SS 645:2019
Installation and
Servicing of Electrical
Fire Alarm System
(Formerly CP 10)
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Key Changes in SS 645 : 2019 –
Scope, General requirements and
Design
29 August 2019
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
OBJECTIVES OF REVISION
• Old Code published in 2005
• In line with the latest Fire Alarm Concept and Technology
• Fire Code 2018 / FSSD New Requirements
• In line with the New Reference Code
- AS 1670.1 : 2015 (AS 1670 : 1995)
- BS 5839-1 : 2017 (BS 5839-1 : 2002)
- BS EN 54-2 : 1998 + A1 : 2006 (BS EN 54-2 : 1997 )
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
TIME LINE FOR THE REVIEW OF SS 645
Total Number of Meetings: 63
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
WORKING GROUP FOR THE REVIEW OF SS 645
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CONTENT OF SS 645
Clause 1, 2 & 3: Scope, Normative references and
Terms and definitions
Clause 4: General requirements
Clause 5: Design considerations
Clause 6: Installation, operation and
maintenance
Annexes: A, B, C, D & E
Tables: 1, A.1 & D.1
Figures : 1 to 12, A.1, C.1-2 & D.1-3
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 1, 2, 3 & 4 – SCOPE AND GENERAL REQUIREMENTS
1. Scope
2. Normative references
4. General requirements
4.1 Equipment colour – Panels & call points shall be RED (bells excluded)
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 4 – GENERAL REQUIREMENTS
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 4 – GENERAL REQUIREMENTS
4.2.2 Clearance requirements
(a) A minimum clearance of 1000 mm shall be maintained from the front of the alarm
panel’s enclosure.
(b) A clear space of at least 300 mm radius, to a depth of 600 mm, measured from the
detector shall be maintained. No goods or materials shall be placed within the area.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 4 – GENERAL REQUIREMENTS
A concealed space less than 800 mm deep in roof or ceiling with electrical wiring installed in
metal conduit/trunking in compliance with SS 638 (CP5) does not require protection.
Remote alarm indicators provided on a zone plan adjacent to fire alarm panels shall be
subjected to the approval from the relevant fire authority.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 4 – GENERAL REQUIREMENTS
(a) A riser area exceeding 0.3 m2 for housing fire risk contents such as electrical or
communication equipment, gas pipe, fuel pipe etc.; or
(d) Areas which are covered with trellises, louvres or perforated panels having 50% or
more evenly distributed effective free openings.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 4 – GENERAL REQUIREMENTS
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 4 – GENERAL REQUIREMENTS
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 4 – GENERAL REQUIREMENTS
(a) All the fire and fault alarm signals shall be promptly and accurately verified with its
subscribers when triggered. The relevant authority shall be informed of the nature of the
alarm as soon as possible, and not exceeding 2 minutes, from the trigger of the fire
alarm.
(b) The records of all fire and fault alarm signals received shall be retained for at least 1
year.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
The performance and functionality requirements of the fire alarm system can be met by employing
one or more pieces of the equipment.
An illustration of the components of a typical fire alarm system and associated systems, functions
and equipment can be seen in Annex A.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Annex A - Fire alarm System and associated systems, functions and equipment
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Annex A - Fire alarm System and associated systems, functions and equipment
(1) Control & Indicating (8) Fire alarm
(3) Automatic fire detection function Equipment routing (12) Fire Alarm receiving function
function
(6) Control and indication function for (14) Ancillary management function
alarm annunciation
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Fire alarm
management equipment
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
(a) A single fault in the transmission paths between main alarm panel
and sub alarm panels and/or between sub alarm panels shall not
prevent an alarm from other sub alarm panels.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.2.2 Zone plan / mimic panel
Zone plans provided shall be securely mounted and easily accessible. The plan shall be in the
form of a permanent diagram that is water resistant and fade resistant. The lettering shall be a
minimum of 3mm and shall include the following information (where applicable):
(a) The layout of the building in which the Fire Alarm System is installed
(c) The location of MAP and SAP and marked “YOU ARE HERE”
(d) The location of special hazards control panel, fire fan control panel and emergency voice
communication control station.
(g) The year of original installation and the date of the latest revision to the zone plan.
