Code - Commentary IS 875 (Part3) - Watermark
Code - Commentary IS 875 (Part3) - Watermark
0
:: IITK-GSDMA-Wind04-V1.0
Interim Report II :: B - Wind Codes
IITK-GSDMA Project on Building Codes
Dr.Krishen Kumar
Dr. N.M. Bhandari
Dr. Prem Krishna
Department of Civil Engineering
Indian Institute of Technology Roorkee
Roorkee
DRAFT Code & Commentary IS:875 (Part 3)
This document has been made available as a “Draft for Comment” and is
not ready for use. It is still in development stage as a part of ongoing
project on Building Codes sponsored by Gujarat State Disaster
Management Authority, Gandhinagar at Indian Institute of Technology
Kanpur.
The views and opinions expressed are those of the authors and not
necessarily of the GSDMA, the World Bank, IIT Kanpur, or the Bureau of
Indian Standards.
Comments and feedbacks may please be forwarded to:
Prof. Sudhir K Jain, Dept. of Civil Engineering, IIT Kanpur, Kanpur
208016, email: [email protected]; [email protected]
CODE COMMENTARY
Foreword
0.1 This Indian Standard IS:875 (Part 3)
(Third Revision) was adopted by the
Bureau of Indian Standards on
________(Date), after the draft finalized
by the Structural Safety Sectional
Committee had been approved by the
Civil Engineering Division Council.
CODE COMMENTARY
*
Criteria for Earthquake Resistant Design of Structures (2002 revision).
IITK-GSDMA-Wind02-V3.0 Page 3 IITK-GSDMA-Wind04-V1.0
DRAFT Code & Commentary IS:875 (Part 3)
CODE COMMENTARY
CODE COMMENTARY
roughness.
(g) The external and internal pressure
coefficients for gable roofs, lean-to
roofs, curved roofs, canopy roofs
(butterfly type structures) and
multi-span roofs were rationalized.
(h) Pressure coefficients were given
for combined roofs, roofs with sky
light, circular silos, cylindrical
elevated structures, grandstands,
etc.
(i) Some requirements regarding
study of dynamic effects in flexible
slender structures were included.
Use of gust energy method to arrive at
the design wind load on the whole
structure was permitted.
0.3.3 The Committee responsible for the
revision of wind maps while reviewing
available meteorological wind data and
response of structures to wind, felt the
paucity of data on which to base wind
maps for Indian conditions on
statistical analysis. The Committee,
therefore, recommended to all
individuals and organizations
responsible for putting-up of tall
structures to provide instrumentation in
their existing and new structures
(transmission towers, chimneys,
cooling towers, buildings, etc.) at
different elevations (at least at two
levels) to continuously measure and
monitor wind data. It was noted that
instruments were required to collect
data on wind direction, wind speed
and structural response of the
structure due to wind (with the help of
accelerometers, strain gauges, etc). It
was also the opinion of the committee
that such instrumentation in tall
structures will not in any way affect or
alter the functional behaviour of such
structures, and the data so collected
will be very valuable in evolving more
accurate wind loading on structures.
0.3.4 It is seen at the time of undertaking
the third revision of this code (during
2003-2004) that:
(i) Not much progress has yet been
made in regard to
instrumentation and collection of
data in India as mentioned in
CODE COMMENTARY
CODE COMMENTARY
0 – Scope
1.1 - C1.1 –
This standard gives wind forces and their This code provides information on wind effects
effects (static and dynamic) that should be for buildings and structures, and their
taken into account when designing buildings, components. Structures such as chimneys, cooling
structures and components thereof. towers and bridges are outside the scope of this
code. There are Indian Standards dealing with
chimneys and cooling towers separately.
Information on bridges (only static forces) is
given in IRS and IRC specifications. For
aerodynamics of bridges, specialist literature may
be consulted. With substantial work being done
worldwide in the area of wind engineering there
*
Rules for Rounding-off Numerical Values (Revised)
IITK-GSDMA-Wind02-V3.0 Page 7 IITK-GSDMA-Wind04-V1.0
DRAFT Code & Commentary IS:875 (Part 3)
CODE COMMENTARY
1.1.1 – C1.1.1–
Wind causes a random time-dependent load, Wind is not a steady phenomena due to natural
which can be seen as a mean plus a turbulence and gustiness present in it. However,
fluctuating component. Strictly speaking all when averaged over a sufficiently long time
structures will exhibit a dynamic response to duration (from a few minutes to an hour), a steady
the fluctuating component (gustiness). component of wind velocity can be defined which
However, short rigid structures can be would produce a static force on a structure.
satisfactorily treated as having an equivalent Superimposed on the mean/static component is
static response. This is the approach taken the time varying component having multiple
by most codes and standards, as is also the frequencies spread over a wide band from
case in this standard. The more flexible frequencies above 100 Hz (turbulence) to less
systems such as tall buildings undergo a than 0.1 Hz (gust or large size eddies). The
dynamic response to the gustiness of wind. greater part of energy in these fluctuating
Methods for computing the dynamic effect of components is associated with the lower
wind on buildings have been introduced in frequency components (less than 1 Hz to about 20
this standard. Hz).
Apart from tall buildings there are several
other structural forms (though outside the
scope of this standard) such as tall-latticed
towers, chimneys, guyed masts that need to
be examined for aerodynamic effect.
1.1.2 – C1.1.2 –
This code also applies to buildings or other The construction period of a structure is much
structures during erection/ construction and smaller than its expected life. Therefore, a smaller
the same shall be considered carefully during return period of 5 to 10 years or longer may be
various stages of erection/construction. In considered for arriving at the design velocity
locations where the strongest winds and icing (factor k1) for construction stages/period of a
may occur simultaneously, loads on structure depending on its importance. In snowfall
structural members, cables and ropes shall area where icing occurs, wind loads have to be
be calculated by assuming an ice covering assessed accordingly. Elements such as cables
based on climatic and local experience. and ropes can undergo a dynamic response in
such cases and have to be examined accordingly.
CODE COMMENTARY
1 – Notations
2.1–
The following notations shall be followed
unless otherwise specified in relevant
clauses:
A= Surface area of a structure or
part of a structure
Ae = Effective frontal area
Az = An area at height z
b= Breadth of a structure or
structural member normal to the
wind stream in the horizontal
plane
Cf = Force coefficient / drag
coefficient
CODE COMMENTARY
CODE COMMENTARY
2 – Terminology
For the purpose of this code, the following
definitions shall apply.
Angle of Attack- Angle between the direction
of wind and a reference axis of the
structure.
Breadth – Breadth means horizontal
dimension of the building measured
normal to the direction of wind.
Depth – Depth means the horizontal
dimension of the building measured in
the direction of the wind.
Note – Breadth and depth are
dimensions measured in relation to
the direction of the wind, whereas
length and width are dimensions
related to the plan.
Developed Height – Developed height is the
height of upward penetration of the
velocity profile in a new terrain. At large
fetch lengths, such penetration reaches
the gradient height, above which the wind
speed may be taken to be constant. At
lesser fetch lengths, a velocity profile of a
smaller height but similar to that of the
fully developed profile of the terrain
category has to be taken, with the
additional provision that the velocity at
the top of this shorter profile equals that
of the unpenetrated earlier velocity profile
CODE COMMENTARY
at that height.
Effective Frontal Area – The projected area of
the structure normal to the direction of
the wind.
