Devicenet Lean: Application Manual
Devicenet Lean: Application Manual
Devicenet Lean: Application Manual
Application manual
DeviceNet Lean
Trace back information:
Workspace R12-2 version a4
Checked in 2012-09-13
Skribenta version 1171
Application manual
DeviceNet Lean
RobotWare 5.15
Table of contents
Manual overview ............................................................................................................................... 7
Product documentation, M2004 ....................................................................................................... 11
Safety ................................................................................................................................................ 13
1 Introduction 15
1.1 About DeviceNet Lean ....................................................................................... 15
1.2 Definition of I/O units ......................................................................................... 18
2 Hardware description 19
2.1 DeviceNet Lean card, DSQC 572 .......................................................................... 19
2.2 Connections ..................................................................................................... 22
2.2.1 Shield grounding and power ...................................................................... 22
2.2.2 Connection of the DeviceNet Lean bus ........................................................ 23
2.2.3 Selecting cables ...................................................................................... 25
3 Configuration 27
3.1 Introduction to configuration ................................................................................ 27
3.2 DeviceNet Lean configuration .............................................................................. 31
4 System parameters 37
4.1 Introduction ...................................................................................................... 37
4.2 Type Bus ......................................................................................................... 39
4.2.1 DeviceNet Lean Master Address ................................................................ 39
4.2.2 Auto Configuration .................................................................................. 40
4.2.3 Bus Scan ............................................................................................... 41
4.2.4 Connector ID .......................................................................................... 42
4.3 Type Unit Type ................................................................................................. 43
4.3.1 Vendor ID .............................................................................................. 43
4.3.2 Product Code ......................................................................................... 44
4.3.3 Production Inhibit Time ............................................................................ 45
4.3.4 Poll Rate ................................................................................................ 46
4.3.5 Quick Connect ........................................................................................ 47
4.4 Type Unit ......................................................................................................... 48
4.4.1 DeviceNet Lean Address .......................................................................... 48
5 Trouble shooting 49
5.1 Bus off ............................................................................................................ 49
5.2 Bus Scan ......................................................................................................... 50
3HAC034095-001 Revision: F 5
© Copyright 2008-2012 ABB. All rights reserved.
Table of contents
Index 105
6 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
Manual overview
Manual overview
About this manual
This manual describes the DeviceNet Lean option and contains instructions for
the DeviceNet Lean master configuration. It also describes the configuration of
supported boards and units.
Usage
This manual should be used during installation and configuration of the DeviceNet
Lean bus and upgrading of the DeviceNet Lean option.
Prerequisites
The reader should have the required knowledge of:
• Mechanical installation work
• Electrical installation work
• System parameter configuration
Organization of chapters
The manual is organized in the following chapters:
Chapter Contents
1 Provides an overview of the DeviceNet Lean fieldbus and includes the fol-
lowing:
• A general description of DeviceNet Lean and the communication
protocol
• Description of how the DeviceNet Lean master unit and I/O units are
connected in a robot system
• Definition of I/O units in the IRC5 controller and the configuration of
the controller
2 Describes the DeviceNet Lean master.
The chapter also describes:
• Communication units
• How to connect the DeviceNet Lean master to an I/O unit
• Termination
• Cable types and data rates
• Repeater functions
3 Provides an overview of the DeviceNet Lean configuration. It also contains
descriptions of workflows.
4 Describes the DeviceNet Lean specific system parameters.
5 Contains information and instructions for trouble shooting the DeviceNet
Lean connection.
Continued
Chapter Contents
6 Provides detailed descriptions of I/O units available from ABB Robotics
that support DeviceNet Lean.
The chapter also describes:
• DeviceNet Lean bus status LEDs at power-up
• How to set the DeviceNet Lean bus address
References
Document references
References Document ID
Application manual - Conveyor tracking 3HAC16587-1
Application manual - Motion coordination and supervision 3HAC18154-1
Application manual - Robot communication and I/O control 3HAC020435-001
Operating manual - IRC5 with FlexPendant 3HAC16590-1
Operating manual - RobotStudio 3HAC032104-001
Product manual - IRC5 3HAC021313-001
Product specification - IRC5 with FlexPendant 3HAC041344-001
Technical reference manual - System parameters 3HAC17076-1
Technical reference manual - RAPID Instructions, Functions 3HAC16581-1
and Data types
Other references
References Description
www.odva.org The web site of ODVA (Open DeviceNet
Vendor Association).
ODVA DeviceNet Specification, revision 2.0 Specification from ODVA (Open DeviceNet
Vendor Associations).
Revisions
Revision Description
- First edition
A The Workflow section is added in the DeviceNet Lean Configuration chapter.
The image of DeviceNet Lean board, DSQC 572, is updated.
Continued
Revision Description
B Updated for the RW 5.13 release.
Changes in the Introduction chapter.
• Added more features of DeviceNet Lean in the subsection What is
DeviceNet Lean? on page 15.
• Updated the section I/O messages - connection types on page 16.
• Updated the subsection General on page 18 in the Definition of I/O Unit
section.
• Updated the subsection Further information on page 18 in the Definition
of I/O Unit section.
Changes in the Configuration chapter.
• Added the subsection Explict Messaging services on page 27 in the
Introduction to configuration section.
• Added the subsection Predefined Unit Types on page 31 in the Devi-
ceNet Lean configuration section.
• Added the subsection Configuration approaches on page 31 in the
DeviceNet Lean configuration section.
• Updated the subsection Predefined Bus on page 31 in the DeviceNet
Lean configuration section.
• Updated the subsection Edit unit type on page 33 in the DeviceNet Lean
configuration section.
• Updated the images in the subsections Edit bus on page 33 and Edit
unit type on page 33 of the DeviceNet Lean configuration section.
Changes in the System Parameters chapter.
• Added the new system parameters Auto Configuration on page 40 and
Bus Scan on page 41 in the type Bus.
• Added the new system parameter Vendor ID on page 43 in the type Unit
Type.
• Updated the system parameters Product Code on page 44 and Produc-
tion Inhibit Time on page 45 in the type Unit Type.
Changes in the Trouble Shooting chapter.
• Added the section Bus Scan on page 50.
• Updated the section Bus off on page 49.
Changes in the Board and Units chapter.
• Updated the subsection I/O units on page 54 in the General section.
C Updated for the RW 5.13.02 release.
Changes in the Introduction chapter.
• Updated the section What is DeviceNet Lean? on page 15.
Changes in the Configuration chapter:
• Added more information in the section Explict Messaging services on
page 27.
• Added the new section Quick Connect on page 30.
• Added the new section POLLED connection on page 30.
• Added more predefined unit types to the table in the section Predefined
Unit Types on page 31.