The zone plan/mimic panel shall be installed in accordance with its floor or building orientation.
The locations of all other fire fighting facilities such as landing valves, hosereels and fire
extinguishers etc. may be included in the zone plan.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
OR
OR
FCC
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.2.11 Records
The following information shall be recorded in the log record:
(a) The name(s) of the member(s) of the premises management to whom responsibility for the fire
detection and fire alarm system is delegated;
(b) Brief details of maintenance arrangements;
(c) Dates and times of all fire alarm signals (regardless of whether the signal is a false alarm or is initiated
as the result of a test, fire drill or genuine fire); if the fire alarm signal has resulted from the operation
of a manual call point or fire detector, the device and its location shall be recorded;
(d) Causes, circumstances surrounding and category of all false alarms (see 6.3);
(e) Dates, times and types of all tests;
(f) Dates, times and types of all faults and detectors;
(g) Dates and types of all maintenance (e.g. service visit or non-routine attention).
For post-investigation purposes, all log records shall be kept for the minimum of 12 months.
A recommended format of the log record is described in Annex B.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.2.11 Records -
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.3 Power supply
5.3.2 Form of supply
Transition between the normal supply and the standby supply, and vice versa, shall not cause
any interruption to the operation of the system or result in a false alarm.
A fault in the normal supply shall not adversely affect the standby supply or vice versa. The
operation of a single protective device should not result in failure of both the normal and
the standby supply.
Normal and standby supplies shall each be independently capable of supplying the maximum
alarm load of the system (see 3.16), irrespective of the condition of the other supply.
5.3.3 Battery charger
The mains supply shall be terminated using a switched socket outlet installed inside the fire
alarm panel or directly at its integral power supply unit.
5.3.4 Battery and battery location
Batteries shall be maintenance-free type and labels shall be fixed to all batteries indicating their
date of installation. The labels shall be so sited that they can be read without disturbing
the batteries.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
ISO ISO
ISO
ISO
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.5.6 Visual alarm devices
5.5.6.1 Location of visual alarm devices
The visual alarm devices shall be located within line of sight in spaces in a
building where there is a chance of the hearing impaired being in isolation. These
isolation spaces include designated bedrooms for the hearing impaired in buildings
with stay-in facilities such as hotels, serviced apartments, hostels, prominent
locations such as toilet cubicles in washrooms, car park floors and lift lobbies. The
visual alarm devices can take the form of flashing beacon or strobe light. In addition,
the visual alarm devices shall also be provided where audible alarm sounders are
located. Where they are not readily visible from all accessible locations, additional
visual alarms shall be provided.
Visual alarms shall be provided in discos, night clubs, and other places of
entertainment outlets or areas where audible alarms can be ineffective (e.g. high
background noise). Where special effects lighting systems are installed, they shall
be interlocked with the fire alarm system to enable these systems to be
automatically cut-off when the fire alarm system is activated.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
(a) Visual alarm devices shall be sufficient in number and their distribution should be readily
visible from all accessible locations.
(b) Visual alarm devices housing shall be red and labelled with the word “Fire” of at least
15mm in height and the lettering colour shall contrast with the background.
(c) Visual alarm devices shall be securely mounted at a height of between 2 metres and 2.5
metres above the finished floor level, such that it is visible from all corners of the floor.
(d) The visual alarm signal shall be clearly distinguishable from any other visual signal used in
the premises.
(e) The visual alarm signal shall flash at a rate within the range of 30 to 130 flashes per minute.
(g) The flashing or strobe lights of visual alarm signal shall be synchronised with the flash rate
of such multiple devices installed within a space or a room. The intensity of the light signal
shall be sufficient to draw the attention of people in the vicinity.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
If a building does not have an approved emergency voice communication system complying
with SS 546, whenever the fire alarm system enters a new fire alarm condition, only the first
alarm audio and visual devices shall be permitted to be deactivated after 3 minutes and any
subsequent alarms may be deactivated immediately. An appropriate instruction shall be
provided for this function.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
In the event of subsequent alarms activation from other zone, the first emergency announcement
shall be replaced by a higher priority or evacuation announcement initiated from the fire alarm system
or manually from the EVC system.
