Preaction System With Model DV-5 Deluge Valve Double Interlock - Electric/Pneumatic Actuation 1-1/2 Thru 8 Inch (DN40 and DN200)
Preaction System With Model DV-5 Deluge Valve Double Interlock - Electric/Pneumatic Actuation 1-1/2 Thru 8 Inch (DN40 and DN200)
Preaction System With Model DV-5 Deluge Valve Double Interlock - Electric/Pneumatic Actuation 1-1/2 Thru 8 Inch (DN40 and DN200)
5
5
6 13
17
18
20
16
11 21
15
7 14
3 8
1
4
19
1 - Model DV-5 Deluge Valve 9 - System Drain Valve (N.C.) 17 - System Shut-Off Valve (N.O.)
2 - Main Control Valve (N.O.) 10 - Main Drain Valve (N.C.) 18 - Air Pressure Gauge
3 - Diaphragm Chamber Supply (Shown at Rear of Valve) 19 - Automatic Air/Nitrogen Supply
Control Valve (N.O.) 11 - Fail-Safe Valve 20 - Low Pressure Alarm Switch
4 - Local Manual Control Station 12 - Waterflow Pressure Alarm Switch 21 - Dry Pilot Actuator
5 - Automatic Sprinklers (Shown at Rear of Valve)
6 - Heat Detectors, Smoke Detectors, 13 - Water Motor Alarm (Optional)
etc. (Fire Detection) 14 - Solenoid Valve
7 - Water Supply Pressure Gauge 15 - Deluge Valve Releasing Panel
8 - Diaphragm Chamber Pressure 16 - Riser Check Valve
Gauge
FIGURE 1 — PART 1 OF 2
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
— SYSTEM SCHEMATIC (Front View)—
TFP1460 Page 3 of 16
5
5
20 17
13
15
21 9
14
12
16
10
1
2
19
1 - Model DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 15 - Deluge Valve Releasing Panel
2 - Main Control Valve (N.O.) (Shown at Front of Valve) 16 - Riser Check Valve
3 - Diaphragm Chamber Supply 8 - Diaphragm Chamber Pressure 17 - System Shut-Off Valve (N.O.)
Control Valve (N.O.) Gauge (Shown at Front of Valve)
18 - Air Pressure Gauge
(Shown at Front of Valve) 9 - System Drain Valve (N.C.) (Shown at Front of Valve)
4 - Local Manual Control Station 10 - Main Drain Valve (N.C.) 19 - Automatic Air/Nitrogen Supply
(Shown at Front of Valve) 11 - Fail-Safe Valve 20 - Low Pressure Alarm Switch
5 - Automatic Sprinklers (Shown at Front of Valve)
21 - Dry Pilot Actuator
6 - Heat Detectors, Smoke Detectors, 12 - Waterflow Pressure Alarm Switch
etc. (Fire Detection) 13 - Water Motor Alarm (Optional)
14 - Solenoid Valve
FIGURE 1 — PART 2 OF 2
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
— SYSTEM SCHEMATIC (Rear View)—
Page 4 of 16 TFP1460
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 28 3/4" x 1/2" 90° Elbow . . . . 1 CH P7 1/2" Swing Check Valve .1 46-049-1-004
Water Pressure Gauge . . 2 92-343-1-005 29 1/2" Cross . . . . . . . . . . . . 1 CH P8 1/2" Globe Valve . . . . . . . 1 46-047-1-004
2 1/4" Gauge Test Valve . . 1 46-005-1-002 30 1/2" Tee . . . . . . . . . . . . . . 2 CH P9 3/4" Angle Valve . . . . . . . 1 46-048-1-005
3 Model MC-1 Manual 31 1/2" x 1/4" x 1/2" Tee . . . . 3 CH P10 1/2" Tubing Connector . . 1 CH
Control Station . . . . . . . . . 1 52-289-2-001 32 3/4" Tee . . . . . . . . . . . . . . 1 CH P11 1/2" x 24" Tubing . . . . . . . 1 CH
4 Model AD-1 Automatic 33 3/4" x 1/2" x 3/4" Tee . . . . 2 CH P12 1/4" Plug . . . . . . . . . . . . . 3 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 34 1/4" x Close Nipple . . . . . 2 CH P13 1/2" Union . . . . . . . . . . . . 2 CH
5 Fail-Safe Valve, 35 1/2" x Close Nipple . . . . . 2 CH P14 1/2" 45° Elbow . . . . . . . . . 1 CH
Model FSV-1 . . . . . . . . . . 1 52-343-1-001 36 1/2" x 1-1/2" Nipple . . . . . 11 CH P15 1/2" 90° Elbow . . . . . . . . . 4 CH
6 Waterflow Pressure 37 1/2" x 2" Nipple . . . . . . . . 2 CH P16 1/2" Cross . . . . . . . . . . . . 1 CH
Alarm Switch (PS10-2A) .1 2571 38 1/2" x 2-1/2" Nipple . . . . . 2 CH P17 1/2" x 1/4" x 1/2" Tee . . . . 1 CH
7 Priming Supply 39 1/2" x 3-1/2" Nipple . . . . . 1 CH P18 1/2" x 1/2" x 1/4" Tee . . . . 1 CH