• Added the fifth step to the procedure in the section Workflow - Automat-
ic configuration.
• Updated the image in the section Edit unit type on page 33.
Changes in the System parameters chapter.
• Added the new system parameters Poll Rate on page 46and Quick
Connect on page 47.
Changes in the Boards and units chapter.
• Updated the table Technical data on page 84 for the DSQC 651 board.
• Updated the table Technical data on page 91 for the DSQC 652 board.
• Updated the table Technical data on page 99 for the DSQC 653 board.
Continued
Revision Description
D Updated for the RW 5.14 release.
The following I/O units are included in the Unit descriptions chapter:
• DSQC 351A and 351B, DeviceNet Lean/INTERBUS gateways on page 59.
• DSQC 377A and DSQC 377B, Queue tracking units on page 66.
• DSQC 378A and DSQC 378B, DeviceNet Lean/CCLink gateways on
page 75.
E Updated for the RW 5.14.02 release.
• Added the new system parameter Connector ID.
F Updated the Introduction section in the chapter System parameters on page 37
for RW 5.15 release.
10 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
Product documentation, M2004
Product manuals
Manipulators, controllers, DressPack/SpotPack, and most other hardware will be
delivered with a Product manual that generally contains:
• Safety information.
• Installation and commissioning (descriptions of mechanical installation or
electrical connections).
• Maintenance (descriptions of all required preventive maintenance procedures
including intervals and expected life time of parts).
• Repair (descriptions of all recommended repair procedures including spare
parts).
• Calibration.
• Decommissioning.
• Reference information (safety standards, unit conversions, screw joints, lists
of tools ).
• Spare parts list with exploded views (or references to separate spare parts
lists).
• Circuit diagrams (or references to circuit diagrams).
Application manuals
Specific applications (for example software or hardware options) are described in
Application manuals. An application manual can describe one or several
applications.
Continued
Operating manuals
The operating manuals describe hands-on handling of the products. The manuals
are aimed at those having first-hand operational contact with the product, that is
production cell operators, programmers, and trouble shooters.
The group of manuals includes (among others):
• Operating manual - Emergency safety information
• Operating manual - General safety information
• Operating manual - Getting started, IRC5 and RobotStudio
• Operating manual - Introduction to RAPID
• Operating manual - IRC5 with FlexPendant
• Operating manual - RobotStudio
• Operating manual - Trouble shooting IRC5, for the controller and manipulator.
12 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
Safety
Safety
Safety of personnel
When working inside the robot controller it is necessary to be aware of
voltage-related risks.
A danger of high voltage is associated with the following parts:
• Units inside the controller, for example I/O units, can be supplied with power
from an external source.
• The mains supply/mains switch.
• The power unit.
• The power supply unit for the computer system (230 VAC).
• The rectifier unit (400-480 VAC and 700 VDC). Capacitors!
• The drive unit (700 VDC).
• The service outlets (115/230 VAC).
• The power supply unit for tools, or special power supply units for the
machining process.
• The external voltage connected to the controller remains live even when the
robot is disconnected from the mains.
• Additional connections.
Therefore, it is important that all safety regulations are followed when doing
mechanical and electrical installation work.
Safety regulations
Before beginning mechanical and/or electrical installations, ensure you are familiar
with the safety regulations described in Product manual - IRC5.
3HAC034095-001 Revision: F 13
© Copyright 2008-2012 ABB. All rights reserved.
This page is intentionally left blank
1 Introduction
1.1 About DeviceNet Lean
1 Introduction
1.1 About DeviceNet Lean
What is DeviceNet?
DeviceNet is a communications link to connect industrial devices. It is a simple
networking solution that reduces both cost and time to wire and install industrial
automation devices, and the direct connectivity provides improved communication
between devices. DeviceNet is an open network standard.
Here are some examples of applications:
• Peer-to-peer data exchange where a DeviceNet product can produce and
consume messages
• Master/slave operation defined as a proper subset of Peer-to-Peer
• A DeviceNet product can function as a client or server, or both
Continued
Hardware overview
The hardware of the DeviceNet Lean fieldbus consists of a master unit, DSQC 572,
and distributed I/O units (called slave units). The DSQC 572 is mounted in a PCI
slot and is connected to the main computer using a cable.
Slave units
The slave units are attached to the fieldbus network and controlled using DSQC
572.
Continued
Illustration, example
The following illustration shows an example of the hardware.
xx0900000106
A DSQC 572, DeviceNet Lean PCI card. Placed in the computer module.
B Terminating resistor (121 Ohm).
C DSQC 608/609, DeviceNet power supply 24 V
D DSQC 652, Distributed digital I/O unit. The maximum length of the drop
cable is 6 m.
E DSQC 608/609, Customer power supply 24 V
F IRC5 controller
Bus configuration
The configuration of the bus is done using RobotStudio, see Operating
manual - RobotStudio.
3HAC034095-001 Revision: F 17
© Copyright 2008-2012 ABB. All rights reserved.
1 Introduction
1.2 Definition of I/O units
General
It is possible to connect any ODVA certified I/O unit that supports the predefined
master/slave connection set to the DeviceNet Lean bus. But, the functionality is
guaranteed only with ABB Robotics I/O unit types. For more information about the
ABB Robotics I/O units, see Boards and units on page 51.
Further information
The following table provides references to additional information:
Information See
How to install the I/O units mechanically and Product manual - IRC5, section Replacement
electrically. of I/O units and gateways, IRC5.
Allowed configurations of I/O units and how Technical reference manual - System para-
to setup the configurations. meters.
18 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
2 Hardware description
2.1 DeviceNet Lean card, DSQC 572
2 Hardware description
2.1 DeviceNet Lean card, DSQC 572
Description
The DSQC 572 is a PCI card mounted in the computer module in the second slot
for PCI cards. DSQC 572 does not use the PCI connector on the mother board,
instead it is connected with a ribbon cable to the motherboard.
xx0700000432
Prerequisites
The following configurations are required to setup the DeviceNet Lean card:
• Main computer revision 11 or later
• RobotWare 5.13 or later version
• DeviceNet Lean option installed
Continued
xx0900000105
Continued
xx0200000292
The following table shows the connections to the DeviceNet Lean connector:
Signal name I/O pin Wire color Function
V- 1 black DeviceNet Lean network negative power (0 V)
CANL 2 blue DeviceNet Lean communication bus terminal (low)
Shield 3 bare Network cable shield
CANH 4 white DeviceNet Lean communication bus terminal (high)
V+ 5 red DeviceNet Lean network positive power (24 V DC)
LEDs
Module Status (MS) LED:
LED color Description
Off No power.
