Introduction To Basic Design (2013/2014) Assignment #2A Report
Introduction To Basic Design (2013/2014) Assignment #2A Report
TO BASIC DESIGN
(2013/2014)
ASSIGNMENT #2A REPORT
SALVATORE LUISO 0000707745
1. We start doing an overall mass balance to find the flow rate and the composition of
the outlet products:
EQUILIBRIUM DATA
T (°C) y x
1
The results are:
We see that the feed is under cooled liquid.
We insert the x‐y plot:
y vs x
1,0
0,9
0,8
0,7
0,6
diagonal
y 0,5 y=x
0,4
0,3 BENZ‐
0,2 TOL EQ.
0,1
0,0
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
x (benzene)
2. We will follow the McCabe‐Thiele procedure, so by doing the following assumptions:
Sensible heats negligible with respect to latent heats (isothermy);
Latent heats equal for all compounds in the mixture and constant in T;
Mixing heat negligible (it could be verified);
2
No heat losses.
These hypothesis are reasonable because the temperature differences in column are few
tens degree and we are dealing with an hydrocarbons mixture.
We do now the heat balance on the feed plate, setting the enthalpy of the saturated liquid
as the reference enthalpy and equal to 0:
~ ~
H L H 0 0
~ ~ ~
H G H 0 (T DP ) c P , L (T DP TB )
~ ~
H F H 0 c~P , L (TF TB )
Where for λ and cp,LIQ we integrate the polynomial equations for each compound from Perry,
8th between TB and TD (at feed composition) for the cP in the second equation and between TB
and TF for the third one. Then we calculate a mean value for both, weighted on composition
of liquid.
Where HG is the enthalpy of the saturated gas at the dew point at the composition of the feed.
So the q-line has the equation:
q z
y x F 4.865 x 1.739
q 1 q 1
Now we can find the rectifying line and, looking at the intersection with the y-axis, we find
the minimum reflux:
L D R 1 y 0.4235 x
y x xD x xD RMIN D 1 1.3495
G G R 1 R 1 x 0 y
Actual typical reflux is between 1.2*RMIN and 2*RMIN. We choose 1.5 times, however we
programmed a calculus sheet the provides automatically the following results, only by
changing the ratio between minimum and actual reflux.
y 0.6693 x 0.329
The stripping line crosses the point (xW,xW) and the intersection between the q-line and the
rectifying line:
3
y 1.3381x 0.0007
We are now able to calculate the flow rates of liquid and gas circulating respectively in the
top and in the bottom section:
α= 1,5
R = α RMIN = 2,024
L= R∙D = 266,41 kmol/h
TOP
G= L+D = 398,02 kmol/h
y vs x
1,0
xD
0,9
0,8
0,7 diagonal y=x
0,6
y rectifying
0,5
0,4235 zF line
0,4
0,329 q‐line
0,3
0,2 stripping line
0,1
0,0 xW Rmin
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
x (benzene)
Now we can draw the stages at maximum reflux and the theoretical stages.
4
y vs x
1,0 3 21
5 4 xD
6
0,9 7
8
0,8 9
10
0,7 11 diagonal y=x
12
0,6 rectifying line
y 13
0,5 q‐line
14
0,4235 zF
0,4 stripping line
15
0,329
0,3 Theoretical stages
16
0,2 17 Stages at total reflux =
12
18
0,1 Rmin
19
20
21
22
23
0,0 x W BENZ‐TOL EQ.
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
x (benzene)
Feed plate is number 11.
3. We want to calculate the heat duties of both the overhead condenser and the reboiler.
Thus, we start to calculate the heat of vaporization of the mixtures at xD and xW: since the 2
mixtures are almost pure it is not so important that the temperature for the calculus is at the
dew point, because bubble and dew point differ from less than 1°C one another; it is also
worthless to weight the heats of vaporization on the composition again because of the purity.
The results are:
As for the condenser we need the gas flow rate circulating in the top section, as for the
reboiler we need the gas flow rate in the bottom section.
5
We want to know also the flow rates of the cooling water in the condenser and of the steam in
the reboiler. They will be needed when we will estimate the operative costs. So we start
calculating the average cP of the water between 30°C and 40°C [see Assignment #1 report]
and heat of vaporization of steam at 4/5 bar. So:
4. The problem suggests us to design a tray column for the operation. We follow the
procedure from Coulson & Richardson’s Chemical Engineering, Vol. 6. We start dividing the
column in 4 critical sections: top, above feed, below feed and bottom. In each section there
are different values of flow rate, composition, temperature, density and other properties, so
we have to find the correct design for each and then we will choose the best that is well-
suited for them all.