Element of Surface Area – The area of
surface over which the pressure
coefficient is taken to be constant.
Force Coefficient- A non-dimensional
coefficient such that the total wind force
on a body is the product of the force
coefficient, the dynamic pressure due to
the incident design wind speed and the
reference area over which the force is
required.
NOTE – When the force is in the direction of
the incident wind, the non-dimensional
coefficient will be called as drag coefficient.
When the force is perpendicular to the
direction of incident wind, the non-
dimensional coefficient will be called as lift
coefficient.
Ground Roughness – The nature of the
earth’s surface as influenced by small
scale obstructions such as trees and
buildings (as distinct from topography) is
called ground roughness.
Gust – A positive or negative departure of
wind speed from its mean value, lasting
for not more than, say, 2 minutes over a
specified interval of time.
Peak Gust – Peak gust or peak gust speed is
the wind speed associated with the
maximum amplitude.
Fetch Length – Fetch length is the distance
measured along the wind from a
boundary at which a change in the type
of terrain occurs. When the changes in
terrain types are encountered (such as,
the boundary of a town or city, forest), the
wind profile changes in character but
such changes are gradual and start at
ground level, spreading or penetrating
upwards with increasing fetch length.
Gradient Height – Gradient height is the
height above the mean ground level at
which the gradient wind blows as a result
of balance among pressure gradient
force, coriolis force and centrifugal force.
For the purpose of this code, the gradient
height is taken as the height above the
mean ground level, above which the
variation of wind speed with height need
not be considered.
CODE COMMENTARY
CODE COMMENTARY
profile.
Topography – The nature of the earth’s
surface as influenced by the hill and
valley configurations in the vicinity of the
proposed structure.
3 – GENERAL
4.1 - C4.1 -
Wind is air in motion relative to the surface For the purpose of this code wind velocity has
of the earth. The primary cause of wind is been considered as that occurring at 10 m height
traced to earth’s rotation and differences in above the general ground level. Several new
terrestrial radiation. The radiation effects are recording stations have been established in the
mainly responsible for convection either country by the Indian Meteorological Department
upwards or downwards. The wind generally over the last two decades, the information from
blows horizontal to the ground at high wind which can help upgrade the wind zoning map of
speeds. Since vertical components of India. However, more extensive data are needed
atmospheric motion are relatively small, the to make this exercise meaningful.
term ‘wind’ denotes almost exclusively the
horizontal wind, vertical winds are always
identified as such. The wind speeds are
assessed with the aid of anemometers or
anemographs, which are installed at
meteorological observatories at heights
generally varying from 10 to 30 meters
above ground.
4.2 – C4.2 -
Very strong winds are generally associated Several atmospheric phenomena are responsible
with cyclonic storms, thunderstorms, dust for wind storms. Cyclonic storms, that hit some
storms or vigorous monsoons. A feature of of the coastal regions of India, are the most
the cyclonic storms over the Indian region is devastating due to extremely high wind speeds in
that they rapidly weaken after crossing the these storms accompanied by storm surge and
coasts and move as depressions/ lows flooding. These can last several hours. The
inland. The influence of a severe storm after current revised draft has recognized the fact that
striking the coast does not, in general exceed the high wind speeds that occur in cyclones far
about 60kilometers, though sometimes, it exceed the wind speeds for design given in the
may extend even up to 120 kilometers. Very code at present, and addresses the problem vis-à-
short duration hurricanes of very high wind vis the 60 km strip at the east coast and the
speeds called Kal Baisaki or Norwesters Gujarat coast by including suitable factors to
occur fairly frequently during summer months enhance the design wind speed, keeping in view
over North East India. the importance of the structure.
Tornados, which are a narrow band phenomenon
of limited time duration often occur during the
summer, mostly in Northern parts of India.
These, however, have extremely high wind
speeds, often higher than the severest cyclones.
4.3 – C4.3 -
The wind speeds recorded at any locality are Higher the intensity of a gust, lower is its
extremely variable and in addition to steady
IITK-GSDMA-Wind02-V3.0 Page 14 IITK-GSDMA-Wind04-V1.0
DRAFT Code & Commentary IS:875 (Part 3)
CODE COMMENTARY
wind at any time, there are effects of gusts, duration. The code specifies the basic wind
which may last for a few seconds. These velocity as that of a gust of 3 second duration; or
gust cause increase in air pressure but their in other words, the wind velocity averaged over a
effect on stability of the building may not be 3-second period. The effect of reduction in the
so important; often, gusts affect only part of average wind pressure with increase in the area
the building and the increased local over which the pressure is considered (the
pressures may be more than balanced by a tributary area) is accounted for by the ‘Area
momentary reduction in the pressure Averaging Factor, Ka’ defined in section 6.1.2. A
elsewhere. Because of the inertia of the maximum reduction of 20% in wind pressures is
building, short period gusts may not cause specified for tributary area beyond 100 m2.
any appreciable increase in stress in main
components of the building although the
walls, roof sheeting and individual cladding Contrary to this, one may consider wind
units (glass panels) and their supporting effects over a limited (small) area of the
members such as purlins, sheeting rails and surface. This is particularly important near
glazing bars may be more seriously affected. the edges and ridge of a structure or sharp
Gusts can also be extremely important for corners elsewhere in a building, where large
design of structures with high slenderness suctions occur due to separation. The area
ratios. of influence being small, there is better
correlation within these areas. These local
area effects are treated elsewhere in the
code.
4.4 – C4.4 -
The response of a building to high wind The dynamic characteristics of a flexible structure
pressures depends not only upon the defined by its time period of vibration and
geographical location and proximity of other damping would affect its response to the gustiness
obstructions to airflow but also upon the or turbulence in wind, which itself gets modified
characteristics of the structure itself. by other structures/ obstructions coming in the
way of the wind, particularly those in the close
vicinity of the structure. The effect of the latter is
difficult to evaluate and a simplified approach has
been added for the first time in the code to
approximate these so called interference effects in
Section 7.
4.5 –
The effect of wind on the structure as a C4.5 –
whole is determined by the combined action The pressures created inside a building due to
of external and internal pressures acting access of wind through openings could be suction
upon it. In all cases, the calculated wind (negative) or pressure (positive) of the same order
loads act normal to the surface to which they of intensity while those outside may also vary in
apply. magnitude with possible reversals. Thus the
design value shall be taken as the algebraic sum
of the two in either directions.
Furthermore, the external pressures (or forces)
acting on different parts of a framework, and the
internal pressures, do not correlate fully. Hence
there is a reduction in the overall effect. This has
been allowed for in clause 6.2.3.13.
4.6 – C4.6 -
The stability calculations as a whole shall be The stability of a structure shall be checked both
done considering the combined effect, as with and without the wind loads, as there may be
well as separate effects of imposed loads
IITK-GSDMA-Wind02-V3.0 Page 15 IITK-GSDMA-Wind04-V1.0
DRAFT Code & Commentary IS:875 (Part 3)
CODE COMMENTARY
and wind loads on vertical surfaces, roofs reversal of the forces under wind besides a
and other part of the building above general reduced factor of safety considered with the wind
roof level. loads.
4.7 –
Buildings shall also be designed with due
attention to the effects of wind on the comfort C4.7 -
of people inside and outside the buildings. Comfort of the inhabitants of a tall flexible
building can be affected by large wind induced
deflections or accelerations, particularly the latter.