Green The device is in normal operation.
Flashing green Configuration error or no configuration.
Flashing red Recoverable fault.
Red Unrecoverable fault.
3HAC034095-001 Revision: F 21
© Copyright 2008-2012 ABB. All rights reserved.
2 Hardware description
2.2.1 Shield grounding and power
2.2 Connections
General
The DeviceNet Lean shield and V- should be interconnected and grounded at only
one place in the DeviceNet Lean network. For more advanced connections with
several power supplies refer to the DeviceNet Specification, see References on
page 8.
Grounding
The following illustration shows an example of cable grounding.
xx0300000525
22 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
2 Hardware description
2.2.2 Connection of the DeviceNet Lean bus
Illustration
The following illustration shows an example of how to connect the DeviceNet Lean
bus.
xx0800000392
A Computer unit
B DeviceNet Lean board
C DeviceNet Lean connector
D 121 ohm, 1%, 0.25 W metal film resistor
E I/O unit
Continued
Physical connection between DeviceNet Lean bus and DeviceNet Lean node
The following figure shows how the next DeviceNet Lean node is connected to the
DeviceNet Lean bus.
xx0400000849
xx0400000674
24 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
2 Hardware description
2.2.3 Selecting cables
xx0800000394
A Terminator
B Trunk line
C Drop line
D Tap
E Zero drop
F Node
G Short drop
H T-connector
3HAC034095-001 Revision: F 25
© Copyright 2008-2012 ABB. All rights reserved.
This page is intentionally left blank
3 Configuration
3.1 Introduction to configuration
3 Configuration
3.1 Introduction to configuration
Controller software
The IRC5 controller must be installed with software that supports DeviceNet Lean
- that is, the option for DeviceNet Lean must be installed.
For description of how to add the DeviceNet Lean option, see Operating
manual - RobotStudio.
Continued
The preceding example shows how to use the -DL_Path and -DL_Service
parameters. The syntax used in the -DL_Path command and in the I/O unit's EDS
file is same. If a Class, Instance, or Attribute below 0x10 is specified, it is important
to include a "0" before the value. For example, the value 8 is written as 08 in the
-DL_Path string.
Following is a short description of the syntax used in the -DL_Path parameter.
"Path length, 20 Class 24 Instance 30 Attribute, Data type, Data type
length"
The following table provides a description of the parameters used in the syntax:
Parameter Description
Path length The byte count for the "20 64 24 01 30 05" string.
Class The DeviceNet Lean Class number.
Instance The instance number of the class.
Attribute The attribute of the specified instance.
Data type The data format of the attribute.
Data type length The length in bytes of the specified Data type. The highest al-
lowed value is 0x20 (32 bytes).
Following are the allowed values of the Data type and Data type length parameters:
Data Type Description Data type length
0x01 Signed 16-bit value 2
0x02 Unsigned 16 bit integer value 2
0x03 Signed 16-bit value 2
0x04 Logical Boolean with values TRUE and FALSE 1
0x05 Signed 8-bit integer value 1
0x08 Unsigned 8-bit integer value 1
0x09 Unsigned 32-bit integer value 4
0x0B 32-bit floating point value 4
0x16 Character string (1 byte per character, 1 byte X
length indicator)
0x18 Unsigned 8-bit integer value 1
0xC1 Logical Boolean with values TRUE and FALSE 1
0xC2 Signed 8-bit integer value 1
Continued
The-OrderNr parameter is used to specify in what order the commands are send
to the I/O unit.
If an FCI command is rejected by the I/O unit, the DeviceNet Lean master will
generate an event message with the error code returned by the I/O unit. The
following table shows some of the possible return values:
General Error Code Semantics
0x02 Resource unavailable.
0x05 Path destination unknown.
0x08 Service not supported.
0x09 Invalid attribute value.
0x0B Already in requested mode/state.
0x0D Object already exists.
0x0E Attribute not settable.
0x13 Not enough data.
0x14 Attribute not supported.
0x16 Object does not exist
CIP routing
To be able to use CIP routing the system parameter Explicit Messaging must be
set in the unit configuration for those units that will use CIP routing. For details
about the unit configuration, refer to Application manual - EtherNet/IP Fieldbus
Adapter.
Continued
Quick Connect
The Quick Connect functionality supported by the DeviceNet Lean master allows
the I/O units to be configured to use Quick Connet. Quick Connect allows the I/O
unit to skip certain startup tests and thereby improve the general startup time of
the I/O unit when used in tool change applications. To activate the Quick Connect
functionality, use the system parameter Quick Connect on page 47.
Additional configuration with Field Bus Commands is not needed to use the Quick
Connect functionality in DeviceNet Lean. If Quick Connect is activated but not
supported by the I/O unit, the connection attempt from the DeviceNet Lean master
might fail.
POLLED connection
By default , the DeviceNet Lean master always tries to create a COS connection
type against a configured I/O unit. If the I/O unit do not support a COS connection,
a POLLED connection is created with a pollrate decided by the DeviceNet Lean
master itself.
If a POLLED connection type is needed or if the pollrate needs to be configured
manually, it is possible to force create a POLLED connection. This is done by
specifying a value other then zero in the Pollrate parameter. For information about
the Pollrate parameter, refer to Poll Rate on page 46.
30 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
3 Configuration
3.2 DeviceNet Lean configuration
Configuration
When the DeviceNet Lean option is installed in the IRC5 system, a number of
predefined types are installed. The following table provides descriptions defining
the types Bus, Unit Type and Unit.
Type Description
Bus A DeviceNet Lean bus must be defined before any communication on
the bus is possible - that is, define rules for the DeviceNet Lean master
to communicate on the network.
Unit Type When creating a unit type, some system parameters are fieldbus spe-
cific. For detailed information about the parameters see System para-
meters on page 37.
Unit See Technical reference manual - System parameters.
Signal See Technical reference manual - System parameters.
Predefined Bus
The predefined bus type DeviceNet_Lean is added by the DeviceNet Lean option.
Configuration approaches
Following are the three general configuration strategies that can be used while
configuring
Continued
Continued
Action Note
4. Warm start the IRC5 controller again to connect to the
configured I/O units.
5 If needed, remap or change the signals added on the I/O
unit to reflect the meaning of the data bits.