Looking at the composition we calculate the molecular weight for each section, so to
determine the mass liquid and vapor flow rates. Then, starting again from composition, we
take the temperature at the bubble point as the temperature of each liquid and the temperature
at the dew point as the temperature of each vapor. Of course the mixtures at the top and at the
bottom are almost pure and the 2 temperatures are quite the same. After we have calculated
the densities at each T, we can find the volumetric flow rate and we can use the following
plot to determine which kind of liquid-flow arrangement we have:
6
With this plot we can have an idea of the structure of the plates. The results are:
INPUT DATA
TOP STAGE
VW VW ρL ρV MMIX( MMIX( FLOW
LW (kg/s) LW (m3/s) (kg/s) (m3/s) (kg/m3) (kg/m3) L) V) PATTERN
5,78 7,16E‐03 8,63 1,33 807,58 6,50 78,15 78,07 Cross flow
ABOVE FEED STAGE
VW VW ρL ρV MMIX( MMIX( FLOW
LW (kg/s) LW (m3/s) (kg/s) (m3/s) (kg/m3) (kg/m3) L) V) PATTERN
6,34 1,07E‐02 9,15 2,01 591,92 4,56 85,7 82,72 Cross flow
BELOW FEED STAGE
VW VW ρL ρV MMIX( MMIX( FLOW
LW (kg/s) LW (m3/s) (kg/s) (m3/s) (kg/m3) (kg/m3) L) V) PATTERN
15,08 2,55E‐02 11,27 2,47 591,92 4,56 85,7 82,72 Cross flow
BOTTOM
STAGE
VW VW ρL ρV MMIX( MMIX( FLOW
LW (kg/s) LW (m3/s) (kg/s) (m3/s) (kg/m3) (kg/m3) L) V) PATTERN
16,19 3,29E‐02 12,09 4,00 491,46 3,02 91,97 91,90 Double pass
We decide to select a plate distance lt = 0.61m (24 in). Then, we calculate the liquid-vapor
LW V
flow factor for each section: FLV . We income with them in the following plot to
VW L
find the K1 factor (line colors are the same of the first plot):
7
The following restrictions apply to the use of the previous plot:
a) Hole size less than 6.5 mm. Entrainment may be greater with larger hole sizes;
b) Weir height less than 15 per cent of the plate spacing;
c) Non-foaming systems;
d) Hole: active area ratio greater than 0.10;
e) Liquid surface tension 0.02 N/m.
L V
We can estimate the flooding velocity: u f K1
V
We want to know the actual velocity but we need the fractional entrainment ψ. As a rough
guide the upper limit of ψ can be taken as 0.1; below this figure the effect on efficiency will
be small. Thus, we insert in the following plot the FLV and at ψMAX = 0.1 we get the
percentage of flooding:
8
FLV Type K1 from plot uf (m/s) Flood % at max ψ=0,1
Top stage 0,060 1,10E-01 1,2 92
Since %FME of all the sections is above 85: ug = 0.85 uf, where ug is the actual velocity. Now
VW
we can calculate the net area An and by setting the coefficient fd based on the
W u g
liquid flow pattern (0.12 for cross flow, 0.24 for double pass) we can know the area of the
An
column Ac and the diameter of the column dc. The results follow:
1 fd
Now, to be sure that there will not be flooding anywhere we take the biggest diameter, i. e.
2.555 m. We calculate now the area of the column Ac, the area of the downcomer Ad
(Ad=fd∙Ac, where we take the cross flow pattern so fd=0.12), the active area Aa (Aa=Ac-2Ad),
the perforated area Ap (Ap≈Aa); then we set the holes diameter dh= 3 mm, the pitch equal to
Ph=3.3∙dh, the weir height hw= 50 mm that is good for Patm and the apron spacing hap=40mm;
2
d
so we calculate also the overall area of holes: Ah 0.907 h A p . Here there is the final
Ph
table:
Ac Ad An Aa Ap dh Ph Ah hw hap
diameter m (m2) (m2) (m2) (m2) (m2) (mm) (mm) (m2) (mm) (mm)
2,555 5,129 0,615 4,513 3,898 3,898 3,0 10 0,325 50 40
To finalize the tray design we need the percentage of the ratio between the downcomer and
A
the column area: d 100 12 . We put it in the following plot and we get the weir length:
Ac
9
→ lw=0.76∙dc=1.942 m. So the clearance area under the downcomer is Ap= lw ∙ hap =0.078 m2.
