TEL12-105F TEL12-105FS: Valve Regulated Lead Acid Battery For Communications Standby Power Applications

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Tel 12-105F

Tel 12-105FS

TEL12-105F FEATURES
• Flame-arresting one-way pressure-relief • Multicell design for ease of
TEL12-105FS •
vent for safety and long life.
Thermally welded case-to-cover bond to
installation and maintenance.
• Not restricted for air transport –
VALVE REGULATED ensure a leak-proof seal. Complies with IATA/ICAO Special
• Flame-retardant polypropylene case
LEAD ACID BATTERY and cover compliant with UL94 V-0
Provision A67
• Not restricted for surface transport –
FOR COMMUNICATIONS with an Oxygen Limiting Index of
classified as non-hazardous material
greater than 28.
STANDBY POWER • Absorbent Glass Mat (AGM)
as related to DOT-CFR Title 49 parts
171-189
APPLICATIONS technology for efficient gas
recombination 99% plus. • Not restricted for water transport –
• Thick positive plate design for maximum classified as non-hazardous material
service float life – 10 year design life. per IMDG Amendment 27.
• Front accessible threaded copper alloy • Battery design allows for 48VDC
terminals for ease of assembly and configuration in a standard 23" relay
reduced maintenance. rack in less than 10" height.
• Complies with UL1778, 924, 1989
• Minimizes battery interconnection cost
and 94 V-0.
and resistance with supplied copper
• UL-recognized component. connectors.
• Can be used in any orientation. Upright,
• TEL12-105F overall length = 22.51"
side or end mounting recommended.
• TEL12-105FS overall length = 21.95"

12 Volts – 100 Ampere Hour Capacity @ 8 Hour Rate


Ampere Hour Capacity to 1.75 Volts per Cell @ 77°F (25°C)

Discharge in Hours 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 10.00 12.00 20.00 24.00 72.00 100.00
Amp-Hr Capacity 66.3 77.6 84.6 89.2 92.5 95.4 98.0 100 102 104 109 110 117 119

C&D Technologies, Inc.


DYNASTY Division
900 East Keefe Avenue
Milwaukee, WI 53212
Phone: 800-396-2789
Fax: 414-961-6506

Form 41-9002 (Rev. 06/02) Printed in the U.S.A.


TEL12-105F/FS
21.95 (TEL 12-105 FS)
[557.5]

21.12 4.94
[536.4] [125.5]

22.51 (TEL 12-105 F)


[571.8]

1.35
[34.2]

[27.3]
1.08
[228.6]
9.00

4.83
20.81 [122.7]
[528.5]

*All dimensions in inches and (millimeters). All dimensions are for reference only.
TEL12-105F/FS – Specifications Contact a C&D Representative for complete dimensional information.

Cells Voltage Maximum Short Circuit Ohms Imped.


Per Unit Per Unit Weight Electrolyte Discharge Current Current 60 Hz (Ω)
6 12.84 80 lbs. Absorbed H2SO4 800 Amps 4000 Amps 0.0030 Ohms
36 kg SG = 1.300 @ 0.1 sec.

Capacity 100 Ah @ 8 hour rate to 1.75 volts per cell @ 77°F (25°C)
98.1 Ah @ 10 hour rate to 1.80 volts per cell @ 20°C (68°F)
Operating Temperature Range Discharge; -40°F (-40°C) to +160°F (71°C), Charge; -10°F (-23°C) to +140°F (60°C)
(with temperature compensation)

Nominal Operating Temperature Range +74°F (23°C) to +80°F (27°C)


Floating Charging Voltage 13.5 to 13.8 VDC/unit Average @ 77°F (25°C)
Recommended Maximum Charging C/5 amperes (21.8 amps @ 100% depth of discharge)
Current Limit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Maximum voltage allowed = 4% P-P
Maximum current allowed = 5.45 amperes RMS (C/20)
Self Discharge Dynasty Telecom batteries may be stored for up to 6 months at 77°F (25°C) and
then a freshening charge is required. For higher temperatures the time interval will
be shorter.
Accessories Inter unit connectors, racks and cabinet systems are avaialble.
Terminal Threaded copper alloy insert terminal to accept 1/4-20 UNC bolt.
Terminal Hardware Initial Torque 110 in.-lbs. (12.4 N-m).

Constant Current Discharge Ratings – Amperes @ 77°F (25°C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 10.00 12.00 20.00 24.00 72.00 100.00
1.75 66.3 38.8 28.2 22.3 18.5 15.9 14.0 12.5 10.2 8.68 5.45 4.59 1.63 1.19
1.80 64.7 38.1 27.8 21.9 18.2 15.7 13.8 12.3 10.1 8.54 5.36 4.52 1.60 1.16
1.85 61.3 36.6 26.8 21.2 17.6 15.2 13.3 11.9 9.75 8.26 5.18 4.37 1.54 1.12
1.90 55.1 33.3 24.5 19.4 16.2 13.9 12.2 11.0 8.97 7.60 4.76 4.01 1.41 1.03

Note: Buss connection designed for 0.375" (1.0 cm) battery spacing
Batteries to be mounted with 0.3" (0.75 cm) spacing minimum and free air ventilation.
Refer to battery installation and operating instructions for additional information. Specifications subject to change without notification.

You might also like