4HS Submersible Pumps: Installation and Operating Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 34

4HS Submersible Pumps

Installation and Operating Manual

man4HS_06_eng.docx LCD 2.24 INV 2.2 H 2.1


Index

1. Introduction of the 4HS submersible pumps range .................................................................................................. 3


2. Safety Instructions .................................................................................................................................................... 4
3. Stocking conditions ................................................................................................................................................... 4
4. Packing content......................................................................................................................................................... 5
5. General technical features .................................................................................................................................... 5
6. Pump installation ...................................................................................................................................................... 6
6.1 Installing pump in the well ................................................................................................................................ 6
6.2 Pump cable........................................................................................................................................................ 7
7 CM installation .......................................................................................................................................................... 8
7.1 Electric wiring .................................................................................................................................................... 9
8. 4HS pumps installation for constant pressure mode.............................................................................................. 10
8.1 Pressure tank .................................................................................................................................................. 11
8.2 Pressure sensor ............................................................................................................................................... 11
8.3 Minimum stop frequency at 0 delivery (f min Q=0) during constant pressure control.................................. 12
9. 4HS pumps performance range .............................................................................................................................. 13
10. 4HS use and programming .................................................................................................................................. 16
10.1 Display ............................................................................................................................................................. 16
10.2 Initial setting ................................................................................................................................................... 16
10.3 Initial view ....................................................................................................................................................... 18
10.4 Menu display ................................................................................................................................................... 19
10.5 Installer parameters ........................................................................................................................................ 19
10.6 Advanced parameters ..................................................................................................................................... 24
11. Protections and alarms ................................................................................................................................... 27
12. Trouble-shooting chart ....................................................................................................................................... 30
13. Technical Assistance ........................................................................................................................................... 31

2
1. Introduction of the 4HS submersible pumps range

4HS is a 4” high speed centrifugal submersible pump for clean water composed by:
 high speed three phase asynchronous motor with wet rotor and canned type resin filled stator.
 Built-in inverter on board driven by a dedicated control module (CM) positioned outside the well.
 High speed multi stage pump entirely made of AISI 304 stainless steel.
Pump driving made by inverter allows:
 Modify the pump speed to grant constant the desired pressure regardless water request. In this way the
pump is operated only and when needed thus avoiding unnecessary waste of energy and granting longer
system life.
 implement the soft start and the soft stop to increase the system life and reducing the current peaks.
 protect the motor from overloading and dry running , overvoltage, undervoltage and possible abnormal
conditions
4HS is used on residential and industrial sectors for water pressurized systems, granting:
 Energy saving
 Simplified and quick installation
 Long life reliability

4HS: submersible pump

CM: control module

3
2. Safety Instructions

NASTEC strongly suggests to reading carefully this operation manual before using and installing its products
Any operation (installation, maintenance and repair) must be carried out by trained, skilled and qualified personnel.
Failure to observe and follow the instruction of this manual may result fatal in dangerous electric shock.

The unit must be connected to the power supply by a switch granting the
complete visual disconnection (separation) from the line before any operation
on the 4HS itself and on the connected load.

Disconnect the unit from the power supply before any operation.

Do not remove for any reason, the cover of the CM and the cable guard
without having visually disconnected the unit from the power supply and
having waited at least 5 minutes.

4HS and pump system must be grounded properly before operation.

For the entire period the CM is powered a high voltage is present on the
output terminals independently if it is running or not the pump.

Do not start the pump for any reason if not completely immersed in water.

Avoid any shock or serious impact during transportation.


Check the 4HS immediately upon delivery and check for damage and/or missing parts. In either case, immediately
notify the supplier.
Damages due to transportation, incorrect installation, or improper use of the device will null and void the warranty.
NASTEC cannot be held responsible for any damage to people and/or property due to improper use of its
products.

3. Stocking conditions

Store the product on its packaging in a dry and well ventilated environment within a temperature range from -20 ° C
and 70 ° C.
If the pump remains in stock for more than a year is recommended to disassemble the rotating parts and test their
functionality. It 'also need to power the electric pump (without running the motor) to allow charging of electrolytic
capacitors of the inverter module.
If the pump has already been put into operation and is then placed in storage, the minimum storage temperature is
4 ° C. Alternatively you need to add anti-freeze fluid.

4
4. Packing content

Packing includes:

 4HS submersible pump with 2,5 meters flat cable length.