There is no criterion included in this code for
control on these parameters. Since there is no real
tall building activity yet in India, the problem has
not attained importance. Likewise, at the plaza
level around a tall building, there may be
accentuated flow conditions, particularly if the
building has other similar structures adjacent to it.
Thus the pedestrians at the plaza level can be put
to inconvenience. A model study is required to
determine the flow pattern and to carryout the
design accordingly.
CODE COMMENTARY
CODE COMMENTARY
regional basic wind speed having a mean generally acceptable value of probability of
return period of 50 years shall be used exceedence as 0.63 for the design wind speed
except as specified in the note of Table 1. over the life of the structure. This has been
termed as the risk level P N in N consecutive years
(Table –1) and the corresponding value of the risk
coefficient, k1, for N taken as 50 years, would be
1.0. The values of k1 for N taken as 5, 25 and 100
years, and for various zones of the country, are
given in Table-1. The designer may, however, use
a higher value of N or k1, if it is considered
necessary to reduce the risk level of an important
structure.
Table 1: Risk coefficients for different classes of structures in different wind speed zones
[Clause 5.3.1]
Mean Probable
design life of
structure in k1 Factor for Basic Wind Speed
years (m/s) of
Class of Structure
33 39 44 47 50 55
All general buildings and structures 50 1.0 1.0 1.0 1.0 1.0 1.0
Temporary sheds, structures such as those
used during construction operations (for
example, formwork and false work), 5 0.82 0.76 0.73 0.71 0.70 0.67
structures during construction stages and
boundary walls
Buildings and structures presenting a low
degree of hazard to life and property in the
event of failure, such as isolated towers in 25 0.94 0.92 0.91 0.90 0.90 0.89
wooded areas, farm buildings other than
residential buildings
Important buildings and structures such as
hospitals, communication buildings, towers, 100 1.05 1.06 1.07 1.07 1.08 1.08
power plant structures
NOTE – the factor k1 is based on statistical concepts, which take account of the degree of reliability required, and
period of time in years during which there will be exposed to wind, that is, life of the structure. Whatever wind
speed is adopted for design purposes, there is always a probability (however small) that it may be exceeded in a
storm of exceptional violence; the greater the period of years over which there will be exposure to the wind, the
greater is the probability. High return periods ranging from 100 to 1000 years (implying lower risk level) in
association with greater period of exposure may have to be selected for exceptionally important structures, such
as, nuclear power reactors and satellite communication towers. Equation given below may be used in such cases
to estimate k1 factors for different periods of exposure and chosen probability of exceedence (risk level). The
probability level of 0.63 is normally considered sufficient for design of buildings and structures against wind
effects and the values of k1 corresponding to this risk level are given above.
1
A B ln ln 1 PN
X N ,P
k1
N
X 50, 0.63 A 4B
where
N = mean probable design life of structure in years;
PN = risk level in N consecutive years (probability that the design wind speed is exceeded at least
once in N successive years), nominal value = 0.63;
XN,P = extreme wind speed for given value of N and PN; and
X50,0.63 = extreme wind speed for N = 50 years and PN = 0.63
A and B are coefficients having the following values for different basic wind speed zones:
Zone A B
33 m/s 83.2 9.2
39 m/s 84.0 14.0
44 m/s 88.0 18.0
47 m/s 88.0 20.5
50 m/s 88.8 22.8
55 m/s 90.8 27.3
Table 2: k2 factors to obtain design wind speed variation with height in different
terrains [Clause 5.3.2.2]
Height (z) Terrain and height multiplier (k2)
CODE COMMENTARY
CODE COMMENTARY
CODE COMMENTARY
5.3.2.3 –
C5.3.2.3 -
Terrain categories in relation to the direction Ground obstructions in the path of wind may be
of wind – As also mentioned in 5.3.2.1, the different for different directions of the wind. As
terrain category used in the design of a such different terrain categories shall be
structure may vary depending on the considered in such a case.
direction of wind under consideration. Where
sufficient meteorological information is
available, the basic wind speed may be
varied for specific wind direction.
5.3.2.4 –
Changes in terrain categories – The velocity C5.3.2.4 -
profile for a given terrain category does not The development of wind profile to full height in
develop to full height immediately with the a particular terrain type cannot occur at the onset
commencement of that terrain category but of that category but would be gradual as the wind
develops gradually to height (hx) which passes over it. Thus the developed height, h x,
increases with the fetch or upwind distance becomes a function of the distance covered by
(x). wind into the terrain category, called the fetch
length, x. The code gives the relationship of h x
a) Fetch and developed height relationship with x for various terrain categories.
– The relation between the developed
height (hx) and the fetch (x) for wind-flow
over each of the four terrain categories
may be taken as given in Table 3.
b) For structures of heights greater than the
developed height (hx) in Table 3, the
velocity profile may be determined in
accordance with the following:
(i) The less or least rough terrain, or
(ii) The method described in Appendix
B.
CODE COMMENTARY
5.3.3 – C5.3.3 -
Topography (k3 factor) – The basic wind The factor k3 is a measure of the enhancement
speed Vb given in Fig. 1 takes account of the that occurs in wind speeds over hills, cliffs and
general level of site above sea level. This escarpments.
does not allow for local topographic features
such as hills, valleys, cliffs, escarpments, or
ridges, which can significantly affect wind
speed in their vicinity. The effect of
topography is to accelerate wind near the
summits of hills or crests of cliffs,
escarpments or ridges and decelerate the
wind in valleys or near the foot of cliffs, steep
escarpments, or ridges.
5.3.3.1 –
C5.3.3.1–
The effect of topography will be significant at No increase in wind speed is indicated for upwind
a site when the upwind slope () is greater ground slopes upto 3o, while a maximum increase
than about 3o, and below that, the value of k3 of 36% is specified for slopes beyond 17 o. Thus
may be taken to be equal to 1.0. The value of maximum effect is seen to occur at the crest of a
k3 is confined in the range of 1.0 to 1.36 for cliff or escarpment and reduces gradually with
slopes greater than 3o. A method of distance from the crest. Also locally, k 3 reduces
evaluating the value of k3 for values greater from the base of a structure to its top.
than 1.0 is given in Appendix C. It may be
noted that the value of k3 varies with height
above ground level, at a maximum near the
ground, and reducing to 1.0 at higher levels.
5.3.4 – C5.3.4 –
Importance Factor for Cyclonic Region (k4)
A belt of approximately 60 km width near sea
Cyclonic storms usually occur on the east coast in certain parts of the country is identified
coast of the country in addition to the Gujarat to be affected by cyclonic storms. The peak wind
coast on the west. Studies of wind speed and velocities in these regions may exceed 70 m/s.
damage point to the fact that the speeds Therefore, factor k4 has been introduced with a
given in the map are often exceeded during maximum value of 1.30. However, the highest
such cyclones. The effect of cyclonic storms value may be used only for structures of post-
is largely felt in a belt of approximately 60 km cyclone importance such as cyclone shelters,
width at the coast. In order to ensure greater hospitals, school and community buildings,
safety of structures in this region (60 km wide communication towers, and power-plant
on the east coast as well as the Gujarat structures, water tanks, while a lower value of
coast), the following values of k 4 are 1.15 may be used for industrial structures,
stipulated, as applicable according to the damage to which can cause serious economic
importance of the structure: losses. For reasons of economy, other structures
may be designed for a k 4 value of unity, that is,
Structures of Post–cyclone Importance 1.30
without considering the effect of the possible
Industrial Structures 1.15
higher wind speeds in cyclonic storms.