Edit bus
Action
1 In RobotStudio, click Configuration Editor and select I/O.
2 Click Bus, then right-click on the bus to edit and select Edit Bus.
3 In the Edit Bus dialog box, type the values for the parameters.
en0900000126
Continued
Action
3 In the Edit Unit Type dialog box, type the values for the parameters.
en0900000120
Action
1 In RobotStudio, click Configuration Editor and select I/O.
2 Click Unit, then right-click in the workspace and select Add Unit.
3 In the Edit Unit dialog box, type the values for the parameters.
en0900000076
Continued
Add signals
Action
1 In RobotStudio, click Configuration Editor and select I/O.
2 Click Signal, then right-click in the workspace and click Add Signal.
3 In the Edit Signal dialog box, type the values for the parameters.
xx0700000205
3HAC034095-001 Revision: F 35
© Copyright 2008-2012 ABB. All rights reserved.
This page is intentionally left blank
4 System parameters
4.1 Introduction
4 System parameters
4.1 Introduction
Unit
These parameters belong to the type Unit in the topic I/O.
Parameter For more information, see ...
Name Technical reference manual - System parameters
Type of Unit Technical reference manual - System parameters
Connect to Bus Technical reference manual - System parameters
Unit Identification Label Technical reference manual - System parameters
Unit Trustlevel Technical reference manual - System parameters
Unit Startup State Technical reference manual - System parameters
Store Unit State at Power Technical reference manual - System parameters
Fail
Regain Communication Technical reference manual - System parameters
Reset
Vendor ID Vendor ID on page 43
Product Code Product Code on page 44
Production Inhibit Time Production Inhibit Time on page 45
Continued
Unit Type
These parameters belong to the type Unit Type in the topic I/O.
Parameter For more information, see ...
Name Technical reference manual - System parameters
Type of Bus Technical reference manual - System parameters
Vendor Name Technical reference manual - System parameters
Product Name Technical reference manual - System parameters
Internal Slave Technical reference manual - System parameters
DeviceNet Lean Address DeviceNet Lean Address on page 48
38 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.2.1 DeviceNet Lean Master Address
Parent
DeviceNet Lean Master Address belongs to the type Bus, in the topic I/O.
Cfg name
DL_MasterAddress
Description
DeviceNet Lean Master Address is the address that the master uses to
communicate.
Usage
DeviceNet Lean Master Address is mandatory for a DeviceNet Lean fieldbus and
decides what address the master should use to communicate with other devices
on the DeviceNet network.
Prerequisites
DeviceNet Lean option must be installed.
Limitations
The DeviceNet Lean Master Address must not use the same address as another
device on the network.
Default value
The default value is 0.
Allowed values
Allowed values are the integers 0-63.
3HAC034095-001 Revision: F 39
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.2.2 Auto Configuration
Parent
Auto Configuration belongs to the type Bus, in the topic I/O.
Cfg name
DL_AutoConfig
Description
Auto Configuration scans the DeviceNet Lean network during the system startup
and configures the found units in the IRC5 controller.
Usage
The Auto Configuration parameter is used as an easy way to find and configure a
new unit on the network. The configuration created by this function should be
updated with signal names that reflect the purpose of the signal. The Auto
Configuration parameter will always be restored to Deactivated at system startup.
Prerequisites
DeviceNet Lean option must be installed.
Limitations
Signals are always configured as single bit digital signals.
Default value
The default value is Deactivated.
Allowed values
Activated or Deactivated.
40 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.2.3 Bus Scan
Parent
Bus Scan belongs to the type Bus, in the topic I/O.
Cfg name
DL_BusScan
Description
The Bus Scan function scans the DeviceNet Lean network during system startup
and display information about found units.
Usage
The Bus Scan function is used to quickly locate an I/O unit and its configuration
parameters, like Vendor ID and Product code. The Bus Scan parameter will always
be restored to Deactivated at system startup.
Prerequisites
DeviceNet Lean option must be installed.
Limitations
The product name and other configuration parameters of an I/O unit is shown only
if the DeviceNet Lean master is able to connect to the unit.
Default value
The default value is Deactivated.
Allowed values
Activated or Deactivated.
3HAC034095-001 Revision: F 41
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.2.4 Connector ID
4.2.4 Connector ID
Parent
Connector ID belongs to the type Bus, in the topic I/O.
Cfg name
ConnectorID
Description
The parameter Connector ID specifies the hardware interface (connection port)
that the DeviceNet Lean option shall use.
Usage
The Connector ID parameter is used to select one of the available connection ports
to use.
Prerequisites
The option DeviceNet Lean (748-1) must be installed.
Default value
First Board
Allowed values
First Board
42 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.3.1 Vendor ID
4.3.1 Vendor ID
Parent
Vendor ID belongs to the type Unit Type, in the topic I/O.
Cfg name
DL_VendorID
Description
Vendor ID is the vendor ID of an I/O unit as specified by the supplier.
Usage
Vendor ID is used as an identification of the I/O unit to secure communication to
the correct device.
Prerequisites
DeviceNet Lean option must be installed.
Allowed values
0 - 65535
3HAC034095-001 Revision: F 43
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.3.2 Product Code
Parent
Product Code belongs to the type Unit Type, in the topic I/O.
Cfg name
DL_ProductCode
Description
Product Code is the product code of an I/O unit as specified by the supplier.
Usage
Product Code is used as an identification of the I/O unit to secure communication
to the correct device.
Prerequisites
DeviceNet Lean option must be installed.
Allowed values
0 - 65535
44 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.3.3 Production Inhibit Time
Parent
Production Inhibit Time belongs to the type Unit Type, in the topicI/O.
Cfg name
DL_ProdInhibitTime
Description
Production Inhibit Time specifies the minimum time, expressed in milliseconds,
between network messages sent by the unit.
Usage
Production Inhibit Time is used to control the minimum time between transmissions
from the I/O unit in order to prevent overloading of the DeviceNet Lean network.
Prerequisites
The DeviceNet Lean option must be installed.
Limitations
Maximum and minimum values might be constrained by the unit.
Default value
The default value is 10.
Allowed values
Allowed values are the integers 5-65535.
3HAC034095-001 Revision: F 45
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.3.4 Poll Rate
Parent
Poll Rate belongs to the type Unit Type, in the topic I/O.
Cfg name
DL_Pollrate
Description
Poll Rate specifies how often the DeviceNet Lean master should exchange input
or output signals with an I/O unit (expressed in milliseconds).
Usage
Poll Rate is used to force the DeviceNet Lean master to create a POLLED
connection type against an I/O unit with the specified Poll Rate time. If the default
value 0 is used, the DeviceNet Lean master will try to use a COS connection against
the I/O unit. If COS is not supported, a POLLED connection will automatically be
created with a pollrate decided by the DeviceNet Lean master.
Note
Prerequisites
The DeviceNet Lean option must be installed.
Limitations
Maximum and minimum values might be constrained by the unit.
Default value
The default value is 0 (deactivated).
Allowed values
Allowed values are the integers 0-65535.
46 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.3.5 Quick Connect
Parent
Quick Connect belongs to the type Unit Type, in the topic I/O.