 CM (control module)
 Pressure transducer
 Operating Manual
 Cable junction kit

Check the 4HS packing immediately upon delivery and check for damage and/or missing parts; in
either cases immediately notify the supplier

5. General technical features

PUMP
Max. temperature of pumped liquid 35 °C (92 °F)
Min. speed of water flow on motor case 0.2 m/s
Characteristics of pumped liquid clean, non-corrosive, non-explosive, free of particles and
fibers, with a maximum sand content of 50 g/m3
Grade of protection IP68
Used Materials Impellers and diffusers in AISI 304 stainless steel
Cable Flat cable ACS – WRAS

CM
Max. temperatura dell’ ambiente d’ installazione 60 °C (140 °F)
Grade of protection IP55 (NEMA 4)
Used Materials Aluminium , LCD membrane with PVC stickers, antipull
plug in polyamide
Analog input 2 x analog input 4-20 mA + 2 settable analog input 4-20
mA or 0-10 V .
Digital input 4 inputs, N.O or N.C settable via software
Digital output 2 output relays 5 A , 250 Vac, N.O. or N.C settable
Auxiliary feeding 24 Vdc (300 mA),10 Vdc (5 mA)
Day and time indication dater with lithium backup battery (unavailable)
User display Backlit LCD display with 16 characters x 2 rows , 5
buttons, buzzer for acoustic
Short circuit protection With fuse (25 Amp)

CERTIFICATIONS
CE

5
6. Pump installation

Entire installation procedure must be performed verifying that pump is not connected to the
mains.

Pump can be installed both vertically and horizontally,


but the outlet should never be below the horizontal
line.

If the pump is not installed in a well, to grant a proper


cooling, a cooling sleeve must be used; doing so the
minimum speed of the pumped liquid has to be
granted.

6.1 Installing pump in the well

To reduce noise transmission it is advised to use plastic pipes.


The pump must always be secured in the well through a special rope attached to loop on the pump head.
It is recommended not to drop the pump in the well by using the electric cable, its integrity must be preserved in all
operations. In this regard it is recommended to fix the cable on cable support or on the pipe.
During operation the pump suction must always remains at least 1.5 meters below the dynamic water level.

6
Do not drop the pump in the well by using the electric cable
Make sure about the electric cable integrity during all the operations.
Ensure the pump in the well with a stainless steel rope to be fixed to the
hole in the pump head

6.2 Pump cable

4HS are equipped, in their standard configuration, with 5 meter flat cable length.

SINGLE PHASE INPUT POWER

brown
red
blue

ground white

POWER SIGNAL

If the distance between the pump and the CM is longer than the supplied cable it is necessary to make a junction
performed by the special kit supplied as standard.
The cable section for additional power conductors must be calculated considering the maximum allowed voltage
drop.

4HS model type of wire total cable length


10 – 50 m 50 – 100 m 100 – 150 m 150 – 200 m
4HS 02/04 2,5 mm2 (AWG
power 4mm2 (AWG 11) 6 mm2 (AWG 9) 10 mm2 (AWG 7)
4HS 04/03 13)
4HS 06/02 signal 1 mm2 (AWG 17) 1,5 mm2 (AWG 15)
4HS 02/08 power 4 mm2 (AWG 11) 6mm2 (AWG 9) 10 mm2 (AWG 7) 16 mm2 (AWG 5)
4HS 04/05
4HS 06/04 signal 1 mm2 (AWG 17) 1,5 mm2 (AWG 15)

7
To make the junction is necessary to follow carefully the instructions inside the kit.

At the time of joining and electrical connection is essential to maintain the


correspondence between the signal cables.

After cable joining and placed the pump in the well you must perform, before
connecting to the CM, a test of insulation: join together the two power cables and,
applying a voltage of 500V, an insulation resistance from the ground higher than 100
Mohm must be verified. Join together the two signal cables and, applying a voltage of
500V, an insulation resistance from the ground higher than 100 Mohm must be verified.

7 CM installation

The CM can be easily fixed to the wall using 2 screws through the holes shown in Figure 2.

Then using the special inserts thus cover can be fixed firmly.

The IP55 protection degree enables the CM installation even in humid and dusty environments. However it is
recommended to protect the CM from the direct exposure to weather and sunlight.

8
7.1 Electric wiring

L1

Input power line (LINE): Output power line (PUMP): Pump signal:
 L1,L2 power line  M1,M2 terminals  S+ (red)
 GND ground  GND ground  S- (white)

Analog inputs: Digital inputs: Communication Digital outputs (relays):


 AN1 (4-20 mA or 0-10 V)  IN1 auxiliary (RS485):  RELAY1: pump run signal
 AN2 (4-20 mA or 0-10 V)  0V  S1+ NO: normally opened
 IN2  S1- COM: common
 0V
 0V NC: normally closed
 +24V  RELAY2: alarm signal
 IN3
 AN3 (4-20 mA)
 0V NO: normally opened
 AN4 (4-20 mA)  IN4 COM: common
 0V  0V NC: normally closed
 +24V
 10V Relays of digital outputs are free
 0V contacts relays (no voltage) Max
AN1 o AN2 terminals can be set as voltage is 250 V AC and max
voltage input (V) or current input (I)
current is 5 A.
through J5 e J9 selector.