Restriction . . . . . . . . . . . . 1 92-020-1-009 40 1/2" x 5" Nipple . . . . . . . . 1 CH P19 1" x 3/4" x 1/2" Tee . . . . . 1 CH
8 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 41 1/2" x 7" Nipple . . . . . . . . 1 CH P20 1/4" x Close Nipple . . . . . 1 CH
9 1/2" Spring Loaded 42 1/2" x 8" Nipple . . . . . . . . 1 CH P21 1/2" x Close Nipple . . . . . 2 CH
Check Valve . . . . . . . . . . 1 92-322-1-002 43 Select Nipple per Table . . 1 CH P22 1/2" x 1-1/2" Nipple . . . . . 8 CH
10 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 44 3/4" x 1-1/2" Nipple . . . . . 6 CH P23 1/2" x 2" Nipple . . . . . . . . 2 CH
11 3/4" Swing Check Valve .1 46-049-1-005 45 3/4" x 2" Nipple . . . . . . . . 1 CH P24 1/2" x 9" Nipple . . . . . . . . 1 CH
12 3/4" Angle Valve . . . . . . . 1 46-048-1-005 46 3/4" x 4" Nipple . . . . . . . . 1 CH P25 Select Nipple per Table . . 1 CH
13 Drip Funnel Connector . . 1 92-211-1-005 P26 Select Nipple per Table . . 1 CH
14 Drip Funnel Bracket . . . . 1 92-211-1-003 P1 250 psi/ 1750 kPa P27 3/4" x 1-1/2" Nipple . . . . . 1 CH
15 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 Air Pressure Gauge . . . . . 1 92-343-1-012 P28 1" x 2" Nipple . . . . . . . . . . 1 CH
16 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 P2 1/4" Gauge Test Valve . . 1 46-005-1-002
17 1/4" x 18" Tubing . . . . . . . 1 CH P3 Model DP-1 Dry Pilot
18 1/2" Tubing Connector . . 2 CH Actuator . . . . . . . . . . . . . . 1 52-280-1-001 Select Appropriate Nipple Sizes
19 1/2" x 12" Tubing . . . . . . . 1 CH P4 Low Air Pressure Nipple per DV-5 Deluge Valve Size
20 1/2" x 18" Tubing . . . . . . . 1 CH Alarm Switch (PS40-2A) .1 2573 Number
1-1/2" (DN40) 2" (DN50)
21 1/4" Plug . . . . . . . . . . . . . 1 CH P5 Solenoid Valve Per Data Ordered
43 1/2" x 1-1/2" 1/2" x 2"
22 3/4" Plug . . . . . . . . . . . . . 1 CH Sheet TFP2180 . . . . . . . . 1 Separately
23 1/2" Union . . . . . . . . . . . . 5 CH P6 1/4" Pressure Relief P25 1/2" x 2-1/2" 1/2" x 2"
24 3/4" Union . . . . . . . . . . . . 1 CH Valve . . . . . . . . . . . . . . . . 1 92-343-1-020 P26 1/2" x 6" 1/2" x 5-1/2"
25 1/4" 90° Elbow . . . . . . . . . 1 CH
26 1/2" 90° Elbow . . . . . . . . . 7 CH
27 3/4" 90° Elbow . . . . . . . . . 1 CH P6
P8 P22 P20
P23 P1
P22 P4
P15 P7 P18 28 P17
P13 P2
44 P14
6 P22 36 P10 P22
P22 P25 P12
P11
P22 P15 P15
16
P16 P23 P3
(GREEN P13 4
TINT) 17 30 P24
P22 P21
P26 P28
31 26 P5
13 (ORDERED
33 P19 SEPARATELY)
22 P27 15 35
PLUG 14 P22
38 P9 23
UNUSED 39
PORTS RISER P21
45 44 CHECK VALVE 26 36
LOCATION P12 P15
FOR OPTIONAL 44 (NOTE 2)
44 32
ELECTRICALLY 36 18 23
44 P12 42
SUPERVISED 36 24
N.O. ALARM 11 44 26 20 30
26
CONTROL VALVE 33 1
39 5 36
(BVS-3/4")
43 27 (HEX ENDS,
12 46 "FSV-1") 29 36 31
8
41
9
38 1 36 3
NOTES: 23 7
21 2 23
1. Supervised Double
Interlock Preaction Trim 40 26
37 35
with Electric/Pneumatic 36 10 19
36 2" (DN50)
Release is comprised 37
of Items 1-46 plus Items 34 31 GROOVE x GROOVE 36 18
MODEL DV-5 26 26
P1-P28. 34 23
25 DELUGE VALVE
2. Use only the Model CV-1FR SHOWN NOTES:
Riser Check Valve. 36 5. See Figure 2 of TFP1305 for
3. All Fittings and Nipples are Deluge Valve Port identification.
galvanized (Standard Order). 8 6. Route all Tubing to Drip Funnel,
4. CH: Common Hardware. Item 15.
FIGURE 2A — PART 1 OF 3
1-1/2 and 2 INCH (DN40 and DN50) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM (52-478-X-127)
— EXPLODED VIEW —
TFP1460 Page 5 of 16
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 23 3/4" Union . . . . . . . . . . . . 1 CH P3 Model DP-1 Dry Pilot
Water Pressure Gauge . . 2 92-343-1-005 24 1/4" 90° Elbow . . . . . . . . . 1 CH Actuator . . . . . . . . . . . . . . 1 52-280-1-001