All other structures 1.0
For non-cyclonic regions the factor k 4 shall
obviously be taken as 1.0.
CODE COMMENTARY
ground level shall be obtained by the the pressure produced by it assumes the mass
following relationship between wind pressure density of air as 1.20 kg/m 3, which changes
and wind velocity: somewhat with the atmospheric temperature and
2 pressure.
p z 0.6 Vz
5– WIND PRESSURES
AND FORCES ON
BUILDINGS/STRUCT
URES
CODE COMMENTARY
CODE COMMENTARY
CODE COMMENTARY
NOTE 1 – The pressure coefficients given in different 3-4 decades. The body of information that has
tables have been obtained mainly from
thus emerged is expected to better represent the
measurements on models in wind tunnels.
wind effects expected in the field. The lack of
NOTE 2 – For pressure coefficients for structures not adequacy of the database, however, remains
covered here, reference may be made to
specialist literature on the subject or advice because of the large variability involved both,
may be sought from specialists in the subject. with respect to the wind – its structure and
directionality - as well as the building geometry.
NOTE 3 – Influence of local values of suction or
pressure may not be of much consequence
for the overall safety of the structure but can
be a cause of local damage to cladding or Typically, pressure coefficient contours over a
glazing. This in turn may have a ‘chain’ effect
and lead to much economic loss.
gable roof may be as seen in Figure C2.
Obviously, it will be ideal to divide the roof into
a large number of zones to specify the pressures
for each zone. This would increase accuracy but
will create difficulties in practical design work.
Making a coarser grid-work will lead to averaged
out values such as in Figure C 3. The approach
adopted in practice is to go by the latter and use
area averages which, in an overall analysis, may
be on the conservative side.
Pressure coefficients are commonly based on the
quasi – steady assumption, whereby the pressure
coefficient is taken to be the ratio of mean
pressure measured over a point divided by the
1
dynamic pressure ( 2 V2) for the mean velocity
of incident wind. Here is the mass density of air
and V the wind velocity. The approach followed
in the present Indian Code as well as the
proposed revision (and several other codes) is to
take V as the peak gust value. Some codes use
the mean wind speed averaged over a longer
period. The approach used implicitly assumes
that the fluctuations in pressure follow directly
those in the velocity. This of course may not be
true, since the wind turbulence gets modified as it
approaches the structure, and eddies form at
separation. However, the method has the
advantage of simplicity, though it may not be
suitable for very large structures. This is for two
reasons – (i) the increasing lack of correlations
over an extended area, and (ii) the dynamics of a
large structural system.
CODE COMMENTARY
(a)
CODE COMMENTARY
(b)
Fig C2. : Contours of Pressure Coefficients over a Pitched Roof (a) C p min (b) Cp mean
CODE COMMENTARY
CODE COMMENTARY
6.2.2.2 –
Building with medium enlarge openings
-Buildings with medium and large openings
may also exhibit either positive or negative
internal pressure depending upon the
direction of wind. Buildings with medium
openings between about 5 to 20 percent of
wall area shall be examined for an internal
pressure coefficient of + 0.5 and later with
an internal pressure coefficient of – 0.5, and
the analysis, which produces greater distress
of the members, shall be adopted. Buildings
with large openings, that is, openings large
than 20 percent of the wall area shall be
examined once with an internal pressure
coefficient of + 0.7 and again with an internal
pressure coefficient of –0.7, and the analysis,
which produces greater distress on the
members, shall be adopted.
Buildings with one open side or opening
exceeding 20 percent of wall area may be
assumed to be subjected to internal positive
pressure or suction similar to those for
buildings with large openings. A few
examples of buildings with one-sided
openings are shown in Fig.2 indicating
values of internal pressure coefficients with
respect to the direction of wind.
In buildings with roofs but no walls, the roofs
will be subjected to pressure from both inside
and outside and the recommendations shall
be as given in 6.2.2.
CODE COMMENTARY
6.2.3.1– C6.2.3.1 –
Table 5 provides mean pressure coefficients for
Walls - The average external pressure
walls of closed rectangular buildings with
coefficient for the walls of clad buildings of
different aspect ratios. Local pressure coefficients
rectangular plan shall be as given in Table 5.
at the edges of the wall, which have relevance to
In addition, local pressure concentration
the design of the cladding and its connections to
coefficients are also given.
the supporting framework are also given in the
Table. Information on force coefficients for free
standing walls is given separately in 6.3.4.11.
6.2.3.2– C6.2.3.2 –
This clause provides information on the roofs of
Pitched, Hipped and Monoslope Roofs of
clad buildings, which are perhaps the most
rectangular clad buildings and effect of
commonly used. Table 6 gives pressure
parapets – The average external pressure
coefficients for pitched roofs with different aspect
coefficients and pressure concentration
ratios and varying roof pitch for two directions of
coefficients for pitched roofs of rectangular
wind incidence - 0o and 90o. The roof surface is
clad building shall be as given in Table 6.
divided into different zones for the purpose of
Where no pressure concentration coefficients
specifying the design pressure values. The values
are given, the average coefficients shall
on the leeward slope are not affected much by the
apply. The pressure coefficients on the under
variations in geometry, which is not so for the
side of any overhanging roof shall be taken in
windward slope where values vary from large
accordance with 6.2.3.5.
pressures to suctions. Local pressure coefficients
Parapets can reduce the wind loads over a for the design of cladding and its connections at
roof. The reduction can be made as given in the edges and ridge are also given – these act
Table 7. upwards, i.e., suction. It is now known that wind
NOTE 1 - The pressure concentration shall be assumed directions other than 0o and 90o can give values
to act outward (suction pressure) at the higher than those at 0o and 90o. However, values
ridges, eaves, cornices and 90 degree are given here for 0o and 90o only, for simplicity
corners of roofs. in design.
NOTE 2 - The pressure concentration shall not be
included with the net external pressure when
computing overall load.
For monoslope and hipped roof also the pressure
NOTE 3 – For hipped roofs, pressure coefficients coefficients can be taken from Table 6, for the
(including local values) may be taken on all applicable roof slope. It has, however, been
the four slopes, as appropriate from Table 6,
and be reduced by 20% for the hip slope. shown that hipped roofs experience smaller
suction as compared to pitched roofs of
For monoslope roofs of rectangular clad corresponding geometry (see Fig. C4 and also
buildings, the average pressure coefficient C5). Thus a relief of 20% is being permitted in
and pressure concentration coefficient for coefficients in the hipped slope.
monoslope (lean-to) roofs of rectangular clad Furthermore, parapets around a roof lead to its
buildings shall be as given in Table 8. shielding. Reduction factors to be used with roof
pressure coefficients depend upon parapet height,
and are given in Table 7. Clad buildings with
monoslope roofs are covered in detail in Table 8.
Pressure coefficients for different angles of wind
incidence are given therein.