9
Read carefully the Guidelines for safety before installing the device.
At the end of the installation check that no other objects are inside the CM or
deposited on the electronic board.
It is recommended to tighten all 4 screws with washers of the cover before
powering the device. Otherwise, you may fail to connect to ground the cover
with a risk of electric shock or even death.

8. 4HS pumps installation for constant pressure mode

CM can manage the rotation speed of pump to maintain constant the pressure in a point of plant regardless the
water demand of the user.
The basic scheme of a line of pumping system capable of achieving this operation is as follows:

10
8.1 Pressure tank

Installation of a pressure tank in the hydraulic system is recommended to compensate leakage of water in the
system (or during minimum water demand) and to avoid continuous start/stop cycling of the pump (check the
appendix for more information).

Selecting the proper volume and pre-charge pressure of the tank is very important; smaller tank volumes will not
compensate adequately for minimum water usage or leakage, while larger volumes make it more difficult for CM to
control the pressure evenly.

Recommended tank volume is equal to the 10% of the maximum water flow of the system (expressed in volume
unit/min)

Example: if the max water flow is 50 liters/min, the pressure tank should have a capacity of 5 liters
If the max water flow is 20 gpm, the pressure tank should have a capacity of 2 gallons

Pre-charge pressure of the pressure tank should be at least 1 bar (15 psi) less than the set-pressure of the system.

Example: if the set-pressure of the system is 4 bar, the pre-charge pressure of the tank should be 3 bar
If the set-pressure of the system is 60 psi, the pre-charge pressure of the tank should be 45 psi

8.2 Pressure sensor

It is possible to use pressure sensor with a linear output signal with range 4 – 20 mA.
Pressure transducer will be powered by any range of DC voltage including the value 24 V.
It is necessary to set the pressure sensor characteristics in the initial configuration menu or in the installer menu
(please check the relevant chapter on setting parameters).

The connection of the pressure sensor is through the analog input terminals

0V (signal GND, if available)

+24V (power supply 24 V dc)

AN1 (signal 4-20 mA)

CM accepts the signal of an additional pressure transducer to be activated automatically if the first transducer fails;
it is enough to connect the wires of the additional pressure transducer to pin AN2 (signal 4-20 mA) and +24V (power
supply 24 V dc).

11
To stabilize the pressure control operated by the CM module, it is suggested to put the
pressure sensor near the well exit, after the check valve.

Pressure sensor and power cables can be close but it is suggested to use a shield cable
connecting the shield to the sensor ground pin.

8.3 Minimum stop frequency at 0 delivery (f min Q=0) during constant pressure control.

Minimum stop frequency is the minimum frequency value that, while maintaining the p_set, water delivery is zero.
Below scheme graphically shows the function:

H
100 Hz

80 Hz

p_set (es: 3 bar)

76 Hz

40 Hz

Progressively closing the water delivery valve reduces flow, causing CM to reduce the pump speed by reducing the
output frequency, to maintain a constant pressure (i.e. 3 bar).
Once the water flow stops (output completely closed), pump will run at minimum frequency to maintain the set
pressure.
Upon determining that the water requirement has stopped, CM stops the pump to save energy. Thus, the pump will
be stopped when minimum frequency is reached.
Once the pump is stopped at min. frequency value, set pressure is maintained in the system.
To maintain the pressure on the pump output line, it is necessary to install a small pressure tank able to compensate
for minor water leakage and to limit the number of pump restarts.
It is important to pinpoint that a particular set pressure corresponds to a single value of min. stop frequency.

If the end user wants to change the set pressure, a new value of min. stop frequency
should also be set.

12
9. 4HS pumps performance range

13
14
15
10. 4HS use and programming

CM software is extremely simple to use, but allows a wide variety of parameters to be set for ideal system
calibration.
Setting Parameters are organized in 2 levels:
1: Installer level
A password is required for this level; these parameters are adjustable by trained professionals
Default password: 001
From the menu a different password can be set up.

2. Advanced level
A second and different password is required; improper setting of these advanced parameters could
compromise the integrity and the life of CM and pump;
Default password 002
It is possible to set up a different password.

Installer and Advanced levels can be entered only with the correct password; otherwise, it is impossible to set
up and/or modify any parameters (they can be only displayed).

10.1 Display

Scroll up

Scroll down
START motor
ENTER

STOP motor
Menu exit
Alarms reset

Screen is a back-lit LCD displaying 2 rows of 16 digits each. Alarms are indicated by an audible signal.

10.2 Initial setting

When the 4HS is switched on for the first time, the initial setting menu is displayed for the initial setting of
parameters to configure pumps and plant characteristics.