When an emergency announcement has been initiated automatically from the fire alarm system, the
first emergency announcement shall be replaced by a higher priority announcement or an evacuation
announcement, to be initiated from the EVC system after maximum 2 minutes of first announcement
and no manual acknowledgement by the building operators.
LINK
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.5.8 Interface with EVC system - Fire Alarm & Messages (Single Zone Alarm)
Alarm from
1 zone Evacuate
Alert Message
Message
Connection for auto annoucement
If EVC provided, alarm bells shall sound for
Record all Announcement &
15seconds before voice announcement is Voice Traffic
broadcasted.
5.5.8 Interface with EVC system - Fire Alarm & Messages (Two Zone Alarm)
Manual call points can be omitted in carparks, irrespective whether the parking facility is standalone type or
forms part of the building
A clearly marked signage with words e.g. ‘In case of fire, call 995’ shall be provided at every manual call point
for manual fire alarm system that is not linked to alarm monitoring station.
5.6.2 Manual call point
Manual call point shall be bright red in colour and shall be of the “break glass” or resettable flexible elements
type.
NOTE – A resettable flexible element can be returned to its original position without replacement, in order for the manual call
point to be able to return to the normal condition.
5.6.6 Location
Manual call points shall be located between 800mm and 1200mm above the finished floor level and shall be easily
In areas where manual call points are likely to be subjected to casual, malicious operation or accidental damage, manual call
point with transparent hinged cover is acceptable. Operation of this two-action manual call point then involves lifting the cover
and operating the manual call point in the normal manner.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
For flat ceilings not exceeding 3.5 m in height, excluding corridors, the distance from any point on the
ceiling of the protected area to the nearest detector does not exceed 5 m (see Figure 4a). In addition,
the distance between detectors shall not exceed:
(a) 7 m for areas other than corridors (see Figure 4a);
(b) 10 m for corridors (see Figure 4b).
(a) Spacing for general protected areas (b) Spacing for Corridors
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
This clause applies to all sloping surfaces including curved surface such as barrel-vaulted ceiling.
Detectors shall be installed between 0.5 m and 1.5 m from the apex and spaced longitudinally at a
maximum of 7 m between detectors. Lower rows of heat detectors shall be no more than 7 m apart,
measured horizontally from adjacent rows, the outside wall or partition. The spacing between heat
detectors within lower rows shall only be extended up to 14 m, provided that the detectors are offset
equally between the detectors on the adjacent rows (see Figure 5).
Figure 5
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Installation of linear heat detectors shall comply with the appropriate requirements of clause 5.7.3.1 to
5.7.3.8 (point detectors) and with the following requirements:
(a) The maximum area covered by each linear heat detection device shall be in accordance with the area
limitation specified in clause 4.4.1 (2000m2 per zone)
(b) All linear heat detection circuits shall be installed so that they are not subject to
mechanical damage.
(c) The heat-sensing portion of the linear heat detection circuit shall not be installed in more than one alarm
zone unless adequate precautions are taken to prevent incorrect alarm zone identification and that a
single fault does not affect more than one alarm zone.
(d) Linear heat detection circuit shall be installed throughout the protected area so that there is not more
than 7m between any two adjacent lines and within 3.5m of any wall or partition. In the roof bays,
there shall be a detection circuit for each apex, even though these apices may be less than 7m apart.
(e) Where the linear heat detector is made up of a number of individual elements, each element shall be
considered as a point-type detector for spacing purpose
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
For flat ceiling, the distance from any point on the ceiling of the protected area to the nearest detector
shall not exceed 7m. In addition, the distance between point-type detectors shall not exceed 10m.
(see Figure 7).
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Optical beam smoke detectors on sloping ceiling, the distance between detector beams and side walls shall not be
extended to more than 14 m. (see Figure 9a)
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
NOTE 1 – For areas with high air velocities i.e. in excess of 3 m/s or air exchange rate exceeding 30 air changes per
hour, the detector spacing may need to be further reduced or more sensitive detection equipment may need to be
installed.
NOTE 2 – Certain applications such as computer rooms and data centres where asset protection is an important
consideration, additional or specific measures should be considered.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Where the ceiling or roof height is more than 12m from the floor, the detector type and location may
require additional engineering considerations of the smoke plume within the building environment.