IITK-GSDMA-Wind02-V3.0 Page 34 IITK-GSDMA-Wind04-V1.0
DRAFT Code & Commentary IS:875 (Part 3)
Fig. C4. : Worst Peak Negative Pressure Coefficients – all azimuths (Meecham 1992)
Wind +0.8 b
+0.8 b
d
d
-0.5
-0.7
-0.4 -0.3
Table 5 External Pressure Coefficients (Cpe) For Walls Of Rectangular Clad Buildings
(Clause 6.2.3.1)
Wind b +0.8
+0.8
d
d
CODE COMMENTARY
Table 10 Pressure Coefficient For Free Standing Double Sloped Roofs (Clause
6.2.3.3)
CODE COMMENTARY
B C M
Wind
direction
M M M M M
A Y
dS
Figure3: External pressure coefficients (Cpe) for multi-span buildings- pitched roofs
[Clause 6.2.3.4 ]
Wind
B D N N X Wind
direction C M M W
direction
= 0o
= 180o
A h
Y
dS
Table11: External pressure coefficients (Cpe) for multi-span buildings – pitch roofs
[Clause 6.2.3.4]
Use Table 6 for same (h/d), and , -0.3 and 0.2 for < 10 o
0.7 -0.2
as appropriate - 0.5 and 0.3 for 10o
Table12: External pressure coefficients (Cpe) for multi-span buildings – saw-tooth roofs
[Clause 6.2.3.4]
Table 13: External pressure coefficients for curved roofs. [Clause 6.2.3.6]
C
–0.4
Wind
C1 H
0.7
H
l
H/l C C1 C2
0.1 -0.8 +0.1 -0.8
0.2 -0.9 +0.3 -0.7
C
0.3 -1.0 +0.4 -0.3
0.4 -1.1 +0.6 +0.4
–0.4
0.5 -1.2 +0.7 +0.7
0.7 H
C2
H NOTE – When the wind is blowing normal to
gable ends, Cpe may be taken as
Wind equal to –0.7 for the full width of the
roof over a length of l/2 from the gable
+0.8 -0.6 ends and –0.5 for the remaining
portion.
L
+0.8 -0.6
[Clause 6.2.3. 7]
h/D = 25
h/D = 7
_
h/D = 1
h
Cpe
Wind
D
Table 15: External pressure coefficients for roofs and bottoms of cylindrical
buildings [Clause 6.2.3. 8]
P
P
Direction e = 0.1 D e = 0.1 D
of wind Cpe
Cpe
1.5 1.0
0.5
45o
Wind
A A
0.2a
a
Cpe = -1.0
Table 16: External pressure coefficients, Cpe for combined roofs. [Clause 6.2.3. 9]
0.8
Direction c d Direction 1 30o
1 2
b b1 b2
a
h1
0.6 h2
a
b1 b2
1.
Cpe 2 h1/h2
0.2 0.5 1.0 1.5 1.8 2.0 2.5 3.0 3.5
0.13
a
Cpe = (h1/h2)-1.7
0
Direction c d Direction
1 2
b
a
Cpe = 2(h1/h2)- h1
- 0.2 e
2.9 h2
a
- 0.4
- 0.6
Values of Cpe
1.1.1.1 Portion 1.1.1.2 Direction 1 Direction 2
a From the Diagram
- 0.8
Cpe = -0.5, (h1/h2) 1.75 -0.4
b
Cpe = +0.7, (h1/h2) > 1.75
-c1.0
and d See 6.2.3.2
e See 6.2.3.5
Table 17: External pressure coefficients, Cpe for roofs with a skylight. – [Clause 6.2.3.10]
-0.8
Wind b -0.6
a
-0.5
h1 h2
b1 b2
b1 > b2 b1 b2
Portion a b a and b
Cpe -0.6 +0.7 See Table 16
CODE COMMENTARY
6.2.3.11 - C6.2.3.11 –
IITK-GSDMA-Wind02-V3.0 Page 53 IITK-GSDMA-Wind04-V1.0
DRAFT Code & Commentary IS:875 (Part 3)
CODE COMMENTARY
6.2.3.12– C6.2.3.12 –
Spheres – The external pressure coefficients The clauses give pressure coefficients and the
for spheres shall be as given in Table 19. corresponding figures/tables are self explanatory.
6.2.3.13– C6.2.3.13 –
Frames – When taking wind loads on frames, Pressure coefficients on different faces of a
of clad buildings it is reasonable to assume structure, namely the walls or the roof slopes are
that the pressures or suctions over the entire given in the code. These values, as explained
structure will not be fully correlated. earlier, are obtained by averaging values of
Therefore when taking the combined effect of measured pressures in different parts of the
wind loads on the frame, the forces obtained structure. For analysing a frame, reactions from
in the frame may be reduced as per values of these different parts will be accounted for. Forces
Kc given in Table 20. on account of internal pressures will also be
included. The frame will experience the
integrated effect of these different force
components, caused by wind which is
characterized by randomness. Thus the forces
from different components are going to be only
partly correlated. A reduction factor on the
computed responses of the frame is thus being
permitted. The factor varies between 0.8 and 1.0.
Table 18: Pressure coefficients at top and bottom roof of grandstands open on
three sides (roof angle up to 5o) [Clause 6.2.3.11]
(h:b:l = 0.8 : 1 : 2.2)
0.4 h
0o +0.9 -0.5 +0.9 -0.5
B D F H
o
45 +0.8 -0.6 +0.4 -0.4
h
135o -1.1 +0.6 -1.0 +0.4
o
180 -0.3 +0.9 -0.3 +0.9
JL KM
A E
B F J K
0o l
C G
D H
L M
Cpe
Wind
CL
D
Table 20: Combination factors for wind pressure contributing from two or more
building surfaces to effects on major structural elements [Clause
6.2.3.13]
Combination
Design case Example diagrams
factor (Kc)
(a) Where wind action
from any single
surface contributes 1.0 ----
75 percent or more to
an action effect.
(b) Pressures from
windward and
leeward walls in
combination with
positive or negative
roof pressures 0.8
CODE COMMENTARY
CODE COMMENTARY
CODE COMMENTARY
1.5 3
h F
1
1.0
IITK-GSDMA-Wind02-V3.0 Page 60 IITK-GSDMA-Wind04-V1.0
Elevation
0.5 1.0 1.5 2.0 2.5 3.0
0.5 a/b F = Cf pd bh
0
1.4
1/4
1.2 1/4
1/2
h/b =
1/2 1/4
h/b = 1/2
1.0
Figure 6: Force coefficients for rectangular clad buildings in uniform flow [Clause
6.3.2.1]
Table 21: Force coefficients Cf for clad buildings of uniform section (acting in the
direction of wind) [Clause 6.3.2.1]
d
Ellipse < 10 0.5 0.6 0.7
b b/d = 1/2
10 0.2 0.2 0.2
Ellipse
b/d = 2
b
8 0.9 1.1 1.5
d
b/d = 1/2 <3 0.3 0.3 0.4
r b r/b = 1/2
3 0.2 0.3 0.3
d
b/d = 1/2
All values 0.5 0.6 0.7
r b r/b = 1/6
b/d = 2
b All values 1.0 1.2 1.9
r/b = 1/12
b r/a = 1/3
r
10 0.5 0.5 0.6
a
a
45o
r/a = 1/48 All values 0.9 1.2 1.6
r b
r/b = ¼
b
r/b = 1/12 All values 0.8 1.1 1.4
Structures that, because of their size and design wind velocity, are in the supercritical flow
regime may need further calculation to ensure that the greatest loads do not occur at some
wind speed below the maximum when the flow will be sub-critical.
The coefficients are for buildings without projections, except where otherwise shown. In this
table Vzb is used as an indication of the airflow regime .