If the initial setting procedure is not ended properly, it is impossible to run the pump.

Initial setting procedure can be repeated.

16
The CM software suggests default values for each parameter. If you wish to change the suggested value, press
ENTER button, wait for the value blinks and act on the scroll keys. Press ENTER again to set the new value that will
end to flash.

A detailed description of parameters of initial setting will follow:

parameter default description


Language English End user communication language.

Italiano / English

Unit bar Select Pressure unit.

bar/psi

Control mode: Constant pressure


F.s. press. sensor 16 Set max pressure of pressure transducer;
Set the pressure value of the transducer when output signal is
20mA = XXX.X [bar] 20 mA equivalent to the higher value of pressure range.

Offset sensors Zero point adjustment of the transducer (4mA) as offset


compensation; automatically done by pressing Enter.
Press ENT for tuning If the transducer is not connected or wrongly connected the
signal PRESS. SENSOR OFF is activated.
Max alarm pres. 10 It’s the maximum pressure suitable in the system. If the
pressure goes over an alarm occurs and pump is stopped.
p = XX.X [bar] Pump is automatically restart if the pressure goes below the
maximum value for time of at least 5 seconds.
Set pressure 3 It is the pressure value to be kept constant.

p = XX.X [bar]

OFF If ON is selected, after a lack of voltage, 4HS returns to its


Auto restart
normal status; if 4HS was powering the pump before voltage
ON/OFF drop, it returns to feed the pump without any kind of advise.
Warning, read again the advice of the chapter 1.
Once the Setting procedure is completed you will get this
indication on the display; set parameters are recorded by 4HS;
INITIAL SET UP
these parameters can be singly set up in the INSTALLER
COMPLETED Parameters menu or ADVANCED Parameters menu. If you
with to reset to initial parameters use the DEFAULT
Parameters menu.

17
10.3 Initial view

When powering the CM LCD display shows: model, release of digit display software (LCD =X.XX) and the release of
inverter software (INV = X.XX) as shown below:

www.nastec.eu www.nastec.eu www.nastec.eu

4HS LCD = X.XX INV = X.XX

The following End User messages are displayed by pushing the scroll buttons:

p_m is the pressure value read by the pressure transducer


Inv: ON/OFF Mot: ON/OFF
By pressing ENTER the pressure set value is displayed.
p_m=XX.X [bar] Holding more than 5 seconds the ENTER button you can change the pressure set
value.
f value is the supply frequency to the motor; by pressing ENTER you can change
Inv: ON/OFF Mot: ON/OFF
the f value manually (word “set” is displayed) , pressing again ENTER you exit this
f = XXX.X [Hz] set possibility (word “set” disappeared).

Inv: ON/OFF Mot: ON/OFF V_in is the voltage supplied to the motor. This value is displayed only if motor is
off; if motor is ON, I value appears , equivalent to the absorbed motor current.
V_in=XXX [V] / I=XX.X [A]

Inv: ON/OFF Mot: ON/OFF cosphi index means the angle phi between the voltage and current absorbed by
the motor.
cosphi = X.XX

Inv: ON/OFF Mot: ON/OFF P is the power in W supplied to the pump.

P = XXXXX [W]

Inv: ON/OFF Mot: ON/OFF

STATUS:NORMAL/ALARM NORMAL status means no alarms.


If an alarm occurs a message blinks on the display and an audible signal is
Inverter Life activated.
xxxxx h : xx m
By pushing ENTER accesses: inverter lifetime, pump lifetime, alarm list.
PUMP lifetime is increasing when pump is powered.
Motor Life

xxxxx h : xx m
To come back to previous views press ENTER.

ALL. XXXXXXXXXXXXX

XXXXXXX h : XX m

Menu Return to MENU list by pressing ENTER.

ENT to enter

First row gives the 4HS status:


 Inv:ON XXX.X Hz CM is powered and feeding the 4HS showing its frequency.
 Inv:ON Mot: OFF CM is powered but 4HS is not running (i.e. motor/pump was stopped due to minimum
frequency being reached).
 Inv:OFF Mot: OFF 4HS is not controlled.

18
10.4 Menu display

Pressing ENTER where you are in *MENU’ / ENT to access] in initial display, the following MENUs are displayed:

MENU
Password required to enter (default 001)
Instal. param.

MENU
Password required to enter (default 002)
Advanced param.

MENU
Installer password required to enter (default 001)
Retrieve Init. Set. It is possible to return to original default set parameters (Change Init. Set.)

MENU’
Password required to enter (default 002)
Change Init. Set.