2 1/4" Gauge Test Valve . . 1 46-005-1-002 25 1/2" 90° Elbow . . . . . . . . . 7 CH P4 Low Air Pressure
3 Model MC-1 Manual 26 3/4" x 1/2" 90° Elbow . . . . 1 CH Alarm Switch (PS40-2A) .1 2573
Control Station . . . . . . . . . 1 52-289-2-001 27 1-1/4" 90° Elbow . . . . . . . 1 CH P5 Solenoid Valve Per Data Ordered
4 Model AD-1 Automatic 28 1/2" Cross . . . . . . . . . . . . 1 CH Sheet TFP2180 . . . . . . . . 1 Separately
Drain Valve . . . . . . . . . . . 1 52-793-2-004 29 1/2" Tee . . . . . . . . . . . . . . 2 CH P6 1/4" Pressure Relief
5 Fail-Safe Valve, 30 1/2" x 1/4" x 1/2" Tee . . . . 3 CH Valve . . . . . . . . . . . . . . . . 1 92-343-1-020
Model FSV-1 . . . . . . . . . . 1 52-343-1-001 31 3/4" Tee . . . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve .1 46-049-1-004
6 Waterflow Pressure 32 3/4" x 1/2" x 3/4" Tee . . . . 2 CH P8 1/2" Globe Valve . . . . . . . 1 46-047-1-004
Alarm Switch (PS10-2A) .1 2571 33 1/4" x Close Nipple . . . . . 2 CH P9 1-1/4" Angle Valve . . . . . . 1 46-048-1-007
7 Priming Supply 34 1/2" x Close Nipple . . . . . 1 CH P10 1/2" Tubing Connector . . 1 CH
Restriction . . . . . . . . . . . . 1 92-020-1-009 35 1/2" x 1-1/2" Nipple . . . . .14 CH P11 1/2" x 24" Tubing . . . . . . . 1 CH
8 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 36 1/2" x 2-1/2" Nipple . . . . . 1 CH P12 1/4" Plug . . . . . . . . . . . . . 3 CH
9 1/2" Spring Loaded 37 1/2" x 3-1/2" Nipple . . . . . 1 CH P13 1/2" Union . . . . . . . . . . . . 2 CH
Check Valve . . . . . . . . . . 1 92-322-1-002 38 1/2" x 4" Nipple . . . . . . . . 1 CH P14 1/2" 45° Elbow . . . . . . . . . 1 CH
10 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 39 1/2" x 4-1/2" Nipple . . . . . 2 CH P15 1/2" 90° Elbow . . . . . . . . . 4 CH
11 3/4" Swing Check Valve .1 46-049-1-005 40 1/2" x 5" Nipple . . . . . . . . 1 CH P16 1/2" Cross . . . . . . . . . . . . 1 CH
12 1-1/4" Angle Valve . . . . . . 1 46-048-1-007 41 1/2" x 7" Nipple . . . . . . . . 1 CH P17 1/2" x 1/4" x 1/2" Tee . . . . 1 CH
13 Drip Funnel Connector . . 1 92-211-1-005 42 1/2" x 8" Nipple . . . . . . . . 1 CH P18 1/2" x 1/2" x 1/4" Tee . . . . 1 CH
14 Drip Funnel Bracket . . . . 1 92-211-1-003 43 3/4" x 1-1/2" Nipple . . . . . 5 CH P19 1-1/4" x 1-1/4" x 1/2" Tee .1 CH
15 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 44 3/4" x 2" Nipple . . . . . . . . 1 CH P20 1/4" x Close Nipple . . . . . 1 CH
16 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 45 1-1/4" x 2" Nipple . . . . . . . 1 CH P21 1/2" x Close Nipple . . . . . 2 CH
17 1/4" x 18" Tubing . . . . . . . 1 CH 46 1-1/4" x 4" Nipple . . . . . . . 1 CH P22 1/2" x 1-1/2" Nipple . . . . . 8 CH
18 1/2" Tubing Connector . . 2 CH P23 1/2" x 2" Nipple . . . . . . . . 3 CH
19 1/2" x 18" Tubing . . . . . . . 2 CH P1 250 psi/ 1750 kPa P24 1/2" x 5" Nipple . . . . . . . . 1 CH
20 1/4" Plug . . . . . . . . . . . . . 1 CH Air Pressure Gauge . . . . . 1 92-343-1-012 P25 1/2" x 10-1/2" Nipple . . . . 1 CH
21 3/4" Plug . . . . . . . . . . . . . 1 CH P2 1/4" Gauge Test Valve . . 1 46-005-1-002 P26 1-1/4" x 2" Nipple . . . . . . . 1 CH
22 1/2" Union . . . . . . . . . . . . 5 CH P27 1-1/4" x 3" Nipple . . . . . . . 1 CH
P7 P4 P22 P6 P20
P22 P22 P1
P22 P18 26 P17
P15 P2
P13
43 P14
P8 35 P10 P22
6 P22 P23 P13 P12
P22 P15 P15
16 P16 P23 P3
(GREEN 4
P23 29 P11
TINT) 17 P21
P24 P25
30 P26 13 P5
32 P9 25 (ORDERED
P27 15 35
21 PLUG 14 P22 SEPARATELY)
P19 UNUSED
22 39
36 31 PORTS RISER P21
43 P12 CHECK VALVE 25 35
44 23 P15
LOCATION (NOTE 2)
FOR OPTIONAL 43
43 P12 35 18 22
ELECTRICALLY 42
SUPERVISED 35 11
25 19 29
N.O. ALARM 43
25 38 1
CONTROL VALVE 32 35
(BVS-3/4") 5
35 (HEX ENDS,
27 28 35 30
"FSV-1")
