanced loading
multi-function, numerical relays are sufficiently versatile to
include all of the commonly required protection functions in h. overheating
a single package, thus simplifying the decisions to be made. i. pole slipping
The following sections provide illustrations of typical protection
schemes for generators connected to a grid network, but not k. loss of excitation
all possibilities are illustrated, due to the wide variation in l. underfrequency
generator sizes and types.
m. inadvertent energisation
19.1 Direct-connected generator
n. overfluxing
A typical protection scheme for a direct-connected generator
is shown in Figure C8.39. It comprises the following protection o. mechanical faults
functions: Figure C8.39 illustrates which trips require an electrical trip
a. stator differential protection and which can be time delayed until electrical power has
been reduced to a low value. The faults that require tripping
b. overcurrent protection – conventional or voltage of the prime mover as well as the generator circuit breaker
dependent are also shown.
c. stator earthfault protection
Loss of excitation
Stator winding temperature Excitation
Unbalanced loading circuit
breaker
Under/overvoltage Low power
interlock
Generator
Mechanical faults (non-urgent) circuit
breaker
N.B. Alarms and time delays omitted for simplicity
Figure C8.39:
Typical protection arrangement for a direct-connected generator
Inadvertent energisation
HV restricted E/F
Generator
Transformer winding temperature circuit
breaker
Loss of excitation Low power
Stator winding temperature interlock
Unbalanced loading
Under/overvoltage
Figure C8.40:
Typical tripping arrangements for generator-transformer unit
G ~ =
= ~
In all cases the fault current contribution of a converter-driven
DGs is in the range of the normal load current (or even lower).
Overcurrent protection is not suitable in such case. Using
distance or differential protection will allow the fault detection
but increases the investment costs.
20.2.2 Tapped lines
Figure C8.41:
Wind turbine generator system using full rated power Smaller (resp. bigger) DGs (e.g. wind or solar power plants)
electronic converters are typically connected to the MV (resp. HV) grid. In rural
80
70
Q / S nom
60
HV MV 1 .0
P
V (%)
50
40 G
30
Q
20 0.5
10
Trip DG
0
0 0.5 1 1.5 2 2.5 3 3.5
time (s)
-1 .0 -0.5 0.5 1 .0 P / S nom
USA-Ireland-AESO Germany Denmark (<100kV)
UK Nordel Belgium (large voltage dips)
Belgium (small voltage dips) Sweden (<100MW) Sweden (>100MW)
New Zealand Hydro-Quebec Italy G
Spain
communication
HV loss of comm.
(PLC)
MV transfer trip
ZE
VT
Figure C8.48:
Islanding detection methods
1
20.3.2 Rate of change of frequency relay
islanded network
the case that the relay settings are determined at site during Nevertheless, because such protection is a common
commissioning. This is to ensure that the Utility requirements requirement of some Utilities, the ‘loss of mains’ protection
are met while reducing the possibility of a spurious trip under may have to be provided and the possibility of spurious trips
the various operating scenarios envisaged. However, it is very will have to be accepted in those cases. Site measurements
difficult to determine whether a given rate of change of over a period of time of the typical rates of frequency change
frequency will be due to a ‘loss of mains’ incident or a load/ occurring may assist in negotiations of the settings with the
frequency change on the public power network, and hence Utility, and with the fine-tuning of the protection that may
spurious trips are impossible to eliminate. Thus the provision already be commissioned.
of Loss of Utility Supply protection to meet power distribution
Utility interface protection requirements may actually conflict
with the interests of the national power system operator. With
the growing contribution of non-dispatched embedded
generation to the aggregate national power demand, the loss
of the embedded generation following a transmission system
incident that may already challenge the security of the system
can only aggravate the problem. [Ref C8.9: Survey of Rate
Of Change of Frequency Relays and Voltage] provides further
details of the operation of ROCOF relays and the problems
that may be encountered.
This section gives examples of the calculations required for Generator data
generator protection. The first is for a typical small generator Prime
Rated Rated Rated Rated
installed on an industrial system that runs in parallel with the kVA kW PF
voltage current frequency speed
mover
type
Utility supply. The second is for a larger generator-transformer
Steam
unit connected to a grid system. 6250 5000 0.8 11000 328 50 1500
turbine
Biased differential protection involves the determination of 31.7 Ω 200A 145A 850A
protection schemes. In this application, the CTs are conventional subjected to fault or overload current in excess of the stator
class 5P CTs that meet the relay requirements in respect of short-time current limits. A curve should be provided by the
knee-point voltage, etc. manufacturer, but IEC 60034-1 demands that an AC generator
should be able to pass 1.5 times rated current for at least 30
Where neutral tail and terminal CTs can saturate at different
seconds. The operating time of the downstream protection
times due to transiently offset magnetising inrush or motor
for a three-phase fault current of 850 A is 0.682 s, so the
starting current waveforms with an r.m.s. level close to rated
voltage controlled relay element should have a minimum
current and where there is a high L/R time constant for the
operating time of 1.09 s (0.4 s time grading margin is used
offset, the use of a 0% bias slope may give rise to maloperation.
to cooperate with the downstream relay - see table C8.2).
