Changes in PEC Part 1, 2017 Edition PDF
Changes in PEC Part 1, 2017 Edition PDF
Changes in PEC Part 1, 2017 Edition PDF
Changes in Chapter I
1.0.1.1 (C) 1.0.1.1 (C)
This Code is intended for the
This Code is intended exclusive use of licensed
as a design electrical practitioners. This
Code is not intended as a
specification or an design specification nor an
instruction manual instruction manual for a non-
licensed electrical
for qualified persons. practitioner, unless under the
supervision of a licensed
electrical practitioner.
Chapter 1. General
Article 1.0- Introduction
BOARD OF ELECTRICAL ENGINEERING Major Changes to the Philippine
PROFESSIONAL REGULATION COMMISSION Electrical Code Part 1 2017 Ed.
PRC @ 45 –”NURTURING THE SPIRIT OF PROFESSIONALISM, INTEGRITY, AND EXCELLENCE! 10
1.0.1.4 Enforcement
(A) This Code is (a) This Code is
intended for intended for
mandatory mandatory
application by the application by
Office of the Building government bodies
Official/EE over exercising legal
electrical jurisdiction over
installations. electrical
installations.
1.0.1.4 Enforcement
(B) The Office of the (b) These government
bodies, only through a
Building Official/EE licensed electrical
shall have the practitioner, shall have the
responsibility of implementing
responsibility of of this Code provision in
implementing the deciding on the approval of
provisions of this equipment and for granting
the special permission
Code. contemplated in this Code,
where it is assured the
equivalent objectives can be
achieved by establishing and
maintaining effective safety.
1.0.1.4 Enforcement
(C) This Code may require (d) This Code may require
new products, constructions, new products, constructions,
or materials that may not yet or materials that may not yet
be available at the time this be available at the time this
Code is adopted. In such Code is adopted. In such
event, the Office of the event, the authority having
Building Official/EE may jurisdiction may permit the
permit the use of the use of the products,
products, constructions, or constructions, or materials
materials that comply with that comply with the most
the most recent previous recent previous Edition of
Edition of this Code adopted this Code adopted by the
by the National Building National Building Code.
Code.
1.0.1.4 Enforcement
Deleted provision on PEC 2009 Part 1
(c) The authority having jurisdiction may
waive specific requirements in this Code or
permit alternate methods where it is
assured that equivalent objectives can be
achieved by establishing and maintaining
safety.
1.0.1.6 Interpretation
Interpretation of this Code Upon the
shall be by licensed electrical
practitioners. In case of recommendation of
conflicting interpretations, the Code Committee,
these may be referred to the Board of Electrical
the PEC Part 1 Committee
for interpretation. Should Engineering shall
disagreement remain, render the final
thereafter, the Committee’s decision in the
interpretation shall be
referred to the Board of interpretation of any
Electrical Engineering who portion of the PEC
shall render the final Part 1, in case of
decision.
controversy.
New Provisions
1.0.1.10 Apprenticeship
(A) RA 7920 or the national electrical
engineering law requires apprenticeship as
one of the qualifications to the registration
and licensure examinations for Registered
Master Electrician (RME), in order to
practice electrical engineering in the
Philippines. Knowledge and understanding of
the PEC1 , and PEC2 form part of the
examination given.
BOARD OF ELECTRICAL ENGINEERING Major Changes to the Philippine
PROFESSIONAL REGULATION COMMISSION Electrical Code Part 1 2017 Ed.
PRC @ 45 –”NURTURING THE SPIRIT OF PROFESSIONALISM, INTEGRITY, AND EXCELLENCE! 16
New Provisions
1.0.1.10 Apprenticeship
(B) An apprentice shall undergo training
under a person holding a valid certificate of
registration and a valid professional license
for the practice of electrical engineering
under RA 7920 or the national electrical
engineering law.
New Provisions
1.0.1.11 Services of Licensed Electrical
Practitioners
For decisions and actions involving a
knowledge of electrical engineering and/or
training in electrical installations and
practices, the services of a licensed
electrical practitioner is required.
DANGER
DO NOT
OPERATE
Change Significance
The definition of device has been editorially
revised for usability and clarity.
The revision is intended to clarify that a device
has the primary function of carrying and
controlling electric energy or current.
For example, this revision clarifies that a snap
switch with a pilot light is a device because its
principal function is to carry and control
electrical energy.
Change Significance
The revision provides clarity by simply describing
the purpose and function of bonding.
The purpose of bonding is to connect two or
more conductive objects together to:
1. Ensure the electrical continuity of the fault current
path
2. Provide the capacity and ability to conduct safely any
fault current likely to be imposed, and
3. Minimize potential differences between conductive
components.
New Provision
2.10.1.8(b)(4) –GFCI
Protection Other than
Dwelling
Outdoor in Public
Spaces – for the
purpose of this section
a public space is
defined as any space
that is for use by, or is
accessible to the
public.
New Provision
2.10.1.8(c)Boat
Hoists
GFCP for personnel
shall be provided for
outlets that supply
boat hoists installed in
dwelling unit locations
AFCI
Tamper-Resistant Receptacles
406.12 All 15- and 20-A 230V nonlocking-type
receptacles in the following areas shall be listed
tamper-resistant receptacles
1. Dwelling Units
2. Guest rooms and guest suites of hotels and motels
3. Child care facilities
4. Preschools and elementary education facilities
5. Business offices, corridors, waiting rooms and the like
in clinics, medical and dental offices and out patient
facilities
6. Places of waiting transportation, gymnasiums, skating
rinks, and auditoriums
7. Dormitories
BOARD OF ELECTRICAL ENGINEERING Major Changes to the Philippine
PROFESSIONAL REGULATION COMMISSION Electrical Code Part 1 2017 Ed.