Cfg name
DL_QuickConnect
Description
Quick Connect specifies whether the DeviceNet Lean master should configure the
I/O unit to use the Quick Connect functionality.
Usage
Quick Connect is used to allow the I/O unit to skip certain startup test sequences.
This shortens the time it takes for the I/O unit to accept a connection from the
DeviceNet Lean master. Primary use of this function is in tool change applications.
Prerequisites
The DeviceNet Lean option must be installed
Default value
The default value is Deactivated.
Allowed values
Activated or Deactivated.
3HAC034095-001 Revision: F 47
© Copyright 2008-2012 ABB. All rights reserved.
4 System parameters
4.4.1 DeviceNet Lean Address
Parent
DeviceNet Lean Address belongs to the type Unit, in the topic I/O.
Cfg name
DL_Address
Description
DeviceNet Lean Address specifies the address that the I/O unit is assumed to be
using on the network, and which the master should try to setup a connection
against.
Usage
DeviceNet Lean Address is a DeviceNet Lean specific parameter that is only
available for DeviceNet Lean units.
Prerequisites
The DeviceNet Lean option must be installed.
Limitations
There can be no sharing of addresses on the DeviceNet Lean network. All addresses
on a DeviceNet Lean network must be unique.
Default value
The default value is 63.
Allowed values
Allowed values are the integers 0-63.
48 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
5 Trouble shooting
5.1 Bus off
5 Trouble shooting
5.1 Bus off
Description
The DeviceNet Lean bus goes bus off when an excessive number of communication
errors are detected and the CAN chip automatically goes off-line.
An event message will inform the users that bus off has occurred. The DeviceNet
Lean bus will automatically try to recover from bus off and if succeeded an event
message will inform the user that the bus has recovered from bus off.
To turn off the automatically bus off recovery, use the system parameter
Automatically Bus Restart. Refer to Technical reference manual - System
parameters.
Consequences
Bus off indicates a serious communication fault such as incorrect baud rate or
physical layer error (short, open, and so on).
Possible causes
The possible causes of bus off are:
• Different baud rates on the master and some I/O units (the I/O units do not
support auto baud rate).
• No or faulty power on the bus.
• Short circuit between CAN high and CAN low.
• Cable length on trunk cables and drop cables.
• Faulty terminations.
• The network cable length exceeds 30 meters.
Recommended actions
The following table provides the action that needs to be taken for the possible
causes of bus off.
Cause Action/Information
Different baud rates on the master and Cycle the power of the units or manually change
some I/O units. the baud rate of the units. (DeviceNet Lean oper-
ates at a baud rate of 500 kbits/s.)
No or faulty power on the bus. See Shield grounding and power on page 22.
Cable length on trunk cables and drop See Selecting cables on page 25.
cables.
Faulty terminations. Refer to Connection of the DeviceNet Lean bus
on page 23.
Note
If the DeviceNet Lean bus goes bus off, the I/O units on the bus can also go bus
off. The only way to recover these units is to cycle the power on the I/O unit.
3HAC034095-001 Revision: F 49
© Copyright 2008-2012 ABB. All rights reserved.
5 Trouble shooting
5.2 Bus Scan
Overview
When a bus scan or auto configuration operation is activated, the DeviceNet Lean
master will send requests to all valid network addresses. If the unit is already
configured against another DeviceNet master, or operating at wrong baud rate, or
is not online, the unit can not be contacted for the data gathering of the required
configuration parameters. If the I/O unit is not found with auto configuration, it
might still be possible that the unit will work if it is manually added.
50 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.1.1 DeviceNet Lean Bus and I/O board status LED description
6.1.1 DeviceNet Lean Bus and I/O board status LED description
General
Each of the units connected to the DeviceNet Lean bus includes LED indicators
which indicate the condition of the unit and the function of the network
communication.
LEDs
The LEDs found on the units connected may be divided into two categories.
Common LEDs
The following LEDs can be found on all units:
• MS - Module status
• NS - Network status
Specific LEDs
Certain units also include the following LEDs:
• DeviceNet Tx - DeviceNet network transmit
• DeviceNet Rx - DeviceNet network receive
MS - Module status
The bicolor (green/red) LED indicates the status of the device. It indicates whether
or not the device has power and is operating properly. The LED is controlled by
software. The following table shows the different states of the MS LED.
LED color Description Remedy/cause
OFF No power applied to the device. Check power supply.
GREEN steady Device is operating in a normal If no light, check other LED
condition. modes.
GREEN flashing Device needs commissioning due Check system parameters.
to missing, incomplete or incorrect Check messages.
configuration. The device may be in
the stand-by state.
RED flashing Recoverable minor fault. Check messages.
RED steady The device has an unrecoverable Device may need replacing.
fault.
RED/GREEN flashing The device is running self test. If flashing for more than a few
seconds, check hardware.
Continued
NS - Network status
The bicolor (green/red) LED indicates the status of the communication link. The
LED is controlled by software. The following table shows the different states of the
NS LED.
LED color Description Remedy/cause
OFF Device has no power or is not online. Check status of MS LED.
The device has not completed the Check power to affected module.
Dup_MAC_ID test yet.
GREEN steady The device is online and has connection If no light, check other LED
in the established state. modes.
For a group 2 device only: the device is
allocated to a master.
For a UCMM capable device: the device
has one or more established connec-
tions.
GREEN flash- Device is online, but has no connections Check that other nodes in the
ing in the established state. network are operative.
The device has passed the Dup_MAC_ID Check parameter to see whether
test, is online, but has no established module has correct ID.
connections to other nodes.
For a group 2 device only: the device is
not allocated to a master.
For a UCMM capable device: the device
has no established connections.
RED flashing One or more I/O connections are in the Check system messages.
time-out state.
RED steady Failed communication device. The Check system messages and
device has detected an error rendering parameters.
it incapable of communicating on the
network.
(Duplicate MAC_ID, or Bus-off).
52 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.1.2 DeviceNet Lean bus status LEDs at power-up
Process
The system performs a test of the MS and NS LEDs during startup. The purpose
of this test is to check that all LEDs are working properly. The test runs as follows:
Order LED action
1 NS LED is switched Off.
2 MS LED is switched On green for approx. 0.25 seconds.
3 MS LED is switched On red for approx. 0.25 seconds.
4 MS LED is switched On green.
5 NS LED is switched On green for approx. 0.25 seconds.
6 NS LED is switched On red for approx. 0.25 seconds.
7 NS LED is switched On green.
Additional LEDs
If a device has other LEDs, each LED is tested in sequence.
