0% found this document useful (0 votes)
318 views2 pages

SEL551C Settings - Generic

This document contains settings for a SEL-551C relay for a feeder and station. It lists various protection elements like phase overcurrent, ground, and negative sequence elements along with their settings ranges and selected values. Settings include pickup currents, time dials, and enabling/disabling elements. The settings are organized into groups for the various current and voltage circuits monitored by the relay.

Uploaded by

Matthew Lee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
318 views2 pages

SEL551C Settings - Generic

This document contains settings for a SEL-551C relay for a feeder and station. It lists various protection elements like phase overcurrent, ground, and negative sequence elements along with their settings ranges and selected values. Settings include pickup currents, time dials, and enabling/disabling elements. The settings are organized into groups for the various current and voltage circuits monitored by the relay.

Uploaded by

Matthew Lee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Relay.

rdb SEL-551C 001


New Settings 1 0551C0AX1X1X

SEL-551C Settings Report

Setting Range Value


Group : 1
RID FEEDER 1
TID STATION A
CTR 1-6000 600
CTRN 1-6000 600
TDURD 0-8000.000 cyc 9.000
50P1P OFF,0.1-16.0A 3.0
50P2P OFF,0.1-16.0A 4.0
50P3P OFF,0.1-16.0A OFF
50P4P OFF,0.1-16.0A OFF
50P5P OFF,0.1-16.0A OFF
50P6P OFF,0.1-16.0A OFF
50ABCP OFF,0.1-16.0A OFF
51P1P OFF,0.1-3.2A 1.2

51P1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51P1TD 0.50-15.00 3.00


51P1RS Select: N, Y N
51P2P OFF,0.1-3.2A OFF

51P2C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51P2TD 0.50-15.00 15.00


51P2RS Select: N, Y N
50N1P OFF,0.1-16.0A OFF

<Filter is Empty>
1 Of 4 4/05/2020 3:18 PM
Relay.rdb SEL-551C 001
New Settings 1 0551C0AX1X1X

Setting Range Value


50N2P OFF,0.1-16.0A OFF
51N1P OFF,0.1-3.2A OFF

51N1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51N1TD 0.50-15.00 15.00


51N1RS Select: N, Y N
50G1P OFF,0.1-16.0A OFF
50G2P OFF,0.1-16.0A OFF
51G1P OFF,0.1-3.2A 0.3

51G1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51G1TD 0.50-15.00 1.50


51G1RS Select: N, Y N
50Q1P OFF,0.1-16.0A OFF
50Q2P OFF,0.1-16.0A OFF
51Q1P OFF,0.1-3.2A OFF

51Q1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51Q1TD 0.50-15.00 15.00


51Q1RS Select: N, Y N
51Q2P OFF,0.1-3.2A OFF

51Q2C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51Q2TD 0.50-15.00 15.00


51Q2RS Select: N, Y N