8 45 46 41
12 35 3
40 10
NOTES: 1
7 22
1. Supervised Double 22 9
Interlock Preaction Trim 20 2
25 34
with Electric/Pneumatic 37
35 19
Release is comprised 39
of Items 1-46 plus Items 35 18
35 3" (DN80) 35 25 25
P1-P27. 33 22
30 GROOVE x GROOVE
2. Use only the Model CV-1FR 33 MODEL DV-5 NOTES:
Riser Check Valve. 24 DELUGE VALVE 35 5. See Figure 2 of TFP1305 for
3. All Fittings and Nipples are SHOWN Deluge Valve Port identification.
galvanized (Standard Order). 8 6. Route all Tubing to Drip Funnel,
4. CH: Common Hardware. Item 15.
FIGURE 2A — PART 2 OF 3
3 INCH (DN80) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM (52-478-X-124)
— EXPLODED VIEW —
Page 6 of 16 TFP1460
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 30 1" x 1/2" 90° Elbow . . . . . 1 CH P10 1/2" Tubing Connector . . 1 CH
Water Pressure Gauge . . 2 92-343-1-005 31 1" x 3/4" x 1" Tee . . . . . . . 1 CH P11 1/2" x 24" Tubing . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . 1 46-005-1-002 32 2" 90° Elbow . . . . . . . . . . 1 CH P12 1/4" Plug . . . . . . . . . . . . . 3 CH
3 Model MC-1 Manual 33 1/4" x Close Nipple . . . . . 2 CH P13 1/2" Union . . . . . . . . . . . . 2 CH
Control Station . . . . . . . . . 1 52-289-2-001 34 1/2" x Close Nipple . . . . . 1 CH P14 1/2" 45° Elbow . . . . . . . . . 1 CH
4 Model AD-1 Automatic 35 1/2" x 1-1/2" Nipple . . . . . 11 CH P15 1/2" 90° Elbow . . . . . . . . . 4 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 36 1/2" x 2-1/2" Nipple . . . . . 2 CH P16 1/2" Cross . . . . . . . . . . . . 1 CH
5 Fail-Safe Valve, 37 1/2" x 3" Nipple . . . . . . . . 1 CH P17 1/2" x 1/4" x 1/2" Tee . . . . 1 CH
Model FSV-1 . . . . . . . . . . 1 52-343-1-001 38 1/2" x 5" Nipple . . . . . . . . 2 CH P18 1/2" x 1/2" x 1/4" Tee . . . . 1 CH
6 Waterflow Pressure 39 1/2" x 7" Nipple . . . . . . . . 2 CH P19 2" x 2" x 1/2" Tee . . . . . . . 1 CH
Alarm Switch (PS10-2A) .1 2571 40 1/2" x 9" Nipple . . . . . . . . 1 CH P20 1/4" x Close Nipple . . . . . 1 CH
7 Priming Supply 41 Select Nipple per Table . . 1 CH P21 1/2" x Close Nipple . . . . . 2 CH
Restriction . . . . . . . . . . . . 1 92-020-1-009 42 Select Nipple per Table . . 1 CH P22 1/2" x 1-1/2" Nipple . . . . . 6 CH
8 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 43 Select Nipple per Table . . 1 CH P23 1/2" x 2" Nipple . . . . . . . . 1 CH
9 1/2" Spring Loaded 44 3/4" x 1-1/2" Nipple . . . . . 1 CH P24 1/2" x 4-1/2" Nipple . . . . . 2 CH
Check Valve . . . . . . . . . . 1 92-322-1-002 45 3/4" x 2" Nipple . . . . . . . . 1 CH P25 1/2" x 11" Nipple . . . . . . . 1 CH
10 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 46 Select Nipple per Table . . 1 CH P26 Select Nipple per Table . . 1 CH
11 3/4" Swing Check Valve .1 46-049-1-005 47 1" x Close Nipple . . . . . . . 2 CH P27 Select Nipple per Table . . 1 CH
12 2" Angle Valve . . . . . . . . . 1 46-048-1-009 48 1" x 3" Nipple . . . . . . . . . . 1 CH P28 Select Nipple per Table . . 1 CH
13 Drip Funnel Connector . . 1 92-211-1-005 49 2" x 3" Nipple . . . . . . . . . . 2 CH P29 2" x 3" Nipple . . . . . . . . . . 2 CH
14 Drip Funnel Bracket . . . . 1 92-211-1-003
15 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 P1 250 psi/ 1750 kPa
16 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 Air Pressure Gauge . . . . . 1 92-343-1-012
Select Appropriate Nipple Sizes
17 1/4" x 24" Tubing . . . . . . . 1 CH P2 1/4" Gauge Test Valve . . 1 46-005-1-002
Nipple per DV-5 Deluge Valve Size
18 1/2" Tubing Connector . . 2 CH P3 Model DP-1 Dry Pilot
19 1/2" x 24" Tubing . . . . . . . 2 CH Actuator . . . . . . . . . . . . . . 1 52-280-1-001 No. 4" 6" 8"
20 1/4" Plug . . . . . . . . . . . . . 1 CH P4 Low Air Pressure (DN100) (DN150) (DN200)
21 3/4" Plug . . . . . . . . . . . . . 1 CH Alarm Switch (PS40-2A) .1 2573 41 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8 -1/2"
22 1/2" Union . . . . . . . . . . . . 5 CH P5 Solenoid Valve Per Data Ordered 42 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2"
23 1" Union . . . . . . . . . . . . . . 1 CH Sheet TFP2180 . . . . . . . . 1 Separately 43 1/2" x 4" 1/2" x 5" 1/2" x 5-1/2"
24 1/4" 90° Elbow . . . . . . . . . 1 CH P6 1/4" Pressure Relief
46 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
25 1/2" 90° Elbow . . . . . . . . . 7 CH Valve . . . . . . . . . . . . . . . . 1 92-343-1-020
26 1/2" Cross . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve .1 46-049-1-004 P26 1/2" x 7" 1/2" x 5-1/2" 1/2" x 3"
27 1/2" Tee . . . . . . . . . . . . . . 2 CH P8 1/2" Globe Valve . . . . . . . 1 46-047-1-004 P27 1/2" x 3-1/2" 1/2" x 6" 1/2" x 8"
28 1/2" x 1/4" x 1/2" Tee . . . . 3 CH P9 2" Angle Valve . . . . . . . . . 1 46-048-1-009 P28 1/2" x 2" 1/2" x 2-1/2" 1/2" x 4"
29 3/4" x 1/2" x 3/4" Tee . . . . 2 CH
P6 P20
P8 P22 P1
P22
P22
P4 P18 P17
P22 P2
P15 P14
P13 30
P10 P22
P12
P22 37 4 P15
P28
6 P23 P3
P24 P27 P7 47
P11
16 P16 P21
P13 P25
(GREEN 27
TINT) 17 P26 P15
P29 P5
13 (ORDERED
28 25
PLUG P24 SEPARATELY)
29 15
UNUSED 42
21 14 P15
P9 P29 PORTS
P19 22 43
36 P12 P21
40 25
LOCATION 31 35
45
FOR OPTIONAL 23 P12 25
35 18
ELECTRICALLY 22
44
SUPERVISED 5
11 47 27
N.O. ALARM 35 (HEX ENDS, 19
46 48
CONTROL VALVE 25 "FSV-1") 35 1
(BVS-3/4") 29 36
RISER
41 26 35 28
CHECK VALVE
32 (NOTE 2) 39
8
49 49 35 3
10
12
NOTES: 7
1 22
1. Supervised Double 39 9
Interlock Preaction Trim 22 25
38 34
with Electric/Pneumatic 20 2 35 19
Release is comprised
of Items 1-49 plus Items 38 35 18
25 25
P1-P29. 22
35 35
4" (DN100)
2. Use only the Model CV-1FR 33 28 NOTES:
FLANGE x GROOVE
Riser Check Valve. 35 5. See Figure 2 of TFP1305 for
33 MODEL DV-5
3. All Fittings and Nipples are 24 Deluge Valve Port identification.
DELUGE VALVE
galvanized (Standard Order). SHOWN 8 6. Route all Tubing to Drip Funnel,
4. CH: Common Hardware. Item 15.
FIGURE 2A — PART 3 OF 3
4, 6, and 8 INCH (DN100, DN150, and DN200) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM (52-478-X-121)
— EXPLODED VIEW —
TFP1460 Page 7 of 16
NOTES: Select Appropriate Nipple Sizes per DV-5 Deluge Valve Size
1. Use only the 2" Model CV-1FR Riser Check Nipple With Model CV-1FR Check Valve
Valve with 1-1/2" and 2" DV-5 Valves. Use Number
1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
corresponding sized Model CV-1FR Riser
1 1/2" x 1-1/2" 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
Check Valves for 3"-8" Model DV-5 Valves.