Optical beam line-type smoke detectors spaced in accordance with Figure 9 shall be mounted not less
than 25 mm and not more than 600 mm below the ceiling or roof. Beam-type smoke detectors may be
installed more than 600mm below the ceiling, provided that the spacing between beams is reduced to
half the mounting height of the beam above the floor taken into account the likely spread of a smoke
plume as a function of height. Additional optical beam line-type detectors should be installed in
vertical shafts, e.g. atria and warehouse etc. at lower levels
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
No more than 40 smoke detectors shall be connected on a single alarm zone. (see 4.4.1)
Where a single alarm circuit is connected with more than 40 point-type smoke detectors, means shall be
specified and provided which ensure that a short circuit or an interruption in this detection alarm circuit
does not prevent the indication of a fire alarm from more than 40 point-type smoke detectors.
The alarm zone limitation shall be 2000 m2 of protected floor area regardless of the number of smoke
detectors provided within the zone.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Flame detectors should not be located in areas in which sources of infra-red or ultraviolet radiation
create the potential for unwanted alarms. Since various techniques can be adopted in the design of
the detector to minimize the potential for unwanted alarms as a result of radiation from non-fire
sources, the guidance of the manufacturer of the detector, in respect of sensitivity of detectors to
such sources, should be taken into account.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.10.2 Application
VIFDS is intended to protect large spaces in commercial and industrial buildings. It is not
recommended in areas where the environment could cause inaccuracy in detection or false alarm.
Such areas include rooms/spaces having varying and non-uniform lighting levels or having
obstructions to the detector. Detectors should be placed to ensure that the risk areas are protected
with minimum shadowing or blind spots.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
NOTE – The solid line denotes mandatory requirements and the dotted line denotes optional requirements
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
5.10 Video image fire detection system (New Clause)
5.10.4.1 General
VIFDS should recognise and detect flame and/or smoke from the captured images and trigger the building fire
alarm. The design and installation of the system should minimise the occurrences of false alarm. All images
captured should be recorded and stored in the system for a specified duration. The system should be able to
supply vital and situational real time live video to control centre within the building and remote locations outside
the building.
The following factors should be taken into consideration when determining the locations of the cameras:
- Manufacturer’s recommendations
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
CLAUSE 5 – DESIGN CONSIDERATIONS
The system shall give consistent fire alarm responses in a specified time not to exceed 30 seconds.
It shall be able to detect reflected fire light when the fire is obstructed and capable of detecting flame and/or
smoke under minimum lighting condition.
The system shall be able to record video images at all times to facilitate fire investigation. The system shall have
adequate storage capacity to store video images for up to a duration of 30 days for immediate retrieval if
need arises. Video records shall contain essential details such as date, time and location of the video images
being taken. Provision shall be made available for transferring the video records to other storage devices.
The system shall be able to give warning on system fault including detector, circuit and other system
components malfunction or failure. The system shall be able to adapt to environmental variations to minimise false
alarm.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Thank You
www.enterprisesg.gov.sg/quality-
standards/standards
This material contains confidential and/or official information. The terms and conditions
governing its use can be found at www.enterprisesg.gov.sg/Terms-of-Use.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Key Changes in SS 645 : 2019 –
Installation, operation and
maintenance
Benedict Koh
Member of Working Group for SS 645 : 2019
29 August 2019
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.1 Installation
6.1.1 General
The fire alarm system installation shall be kept separate
and distinct from other system installations.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.1 Installation
(a) Any cable specifications stipulated by the manufacturer as important for the compliance
with the requirements of the Electromagnetic Compatibility (EMC) Directive should be
adhered to.