3HAC034095-001 Revision: F 53
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.1.3 I/O units
General
You can connect up to 20 I/O units to the same controller, but the number of I/O
units that are practical to connect always depends on the amount of the total
network traffic they produce.
Requirements
54 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.1.4 Coil neutralization
External units
External relay coils, solenoids, and other units that are connected to the controller
must be neutralized. The following sections describe how this can be done.
Note
The turn-off time for DC relays increases after neutralization, especially if a diode
is connected across the coil. Varistors give shorter turn-off times. Neutralizing
the coils lengthens the life of the switches that control them.
xx0100000163
xx0100000164
xx0100000165
3HAC034095-001 Revision: F 55
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.1.5 Setting DeviceNet Lean bus ID
Description
Each I/O unit is given a unique address (ID).
xx0100000245
A Connector X5
B Address pins
C Address key
Note
Connector X5
Continued
3HAC034095-001 Revision: F 57
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.2.1 Overview of I/O units
Overview
This section provides description of the I/O units that support DeviceNet Lean
communication.
Board Name of unit Type of unit Article number
designation
DSQC 351B DeviceNet/INTERBUS Gateway unit 3HNE00006-1
DSQC 377B Queue tracking Encoder interface unit 3HNE01586-1
DSQC 378B DeviceNet/CCLink Gateway unit 3HNE00421-1
DSQC 651 AD combi I/O Distributed I/O unit 3HAC025784-001
DSQC 652 Digital I/O Distributed I/O unit 3HAC025917-001
DSQC 653 Digital I/O with relay outputs Distributed I/O unit 3HAC025918-001
58 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.2.2 DSQC 351A and 351B, DeviceNet Lean/INTERBUS gateways
Description
The DSQC 351A and 351B are the circuit boards normally mounted in the control
module. As an option, it may also be mounted in an external I/O unit.
The units handle input and output signals between the DeviceNet Lean system
and the INTERBUS system.
There are no functional differences between DSQC 351A and DSQC 351B.
Communication concept
The INTERBUS system is able to communicate with a number of external devices,
depending on the number of process words occupied by each unit. The robot
controller may be equipped with several DSQC 351A/B boards. The INTERBUS
inputs and outputs are accessible in the robot controller as general inputs and
outputs.
The following figure is an outline diagram of the communication concept:
xx0100000224
Note
A link is connected between pin 5 and 9 in the plug on the interconnection cable
connected to the OUT connector (connector X21) of each unit. The link informs
the INTERBUS unit that more units are connected further out in the chain. (The
last unit does not have a cable connected and therefore no link.)
Continued
xx0100000225
Parts
The table below refers to Illustration of DSQC 351A/B on page 60.
Item Description
X3 Back-up feed supply
See section Connector X3 on page 61 for connection tables!
X5 DeviceNet Lean connector
See section Connector X5 on page 62!
X20 INTERBUS, input
See section Connector X20 on page 62 for connection tables!
X21 INTERBUS, output
See section Connector X21 on page 62 for connection tables!
Continued
Technical data
Supply
The INTERBUS gateway must be fed externally to avoid shutting down the
INTERBUS net if a robot cell is switched off. The 24V power supply must be fed
from an external power source and be connected to connector X3.
Connector X3
xx0100000221
Continued
Connector X5
xx0100000244
Connector X20
xx0100000220
Connector X21
xx0100000220
Continued
Note
General LEDs
The significance of the LEDs are specified in section DeviceNet Lean Bus and I/O
board status LED description on page 51.
Continued
Input map
The figure below shows the digital input mapping.
en0400000799
m The number of words (16 bit) that the unit has been configured to, using the
Fieldbus Command TypeDataWidth.
INTER- The status of the INTERBUS communication can be monitored using the signal
BUS INTERBUS Status. When INTERBUS Status is set it indicates that the unit is in
Status data communication with the PLC/master controlling it, i.e. bus is active (the BA
LED is lit).
N.U. Not used. The signal position is reserved for future use and shall not be used.
The INTERBUS Status signal is located in the last bit of the last byte of the input
area. For example, if the DataWidth is set to 4 (words) there are 8 bytes of input
data (bit 0-63), and the INTERBUS Status is located in the last bit of the 9th byte
i.e. bit 71.
Output map
The figure below shows the digital output mapping.
en0400000800
m The number of words (16 bit) that the unit has been configured to, using the
Fieldbus Command TypeDataWidth.
Continued
Additional information
The data areas of the gateway are byte-consistent, which means that signals
within the same byte (groups of 8 bits) are handled as one piece and are guaranteed
to belong to the same bus-cycle. Normally this does not cause any problems, but
if a signal group has been defined across the byte boundaries as for example, a
16 bit group signal this needs to be considered. It is important to make sure that
undesired behaviors are avoided in the case when the group signal is updated at
exactly the same time as the gateway is being polled/scanned by one of the masters.
The values for the Fieldbus Command Types are stored in flash memory of the
gateway module. Any change of these values requires a reset (or power cycle) of
the gateway module before it actually assumes these new values. By using the
standard configuration files for the gateways, the robot controller will automatically
issue a reset command to activate the modified configuration.
3HAC034095-001 Revision: F 65
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.2.3 DSQC 377A and DSQC 377B, Queue tracking units
Description
The encoder units DSQC 377A and DSQC 377B provides connection for one
encoder and one digital input (synchronization switch), and includes queue tracking
functions.
There are no functional differences between DSQC 377A and DSQC 377B.
Usage
The encoder unit is normally used for installation on a conveyor to enable the robot
programs to synchronize to the motion (position) of the conveyor.
The digital input is used for synchronization switch (also called sync signal), which
means conveyor synchronization point.
xx0400000751
Continued
Parts
Item Description
X3 Back-up feed supply
See the section Connector X3 on page 68 for connection tables.
X5 DeciceNet Lean connector
See the section Connector X5 on page 69
X20 Conveyor connection
See the section Connector X20 on page 69 for connection tables.
Technical data
Continued
Encoder connections
The wiring diagram in the figure below shows how to connect the encoder and
sync signal switch to the encoder unit. As can be seen from the illustration, the
encoder is supplied with 24 VDC and 0 V. The encoder has two channels. The main
unit uses quadrature decoding to compute position and direction information.
xx0100000234
Connector X3
xx0100000221
Continued
Connector X5
xx0100000244
Connector X20
xx0100000235
Continued
Continued
Input map
The figure below shows the input mapping.
Note
Pay attention to the order of the bits for the analog signals.
en0400000816
Note
Continued
Continued
Output map
The following figure shows the output signals mapping.
en0400000817
Note
Continued
Additional information
For detailed information on using the DSQC 377A/B in an application refer to
Application manual - Motion coordination and supervision.
NOTE!