2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2"
2. Nipples 1-7 vary in length relative to the
Model DV-5 size and Riser Check Valve 3 1/2" x 3-1/2" 1/2" x 3-1/2" 1/2" x 4-1/2" 1/2" x 4" 1/2" x 5" 1/2" x 5-1/2"
used. Select per the appropriate table. All 4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
other nipples packed unassembled shall be 5 1/2" x 6" 1/2" x 5-1/2" 1/2" x 5" 1/2" x 7" 1/2" x 5-1/2" 1/2" x 3"
installed per the appropriate trim exploded 6 1/2" x 2-1/2" 1/2" x 2" 1/2" x 2" 1/2" x 3-1/2" 1/2" x 6" 1/2" x 8"
view, Figure 2A Part 1, 2, or 3.
7 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2" 1/2" x 2-1/2" 1/2" x 4"
3. Install subassemblies in alphabetical order.
System
4. See Figure 2 of TFP1305 for Deluge Valve
Main Drain 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
Port identification.
Size
5. Route all Tubing to Drip Funnel.
Main
6. When DV-5 trips, the Fail-Safe Valve opens, Drain 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
partially diverting the diaphragm supply to
Size
drain, allowing diaphragm chamber to remain
de-pressurized after a decrease in system
flow. LOW AIR
WATERFLOW VENT FITTING SYSTEM PRESSURE SYSTEM
PRESSURE (GREEN TINT) AIR SUPPLY ALARM SWITCH AIR SUPPLY
ALARM SWITCH CONTROL VALVE PRESSURE
(NORMALLY GAUGE
OPEN) 1/2 INCH NPT
3/4 INCH NPT CONNECTION
CONNECTION FOR DRIP F FOR SYSTEM G 1/2 INCH
WATER MOTOR FUNNEL AIR SUPPLY
AUTOMATIC CONDUIT
ALARM WITH 1-1/4
DRAIN CONNECTION
B VALVE INCH NPT FOR "ELECTRIC
CONNECTION DETECTION"
TO DRAIN DRY PILOT
NIPPLE NIPPLE ACTUATOR
4 PLUG 5 NIPPLE NIPPLE SOLENOID
(NORMALLY
UNUSED 6 7 VALVE,
CLOSED)
PORTS ORDERED
SYSTEM
RISER SEPARATELY
MAIN DRAIN
CHECK VALVE NIPPLE (NORMALLY
CONNECTION
(NOTE 1) 2 CLOSED)
(SIZED PER
NIPPLE TABLE)
1 SYSTEM MAIN
DRAIN VALVE NIPPLE DIAPHRAGM
(NORMALLY 3 CHAMBER
MAIN
CLOSED) PRESSURE
DRAIN VALVE
GAUGE
(NORMALLY
CLOSED)
E
ALARM MANUAL
CONTROL
TEST VALVE A D STATION
(NORMALLY
CLOSED)
FAIL-SAFE
SYSTEM VALVE
WATER 4" (DN100) (NORMALLY
SUPPLY
C FLANGE x GROOVE DIAPHRAGM
CLOSED)
MODEL DV-5 CHAMBER SUPPLY
PRESSURE
DELUGE VALVE CONTROL VALVE
GAUGE MAIN DRAIN 1/2 INCH NPT
SHOWN (NORMALLY
CONNECTION CONNECTION FROM OPEN)
(SIZED PER TABLE) WATER SUPPLY
FIGURE 2B
1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM
— OPERATIONAL COMPONENTS —
Page 8 of 16 TFP1460
* MINIMUM CLEARANCE.
A* B C* D*
E*
1/2" NPS M
DIAPHRAGM
CHAMBER SUPPLY
CONNECTING TRIM
(FIELD FABRICATED) L
MAIN
2" NPS 1-1/4" NPS
G CONTROL
DRAIN DRAIN
VALVE
H J K
FIGURE 3
1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM
— NOMINAL INSTALLATION DIMENSIONS —
TFP1460 Page 9 of 16
WARNING
The Model DV-5 Double Interlock Pre-
action System with Electric/Pneumatic 0
Actuation described herein must be 20 60 100 140 180 200 250
installed and maintained in compli-
ance with this document, as well as WATER SUPPLY PRESSURE IN PSI
with the applicable standards of the
National Fire Protection Association, GRAPH A
in addition to the standards of any DOUBLE INTERLOCK PREACTION SYSTEM
other authorities having jurisdiction. AIR PRESSURE REQUIREMENTS
Failure to do so may impair the per-
formance of the related devices.
• Dry Pilot Actuator
The owner is responsible for maintain- Technical • Pressure Operated Relief Valve
ing their fire protection system and de-
vices in proper operating condition. Data To ease field assembly of the trim ar-
The installing contractor or manufac- rangement, the trim components are
turer should be contacted with any Approvals provided par tially assembled as
questions. UL and C-UL Listed. FM Approved. shown in Figure 2B.
Deluge Valve The trim arrangement is provided with
Model DV-5. galvanized or black nipples and fit-
Riser Check Valve tings. The galvanized trim is intended
Model CV-1FR. for non-corrosive or corrosive condi-
tions, whereas the black trim is princi-
NOTE pally intended for use with AFFF sys-
1-1/2 inch (DN40) risers utilize a 2 inch tems.
(DN50) Riser Check Valve in combina-
tion with the 1-1/2 inch (DN40) Model NOTE
DV-5 Deluge Valve. When the system pressure is greater
than 175 psi (12,1 bar), provision is to
be made to replace the standard order
Valve Trim 300 psi (20,7 bar) Water Pressure
The Double Interlock Preaction Sys- Gauges, shown in Figure 2A/2B with
tem with Electric/Pneumatic Actuation separately ordered 600 psi (41,4 bar)
Trim (Fig. 2A/2B) forms a part of the Water Pressure Gauges.
laboratory listings and approvals. The
trim is necessary for proper operation System Design Considerations
of the DV-5 Valve. Because a double interlock preaction
system requires time for a drop in sys-
Each package of trim includes the fol- tem air pressure to occur (concurrently
lowing items: with the response time for the separate
fire detection system) before it will al-
• Water Supply Pressure Gauge low water to enter the system piping,
• Diaphragm Chamber this system has characteristics similar
Pressure Gauge to a dry pipe sprinkler system. There-
• Diaphragm Chamber Connections fore, the system design considerations
• Manual Control Station for a dry pipe system are normally
applied to a double interlock preaction
• Main Drain Valve system — including a 30% increase in
• System Drain Valve design area; a maximum 1 minute
• Alarm Test Valve water delivery time for system capaci-
• Automatic Drain Valve ties of 750 gallons (2800 litres) or
more; and, prohibition of gridded sys-
• System Air Pressure Gauge tem piping.