(b) Correct earthing of equipment is vital for adequate EMC performance as well as electrical
safety;
(c) In the case where screened cables are used, exposure of the cores outside of the screen
should be kept to a minimum, consistent with practical installation requirements;
(d) Where the manufacturers of the control equipment advise that the system is sensitive to multiple
screen earths for each circuit, then their instructions in respect of these should be followed;
(e) Where required, the screen should have continuity throughout the whole circuit;
(f) Where it is necessary to cross fire alarm system cables with those that can potentially cause
interference, the cables should be crossed at right angles.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.1 Installation
6.1.5 Joints and terminations
Joints in conductors shall not be permitted except in runs in excess of 100 m. Joints and terminations
shall only be made in a suitable metal terminal box in an accessible space. Cable joined shall be
appropriately marked within the terminal box. The terminal box shall be marked ‘FIRE ALARM’ in
contrasting colour.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.2 Operations
The owner shall appoint a competent person to
supervise and coordinate all matters in relation to the
fire alarm systems. The person should be trained in
COMPETENT PERSON
operating the fire alarm system effectively.
When a signal is announced on the fire alarm panels,
fire or non-fire, the person should be capable of analysing
and interpreting the signal correctly and taking
appropriate actions.
In a false alarm or other fault annunciation, the source
of the false alarm or fault signal shall be made available
in a log record. Recommendations to prevent recurrence
of such events should also be included in the log record.
The person shall also be responsible for keeping all the
log records on routine preventive maintenance, repair and
alteration works carried out on the systems. (see Annex B)
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.2 Operations - Event Log Record – Kept for minimum of 12 Months
Annex B
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.3 Maintenance
6.3.1 General
The arrangements for maintenance with or without service contract shall be such as will ensure that a
competent person is available on call at all times to provide service in the event of any fault that
develops at the installation.
6.3.2 Limitation of false alarms (new sub-clause)
It is a common misconception that most false alarms arise from faults in equipment. In fact, most false
alarms arise from a combination of environment influences, fire-like phenomena, inappropriate action
by people in the building and accidental damage.
Note - It should not be assumed that, in the absence of other information, a false alarm needs to have arisen
from an equipment fault.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.3 Maintenance
6.3.2.2 Preventive maintenance (new sub-clause)
The number of false alarms that can be anticipated is virtually proportional to the number of automatic
fire detectors installed. The constant of proportionality will normally be highest where the fire detectors
are smoke detectors. Systems incorporating only manual call points or manual call points in
conjunction with heat detectors do not normally produce many false alarms.
Smoke detection systems with signal processing incorporating techniques specifically intended to
discriminate between certain unwanted alarms and real fires, are likely to offer better immunity to false
alarms.
Systems with pre-alarm warning feature enable investigation of conditions that would lead to an
unwanted alarm if no action is taken.
Owner’s representative, competent contractor or servicing organisation shall inspect the signal
processing data available from the smoke detection systems regularly and investigate any pre-alarm
warning.
For smoke detection systems without signal processing, regular cleaning or replacement of smoke
detectors is necessary.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.3 Maintenance
Preventive Maintenance
Sprinkler/Flow Switches Call Point
- use flow switch with - additional hinged
Timer Delay cover
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
Preventive Maintenance
Contamination
The optical initial set-up value of a new detector is stored in the integrated
EEPROM during the final inspection. The contamination value specifies by how
much this analog value has increased in comparison with the delivery state.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.3 Maintenance
6.3.3.1 General
Where the heat-sensitive element of thermal detectors or the enclosure of other detectors are found to
be coated with paint or any other material likely to affect the operation of the detectors, such material
shall be cleaned off or if necessary, have the detector replaced.
6.3.3.4 Monthly
(a) Simulate fire and fault condition at the manual call points and detectors on all alarm zones to ensure it is
operational. Confirm with the monitoring station that the fire alarm and fault signals have been received.
6.3.3.5 Annual
(a) The maintenance personnel should arrange to check the operation of at least 20 percent of the manual
call points and detectors in an installation each year. The selection of manual call points and detectors
to be tested should be spread over as many zones as possible and should be made in such a way that
all manual call points and detectors in an installation should have been checked at least once in 5 years.
