Defining Size and Location of Capacitor in Electrical System (1) - EEP
Defining Size and Location of Capacitor in Electrical System (1) - EEP
Defining Size and Location of Capacitor in Electrical System (1) - EEP
Premium Membership
Get access to premium HV/MV/LV technical articles, electrical guides, studies and
much more! Apply 20% OFF Code: EEP09PE
More Information
Power Substation / Testing and Commissioning
Content
Type of Capacitor Bank as per Its Application:
1. Fixed type capacitor banks
2. Automatic type capacitor banks
3. Types of APFC – Automatic Power Factor Correction
Type of Capacitor as per Construction
Selecting Size of Capacitor Bank
Selection of Capacitor as per Non Liner Load
Configuration of Capacitor:
1. Star-Solidly Grounded
2. Star-Ungrounded
3. Delta-connected Banks
Effect of series and Parallel Connection of capacitor:
1. Parallel Connection
2. Series Connection
Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 1/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
The reactive power supplied by the fixed capacitor bank is constant irrespective of any
variations in the power factor and the load of the receivers. These capacitor banks are
switched on either manually (circuit breaker / switch) or semi automatically by a
remote-controlled contactor.
These capacitors are applied at the terminals of inductive loads (mainly motors), at bus
bars.
Disadvantages:
Fixed Capacitor may provide leading power factor under light load conditions, Due to
this result in overvoltages, saturation of transformers, mal-operation of diesel
generating sets, penalties by electric supply authorities.
Application:
Go to Content ↑
The reactive power supplied by the capacitor bank can be adjusted according to
variations in the power factor and the load of the receivers.
Where the kvar rating of the capacitors is less than, or equal to 15% of the supply
transformer rating, a fixed value of compensation is appropriate.
Go to Content ↑
Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 3/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
Advantages:
Application:
Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 4/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
Go to Content ↑
Application:
2. Heavy-duty
Application:
Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 5/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
3. LT Capacitor
Application:
Go to Content ↑
For HT capacitors the minimum ratings that are practical are as follows:
Unit sizes lower than above is not practical and economical to manufacture.
When capacitors are connected directly across motors it must be ensured that the
rated current of the capacitor bank should not exceed 90% of the no-load current of the
motor to avoid self-excitation of the motor and also over compensation.
Precaution must be taken to ensure the live parts of the equipment to be compensated
should not be handled for 10 minutes (in case of HT equipment) after disconnection of
supply.
Crane motors or like, where the motors can be rotated by mechanical load and motors
with electrical braking systems, should never be compensated by capacitors directly
across motor terminals. Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 6/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
For direct compensation across transformers the capacitor rating should not
exceed 90 % of the no-load KVA of the motor.
Go to Content ↑
Selection of Capacitor is depending upon many factor i.e. operating life, Number of
Operation, Peak Inrush current withstand capacity.
For selection of Capacitor we have to calculate Total Non-Liner Load like: UPS,
Rectifier, Arc/Induction Furnace, AC/DC Drives, Computer, CFL Blubs, and CNC
Machines.
Calculation of Non liner Load, Example: Transformer Rating 1MVA,Non Liner Load
100KVA
% of non Liner Load = (Non Liner Load/Transformer Capacity) x100 = (100/1000)
x100=10%.
According to Non Linear Load Select Capacitor as per Following Table.
% Non Liner
Type of Capacitor
Load
<=10% Standard Duty
Up to 15% Heavy Duty
Up to 20% Super Heavy Duty
Capacitor +Reactor
Up to 25%
(Detuned)
Above 30%
Go to Content ↑
Configuration of Capacitor
Power factor correction capacitor banks can be configured in the following ways:
Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 7/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
Go to Content ↑
1. Star-Solidly Grounded
Initial cost of the bank may be lower since the neutral does not have to be insulated
from ground.
Capacitor switch recovery voltages are reduced
High inrush currents may occur in the station ground system.
The grounded-Star arrangement provides a low-impedance fault path which may
require revision to the existing system ground protection scheme.
Typically not applied to ungrounded systems. When applied to resistance-grounded
systems, difficulty in coordination between capacitor fuses and upstream ground
protection relays (consider coordination of 40 A fuses with a 400 A grounded
system).
Application: Typical for smaller installations (since auxiliary equipment is not
required)
Go to Content ↑
2. Star-Ungrounded
Industrial and commercial capacitor banks are normally connected ungrounded Star,
with paralleled units to make up the total kvar.
If only one unit is needed to make the total kvar, the units in the other phases will
not be overloaded if it fails.
In industrial or commercial power systems the capacitors are not grounded for a variety
of reasons. Industrial systems are often resistance grounded. A grounded Star
connection on the capacitor bank would provide a path for zero sequence currents and
the possibility of a false operation of ground fault relays.
Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 8/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
Also, the protective relay scheme would be sensitive to system line-to-ground voltage
Unbalance, which could also result in false relay tripping.
Go to Content ↑
3. Delta-connected Banks
Delta-connected banks are generally used only at distributions voltages and are
configured with a Single series group of capacitors rated at line-to-line voltage. With
only one series group of units no overvoltage occurs across the remaining capacitor units
from the isolation of a faulted capacitor unit.
Therefore, unbalance detection is not required for protection and they are not treated
further in this paper.
Go to Content ↑
This is the most popular method of connection. The capacitor is connected in parallel
to the unit. The voltage rating of the capacitor is usually the same as or a little higher
than the system voltage.
Go to Content ↑
Series Connection
This method of connection is not much common. Even though the voltage regulation is
much high in this method,
Stop 📃
https://electrical-engineering-portal.com/defining-size-and-location-of-capacitor-in-electrical-system-1 9/10
23/10/2019 Defining size and location of capacitor in electrical system (1) | EEP
One is that because of the series connection, in a short circuit condition the capacitor
should be able to withstand the high current. The other is that due to the series
connection due to the inductivity of the line there can be a resonance occurring at a
certain capacitive value.
This will lead to very low impedance and may cause very high currents to flow
through the lines.
Go to Content ↑
Jignesh Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E (Electrical). He is
member of Institution of Engineers (MIE), India. He has more than 13 years experience
in transmission & distribution-energy theft detection and maintenance electrical projects.