• Air Supply Connections
In order to readily perform the System
• Low Air Pressure Alarm Switch Inspection Procedure described in the
• Waterflow Pressure Alarm Switch Care and Maintenance section, it is
Page 10 of 16 TFP1460
9.0 0,600
0)
N4
8.0
(D 0,500
0)
7.0
N5
CH
(D
6.0
IN
0,400
H
/2
NC
1-1
5.0
2I
0)
N8
4.0
(D
)
00
H
N1
NC
0,200
H
NC
)
50
4I
N1
(D
2.0
)
00
H
NC
N2
(D
6I
H
0,100
NC
0,090
8I
0,080
1.0 0,070
0.9 0,060
0.8
0.7 0,050
0.6 0,040
0.5
0,030
0.4
50 100 200 400 600 1000 2000 3000
FLOW RATE IN GALLONS PER MINUTE (GPM)
The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe with C=120, is as
follows:
15 feet of 1-1/2 Sch. 40 pipe for the 1-1/2 inch Valve Combination** calculated on a typical flow rate of 100 GPM.
28 feet of 2 inch Sch. 40 pipe for the 2 inch Valve Combination* calculated on a typical flow rate of 175 GPM.
37 feet of 3 inch Sch. 40 pipe for the 3 inch Valve Combination* calculated on a typical flow rate of 350 GPM.
48 feet of 4 inch Sch. 40 pipe for the 4 inch Valve Combination* calculated on a typical flow rate of 600 GPM.
73 feet of 6 inch Sch. 40 pipe for the 6 inch Valve Combination* calculated on a typical flow rate of 1500 GPM.
103 feet of 8 inch Sch. 30 pipe for the 8 inch Valve Combination* calculated on a typical flow rate of 2500 GPM.
GRAPH B
DELUGE AND CHECK VALVE COMBINATION*
— NOMINAL PRESSURE LOSS VERSUS FLOW —
* Model DV-5 Deluge Valve combined with Model CV-1FR Riser Check Valve
**1-1/2 inch Model DV-5 Deluge Valve combined with 2 inch Model CV-1FR Riser Check Valve
TFP1460 Page 11 of 16
must be installed with smooth bends Automatic Drain Valve (4, Fig. 2A) is to to a temperature greater than their
that will not restrict flow. be temporarily replaced with a 1/2 inch maximum rated ambient must also be
NPT plug, the 3/32 inch Vent Fitting (17 replaced.
Step 5. The main drain and drip funnel
- Fig. 2A) is to be temporarily replaced
drain may be interconnected provided Step 8. Service the air dryer, if appli-
with a 1/4 inch NPT plug, and the Dia-
a check valve is located at least 12 cable, in accordance with the manu-
phragm Cover Bolts must be uni-
inches (300 mm) below the drip funnel. facturer’s instructions.
formly and securely tightened using
Step 6. Suitable provision must be a cross-draw sequence. After tight- Step 9. Open the System Air Supply
made for disposal of drain water. ening, double-check to make certain Control Valve and allow the system to
Drainage water must be directed so that all of the Diaphragm Cover Bolts automatically re-establish its nominal
that it will not cause accidental dam- are securely tightened. system air pressure per Graph A. Ob-
age to property or danger to persons. serve the Automatic Drain Valve for
leaks. If there are leaks, deter-
Step 7. Connect the Diaphragm
mine/correct the cause of the leakage
Chamber Supply Control Valve to the
inlet side of the system’s main control Valve Setting problem within the Riser Check Valve.
valve in order to facilitate setting of the Step 10. Reset the actuation system.
DV-5 Valve (Fig. 3). Procedure Manual Actuation — Push the operat-
Step 8. Unused pressure alarm Steps 1 through 15 are to be per- ing lever up; however, do not close the
switch connections must be plugged. formed when initially setting the Model hinged cover at this time.
Step 9. A suitable automatic supervi- DV-5 Deluge Valve; after an opera- Electric Actuation — Reset the electric
sory air (nitrogen) supply, as described tional test of the fire protection system; detection system in accordance with
in the Technical Data Section, is to be or, after system operation due to a fire. the manufacturer’s instructions to de-
installed in accordance with the appli- Step 1. Close the Main Control Valve. energize the Solenoid Valve.
cable Technical Data Sheet. Refer to
Step 2. Close the Diaphragm Cham- Step 11. Open the Diaphragm Cham-
Graph A for the system air pressure
ber Supply Control Valve and the Sys- ber Supply Control Valve and allow full
requirements.
tem Air Supply Control Valve. pressure to build up in the Diaphragm
An air dryer, when specified, is to be Chamber.
installed as required by the Authority Step 3. Open the Main Drain Valve,
System Drain Valve, and all auxiliary Step 12. Operate (open) the Manual
Having Jurisdiction.
drains in the system. After water Control Station to vent trapped air from
Step 10. The Pressure Relief Valve ceases to discharge, close the System the Diaphragm Chamber. If necessary,
(P6 - Fig. 2A) is factory set to relieve at Drain Valve and auxiliary drain valves. first open the hinged cover, and then
a pressure of approximately 45 psi (3,1 Leave the Main Drain Valve open. fully pull down on the operating lever.
bar), which can typically be used for a SLOWLY close the operating lever, by
maximum system pressure of 40 psi NOTE pushing it up, after aerated water
(2,8 bar). The Pressure Relief Valve Do not open the Inspector’s Test Con- ceases to discharge from the Manual
may be reset; however, it must be reset nection and auxiliary drains if resetting Control Station drain tubing. Close the
to relieve at a pressure that is in ac- after a system test; otherwise, system hinged cover and insert a new break
cordance with the requirements of the air pressure will be relieved unneces- rod in the small hole through the top of
Authority Having Jurisdiction. sarily. the enclosing box.