Such waveforms can be encountered when plant of similar
With a current setting of 87.5 A, the operating time of the
rating to the generator is being energised or started.
voltage controlled relay element at a TMS of 1.0 is:
Differences between CT designs or differing remanent flux
levels can lead to asymmetric saturation and the production 0.14
of a differential spill current. Therefore, it is appropriate to 0 .02
= 3.01 s
select a non-zero setting for K1, and a value of 5% is usual
850
−1
in these circumstances. 87.5
21.1.2 Voltage controlled overcurrent protection Therefore a TMS of:
At normal voltage, the current setting must be greater than 21.1.3 Stator earthfault protection
the maximum generator load current of 328 A. A margin must The maximum earthfault current, from Table C8.3, is 200 A.
be allowed for resetting of the relay at this current (reset ratio Protection for 95% of the winding can be provided if the relay
= 95%) and for the measurement tolerances of the relay (5% is set to detect a primary earthfault current of 16.4 A, and
of IS under reference conditions), therefore the current setting this equates to a CT secondary current of 0.033 A. The nearest
is calculated as: relay setting is 0.04 A, providing protection for 90% of the
winding.
I vcset > 328 × 1.05
0.95 The protection must grade with the downstream earthfault
> 362.5 A protection, the settings of which are also given in Table C8.3.
At an earthfault current of 200 A, the downstream protection
The nearest settable value is 365 A, or 0.73 In. has an operation time of 0.73 s. The generator earthfault
protection must therefore have an operation time of not less
The minimum phase-phase voltage for a close-up single-phase
than 1.13 s. At a TMS of 1.0, the generator protection relay
to earthfault is 57%, so the voltage setting VS must be less
operating time will be:
than this. A value of 30% is typically used, giving VS = 33 V.
The current setting multiplying factor K must be chosen such
that KIS is less than 50% of the generator steady-state current
0 .14
contribution to an uncleared remote fault. This information is
s
( )
0 .02
not available (missing data being common in protection 200 − 1
studies). However, the maximum sustained close-up phase 20
fault current (neglecting AVR action) is 145 A, so that a setting 1.13 = 0.38
chosen to be significantly below this value will suffice. A value = 2.97 s, so the required TMS is
2.97
of 87.5 A (60% of the close-up sustained phase fault current)
is therefore chosen, and hence K = 0.6. This is considered Use a setting of 0.4, nearest available setting.
to be appropriate based on knowledge of the system circuit 21.1.4 Neutral voltage displacement protection
impedances. The TMS setting is chosen to co-ordinate with
the downstream feeder protection such that: This protection is provided as back-up earthfault protection
for the generator and downstream system (direct-connected
a. for a close-up feeder three-phase fault, that results in almost generator). It must therefore have a setting that grades with
total voltage collapse as seen by the relay the downstream protection. The protection is driven from the
b. for a fault at the next downstream relay location, if the relay generator star- connected VT, while the downstream protection
voltage is less than the switching voltage is current operated.
It is therefore necessary to translate the current setting of the slipping conditions, a drop-off time delay td2 is provided and
downstream setting of the current-operated earthfault set to 0.5 s.
protection into the equivalent voltage for the NVD protection.
21.1.6 Negative phase sequence current protection
The equivalent voltage is found from the formula:
V eff =
( Ipe × Z e ) × 3 This protection is required to guard against excessive heating
from negative phase sequence currents, whatever the cause.
VT ratio The generator is of salient pole design, so from IEC 60034-1,
48 × 31.7 × 3 the continuous withstand is 8% of rating and the I 22 t value is
= 20 s. Using Equation C8.1, the required relay settings can
100
found as
= 45.6 V
where: I2>> = 0.05 and K = 8.6 s.
Veff = effective voltage setting The nearest available values are I2>> = 0.05 and K = 8.6 s.
Ipe = downstream earthfault current setting The relay also has a cooling time constant Kreset that is normally
set equal to the value of K. To co-ordinate with clearance of
Ze = earthing resistance heavy asymmetric system faults, that might otherwise cause
Hence a setting of 48 V is acceptable. Time grading is unnecessary operation of this protection, a minimum operation
required, with a minimum operating time of the NVD protection time tmin should be applied. It is recommended to set this to
of 1.13 s at an earthfault current of 200 A. Using the expression a value of 1. Similarly, a maximum time can be applied to
for the operation time of the NVD element: ensure that the thermal rating of the generator is not exceeded
(as this is uncertain, data not available) and to take account
t = K/(M-1)sec of the fact that the MiCOM P343 characteristic is not identical
where: with that specified in IEC 60034.
V The recommended setting for tmax is 600 s.
M=
V snvd
and 21.1.7 Overvoltage protection
V = voltage seen by relay This is required to guard against various failure modes, e.g.
AVR failure, resulting in excessive stator voltage. A two-stage
Vsnvd = relay setting voltage protection is available, the first being a low-set time-delayed
the value of K can be calculated as 3.34. The nearest settable stage that should be set to grade with transient overvoltages
value is 3.5, giving an operation time of 1.18 s. that can be tolerated following load rejection. The second is
a high-set stage used for instantaneous tripping in the event
21.1.5 Loss of excitation protection of an intolerable overvoltage condition arising.
Loss of excitation is detected by a mho impedance relay Generators can normally withstand 105% of rated voltage
element, as detailed in Section 16.2. The standard settings continuously, so the low-set stage should be set higher than
for the MiCOM P340 series relay are: this value. A setting of 117.7 V in secondary quantities
Xa = -0.5 X'd × (CT ratio/VT ratio) (corresponding to 107% of rated stator voltage) is typically
used, with a definite time delay of 10 s to allow for transients
(in secondary quantities) due to load switch-off/rejection, overvoltages on recovery
= -0.5 × 0.297 × 19.36 × 500/100 from faults or motor starting, etc.
Table C8.4:
Small generator protection example – relay settings
This completes the settings required for the generator, and Zb 0.656 Ω
the relay settings are given in Table C8.6. Of course, additional Zc 0.206 Ω
protection is required for the generator transformer, according Pole slipping protection 90°
C8 22. References
C8