TEL12-105F TEL12-105FS: Valve Regulated Lead Acid Battery For Communications Standby Power Applications
TEL12-105F TEL12-105FS: Valve Regulated Lead Acid Battery For Communications Standby Power Applications
TEL12-105F TEL12-105FS: Valve Regulated Lead Acid Battery For Communications Standby Power Applications
Tel 12-105FS
TEL12-105F FEATURES
• Flame-arresting one-way pressure-relief • Multicell design for ease of
TEL12-105FS •
vent for safety and long life.
Thermally welded case-to-cover bond to
installation and maintenance.
• Not restricted for air transport –
VALVE REGULATED ensure a leak-proof seal. Complies with IATA/ICAO Special
• Flame-retardant polypropylene case
LEAD ACID BATTERY and cover compliant with UL94 V-0
Provision A67
• Not restricted for surface transport –
FOR COMMUNICATIONS with an Oxygen Limiting Index of
classified as non-hazardous material
greater than 28.
STANDBY POWER • Absorbent Glass Mat (AGM)
as related to DOT-CFR Title 49 parts
171-189
APPLICATIONS technology for efficient gas
recombination 99% plus. • Not restricted for water transport –
• Thick positive plate design for maximum classified as non-hazardous material
service float life – 10 year design life. per IMDG Amendment 27.
• Front accessible threaded copper alloy • Battery design allows for 48VDC
terminals for ease of assembly and configuration in a standard 23" relay
reduced maintenance. rack in less than 10" height.
• Complies with UL1778, 924, 1989
• Minimizes battery interconnection cost
and 94 V-0.
and resistance with supplied copper
• UL-recognized component. connectors.
• Can be used in any orientation. Upright,
• TEL12-105F overall length = 22.51"
side or end mounting recommended.
• TEL12-105FS overall length = 21.95"
Discharge in Hours 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 10.00 12.00 20.00 24.00 72.00 100.00
Amp-Hr Capacity 66.3 77.6 84.6 89.2 92.5 95.4 98.0 100 102 104 109 110 117 119
21.12 4.94
[536.4] [125.5]
1.35
[34.2]
[27.3]
1.08
[228.6]
9.00
4.83
20.81 [122.7]
[528.5]
*All dimensions in inches and (millimeters). All dimensions are for reference only.
TEL12-105F/FS – Specifications Contact a C&D Representative for complete dimensional information.
Capacity 100 Ah @ 8 hour rate to 1.75 volts per cell @ 77°F (25°C)
98.1 Ah @ 10 hour rate to 1.80 volts per cell @ 20°C (68°F)
Operating Temperature Range Discharge; -40°F (-40°C) to +160°F (71°C), Charge; -10°F (-23°C) to +140°F (60°C)
(with temperature compensation)
Note: Buss connection designed for 0.375" (1.0 cm) battery spacing
Batteries to be mounted with 0.3" (0.75 cm) spacing minimum and free air ventilation.
Refer to battery installation and operating instructions for additional information. Specifications subject to change without notification.