Sizing A MV Generator Circuit Breake1
Sizing A MV Generator Circuit Breake1
This is also true of the X/R ratio, which is lower when the fault
is supplied by the grid. This current is therefore the
requirement that determines the breaking capacity of the circuit
breaker.
However, when a circuit breaker is chosen for protecting a
generator, in accordance with the new Standard IEC/IEEE
62271-37-013 Ed. 1: High-voltage switchgear and controlgear –
Part 37-013:
Alternating current generator circuit breakers, short-circuit
overcurrent is only one of the parameters required for this
specific application. One must also consider the fault in B,
supplied by the generator, characterized by higher levels of
asymmetry and higher time constants (Figure 2).
1. System-source,
2. Generator-source and
3. Out-of-phase conditions.
In the case of generator-source breaking capacity, the first
value refers to maximum breaking capacity with 110%
asymmetry and the second to 74% breaking capacity but
130% asymmetry (called class G1 in the Standard). The same
value means that the circuit breaker is able to interrupt at
maximum breaking capacity with 130% asymmetry (called class
G2 in the Standard).
Scc=2000 MVA
X/R=10
Vn=150 kV
Transformer with 3 windings:
Generators:
First, we must make sure that the Vcc_12; Vcc_13; Vcc_23 values are
given according to the same basis. After this, the values of the
short-circuit impedances for each winding can be obtained from
the following relations:
Figure 5 –
Layout of the installation
The short-circuit current for a fault between the machine circuit
breaker and generator G1 will be calculated first:
The symmetrical short-circuit current at instant t=0 can be
obtained from this value.
Ip = 56.70 kA
Issf_sym = 21.38 kA
idc% = 53,75%
Note that the value of the symmetrical component is slightly
different from the one observed at instant t=0.
Ip = 80 kA
Considering a 45ms instant, the remaining current values are as
follows:
Isym = 22.52 kA
idc% = 118%
Table 1 – ABB’s generator circuit breaker VD4G family
System-source Generator-source breaking Out-of-phase breaking
breakingcapacity [kA] capacity [kA] capacity [kA]
VD4G-50 50 50/37 25
VD4G-40 40 25/25 20
VD4G-25 25 16/16 12.5
5 accidental energization;
37 underpower relay
49R (51R) rotor overload;
60 voltage balance relay;
78 ou of step.
A few typical protection system configurations are illustrated in
Figure 12 as well as an example ABB’s protection relay
type REG630 which is recommended in this case.