Table 22: Force coefficients for low walls or hoardings (< 15 m high). [Clause 6.3.2.2]
b
b
h
h
h
16 32 1.4
20 40 1.5
40 80 1.75
60 120 1.8
80 or more 160 or more 2.0
Table 23: Force coefficients for solid shapes mounted on a surface. [Clause 6.3.2.3]
CIRCULAR DISC
1.2
Table 24: Force coefficients (Cf) for individual structural members of infinite length [Clause 6.3.3.1(a)]
½b Ft Ft Ft Ft Ft Ft
b Fn 0.1 b
Fn Fn
b 0o 0o b
0 o 0 o o
0 b 0o b Fn
b b
Fn b
Fn
Wind 0.1b 0.45 b 1.1 0.43 b
b
Cfn Cft Cfn Cft Cfn Cft Cfn Cft Cfn Cft Cfn Cft
Degrees
0 +1.9 +0.95 +1.8 +1.8 +1.75 +0.1 +1.6 0 +2.0 0 +2.05 0
45 +1.8 +0.8 +2.1 +1.8 +0.85 +0.85 +1.5 -0.1 +1.2 +0.9 +1.85 +0.6
90 +2.0 +1.7 -1.9 -1.0 +0.1 +1.75 -0.95 +0.7 -1.6 +2.15 0 +0.6
135 -1.8 -0.1 -2.0 +0.3 -0.75 +0.75 -0.5 +1.05 -1.1 +2.4 -1.6 +0.4
180 -2.0 +0.1 -1.4 -1.4 -1.75 -0.1 -1.5 0 -1.7 2.1 -1.8 0
Ft Ft Ft Ft Ft
o 0.5 b Fn Fn b Fn *
b 0 b
Fn 0o b 0o 0o Fn b
0o
1.6 b
b 0.48 b
b 0.1 b
Cfn Cft Cfn Cft Cfn Cft Cfn Cft Cfn Cft
Degrees
0 +1.4 0 +2.05 0 +1.6 0 +2.0 0 +2.0 0
45 +1.2 +1.6 +1.95 +0.6 +1.5 +1.5 +1.8 +0.1 +1.55 +1.55
90 0 +2.2 +0.5 +0.9 0 +1.9 0 +0.1 0 +2.0
NOTE: In this table, the force coefficient Cf is given in relation to the dimension b and not, as in other cases, in relation to effective frontal area Ae.
CODE COMMENTARY
Table 25: Reduction factor K for individual members. [Clause 6.3.3.1 (a)]
l /b or l /D 2 5 10 20 40 50 100
Circular cylinder, 0.58 0.62 0.68 0.74 0.82 0.87 0.98 1.00
subsritical flow
Circular cylinder, 0.80 0.80 0.82 0.90 0.98 0.99 1.00 1.00
supercritical flow
(DVz 6 m2/s)
Flat plate perpendicular 0.62 0.66 0.69 0.81 0.87 0.90 0.95 1.00
to wind (DVz 6 m2/s)
Table26: Force coefficients for wires and cables (l/d =100). [Clause 6.3.3.1(d)]
ii. DVz greater than 6 m2/s The solidity ratio of the frame also effects the
value of Cf. The solidity ratio implies the ratio of
shall be as given in Table 27 according to
the type of the member, the diameter (D), the net exposed area of the frame members divided
design wind speed (Vz) and the solidity ratio by the gross area bound by these members. See
Fig. C6.
().
Shaded area
Area a b c d
a b
c
d
IITK-GSDMA-Wind02-V3.0 Page 68 IITK-GSDMA-Wind04-V1.0
CODE COMMENTARY
where
Cf super = force coefficient for the supercritical
circular members as given in Table 27.
Cf sub = force coefficient for subcritical circular
members as given in Table 27.
Cf flat = force coefficient for the flat sided
members as given in Table 27,
Acirc sub = effective area of subcritical circular
members,
Aflat = effective area of flat-sided members,
Asub = Acirc sub + A flat, and
Area of the frame in a supercritical flow
γ
Ae
Effective solidity
Ratio,
0.40
0.35
0.30
0.25
0.15
Table 30: Overall force coefficient for square towers composed of rounded members
[Clause 6.3.3.4 (d)]
Solidity Force Coefficient for
Ratio of
Sub-critical flow Supercritical flow
Front Face
(DVz < 6 m2/s)
(DVz 6 m2/s)
Onto face Onto corner Onto face Onto corner
0.05 2.4 2.5 1.1 1.2
0.1 2.2 2.3 1.2 1.3
0.2 1.9 2.1 1.3 1.6
0.3 1.7 1.9 1.4 1.6
0.4 1.6 1.9 1.4 1.6
0.5 1.4 1.9 1.4 1.6
Table 31: Overall force coefficient for equilateral-triangular towers composed of rounded
members [Clause 6.3.3.4 (e)]
6 – INTERFERENCE
EFFECTS
7.1 - C7.1 -
the buildings of 5 times the dimension (b) of shielding (i.e., take IF as unity) in such cases or
the interfering building normal to the direction take specialist advice. The code recommends IF
of wind. Interference effect beyond 20b may values in the range of 1.0 to 1.25 considering
be considered to be negligible (Figure 8). For worst wind direction.
intermediate distances, linear interpolation
may be used. Figure C7 shows how the value of IF varies for a
typical case. Use of interference factors will be of
greater relevance for buildings in terrain
categories 1 and 2.
Wind b
2b x 5b IF = 1.25
x = 10 b IF = 1.10
x = 20b IF = 1.00
Figure 8 : Interference factor (IF) for roof of low buildings [Clause 7.2]
Fig. C7 : Typical Interference factor contours for design pressure coefficients over the roof of a
Gabled building (TB) as a building of same size is placed at different positions in plan (Kwatra
2000)
may be assumed as follows for interference Interference could increase the dynamic response
caused by a tall building of same or greater substantially in either directions, generally to
height. different extent as one might expect. Interference
effects are primarily due to modifications in the
Zone Z2 Z2 Z3 Z4
incident and wake flow characteristics. The
IF 1.35 1.25 1.15 1.07 turbulence characteristics (like eddy sizes etc.)
approaching the building face and then releasing
from the sides are effected. Interfering structures
The interference effect due to buildings of some times bring the vortex shedding frequency
height less than one-third may be considered close to the natural frequency of structure as well
to be negligible while for interference from a as they may push it away from the natural
building of intermediate height, linear frequency. Figure C8 is a typical representation of
interpolation may be used between one–third contours of IF for the response of a tall building
and full height. over a rectangular plan when interfered with a
similar building in different plan positions. There
is a decrease in the interference effect as the
height of the interfering structure(s) becomes
smaller than the affected structure/building,
becoming insignificant for height of interfering
structure smaller than one-third the height of the
building under interference. The complex
phenomenon of interference due to several
upstream or downstream structures has to be
studied through the wind tunnel studies but
generalization is not possible. Even for an
isolated one or two structure situation, the values
of IF provided in the code are given to provide
guidelines only.