To exit the Menu level and return to INITIAL DISPLAY is enough to press STOP button

10.5 Installer parameters

Most of the installer parameters are already set up during the initial configuration (chapter 6.2 Settings). Through
this menu is possible to change again the previous parameters or enable further parameters allowing a perfect
calibration of the pumping system in relation to the plant.

parameter desciption Const.press.2val

Constant temp.
Constant press.

Fix speed 2 val.


External speed

Constant flow
Fix speed
default

Mode of control:
Const. press.

 Constant pressure: CM changes the speed of pump to keep the


pressure constant, independent of water demand
Control mode  Fixed frequency: CM feeds the pump a set frequency, so the speed of
motor is kept constant.
 Constant press.  Constant pressure control with two values; the two values are
selected by opening or closing the digital input 2.
 Fix speed
 Fixed frequency control with two values to be selected by opening or
 Const.press.2val closing the digital input 2.
 Fix speed 2 val.  External speed: control motor frequency by using analogical input 4-
 External speed 20 mA connected to input AN4.
 Constant temp.  Constant temp.: CM changes the speed of pump to keep the
 Const. flow temperature constant. An analogical signal 4-20 mA coming from a
temperature sensor must be connected to input AN3.
 Constant flow: CM changes the speed of pump to keep the flow
constant. An analogical signal 4-20 mA coming from a flow sensor
must be connected to input AN3.

19
parameter desciption

Const.press.2val

Constant temp.
Constant press.

Fix speed 2 val.


External speed

Constant flow
Fix speed
default
Unit
bar
Pressure unit
 
bar/psi

Unit °C Temperature unit



°C / °F

F.s. press.sensor
16 Maximum pressure of pressure transducer;
Set the pressure value of the transducer 
when output signal is 20 mA equivalent to the
20mA = XX.X [bar] highest value of pressure range
(i.e. 0 – 10 bars transducer range) 10 bars =
20 mA
F.s. temp.sensor 100 Full scale of the temperature sensor.
From the plate data of the sensor can read the 
20mA = XXX.X [°C] temperature at which the sensor provides
output 20 mA.
Min temp. sensor 0 Full scale of the temperature sensor.
From the plate data of the sensor can read the 
4mA = - XXX.X [°C] temperature at which the sensor provides
output 4 mA.
F.s. flow sensor 100 Full scale of the flow sensor.
From the plate data of the sensor can read the 
20mA = XXX.X [m3/h] flow at which the sensor provides output 20
mA.

Offset sensors
Zero point adjustment of the transducer
(4mA) as offset compensation; automatically  
done by pressing Enter.
Press ENT If the transducer is not connected or
connected improperly, the signal an alarm is
activated when pressing ENTER.

Max alarm pres.


10 Maximum pressure allowed in the system. If
the pressure goes over this value, an alarm 
occurs and the pump is stopped. Pump is
p = XX.X [bar] automatically restarted if the pressure goes
below the maximum value for a period of at
least 5 seconds.
0 Minimum pressure allowed in the system. If
the pressure goes lower than the set value, an 
alarm occurs and the pump is stopped. Pump
Min alarm pres. is automatically restarted if the pressure goes
higher than the minimum value for a period of
p = XX.X [bar] at least 5 seconds. This parameter is
particularly useful in the event a system pipe
breaks. It is suggested to set a value higher
than 0.

20
parameter desciption

Const.press.2val

Constant temp.
Constant press.

Fix speed 2 val.


External speed

Constant flow
Fix speed
default
Set pressure 3 The pressure value to be kept constant.
 
p = XX.X [bar]

p loss compens. 0 Pressure compensation at the maximum


frequency for each pump. Acting on the green  
p = XX.X [bar] button you can reverse the sign.

Set pressure 2 3 The pressure value to be kept constant.



p = XX.X [bar]

p loss compens. 2 0 Pressure compensation at the maximum


frequency for each pump. Acting on the green 
p = XX.X [bar] button you can reverse the sign.

Press. set update 5 Time to update p set for losses compensation.


 
t = XX [s]

To ensure proper operation of pressure control is recommended to place the sensor near the pump.
To compensate the pressure loss in the pipes (proportional to flow) it is possible to vary the pressure set in a linear
relation with respect to frequency. If Q = 0, Set pressure is granted while at the max output frequency will be
granted the Set pressure + p loss compens.

It can perform the following test to verify the correct value of p loss compensation:
1. install a pressure gauge away from the pressure sensor
2. open completely the valve
3. check the pressure gauge
--> Set the value of p loss compens. equal to the difference of the values from the two gauges.

21
parameter desciption

Const.press.2val

Constant temp.
Constant press.

Fix speed 2 val.


External speed

Constant flow
Fix speed
default
Operating freq. 50 Set the frequency value (or the speed) to feed
the pump.  
f = XXX [Hz]

Operating freq. 2 50 Set the frequency value (or the speed) to feed
the pump. 
f = XXX [Hz]

Temperature set 25 Temperature value to be maintained constant.