To reset the Pressure Relief Valve, first Step 4. Depress the plunger of the Step 13. Inspect the drain connections
loosen the jam nut and then adjust the Automatic Drain Valve to verify that it from the Manual Control Station and
cap accordingly — clockwise for a is open and that the DV-5 Valve is the Dry Pilot Actuator. Any leaks must
higher pressure setting or counter- completely drained. be corrected before proceeding to the
clockwise for a lower pressure setting. next step.
After verifying the desired pressure Step 5. Clean the Strainer in the Dia-
phragm Chamber Supply connection Step 14. Verify the ability for the DV-5
setting, tighten the jam nut.
by removing the clean-out plug and Diaphragm to hold pressure as fol-
Step 11. The Low Pressure Alarm strainer basket. The Strainer may be lows:
Switch (Item P4 - Fig. 2A) is to be flushed out by momentarily opening With the diaphragm chamber pressur-
adjusted to operate on falling pressure the Diaphragm Chamber Supply Con- ized per Step 12, temporarily close the
at approximately 6 psi (0,4 bar) below trol Valve. Diaphragm Chamber Supply Control
the minimum Double Interlock Dry
Step 6. Inspect for and clear all ice Valve and observe the Diaphragm
System air pressure requirement
plugs where system piping has been Chamber Pressure Gauge for a drop in
shown on Graph B.
exposed to freezing conditions and pressure.
Use the instructions provided with the when there has been a flow of water If a drop in pressure is noted, the DV-5
switch to adjust the pressure setting. into the system. Diaphragm is to be replaced and/or
Step 12. Conduit and electrical con- Step 7. Replace all damaged or oper- any leaks must be corrected before
nections are to be made in accordance ated sprinklers. Replacement sprin- proceeding to the next step.
with the requirements of the authority klers must be of the same type and If the Diaphragm Chamber Pressure
having jurisdiction and/or the National temperature rating as those that oper- Gauge does not indicate a drop in
Electric Code. ated. pressure, re-open the Diaphragm
Step 13. Before a system hydrostatic Chamber Supply Control Valve and
test is performed in accordance with NOTE proceed to the next step.
NFPA 13 system acceptance test re- In order to prevent the possibility of a
subsequent operation of an over- Step 15. Slowly open the Main Control
quirements, the DV-5 Diaphragm
heated solder type sprinkler, any sol- Valve. Close the Main Drain Valve as
Chamber is to be depressurized; the
der type sprinklers possibly exposed soon as water discharges from the
TFP1460 Page 13 of 16
drain connection. Observe the Auto- authorities and all personnel who may
matic Drain Valve for leaks. If there are Care and be affected.
leaks, determine/correct the cause of
the leakage problem. If there are no Maintenance Before closing a fire protection system
main control valve for maintenance
leaks, the DV-5 Valve is ready to be
The following procedures, inspections, work on the fire protection system that
placed in service and the Main Control
and maintenance must be performed it controls, permission to shut down the
Valve must then be fully opened.
as indicated, in addition to any specific affected fire protection system must be
requirements of the NFPA, and any obtained from the proper authorities
NOTES
impairment must be immediately cor- and all personnel who may be affected
When the Main Control Valve is
rected. by this action must be notified.
opened, the pressure on the Dia-
phragm Chamber may increase. This The owner is responsible for the in-
increase in pressure is normal, and if spection, testing, and maintenance of System Inspection Procedure
the pressure is greater than 250 psi their fire protection system and de-
(17,2 bar), the pressure is to be re- vices in compliance with this docu-
lieved by partially and temporarily ment, as well as with the applicable Step 1. Close the Main Control Valve
opening the Manual Control Station; standards of the National Fire Protec- (Fig. 1) and then open the DV-5 Main
however, do not allow the pressure as tion Association (e.g., NFPA 25), in Drain Valve (Fig. 2B).
indicated on the Diaphragm Chamber addition to the standards of any
Pressure Gauge to drop below the authority having jurisdiction. The in- Step 2. Manually operate Deluge
supply pressure shown on the Water stalling contractor or product manufac- Valve Releasing Panel, and verify the
Supply Pressure Gauge, since this ac- turer should be contacted relative to following:
tion may result in tripping of the DV-5 any questions.
Valve. • Verify the operation of the Releasing
It is recommended that automatic Panel and its associated alarms.
After setting a fire protection system, sprinkler systems be inspected,
notify the proper authorities and ad- • Verify that there is no leakage from
tested, and maintained by a qualified the Dry Pilot Actuator (Fig. 2B).
vise those responsible for monitoring Inspection Service in accordance with
proprietary and/or central station local requirements and/or national
alarms. NOTES
codes. During this procedure, the Solenoid
It is recommended that the System Valve is opened; however, the Dry Pi-
Inspection Procedure be performed at lot Actuator should remain closed and
least semi-annually by a qualified In- the DV-5 Deluge Valve Diaphragm
spection Service. The Double Interlock Chamber should remain pressurized.
Preaction System Inspection Proce- This procedure is used to verify that
dure may be followed in lieu of per- the DV-5 Deluge Valve will remain set
forming any of the operational tests if the electric detection system oper-
recommended in the Technical Data ates but the sprinkler system remains
Sheets for the Model DV-5 Deluge in its normally pressurized condition.
Valve, Riser Check Valve, 24 VDC So-
lenoid Valve, Dry Pilot Actuator, and Step 3. Open the Inspector’s Test Con-
Model MC-1 Manual Control Station. nection but be prepared to close it im-
mediately after verifying that the Low
NOTES Pressure Alarm Switch (Fig. 2B) and
It is recommended that the individuals its associated alarms operate properly.
responsible for the care and mainte- The Low Pressure Alarm Switch
nance of the Double Interlock Preac- should operate at the previously estab-
tion System develop a working under- lished pressure (refer to Installation
standing of the system, in general, section, Step 11).
prior to performing inspection and/or Close the Inspector’s Test Connection.
maintenance procedures. These in-
structions, as well as individual in- Step 4. Close the Diaphragm Chamber
structions for the deluge valve, riser Supply Control Valve (Fig. 2B).
check valve, solenoid valve, dry pilot Step 5. Close the System Shut-off
actuator, manual control station, Valve (Fig. 1) after the system air pres-
switches, and pressure maintenance sure has been restored to normal.
device should be reviewed.