Figure 9 : Interference zones for tall rectangular buildings of same or greater height
4b 3b 5b 10b 7.3]
[Clause 15b 20b
C 8: A typical set of contours for IF for the response of a rectangular tall building interfered
with by a similar building placed in different positions in plan, as the wind blows from
right to left. [Abhay Gupta (1996)]
7 DYNAMIC EFFECTS
8.1 - General C8.1 –
Flexible slender structures and structural Section 8 of the code contains methods of
elements shall be investigated to ascertain evaluating the dynamic effects of wind on flexible
the importance of wind induced oscillations structures that can oscillate in the wind. The wind
or excitations along and across the direction on earth’s surface is turbulent in nature that gives
of wind. rise to randomly varying wind pressures about a
certain value associated with the mean wind
In general, the following guidelines may be
velocity. The dynamic part of the wind pressures
used for examining the problems of wind-
would set up oscillations in a flexible structure,
induced oscillations:
which may be defined as one having the
a) Buildings and closed fundamental time period of vibration more than
structures with a height to minimum lateral 1.0 second. Oscillations will thus be caused in the
dimension ratio of more than about 5.0, or along-wind direction. Furthermore, flexible
b) Buildings and structures structures also respond in the across-wind
with natural frequency in the first mode less direction on account of vortex shedding. In the
than 1.0 Hz. cross-wind direction, a flexible structure would
Any building or structure which satisfies tend to oscillate due to shedding of the eddies
either of the above two criteria shall be alternately from either sides of the structure at
examined for dynamic effects of wind. For regular intervals, thus imposing a dynamic force
buildings and closed structures with natural that has a major component in a direction normal
frequency in the first mode more than 1 Hz, to that of the wind and only a small component
the gust factor G may be taken as 0.90. along the direction of wind. This force due to
regular shedding of the eddies was first observed
NOTE 1 – The fundamental time period (T) may
either be established by experimental by Von Karman and the frequency of eddy
observations on similar buildings or calculated by shedding is dependent on structure size, shape
any rational method of analysis. In the absence of and wind velocity, all grouped into a non-
such data, T may be determined as follows for dimensional parameter called Strouhal Number.
multi-storied buildings: The IS:875(Part 3) – 1987 code does not lay
(a) For down any specific procedure for determining the
moment resistant frames without bracings or design wind force related to the cross-wind
shear walls for resisting the lateral loads motion.
T = 0.1 n
where
Structures which are relatively stiff are not
n = number of storeys including basement storeys; dynamically sensitive to wind. The dynamic
S r Vd
b
where
Sr = Strouhal number,
Vd = design wind velocity, and
b = breadth of a structure or structural
member normal to the wind direction as well
as the axis of the structure/member.
a) Circular
Structures – For structures circular
in cross-section:
Sr = 0.20 for bVd not greater than
7, and
= 0.25 for bVd greater than 7.
b) Rectangular
Structures – For structures of
rectangular cross-section:
Sr = 0.15 for all values of bVd.
NOTE 1 – Significant cross wind motions
may be produced by vortex shedding if the
natural frequency of the structure or
structural element is equal to the frequency
of the vortex shedding within the range of
expected wind velocities. In such cases,
further analysis should be carried out on the
basis of references given in Note 8 of 8.1.
NOTE 2 – Unlined welded steel
chimneys/stacks and similar structures are
prone to excitations by vortex shedding.
NOTE 3 – Intensification of the effects of
Level at which
action effects
are calculated
s
z
1 2 I h g v Bs s R
G
1 2 g v I h
where
s = height of the level at which action
effects are calculated for a structure
h = average roof height of a structure
above the ground
Ih = turbulence intensity, obtained from
1
Bs
1
36(h s) 2
64bsh
2 0.5
2 Lh
gR 2 log e (3600 f 0 )
1
S
4 f 0 h(1 g v I h ) 4 f 0 b0 h (1 g v I h )
1 1
Vh Vh
E = (/4) times the spectrum of
turbulence in the approaching wind
stream, given as follows:
N
E
1 70 N 2 5/6
9 – CROSS-WIND
RESPONSE
Clause 10.2 gives, method for determining Forces causing cross-wind response of tall
equivalent static forces and base overturning structures are of three kinds.
moments and G for tall enclosed buildings
(a) Incident turbulence :
and towers of rectangular cross-section.
Turbulence In the wind gives rise to fluctuations
Calculation of cross–wind response is not
in wind speeds and directions which in turn
required for lattice towers.
produces forces varying with time. The
magnitude of the across-wind force (also called as
lift) and the pitching moment thus produced
would depend not only on the turbulence level but
also the mean wind speed and the angle of attack
(angle of wind incidence in elevation). This effect
is important for canopy and similar roofs and
bridge decks particularly with fast rate of change
of the lift and moment coefficients with respect to
the angle of attack. Computation of these forces
need wind tunnel studies and / or CFD analysis
and are outside the scope of this Code.
(b) Cross-wind displacement :
Mechanisms that may get activated under the
cross-wind displacements are of different nature.
The excitations under all these mechanisms are
dependent on displacement and their derivatives
including rotations. They are named differently
depending upon the type of excitation, such as
galloping, flutter, lock-in, etc. All these
excitations are also affected by turbulence in the
wind. They occur only in very flexible structures
with damping that is a fraction of 1% of the
critical damping. The analysis of these structures
is also beyond the scope of this Code.
(c) Wake Excitation: It is the most
common type of across-wind excitation and
is caused by shedding of the vortices by a
structure at regular intervals alternately
from its two opposite sides. The periodicity
of eddy shedding is defined by Strouhal
Number that depends on the shape of cross-
section of the structure. Resonance would
0.6V z 2 2 3 C fs
M 0 0 .5 g R b h K
1 g v I h k 2
2 m
3
where the value K m is the mode
k 2
shape correction factor for cross–wind base
overturning moment.
10.2.3– C10.2.3 -
Cross–wind force spectrum coefficient Since the spectra given in the Code are based on
(Cfs) linear mode shape, these need a correction to be
applied for the non-linear mode shapes defined by
The reduced velocity (Vn) shall be calculated
mode shape power exponent (k) values other than
as follows:
unity. Thus a correction factor k m has been
Vz incorporated in the expression for G.
Vn
f 0 b(1 g v I h )
Values of the cross–wind force spectrum
coefficient generalized for a linear mode
shape (Cfs) shall be calculated from the
reduced velocity (Vn) given in Figures 10–13.
-1.0
Turbulence intensity
-1.5
Figure 10: Cross–wind force spectrum coefficient for aat 2h/3
3:1:1of 0.12
square section
Log10 (Cfs)
[Clause 10.2.3]
-2.0 Turbulence intensity
at 2h/3 of 0.20
-2.5
3:1:
1
-3.0
-3.5
-1.0
Figure 11: Cross–wind force spectrum coefficient for a 6:1:1 square section [Clause
Log 10 (Cfs)
-1.5 10.2.3]
Turbulence intensity
-2.0 at 2h/3 of 0.12
-3.0
-3.5 6:1:1
-4.0
0 2 4 6 8 10 12 14 16
Reduced Velocity Vn
6:2:1
0 2 4 6 8 10 12 14 16 18
-1.0
-3.0
-3.5
-4.0
-1.5
Turbulence intensity at
2h/3 of 0.20
-2.0
-2.5
6:1:-3.0
2
Figure 13: Cross–wind force spectrum coefficient for a 6:1:2 rectangular section
-3.5 [Clause 10.2.3]
-4.0
0 2 4 6 8 10 12 14
16
Reduced Velocity Vn
Appendix A
(Clause 5.2)
Basic Wind Speed at 10m Height for some Important Cities/Towns
Cuttack 50 Pune 39
Darbhanga 55 Raipur 39
Darjeeling 47 Rajkot 39
Dehradun 47 Ranchi 39
Delhi 47 Roorkee 39
Durgapur 47 Rourkela 39
Gangtok 47 Simla 39
Guwahati 50 Srinagar 39
Gaya 39 Surat 44
Gorakhpur 47 Tiruchirapalli 47
Hyderabad 44 Trivandrum 39
Imphal 47 Udaipur 47
Jabalpur 47 Vadodara 44
Jaipur 47 Varanasi 47
Jamshedpur 47 Vijaywada 50
Jhansi 47 Visakhapatnam 50
Jodhpur 47
Appendix B
[Clause 5.3.2.4 (b)(ii)]
Changes in Terrain Categories
Wind h4 x4
Direction
h4
A
Category 2 x4 Category 4
(a) Determination of Velocity Profile Near a Change in Terrain Category from less
rough to more rough.
h2 x2
Wind
Direction
h2
Category 4 A
Category 2
x2
(b) Determination of Velocity Profile Near a Change in Terrain Category (more rough to
less rough)
A B
Category 3 Category 1 Category 4
x1 x2
h1
Height
h4
h1
Height
h4
h4
(c) Determination of Design Profile Involving More Than One Change in Terrain Category
where
L = actual length of the upwind slope in the
wind direction,
Z = effective height of the feature, and
= upwind slope in the wind direction.