Now there are some restrictions that we have to control in each section. First we check the
2/3
L
weeping. Thus, we calculate the weir crest: how 750 W , so we can income in the
L lw
following plot with the sum how+hw to get the coefficient K2 needed to calculate the minimum
vapor velocity through the holes (based on the hole area) u h 2
K 0.9 25.4 d h :
v 1/ 2
10
Vw
To check the weeping it must be u h u h , where uh is the actual vapor velocity.
W Ah
The results:
At this point we want to estimate the pressure drops in each plate. Let’s call hb = how+hw. For
each section we calculate the total pressure drops between the plates hT = hd + hb + hR, where
H 2O
hR 12.5 and hd is taken from the following plot incoming with: percentage ratio
L
between the hole area and the perforated area and the ratio between the plate thickness
(typically 3 mm for steel alloy) and the hole diameter.
2
u v
With C0 we calculate hd 51 h
C0 L
11
hR (mm) hd (mm) hT (mm)
Top 15,5 10,0 93,3
It’s time for the second check: the downcomer flooding. The liquid flow rate in the
downcomer Lwd is calculated taking the real fractional entrainment ψ from FLV-ψ plot,
L
incoming with 85% flooding: Lwd w . Then we need Am, that is either the downcomer
1
area Ad or the clearance area under the downcomer Aap; whichever is the smaller. Finally the
2
Lwd
head loss in the downcomer is: hdc 166 .
L Am
For safe design the liquid head hb in the downcomer hb = hT + hdc + how+hw should not exceed
half the plate spacing lt, to avoid flooding. Allowing for the weir height:
hb 0.5 (lt hw )
L hb Ad
Meanwhile the residence time in the downcomer should be greater than 3 to
Lw
5 seconds. If both the liquid head and the residence time are nearby their limit, try to change
the configuration to get a safer design. The results:
Further step is to calculate the column height. To do this, we need the plate efficiency: even if
we chose sieve plates, as a rough estimate the efficiency could be got either from the usual
plot for bubble-cap efficiencies or from the interpolating equation:
oa 0.492 F hk 0.245
, where μF is the viscosity of the feed and αhk is the relative
volatility in each section. The results:
12
Column height αHK μL (feed) cP αHK μL ηoa
Top 2,213 2,81E-01 6,21E-01 0,55
We choose to take an average efficiency of 0.53, so the actual number of plates in the column
is 43. We are almost at the end.
For the column height we need the top and the bottom height. As for the former we set HT=1
m to allow disengagement between liquid and gas, as for the latter HB it’s the sum of:
the height that multiplied by the column area gives a volume that can keep inside the
amount of liquid product flow rate for 3 minutes;
the height that multiplied by the column area gives a volume that can keep inside the
amount of liquid actually inside the column on all plates;
the diameter of the gas nozzle and his distance from the first plate.
Our design is going to be completed. Actually nozzle diameters are still missing. We assume
that gases should have a velocity of 10-20 m/s (we choose 10 to avoid flooding), and liquids
of 1 m/s, so we calculate a diameter and then we check on the standard the nearest one:
d F 127 mm u F 0.99m / s
d GAS ,TOP 406.4mm u GAS ,TOP 10.54m / s
4G
d 'b d LIQ ,TOP 101.6mm so actual velocities are: u LIQ ,TOP 0.93m / s
u
d GAS , BOTTOM 711mm u GAS , BOTTOM 10.32m / s
d LIQ , BOTTOM 219.1mm u LIQ , BOTTOM 0.91m / s
5. We want to estimate now the investment and the operating costs of the equipment.
Among the different methods in the literature we choose Guthrie method, because more
reliable than other but still simple. As we are dealing with a tray column Guthrie suggests us
to estimate separately the tray stack cost and the vessel cost. We start with the first one and
we implement this graphical method on a calculus sheet, thus to make the procedure
13
automatic. The following plot is a collection of real values that relate the tray stack height in
foot (with a tray spacing of 24 in) to a tray cost, shop installed.
DATA
Tray stack height Diameter Tray spacing Tray height
31,15 m 2,56 m 0,61 m 25,62 m
102,16 ft 8,38 ft 24,02 in 84,03 ft
100000 Guthrie Method
Tray cost, shop installed, $
10000
6 y = 66,667x
7 y = 90x
8 y = 125x
9 y = 150x
1000
10 y = 166,4x + 67,8
100
1 10 100
Tray stack height, ft. (24 in spacing)
Different line is to be chosen following the diameter: here we take that one for 8 ft diameter.