Step 6. Manually restore the electric
The following procedures pertain to fire detection system to a normal con-
the automatic control valve portion of dition in accordance with the manufac-
the Double Interlock Preaction Sys- turer’s instructions. The Solenoid Valve
tem. Refer to the manufacturer’s in- will then be de-energized and returned
structions and NFPA 25 for care and to its normally closed position.
maintenance procedures for all other
devices (e.g., electric detection, main Step 7. Open the Diaphragm Chamber
control and system shut-off valves, su- Supply Control Valve (Fig. 2B).
pervisory devices, sprinklers, etc.). Step 8. Open the Main Control Valve
Before performing the System Inspec- (Fig. 1) one turn beyond the position at
tion Procedure, which will result in op- which water just begins to flow from
eration of alarms, notify the proper the Main Drain Valve.
Page 14 of 16 TFP1460
Step 9. Close the Main Drain Valve Step 1. Take the sprinkler system out
(Fig. 2B). of service by using Steps 1 through 4 Limited
of the Resetting Procedure.
Step 10. Close the Air Supply Control
Valve (Fig. 2B). Step 2. Remove the FSV-1 from the Warranty
Double Interlock Preaction Trim. Products manufactured by Tyco Fire
Step 11. Open the Dry Pilot Actuator
by partially opening the System Main Step 3. Refer to Technical Data Sheet Products are warranted solely to the
Drain Valve (Fig. 2B) to relieve air pres- TFP1386 and completely disassem- original Buyer for ten (10) years
sure at the inlet to the Actuator. Verify ble the FSV-1. against defects in material and work-
that there is no leakage from the Dry manship when paid for and properly
Step 4. Clean all parts, and replace installed and maintained under normal
Pilot Actuator.
worn or damaged parts as necessary use and service. This warranty will ex-
NOTES Step 5. Reassemble the FSV-1 in ac- pire ten (10) years from date of ship-
During this procedure, the Dry Pilot cordance with Technical Data Sheet ment by Tyco Fire Products. No war-
Actuator is opened; however, the So- TFP1386 and then reinstall the FSV-1 ranty is given for products or
lenoid Valve should remain closed and into the Double Interlock Preaction components manufactured by compa-
the DV-5 Deluge Valve Diaphragm Trim. nies not affiliated by ownership with
Chamber should remain pressurized. Tyco Fire Products or for products and
Step 6. Place the system into service components which have been subject
This procedure is used to verify that in accordance with the Resetting Pro- to misuse, improper installation, corro-
the DV-5 Deluge Valve will remain set cedure section and then perform the sion, or which have not been installed,
if the Dry Pilot Actuator operates due System Inspection Procedure to verify maintained, modified or repaired in ac-
to loss of system air pressure and the proper operation of the system, as well cordance with applicable Standards of
electric detection system remains in a as the FSV-1 Fail-Safe Valve. the National Fire Protection Associa-
normal condition. tion, and/or the standards of any other
Quarterly Waterflow Alarm Test Authorities Having Jurisdiction. Mate-
Step 12. Open (energize) the Solenoid Procedure
Valve by operating the deluge valve rials found by Tyco Fire Products to be
Testing of the system waterflow alarms defective shall be either repaired or
releasing panel, and verify the follow- must be performed quarterly. To test
ing: replaced, at Tyco Fire Products’ sole
the waterflow alarm, open the Alarm option. Tyco Fire Products neither as-
Test Valve, which will allow a flow of
• Verify that the DV-5 Valve operates, water to the Waterflow Pressure Alarm
sumes, nor authorizes any person to
as is indicated by a discharge of assume for it, any other obligation in
Switch and/or Water Motor Alarm. connection with the sale of products or
water from the System Main Drain Upon satisfactory completion of the
Valve and the Automatic Drain parts of products. Tyco Fire Products
test, close the Alarm Test Valve. shall not be responsible for sprinkler
Valve. The Automatic Drain Valve
may or may not close depending on system design errors or inaccurate or
the flow past the partially open Main incomplete information supplied by
Control Valve. Buyer or Buyer’s representatives.
• Verify that the Model FSV-1 Fail- IN NO EVENT SHALL TYCO FIRE
Safe Valve has operated as is indi- PRODUCTS BE LIABLE, IN CON-
cated by water discharging into the TRACT, TORT, STRICT LIABILITY OR
Drip Funnel from the 1/2 inch drain UNDER ANY OTHER LEGAL THE-
tube connected to the Model FSV-1 ORY, FOR INCIDENTAL, INDIRECT,
Fail-Safe Valve. SPECIAL OR CONSEQUENTIAL
• Verify that the Waterflow Pressure DAMAGES, INCLUDING BUT NOT
Alarm Switch (Fig. 2B) and its asso- LIMITED TO LABOR CHARGES, RE-
ciated alarms properly operate. GARDLESS OF WHETHER TYCO
• Verify that the Water Motor Alarm, if FIRE PRODUCTS WAS INFORMED
applicable, properly operates. ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
NOTE SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
This procedure simulates opening of
both the Dry Pilot Actuator (loss of EQUAL TO THE SALES PRICE.
system air pressure) and Solenoid THE FOREGOING WARRANTY IS
Valve (operation of the deluge valve MADE IN LIEU OF ANY AND ALL
releasing panel) to verify automatic OTHER WARRANTIES EXPRESS OR
system operation. IMPLIED, INCLUDING WARRANTIES
Step 13. Reset the Double Interlock OF MERCHANTABILITY AND FIT-
Preaction System in accordance with NESS FOR A PARTICULAR PUR-
the Resetting Procedure section. POSE.
Fail-Safe Valve
If water does not discharge from the
1/2 inch tube connected to the Model
FSV-1 Fail-Safe Valve during Step 12
of the System Inspection Procedure,
the Model FSV-1 Fail-Safe Valve is to
be disassembled, cleaned, and in-
spected as follows:
TFP1460 Page 15 of 16
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446