If the zone downwind from the crest
of the feature is relatively flat ( < 3o) for a
distance exceeding Le, then the feature
should be treated as an escarpment. If not,
then the feature should be treated as a hill or
ridge. Examples of typical features are given
in Figure 15.
NOTE:1–No difference is made, in evaluating
k3 between a three dimensional hill
and a two dimension ridge.
NOTE: 2 – In an undulating terrain, it is often
not possible to decide whether the
local topography to the site is
significant in terms of wind flow. In
such cases, the average value of the
terrain upwind of the site for a
distance of 5 km should be taken as
the base level from wind to assess
the height z, and the upwind slope ,
of the feature.
Slope C
3 < 17
o o
1.2 (z/L)
> 17o 0.36
and s is a factor derived in accordance with
C-2.1 appropriate to the reference height, H
on the structure above the mean local ground
level, and the distance, X from the summit or
crest, relative to the effective length, Le.
C-2.1 The factor, s, should be determined
from:
(a) Fig. 16 for cliffs and escarpments,
and
(b) Fig. 17 for hills and ridges.
NOTE: Where the downwind slope of a hill or
ridge is greater than 3o, there will be large regions
of reduced accelerations or even shelter and it is
not possible to give general design rules to cater
for these circumstances. Values of s from Fig. 17
may be used as upper bound values.
Wind
Downwind Slope > 3o
Wind
Crest
Downwind slope < 3o
Crest Crest
2.0 2.0
1.5 1.5
1.5 1.5
0.8
-1.5 -1.0 -0.5 0 0 0.5 1.0 1.5 2.0 2.5
Upwind X/Le Downwind X/Le
Figure 17: Factors for ridge and hill
1. Ahmad, Shakeel, “Wind pressures on low rise hip roof buildings”. Ph.D. Thesis, Civil
Engineering Department, University of Roorkee (Now Indian Institute of Technology
Roorkee), May 2000.
2. Bailey, P.A., and Kwok, K.C.S., “Interference Excitation of Twin Tall Buildings”. Journal of
Wind Engineering and Industrial Aerodynamics, Vol. 21, 1985, pp. 323–338.
3. Bayar, D.C., “Drag coefficients of latticed towers”. Journal of Structural Engineering, ASCE,
Vol. 112, 1986, pp. 417–430.
4. Bowen, A.J., “The prediction of mean wind speeds above simple 2D hill shape”. Journal of
Wind Engineering and Industrial Aerodynamics, Vol. 15, 1983, pp 259–220.
5. Cook, N.J., The designer’s guide to wind loading of building structures – Part 1”.
Butterworths, London, 1985.
6. Davenport, A.G., “Gust loading factors”. Journal of the Structural Division, ASCE, Vol. 93,
1967, pp. 11–34.
7. Gumley, S.J., “A parametric study of extreme pressures for the static design of canopy
structures”. Journal of Wind Engineering and Industrial Aerodynamics, Vol. 16, 1984, pp 43–
56.
8. Gupta, Abhay, “Wind tunnel studies on aerodynamic interference in tall rectangular
buildings”. Ph.D. Thesis, Civil Engineering Department, University of Roorkee (Now Indian
Institute of Technology Roorkee), 1996.
9. Holmes, J.D., “Mean and fluctuating internal pressures induced by wind”. Proc. 5 th
International Conference on Wind Engineering, Fort Collins, 1979, pp. 435–450.
10. Holmes, J.D., “Recent development in the codification of wind loads on low–rise structures”,
Proc. Asia–Pacific Symposium on Wind Engineering, Roorkee, India, December 1985, pp.
iii–xvi.
11. Hussain, M., and Lee, B.E., “A wind tunnel study of the mean pressure forces acting on large
groups of low rise buildings”. Journal of Wind Engineering and Industrial Aerodynamics, Vol.
6, 1980, pp 207–225.
12. Krishna, P., “Wind load on curved roof”, Proceeding of Second Asia Pacific Conference on
Wind Engineering (APCWE-II), Beijing, China, 1989.
13. Kwatra, Naveen, “Experimental studies and ANN modelling of wind loads on low buildings”.
Ph.D. Thesis, Civil Engineering Department, University of Roorkee (Now Indian Institute of
Technology Roorkee), February 2000.
14. Lakshmanan, N., Arunachalam, S. and Harikrishna, P., “Parameters of risk coefficients for
structures located in cyclone prone regions”. Proc. of the National Conference on Wind
Engineering, 145–153, April 2002, Roorkee.
15. Letchford, C.W. and Holmes, J.D., “Wind loads on freestanding walls in turbulent boundary
layers”. Journal of Wind Engineering and Industrial Aerodynamics, Vol. 51, 1994, pp 1 to 27.
16. Macdonald, P.A., Holmes, J.D., and Kwok, K.C.S., “Wind loads on circular storage bins, silos
and tanks. II. Effect of grouping”. Journal of Wind Engineering and Industrial Aerodynamics,
Vol. 34, 1990, pp. 77–95.
17. Meecham, D., “The improved performance of hip roofs in extreme wind – A case study”,
Journal of Wind Engineering & industrial Aerodynamics, Vol. 41-44, p.1717-1726, 1992.
18. Melbourne, W.H., “Cross–wind response of structures to wind action”. 4 th International
Conference on Wind Engineering Effects on Buildings and Structures, Cambridge University
Press, London, 1975.
19. Paterson, D.A., and Holmes, J.D., “Computation of wind flow over topography”. Preprints,
Journal of Wind Engineering and Industrial Aerodynamics, Vol. 46–47, 1993, pp 471–476.
20. Robertson, A.P., Hoxey, R.P., and Moran, P., “A full scale study of wind loads on agricultural
canopy structures and proposal for design”. Journal of Wind Engineering and Industrial
Aerodynamics, Vol. 21, 1985, pp 167–205.
21. Saathoff, P. and Stathopoulos, T., “Wind loads on buildings with sawtooth roofs”. J. Struct.
Engrg., ASCE, 118(2) 429–446.
22. Sachs, P., “Wind forces in engineering”. Pergamon Pres, 1978.
23. Saunders, J.W., and Melbourne, W.H., “Tall rectangular building response to cross–wind
excitation”. Proc. 4th International Conference on Wind Effects on Buildings and Structures,
Cambridge University Press, September 1975, pp. 369–379.