0% found this document useful (0 votes)
583 views1 page

Blowdown Vessel Calculation

THis calculation sheet has been made by me. THis is to carry out blowdown vessel sizing based on velocity & flowrate. It also depends on the upstream pressure and control valve downstream pressure. It is presumed that basics of expansion due to sudden drop in pressure is well understood.

Uploaded by

Omkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
583 views1 page

Blowdown Vessel Calculation

THis calculation sheet has been made by me. THis is to carry out blowdown vessel sizing based on velocity & flowrate. It also depends on the upstream pressure and control valve downstream pressure. It is presumed that basics of expansion due to sudden drop in pressure is well understood.

Uploaded by

Omkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

BLOWDOWN DRUM SIZING

MCR Flow 63 TPH


Blowdown 100%

Blowdown Flow 63000 kg/hr


17.5 kg/s

Operating temperature 170.4 deg. C


Operating pressure 700 kPa(g)
Density 896.6 kg/m3

Volumetric Flow 0.0195182 m3/s


Allowable Evaporation
Velocity 11 fpm

0.05588 m/s

Calculated c/s area 0.3492874 m2

Dia 0.4447265 m
444.72653 mm

If outlet goes is blocked for 5 min


0.0833333 hr
5250 kg

Volume to be stored 5.8554539 m3

Length 37.695075 m