Tray base cost $12.769
Now we need some adjustment factors to get the equipment cost. As for the material, we
use stainless steel:
Tray Cost, $ ‐ [Base cost (Fs + Ft + Fm)] Index
Adjustment factor
Tray
Tray spacing, In. Fs type Ft Tray material Fm
24 1,0 Grid(no downcomer) 0,0 Carbon steel 0,0
18 1,4 Plate 0,0 Stainless 1,7
12 2,2 Sieve 0,0 Monel 8,9
Trough or valve 0,4
Bubble
cap 1,8
14
Here tray spacing is 24 Sieve tray are used We select stainless steel
Fd= 1,0 Fp= 0,0 Fm= 1,7
Tray cost $34.478
Now we calculate the cost of the vessel. To do this we use another plot that relates the
column diameter, the column height, the vessel configuration to a base equipment cost. So:
15
All the column is in stainless steel Fm= 3,67 Fp= 1,00
Vessel cost (CEQ) $165.150
Guthrie method takes into account also the costs for installation and labor, thus to have the
erected cost.
Field installation modules
Module 5A 5B 5C 5D 5E
Base dollar magnitude, $ 100,000 Up to 2 2 to 4 4 to 6 6 to 8 8 to 10
Bare module cost 423,0 412,1 406,8 405,7 402,0
Since our equipment cost is below $200000, the factor we are interested in is the first
(divided by 100 in this procedure: 100*f = 423.0).
Bare module cost (erected eq.)
CEQ,erected=(CEQ‐CB‐EQ)+f ∙ CB‐EQ= $310.500
Total cost (erected + tray) $344.978
This is the final equipment cost but it is US $1968 so we need some coefficients to actualize it.
We take the Chemical Engineering Plant Cost index of 1968 for the equipments (=109.9) and
we update it with the CEPCI of September 2012, choosing the tag heat exchangers & tanks:
16
Then we apply the comparative price levels factor from United States to Italy again in
September 2012:
17
Finally, we actualize the Italian cost with index from ISTAT in April 2014:
Let’s discuss now about operative costs. It’s difficult to know something about them because
we don’t know the other characteristics of the plant, however we can estimate at least the cost
of pumping cooling water into the condenser, steam into the reboiler and reflux to the top. As
for the first and the second we find the corresponding amount of ECO (Equivalent
combustible oil, a standard liquid fuel with 10000 kcal/kg) per m3 of water and per kg of
steam at 5 bar. Then we need the average industrial fuel price in Italy:
kgECO
m H 2O C fuel
m H3 2O s h d
C cond , annual (3600 ) (24 ) (365 ) 176039€
H 2O h d y
kgECO s h d
C reboil , annual m steam C fuel (3600 ) ( 24 ) (365 ) 3455975€
kg steam h d y
As for the reflux pumping we set a total dynamic head H = 36.15, that is the height of the
column allowing 5 m for pressure drops in the line. By considering a system efficiency
QgH
(motor+pump) = 60%, the power needed is P 3.42kW . Now we take the cost of
18
electric energy in Italy from Authority of Energy: CE = 0.2 €/kWh; and we estimate the
annual operative cost:
h d
C reflux ,annual P * 24 * 365 * C E 5992€
d y
Last step is to calculate the Net Present Cost assuming an interest rate i = 0,11 and a number
of years n=10:
(1 i ) n 1
NPC C capital C op ,annual n
23486957€
i (1 i )
Let’s spend some words on the P&ID. We designed the tray column connected to a BEM
condenser and to a natural circulation reboiler. As for the condenser see Assignment #1
report. From the condenser, the reflux is pumped to the top; a temperature indicator and
control is set in the top section of the column in the most appropriate tray, so to actuate the
control valve on the reflux line. Other temperature indicators are set on the feed line and on
the bottom section to have a look if the process is doing well. As well as in the buffer tank for
the condenser, in the bottom section a level indicator and control acts on a control valve
down the process so to maintain the desirable liquid level in the column. Low alarm level and
level switch are also present on the column: they eventually switch off the pump to prevent
gas bubbles going inside it.
A flow indicator and control is responsible of the flow rate of the feed.
A pressure safety valve and a hand switch on the relief line are set both on the top outlet gas
line and on the buffer tank.
19