T = XXX.X [°C]

Flow set 10 Flow value to be maintained constant.



Q = XXX.X [m3/h]

Set f. min Q=0 40 Minimum frequency at which the pump must


stop.   
fmin = XXX [Hz]

Stop delay Q=0 5 Delay for which the pump will stop once the
minimum frequency is reached (f min Q=0)   
t = XX [s]

Ramp Q=0
20 Ramp time from freq min Q=0 to motor freq
min. If, during this time, the p checked goes   
below the (p_set -delta start pres), CM powers
t = XX [s] the motor again; otherwise, CM will stop the
pump following the min freq. of motor ramp.

Delta start pres 0.3 This value represents the pressure drop below
the set pressure required to start the pump.  
p = XX.X [bar]

22
parameter desciption

Const.press.2val

Constant temp.
Constant press.

Fix speed 2 val.


External speed

Constant flow
Fix speed
default
Delta stop press 0.5 It 's the increase of pressure respect to
pressure set which must be passed so that  
p = XX.X [bar] there is a forced shutdown of the pump.

Delta start temp. 0.5 The common parameters than you should get
the temperature above the temperature set 
T = XXX.X [°C] so that the pump, arrested earlier, are
restarted.
Delta stop temp. 1 It 's the temperature rise compared to
temperature set which must be passed so that 
T = XXX.X [°C] there is a forced shutdown of the pump.

Ki
Kp and Ki parameters allow the dynamic
control of system by CM; set values (Ki=50,   
Kp=4) are usually enough to get a valid
XXX dynamic control; if the set pressure do not
consent a valid control, proceed as follows;
Kp increase or reduce Ki while keeping Kp
constant; if the problem persists, increase Kp
XXX value and increase or reduce the Ki value
again till a good dynamic control is reached.
PI control
Dire
ct
Direct: increasing misured pressure, CM
decreases motor frequency. 
Direct/Reverse Inverse: increasing misured pressure, CM
increase motor frequency.

Digital input 1
N.O. By selecting N.A. (normally open) CM runs
the motor if the digital input 1 is open; motor 
will be stopped if the digital input 1 is closed.
N.O. / N.C. By selecting N.C. (normally closed) CM runs
the motor if the digital input 1 is closed; motor
will be stopped if the digital input 1 is opened.

Digital input 2
N.O. By selecting N.A. (normally open) CM runs
the motor if the digital input 2 is open; motor 
will be stopped if the digital input 2 is closed.
N.O. / N.C. By selecting N.C. (normally closed) CM runs
the motor if the digital input 2 is closed; motor
will be stopped if the digital input 2 is opened.

Digital input 3
N.O. By selecting N.A. (normally open) CM runs
the motor if the digital input 3 is open; motor 
will be stopped if the digital input 3 is closed.
N.O. / N.C. By selecting N.C. (normally closed) CM runs
the motor if the digital input 3 is closed; motor
will be stopped if the digital input 3 is opened.

Digital input 4
N.O. By selecting N.A. (normally open) CM runs
the motor if the digital input 4 is open; motor 
will be stopped if the digital input 4 is closed.
N.O. / N.C. By selecting N.C. (normally closed) CM runs
the motor if the digital input 4 is closed; motor
will be stopped if the digital input 4 is opened.

23
parameter desciption

Const.press.2val

Constant temp.
Constant press.

Fix speed 2 val.


External speed

Constant flow
Fix speed
default
Change PASSWORD1 Pressing ENT allows the installer level
password (1st level) (default 001) to be 
ENT changed.

10.6 Advanced parameters

All the advanced parameters, due to their importance, are automatically set during initial setup. However, it is
always possible to modify individual parameters or modify the password 2:

parameter default description


230 Motor rated voltage (as shown in the motor plate)
Rated motor Volt. Average voltage drop due to the inverter is between 20
V and 30 Vrms based on load condition, so when the
V = XXX [V] input voltage is 230 V the average output voltage will
be between 200 V and 210 Vrms.

Voltage boost 1 Refers to the voltage increase during the start up of the
motor.
V = XX [%]

Max motor Amp. 12 Max current absorbed by the motor.


This parameters allows the possibility to limit the
I = XX.X [A] current to the motor limiting as well the hydraulic
performances.
Max motor freq. 110 Maximum frequency of the motor. Note: by reducing
the maximum frequency of the motor, maximum
f = XXX [Hz] current will be reduced as well.

