C&D Tel 12-160F PDF
C&D Tel 12-160F PDF
C&D Tel 12-160F PDF
NR
CY
TU
CL
RE
121022
E
12-380
LEAD
TRUE
FRONT
ACCESS
®
TEL12-160FW
TEL12-160F
TEL12-180F
THE MOMENT OF TRUTH HAS ARRIVED
TRUE Performance - 100% out of box capacity ratings at installation
TRUE Front Access Terminals - ensuring reliability & connection versatility
TRUE High Energy Density - highest true energy density solution in the market
TRUE Long life design - Telcordia SR-4228 industry leading 13 year service life
TRUE Seismic System - highest capacity energy storage system seismic NEBS tested
TRUE Flexibility - multiple models to fit each customers unique power system demands
12-1022/0512/CD www.cdtechno.com
SPECIFICATIONS
Ampere Hour Capacity to 1.75 Volts per Cell @ 77°F (25°C)
Discharge in Hrs.
Model 1 2 3 4 5 6 7 8 9 10 12 16 20 24 36 48 72 100
TEL12-160FW 111.1 127.4 137.2 143.8 149.0 153.1 156.7 159.7 162.1 164.1 167.6 172.9 176.6 179.6 185.4 189.0 193.2 195.8
TEL12-160F 107.1 124.4 134.6 141.5 146.7 150.8 154.3 157.3 159.5 161.5 164.7 169.4 172.6 174.9 179.2 181.4 183.4 183.8
TEL12-180F 123.1 143.5 155.2 163.2 169.2 174.0 177.9 181.2 184.0 186.4 190.4 196.3 200.3 203.3 208.9 211.9 214.6 215.5
Recommended Maximum Charging C20/5 Amperes (40.1A for TEL12-180F; 34.5A for TEL12-160F;
Current Limit 35.3A for TEL12-160FW)
Float Charging Voltage 13.5 to 13.8 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C20/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. Batteries stored at temperatures greater than 77°F
(25°C) will require recharge sooner than batteries stored at lower
temperatures. See C&D bulletin 41-7272, Self-Discharge and Inventory
Control for details.
Equalize charge and cycle 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
service voltage
12-1022/0512/CD 2 www.cdtechno.com
DIMENSIONS
A B C D E F G H
MODEL in mm in mm in mm in mm in mm in mm in mm in mm
TEL12-160FW 16.56 420.57 17.72 449.99 18.22 462.79 16.37 415.90 9.69 246.05 10.10 256.54 6.94 176.33 6.88 174.70
TEL12-160F 20.35 516.86 21.51 546.25 22.01 559.05 20.16 512.17 10.73 272.47 11.14 282.96 4.95 125.73 4.86 123.39
TEL12-180F 20.35 516.86 21.51 546.25 22.01 559.05 20.16 512.17 12.19 309.55 12.60 320.04 4.95 125.73 4.86 123.39
* All dimensions in inches and (millimeters). All dimensions are for reference only. Contact a C&D Representative for complete dimensions information.
* Note: Batteries to be mounted with 0.5 IN (12.5mm) spacing minimum and free air ventilation.
Additional ratings and application information is available in the Battery Selection Program at www.cdstandbypower.net
12-1022/0512/CD 3 www.cdtechno.com
FRONT ACCESS BATTERY RACK SYSTEMS
• TRUE High Energy Density with TEL12-180F • TRUE Seismic Systems Shaker Table Tested
• Front Access for Ease of Installation and Maintenance • Tested to GR-63-CORE and GR-1089-CORE
• Pre Wired from the Factory • Cable Management System
• Integrated Grounding Hardware and Multiple Grounding points • Thermal Management Features Ensuring Long Life
Five Tier Seismic Zone 2 Five Tier Seismic Zone 4 Six Tier Seismic Zone 4
NEBS Zone 2 5Tier Racks NEBS Zone 4 5Tier Racks NEBS Zone 4 6Tier Racks
System Part System Part System Part Description
Description Description
Number Number Number
110-7050-01 (+) 24VDC Top (+) 24VDC Top (+) 24VDC Top
110-7051-01 110-7052-01
Common Bus Common Bus Common Bus
(+) 24VDC 10x 100A (+) 24VDC 10x 100A (-) 48VDC Top
110-7050-02 110-7051-02 110-7052-05
Ckt Bkrs Ckt Bkrs Common Bus
Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc.
without notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes
no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its control,
1400 Union Meeting Road C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suitability
P.O. Box 3053 • Blue Bell, PA19422-0858 of such product(s) for any particular use or in any specific application or arising from any course of dealing or usage
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630 of trade. The user is solely responsible for determining the suitability of the product(s) featured herein for user’s
customersvc@cdtechno.com intended purpose and in user’s specific application.
www.cdtechno.com Copyright 2012 C&D TECHNOLOGIES, INC. Printed in U.S.A. 12-1022 0512/CD