The checking of the manual call points and detectors should take the form of in-situ testing to ensure it
is operational.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
Operation and maintenance manuals and “as installed” drawings of the complete installation including
the following:
Symbols as shown in Annex E shall be used on all drawings relevant to the fire alarm systems.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
SECTION SIX – INSTALLATION, OPERATION AND MAINTENANCE
6.4 Operation and maintenance manuals and “as installed” drawings
Annex E (Normative)
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Thank You
www.enterprisesg.gov.sg/quality-
standards/standards
This material contains confidential and/or official information. The terms and conditions
governing its use can be found at www.enterprisesg.gov.sg/Terms-of-Use.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Key Changes in SS 645 : 2019 –
Guidance for the selection of
detectors (Annex D)
29 August 2019
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Heat Detector Smoke
Detector
Carbon
Flame
Monoxide
Detector
Fire Detector
Video Image
Fire Detector
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
A.3 Heat detectors
A.3.1 General
• Unsuitable for the protection of places where large losses could be caused by small fires
• Before final selection of a detector, estimate the likely damage caused before operation of the heat
detector.
• Attention to the design size to which a fire must develop before detection.
Table A1 - Increased fire size required for equivalent heat detector effectiveness based on ceiling height
Heat detector mounting height Fire size ratio required for equivalent
(m) detection performance
3 1
6 5.5
9 15.5
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Smoke
Detector
Heat Detector
Carbon
Flame
Monoxide
Detector
Fire Detector
Video Image
Fire Detector
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
A.4.2.6 Ducts
• Install smoke detectors used for sensing smoke in air-handling ducts
• Choose where the best sample of smoke can be obtained.
• Air-sampling probes are necessary for adequate response.
• Installation in accordance to manufacturer’s recommendations
• Conduct tests for a satisfactory sampling of the ducted air.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Smoke
Heat Detector
Detector
Carbon Flame
Monoxide Detector
Fire Detector
Video Image
Fire Detector
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
A.5 Carbon monoxide fire detectors (new sub-clause)
A.5.1 General
• Limited service life because, as the sensor ages, it may become less sensitive.
• Maintenance strictly in accordance with the manufacturer's requirements.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
A.5.2.2 Stratification
• CO fire detectors may be less affected by stratification.
A.5.2.3 Airflow
• Air movement does not significantly affect the response of the CO fire detector
• Note: CO gas has greater mobility than smoke but it can be diluted by ventilation
systems.
• Same considerations as for smoke detector should be taken in account.
• Recirculating systems confined to a single room has little effect on dilution as this is
similar to the natural diffusion of the CO gas.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
A.5.2.4 Ducts
CO fire detectors are not considered suitable for use with duct sampling units due
to CO dilution.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Smoke
Heat Detector
Detector
Carbon
Monoxide Flame
Fire Detector Detector
Video Image
Fire Detector
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
Ultraviolet (UV) flame detectors Single-channel infra-red (IR)
flame detectors
• Solar blind and resistant to giving false alarms for high • Solar blind by using filtering techniques.
temperature heat sources.
• Limited detection range
• Suitable for both hydrocarbon and metal-based fires.
• Sensitive to black-body radiation leading to a possible
• Operate quickly but the ability to do so may increase generation of false alarm.
the number of false alarms from the device
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
Ultraviolet (UV)/ infra-red (IR) Dual-channel infra-red (IR/IR) flame
single-channel flame detectors detectors
• Contain two sensors. • Designed with an additional infra-red to measure the
background IR radiation level.
• Only alarms when both UV and IR are detected.
• Produce fewer false alarms than either single-channel
• Lower reliability.
UV or IR detectors and are solar blind.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Smoke
Heat Detector
Detector
Carbon Flame
Monoxide Detector
Fire Detector
Video Image
Fire Detector
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Annex D
Guidance For The Selection Of Detectors
(Informative)
A.7 Video image fire detectors (new sub-clause)
A.7.1 General
• A discrete, self-contained automatic flame and/or smoke detection video camera
device.
• Use of video image analysis with the clear line-of-sight in real time.
• Displayed through alarms and video signals through networking and interfacing
devices.
• Connected directly to the signalling line circuits of a fire alarm system.
• Ability to provide early warning and early response to a fire incident.
• Also for applications where traditional technologies are not practical or effective.
• Detect smoke particles and with minimum lighting conditions.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.
Thank You
www.enterprisesg.gov.sg/quality-
standards/standards
This material contains confidential and/or official information. The terms and conditions
governing its use can be found at www.enterprisesg.gov.sg/Terms-of-Use.
Information on this slide is confidential. It shall not be used or referred to by third parties without prior written consent from Enterprise Singapore.