PRC @ 45 –”NURTURING THE SPIRIT OF PROFESSIONALISM, INTEGRITY, AND EXCELLENCE! 39
New Term
Neutral Conductor- the conductor
connected to the neutral point of a
system that is intended to carry current
under normal conditions.
Art. 690.12
No provisions for a rapid shutdown of PV
systems existed in the PEC 2009
A new 690.12 entitled “Rapid Shutdown of PV
System on Buildings” was added in PEC 2017.
This new section applies to PV system installed
on building roofs and would required that PV
source circuits be de-energized from all sources
within 10 seconds or when the utility supply is
de-energized or which the PV power source
disconnecting means is opened.
Firefighters typically use rooftop venting techniques when battling a blaze (Photo courtesy of Matthew
Paiss, San Jose (CA) Fire Department).
Firefighters sometimes have to contend with fires within PV system arrays (Photo courtesy of Matt Paiss,
San Jose Fire Department).
Covering panels with a heavy tarp is one approach that firefighters use to reduce voltage on a PV system
(Photo courtesy of Matthew Paiss, San Jose (CA) Fire Department).
In Stamford, Conn., city officials are considering regulations that would require
BOARD OF ELECTRICAL ENGINEERING Major Changes to the Philippine
rooftop panels to be spaced in a fashion that
PROFESSIONAL REGULATION COMMISSION would give firefighters
Electrical roomPart
Code to safely
1 2017 Ed.
move around a structure’s roof. Wider pathways between arrays would allow
firefighters to steer clear of energized panels and leave room for venting.
PRC @ 45 –”NURTURING THE SPIRIT OF PROFESSIONALISM, INTEGRITY, AND EXCELLENCE! 50
ED ISSUES
PRC @ 45 –”NURTURING THE SPIRIT OF PROFESSIONALISM, INTEGRITY, AND EXCELLENCE!
. Author(s): Robert Duval. Published on January 6, 2014. 2 52
L MOBILE
ISING
R INDEX
T INDEX
NT
MER
NFPA
L
RG
TISEMENT
1 2 3 4 5 6 7 8 9 Next >
LAST SPRING, PHILIP STITTLEBURG, chief of the fire department in La Farge, Wisconsin, and chair
of NFPA’s Board of Directors, contacted the association about a fire that had recently occurred in his
town. On May 14, 2013, t he La Farge Fire Department responded to an automatic fire alarm at an office
building in its fire district. When the first responding units arrived, they found a fire in a concealed space
within the building. But what may have appeared at first glance as a routine fireground operation turned
out to be anything but ordinary.
Firefighters would soon learn that the building’s concealed spaces were insulated with a recycled cotton-
based denim material that was rapidly consumed by the growing fire, which eventually spread into an attic
space constructed of lightweight wood trusses and equipped with automatic sprinklers. The building’s
pitched roof structure was covered with arrays of photovoltaic (PV) panels that made vertical ventilation
of the attic space by the firefighters nearly impossible.
Over the course of 18 hours, the officers and firefighters from La Farge, along with those from numerous
surrounding departments, were faced with a growing array of challenges, including the location of the fire,
the materials used in the building’s construction, the limitations of the town’s firefighting infrastructure,
and more. The fire would eventually destroy a significant portion of building, resulting in an estimated
$13 million inproperty damage and related losses.
BOARD OF
After Chief Stittleburg ELECTRICAL
contacted ENGINEERING
NFPA, and
Major Changes to the Philippine
as more became known about the details and circumstances
LAST SPRING, PHILIP STITTLEBURG, chief of the fire department in La Farge, Wisconsin, and chair
of NFPA’s Board of Directors, contacted the association about a fire that had recently occurred in
his town. On May 14, 2013, the La Farge Fire Department responded to an automatic fire alarm at
an office building in its fire district. When the first responding units arrived, they found a fire in a
concealed space within the building. But what may have appeared at first glance as a routine
fireground operation turned out to be anything but ordinary.
More than 7,000 sol ar panel s on the roof of a burning warehouse in Burl ington County proved too
much of a hazard for firefighters, l ocal official s said today.
“We may very wel l not be abl e to save buil dings that have al ternative energy,” Wil l iam Kramer,
New Jersey’s acting fire marshal l , said after Del anco Fire Chief Ron Hol t refused to send his
firefighters onto the roof of the 300,000-square foot Dietz & Watson facil ity, abl aze since Sunday
afternoon. July 14, 2014
Sol ar panel s are particul arl y hazardous to firefighters for a number of reasons, according to Ken
Wil l ette, a division manager with the National Fire Protection Association.
“There is a possibil ity of el ectric shock because the el ectricity to the panel s can’t be shut off,” he
New Article
6.91 Large-Scale Photovoltaic Electric
Power Production Facility
Covers installation of large-scale PV electric
power production facilities with generating
capacity of no less than 5000 kW and not
under exclusive utility control.
New Article
6.94 Wind Electric Systems
Applies to wind (turbine) electric systems that consist of
one or more wind electric generators, and their related
alternators, generators, inverters, controllers and
associated equipment.
New Articles
7.6-Energy Storage System
Applies to all permanently installed energy
storage systems operating at over 50 volts ac
or 60 volts dc that may be stand-alone or
interactive with other electric power
production sources.
New Articles
7.12-Direct Current Microgrids
Applies to direct current microgrids.