Min motor freq. 40 Minimum frequency of the motor. Note: for 4HS pump
is not advisable to set minimum frequency lower than
f = XXX [Hz] 40 Hz in order to protect the integrity of the thrust
bearings.
5 Ramp-up time to reach the speed required to achieve
the set pressure (or frequency value). Longer times
Ramp up time
delay the system reaching the pre set value but better
t = XX [sec] protect system components.
Excessively long ramp-up times can create difficulties in
CM setup, and can also cause false overload alarms.
5 Ramp-down time to reach zero speed. Longer times
keep the system pressurized, while protecting the
Ramp down time
system components.
t = XX [sec] Excessively long ramp-down times can create
difficulties in CM setup. Excessively short ramp-down
times can cause false overload alarms.

24
parameter default description
0.5 Time to reach the minimum frequency of the motor
Ramp f min mot.
and vice versa.
t = XX [sec] Note: it’s important to keep this time less than one
second.

Dry run cosphi 0.50 If the pump goes into dry-running, the cosphi reaches
its lowest level. Typically the value 0.50 is sufficient to
cosphi = X.XX detect dry running pump 4HS.

PWM 10 Carrier frequency (switching frequency).


It is possible to chose PWM in the range of 2.5 ,4, 8, 10,
f = XX [kHz ] 12 kHz .

50 This parameter allows you to change the V / f


characteristic with which MINT feeds the engine. The
linear characteristic corresponds to constant torque
V/f lin. --> quad. with variable speed. The quadratic characteristic is
normally used with centrifugal pumps. The selection of
XXX % torque characteristic should be done ensuring a
smooth operation, a reduction of energy consumption
and a lower level of heat and acoustic noise.

25
parameter default description

OFF If ON is selected, after a lack of voltage, 4HS returns to


Autorestart
its normal status; if 4HS was powering the pump
ON/OFF before voltage drop, it returns to feed the pump
without any kind of advise.
Warning, read again the advice of the chapter 1.
Change PASSWORD2 Pressing ENT allows the advanced level password (2st
level) (default 002) to be changed.
ENT

26
11. Protections and alarms

Anytime a protection occurs a blinking message is displayed together an acoustic alarm; on STATUS on INITIAL VIEW
the protection is displayed; by pressing STOP button (only and exclusively from the this position of STATUS on
INITIAL VIEW) is possible to try to reset the alarm; if CM does not reset the alarm it is displayed again together an
acoustic sound.

ALARM MESSAGE ALARM DESCRIPTION POSSIBLE SOLUTION

Motor overload: input  Check other possible causes about the


current of the motor is over current
OVERCURRENT MOT. higher the rated motor
current set as parameters

UNDERVOLTAGE Supply voltage too low Check possible causes of undervoltage

OVERVOLTAGE Supply voltage too high Check possible causes of overvoltage

 Make sure than ambient temperature


OVER TEMP. INV. Inverter over temperature
is less than 35 °C

 Check if the pump is primed

If pumps cosphi is lower than the set dry


running cosphi for at least 2 seconds, CM stops
the pump. CM tries to run the pumps every
Motor cosphi is lower than
10, 20, 40, 80, 160 minutes and then the pump
NO WATER the set value of dry running
is definitely stopped with NOWATER indication.
cosphi
(DRY RUN COSPHI)
WARNING: if dry running protection occurs, CM
tries to start the pump automatically without
any advice.

Be sure to have cut power supply before to


make maintenance.

 Check the pressure transducer


PRESS. SENS. FAULT Pressure sensor error  Check the wiring of pressure transducer
(signal into AN1 or AN2)

Flow sensor error  Check the flow transducer


FLOW SENS. FAULT
 Check the wiring of transducer (AN3)

Temperature sensor error  Check the temperature transducer


TEMP. SENS. FAULT
 Check the wiring of transducer (AN3)

27
ALARM MESSAGE ALARM DESCRIPTION POSSIBLE SOLUTION

Measured pressure value  Make sure about the possible causes to


has reached the maximum reach the max pressure
OVER PRESSURE pressure accepted by the  Check the max pressure value set
system

 Make sure about the possible causes to


Measured pressure value reach the min pressure (i.e. broken
UNDER PRESSURE has reached the lowest pipe)
pressure accepted by the  Check the min pressure value set
system

The current drawn by the


load exceeds the capacity
 Check the voltage drop along the supply
of inverter.
cable to the motor
CM is nevertheless able to
 Check the line voltage
continue to power the load
OVERLOAD INV.  Reduce the max motor frequency value
for 10 minutes with an
(Installer parameter menu)
output current of 101%
 Contact assistance
nominal one and for 1
minute with an output
current of 110% nominal
one

Communication between  Check the wiring connections


NO COMMUNICATION pump and CM is
interrupted  In the Status display (where the alarm NO
COMMUNICATION is displayed) try to reset
the alarm pushing STOP button

A button of keyboard is  Make sure buttons are involuntarily


KEYBOARD FAULT kept pressed for more than pressed
30 seconds  Call service assistance

Digital input contact Check the input digital configuration


DIGITAL INPUT opened /closed (under Installer Parameters menu ,
digital input 1 and digital input 2)

28
ALARM MESSAGE ALARM DESCRIPTION POSSIBLE SOLUTION

If pumps cosphi is lower than the dry running cosphi for at least 2 seconds,
CM stop the pump. 4HS try to run the pumps every 10, 20, 40, 80, 160
minutes and then the pump is definitely stopped.