If anotherDeviceNet Lean Master Addressthan the default value (2) is used, see
detailed information about DeviceNet Lean Master Address on page 39.
74 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.2.4 DSQC 378A and DSQC 378B, DeviceNet Lean/CCLink gateways
Description
The DSQC 378A and DSQC 378B units offer an interface between the CCLink bus
and the DeviceNet Lean bus as used on the robot system. The units are regarded
as intelligent devices by the CCLink PLC.
There are no functional differences between DSQC 378A and DSQC 378B.
Communication concept
The CCLink can communicate with a number of external devices, depending on
the number of stations occupied by each unit. There is a maximum of 64 stations,
each capable of up to 32 I/O points and 8 points word data. The units are setup to
have between 1 and 4 occupied stations each. The CCLink unit is connected to
the CCLink PLC by a twisted pair cable with shield.
The CCLink inputs and outputs are accessible in the robot controller as general
inputs and outputs.
Following figure is an outline diagram of the communication concept:
xx0400000826
Note
The CCLink cable must be terminated with termination resistors (110 ohm) in
both ends.
Continued
xx0400000825
DSQC 378A
xx1000001343
DSQC 378B
Parts
Item Description
X3 Back-up feed supply
See section Connector X3 on page 77 for connection tables!
X5 DeviceNet Lean connector
See section Connector X5 on page 77!
X8 CCLink network connector
See section Connector X8 on page 77 for connection tables!
Technical data
Continued
Unit setup
The unit must be given an ID address, and setup parameters must be entered into
the system.
Connector X3
xx0100000221
Connector X5
xx0100000244
Connector X8
xx020000
Continued
Continued
Note
Read the figure line by line. The Operation column describes the operation status
depending on the status of the four LEDs.
en0400000827
General LEDs
The significance of the LEDs are specified in section DeviceNet Lean Bus and I/O
board status LED description on page 51.
Continued
Input map
The figure below shows the digital input mapping.
en0400000823
m The size in bytes (8 bit) that the unit has been configured to, using the Fieldbus
Command TypesOccStat and BasicIO. See table in section Fieldbus Command
Types on page 81.
CCLink The status of the CCLink communication can be monitored using the signal
Status CCLink Status. When CCLink Status is set it indicates that the CCLink commu-
nication is OK.
N.U. Not used. The signal position is reserved for future use and shall not be used.
The CCLink Status signal is located at the last bit of the last byte of the input area.
For example, if OccStat is set to 2 and BasicIO is set to 0 there are 6 bytes of
input data (bit 0-47), and the CCLink Status is located in the last bit of the 7th byte
i.e. bit 55.
Output map
The figure below shows the digital output mapping.
en0400000824
m The size in bytes (8 bit) that the unit has been configured to, using the Fieldbus
Command TypesOccStat and BasicIO. See table in section Fieldbus Command
Types on page 81.
Continued
Continued
Additional information
The data areas of the gateway are byte-consistent, which means that signals
within the same byte (group of 8 bits) are handled as one piece and are guaranteed
to belong to the same bus-cycle. Normally this does not cause any problems, but
if a signal group has been defined across the byte boundaries as for example, a
16 bit group signal this needs to be considered. It is important to make sure that
undesired behaviors are avoided in the case when the group signal is updated at
exactly the same time as the gateway is being polled/scanned by one of the masters.
The values for the Fieldbus Command Types are stored in flash memory of the
gateway module. Any change of these values requires a reset (or power cycle) of
the gateway module before it actually assumes these new values. By using the
standard configuration files for the gateways, the robot controller will automatically
issue a reset command to activate the modified configuration.
82 3HAC034095-001 Revision: F
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.2.5 DSQC 651, AD combi I/O
Description
The DSQC 651 is a circuit board normally mounted inside the robot controller. As
an option, it may also be mounted in an external I/O module.
The combi I/O unit handles digital and analog communication between the robot
system and any external systems.
Illustration
The following figure shows the DSQC 651 unit:
xx0600002853
Continued
Parts
The following table refers to the illustration in section Illustration on page 83.
Item Description
A Status LEDs
X1 Digital outputs
See Connector X1 on page 86 for connection table!
X3 Digital inputs
See Connector X3 on page 86 for connection table!
X5 DeviceNet connector
See Connector X5 on page 87!
X6 Analog outputs
See Connector X6 on page 87!
Technical data
Continued
Analog outputs Number of analog outputs: 2 (galvanically isolated from the controller
electronics)
Short-circuit protected outputs
Output voltage:
• 0-10 VDC
Load Impedance:
• min 2 kohm
Resolution:
• 12 bits
Inaccuracy (Over temperature range + 5 C to +70 C):
• maximum 25 cmV (0.5 % of full scale)
Supply voltage 24 VDC
Power supply, digital, Integrated power supply in controller.
and analog I/O Separate 24 VDC power, supplied by customer in non-ABB external
I/O unit.
External supply for Reverse polarity protection.
digital outputs Voltage:
• 19 - 35 V
Analog supply Analog supply +16/-8V internally on the board.
From the DeviceNet cable 24 Volt. DC/DC converter“ flyback”
Isolation voltage:
• 500 VDC
Voltage:
• 16 V / -8V
Current consumption:
• 40mA (approx)
SW connections Support for the following connections:
• POLLED
• Change-Of-State
• Change-Of-State with acknowledge suppression (not suppor-
ted by DeviceNet Lean)
• Cyclic (not supported by DeviceNet Lean)
• Cyclic with acknowledge suppression (not supported by
DeviceNet Lean)
Unit setup
The unit must be given an address, and setup parameters must be entered into
the system.
Continued
Connector X1
If supervision of the supply voltage is required, a bridge connection can be made
to an optional digital input. This also requires the particular unit to have a separate
power supply, in order to be able to monitor the regular power supply voltage.
The supervision instruction must be written in the RAPID program.
xx0200000264
Connector X3
xx0200000264
Continued
The input current is 5.5 mA (at 24 V) on the digital inputs. A capacitor connected
to ground, to prevent disturbances, causes a short rush of current when setting
the input.
When connecting outputs, sensitive to pre-oscillation current, a series resistor (100
Ohms) may be used.
Connector X5
xx0100000244
Connector X6
xx0200000265
LEDs
The significance of the LEDs are specified in section DeviceNet Lean Bus and I/O
board status LED description on page 51.
Input map
The following figure shows the digital input mapping.
xx0300000613
Continued
Output map
The following figure shows the analog and digital output mapping.
Note
Pay attention to the order of the bits for the analog signals.
en0600002851
LSB The least significant bit of the binary number representing the analog signal.
MSB The most significant bit of the binary number representing the analog signal.
Numerical format
The numerical representation of the values are described in the following table:
Signal Analog physical value Hexadecimal number Bit value
AO 1-AO 2 +10 V 0xFFFF MaxBitVal = 65535
AO 1-AO 2 +5 V 0x7FFF
AO 1-AO 2 0V 0x0 MinBitVal = 0
Continued
Additional information
The following table shows the physical type of the signals, resolution, and so on.
Signal Type Range Resolution Encoding type
AO 1 Voltage 0 V .. +10 V 12 bit Unsigned
AO 2 Voltage 0 V .. +10 V 12 bit Unsigned
3HAC034095-001 Revision: F 89
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.2.6 DSQC 652, Digital I/O
Description
The DSQC 652 is a circuit board normally mounted inside the robot controller. As
an option, it may also be mounted in an external I/O module.
The unit handles digital input and output signals between the robot system and
any external systems.
Illustration
The following figure shows the DSQC 652 board:
xx0600002855
Continued
Parts
The following table refers to the illustration in section Illustration on page 90.
Item Description
A Status LEDs
X1 Digital outputs
See section Connector X1 on page 93 for connection table!
X2 Digital outputs
See Connector X2 on page 93for connection table!
X3 Digital inputs
See Connector X3 on page 95 for connection table!
X4 Digital inputs
See Connector X4 on page 95 for connection table!
X5 DeviceNet connector
See Connector X5 on page 96!
Technical data
Continued
Unit setup
The unit must be given an address, and setup parameters must be entered into
the system.
Continued
Connector X1
If supply voltage supervision is required, a bridge connection can be made to an
optional digital input. The supervision instruction must be written in the RAPID
program.
xx0200000264
Connector X2
If supply voltage supervision is required, a bridge connection can be made to an
optional digital input. The supervision instruction must be written in the RAPID
program.
xx0200000264
Continued
Continued
Connector X3
xx0200000264
The input current is 5.5 mA (at 24 V) on the digital inputs. A capacitor connected
to ground, to prevent disturbances, causes a short rush of current when setting
the input.
When connecting outputs, sensitive to pre-oscillation current, a series resistor (100
Ohms) may be used.
Connector X4
xx0200000264
Continued
The input current is 5.5 mA (at 24 V) on the digital inputs. A capacitor connected
to ground, to prevent disturbances, causes a short rush of current when setting
the input.
When connecting outputs, sensitive to pre-oscillation current, a series resistor (100
ohms) may be used.
Connector X5
xx0100000244
LEDs
The significance of the LEDs are specified in section DeviceNet Lean Bus and I/O
board status LED description on page 51.
Input map
The following figure shows the digital input mapping.
xx0300000613
Output map
The following figure shows the digital output mapping.
en0400000716
Continued
3HAC034095-001 Revision: F 97
© Copyright 2008-2012 ABB. All rights reserved.
6 Boards and units
6.2.7 DSQC 653, Digital I/O with relay outputs
Description
The DSQC 653 is a circuit board normally mounted inside the robot controller. As
an option, it may also be mounted in an external I/O module.
The unit handles input and output signals between the robot system and any
external systems through relay outputs and digital inputs.
Illustration
The following figure shows the DSQC 653 board:
xx0600002857
Continued
Parts
The following table refers to the illustration in section Illustration on page 98.
Item Description
A Status LEDs
X1 Relay outputs
See section Connector X1 on page 101 for connection table!
X3 Digital inputs
See section Connector X3 on page 102for connection table!
X5 DeviceNet connector
See section Connector X5 on page 102!
Technical data
Continued
Unit setup
The unit must be given an address, and setup parameters must be entered into
the system.
en0500001565
Continued
The following illustration shows how to connect the digital inputs for the connector
X3.
en0500001566
Connector X1
xx0100000235
Continued
Connector X3
xx0100000235
The input current is 5.5 mA (at 24 V) on the digital inputs. A capacitor connected
to ground, to prevent disturbances, causes a short rush of current when setting
the input.
When connecting outputs, sensitive to pre-oscillation current, a series resistor (100
Ohms) may be used.
Connector X5
xx0100000244
Continued
LEDs
The significance of the LEDs are specified in section DeviceNet Lean Bus and I/O
board status LED description on page 51.
Input map
The following figure shows the digital input mapping.
en0600002850
Output map
The following figure shows the digital output mapping.
en0600002849
Index
A DeviceNet/CCLink gateway, 75
addressing range, 31 DeviceNet/INTERBUS gateway, 59
B I
bus off I/O messages
causes, 49 change-of-state connection, 16
consequences, 49 I/O units, 31
remedy, 49 allowed I/O units, 54
bus scan, 50 distributed I/O units, 58
DSQC 351B, 59
C DSQC 377B, 66
cable grounding. See shield grounding., 22 DSQC 378B, 75
cable length, 25 DSQC 651, 83
maximum cable length, 54 DSQC 652, 90
CCLink gateway, 75 DSQC 653, 98
CIP routing, 29 INTERBUS gateway, 59
coil neutralization, 55
Connector ID, 42 L
connector X5, 56 LED, 51
controller software, 27 common LEDs, 51
DeviceNet Rx, 52
D DeviceNet Tx, 52
DeviceNet, 15 module status, 20, 51
bus ID, 56 network status, 20, 52
DeviceNet/CCLink gateway, 75 specific LEDs, 51
DeviceNet/INTERBUS gateway, 59 test run, 53
DeviceNet Lean, 15
addressing range, 31 Q
bus ID, 56 queue tracking unit, 66
configuration, 31
connector, 20, 23 S
PCI card, 17 safety, 13
predefined bus, 31 shield grounding, 22
software configuration, 27 signals, adding, 35
DeviceNet Lean cable, 25 system parameters
cable type, 25 DeviceNet Lean Address, 39, 48
incoming, 24 Product Code, 9, 37, 44
outgoing, 24 Production Inhibit Time, 9, 37, 45
distributed I/O units, 58
drop cable, 17 T
drop line, 25 termination resistor, 24, 54
DSQC 351B, 59 topic I/O
DSQC 377B, 66 Bus, 31
DSQC 378B, 75 Unit, 31
DSQC 572, 16–17 Unit Type, 31
installation, 19 topic I/O type
DSQC 651, 58, 83 Bus, 37
DSQC 652, 58, 90 Unit, 37
DSQC 653, 58, 98 Unit Type, 38
trouble shooting, bus off, 49
G trunk line, 25
gateway
ABB AB
3HAC034095-001, Rev F, en
Discrete Automation and Motion
Robotics
S-721 68 VÄSTERÅS, Sweden
Telephone +46 (0) 21 344 400
www.abb.com/robotics