ATTENTION: if dry running protection occurs, CM try to start the pump


automatically without any advice.

Be sure to have cut power supply before to make maintenance.

CM will stop the pump if the input motor current is higher than the set motor
current for long time. By pressing START button is possible to run the pumps
again.

CM will stop the pump if the input voltage is higher than the set voltage for
long time. By pressing START button is possible to run the pumps again.

CM will stop the pump if the input voltage is lower than the set voltage for
long time. By pressing START button is possible to run the pumps again.

29
12. Trouble-shooting chart

LCD does not switch on  Check the connecting flat cable between the LCD board (fixed to the
after powering the CM cover) and the control board.
 Check the fuses.
 Check the feeding cable are properly connected (L1, L2, ground).

Power line of CM is  Check the leakage current to ground of EMC filter.


interrupted by the  following a rapid off/on operation the power supply differential
differential protecting contactor can interrupt again the power . After turning off the 4HS is
contactor therefore recommended to wait at least 1 minute before start the
system.

When performing the  check that the sensor cable is properly connected to the sensor device
Offset operation of the and CM.
pressure device, SENS.  Make sure that the sensor and its cable are no damaged.
PRESS. OFF alarm  Check that the range of pressure sensor is of 4 -20 mA type and the
occurs value of 15 V will be within its voltage feeding range.

Frequency and  Check if the water tank and its air pressure are correct. In addition, it is
pressure oscillation on suggested to increase the tank volume or reduce the pre-charge
constant pressure pressure.
control mode  Check the ki e kp parameters (Installer Parameters menu).
At first, it is advisable to increase the Ki value. If it not enough, reduce
of one unit the Kp value.

During constant  Make sure that the value f min Q=0 (minimum frequency with Q=0)
pressure control, pump (Installer Parameters menu) is properly set up. Otherwise repeat the
stops and starts procedure.
continuously..  Increase the value of parameter stop delay Q=0 (Installer Parameter
menu).
 Increase the value of “Ramp Q=0” parameter (Installer Parameters
menu).

Measured pressure  Decrease the delta start pressure (Installer Parameters menu).
p_m drops too much  Decrease the delta start pressure (Installer Parameters menu).
before 4HS turning on  Check if the water tank and its air pressure are correct. In addition it is
the pump. suggested to increase the tank volume or reduce the pre-charge
pressure.
 Modify the value of ki e kp parameters (Installer Parameters menu).
At first, it is advisable to reduce the Ki value. If it is not enough,
increase of one unit the Kp value.

30
13. Technical Assistance

For more technical information contact the authorized reseller providing the following informations. Easier and
faster will be the solution of the problem if full information will be provided.

4HS model LCD version (shown when CM is power INV version (shown when CM is power
supplied) supplied)
4HS - / LCD = _.__ INV = _.__

Line voltage: ___ [V] Line Frequency: 50 Hz 60 Hz

Description of the problem:

Motor cable length [m]: _____ Motor cable section [mm2]:____

Pressure tank volume: _____ [liter] Precharge pressure : _____ [bar]

Pressure sensor signal range (in accordance to the value reported on the sensor plate)

4 mA = ___ [bar]

20 mA = ___[bar]

Used input digital & uses Used digital output and uses

electric and hydraulic scheme of the (better if explained pipes length and diameter , check valves and ball valves
position, , pressure tank position, pressure sensor position, , main switches position, control boxes, etc.)

Set parameters: please fill in the software scheme with the set parameters and attach the scheme to the email or
send it to us by fax.

31
DECLARATION OF CONFORMITY
In according with:

Machine Directive 2006/42/EC

EMC Directive 2004/108/CE

4HS 02/04, 02/08, 04/03, 04/05, 06/02, 06/04 conform to the following regulations:

EN 55011 Class A
EN 60335-1, EN60335-2-41

Vicenza, 06/09/2011

Ing. Marco Nassuato


Operation Manager

32
NOTE

Copyright NASTEC srl 2011


Nastec reserves the right to modify informations in this manual without any notice.
Nastec srl, Via della Tecnica, 8, 36024, Mossano, Vicenza, Italy, Tel. +39 0444 886289, Fax +39 0444 776099, www.nastec.eu,
[email protected]

33
34

You might also like