CL03 - Studio 5000 Logix Designer Basics Lab - Lab Manual
CL03 - Studio 5000 Logix Designer Basics Lab - Lab Manual
CL03 - Studio 5000 Logix Designer Basics Lab - Lab Manual
The variety of uses for the hardware, software and firmware (hereinafter “Products”) described in this Documentation, mandates
that those responsible for the application and use of those Products must satisfy themselves that all necessary steps have been
taken to ensure that each application and actual use meets all performance and safety requirements, including any applicable
laws, regulations, codes and standards in addition to any applicable technical documents.
In no event will Rockwell Automation, Inc., or any of its affiliate or subsidiary companies (hereinafter “Rockwell Automation”) be
responsible or liable for any indirect or consequential damages resulting from the use or application of the Products described in
this Documentation. Rockwell Automation does not assume responsibility or liability for damages of any kind based on the
alleged use of, or reliance on, this Documentation.
No patent liability is assumed by Rockwell Automation with respect to use of information, circuits, equipment, or software
described in the Documentation.
Except as specifically agreed in writing as part of a maintenance or support contract, equipment users are responsible for:
• properly using, calibrating, operating, monitoring and maintaining all Products consistent with all Rockwell Automation
or third-party provided instructions, warnings, recommendations and documentation;
• ensuring that only properly trained personnel use, operate and maintain the Products at all times;
• staying informed of all Product updates and alerts and implementing all updates and fixes; and
• all other factors affecting the Products that are outside of the direct control of Rockwell Automation.
Reproduction of the contents of the Documentation, in whole or in part, without written permission of Rockwell Automation is
prohibited.
Throughout this manual we use the following notes to make you aware of safety considerations:
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the drive to alert people that dangerous voltage may be present.
Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures.
Studio 5000 Logix Designer®: Basics Lab
Contents
Before you begin ........................................................................................................................................... 5
Section 4: Downloading the Project from the Computer to the Controller ................................................. 54
Objective: ........................................................................................................................................................................................ 54
Downloading the Project to the Controller ...................................................................................................................................... 55
3 of 110
Section 6: Adding Logic and Tags Online .................................................................................................. 62
Objective: ........................................................................................................................................................................................ 62
Adding a MOV Instruction to the Logic ........................................................................................................................................... 62
Adding the Timer to the Logic ......................................................................................................................................................... 65
Testing Your Logic .......................................................................................................................................................................... 70
Section 8: (Optional) Creating and Using User Defined Types (UDT) ...................................................... 77
Objective: ........................................................................................................................................................................................ 77
Creating User Defined Types.......................................................................................................................................................... 77
Add the UDT tag to an instruction ................................................................................................................................................... 81
Monitoring UDT Tags ...................................................................................................................................................................... 84
4 of 110
Before you begin
Tip Text – The text inside this gray box is supplemental information. This text can include FYIs, useful tips,
and other related information
5 of 110
About Studio 5000 Logix Designer
Studio 5000 software includes the Logix Designer application for the programming and configuration of Allen-Bradley
ControlLogix and CompactLogix programmable automation controllers. Logix Designer is the progression of RSLogix 5000
software, and will continue to be the package you use to program Logix5000 controllers for discrete, process, batch, motion,
safety, and drive-based systems. Logix Designer offers an easy-to-use, IEC61131-3 compliant interface, symbolic programming
with structures and arrays and a comprehensive instruction set that serves many types of applications. It provides ladder logic,
structured text, function block diagram and sequential function chart editors for program development as well as support for the
S88 equipment phase state model for batch and machine control applications.
CompactLogix brings together the benefits of the Logix platform — common programming environment, common networks,
common control engine — in a small footprint with high performance. The CompactLogix platform is perfect for tackling smaller,
machine-level control applications, with or without integrated motion, with unprecedented power and scalability. CompactLogix is
ideal for systems that require standalone and system level control over EtherNet/IP, ControlNet, or DeviceNet. Think
CompactLogix when you need economical, reliable control.
6 of 110
About Logix Controllers
ControlLogix controllers support intensive process applications and provide fast processing of motion instructions in a single
integrated solution.
ControlLogix provides modular network communications that let you purchase only what you need. Interface using ControlLogix
communication modules via a ControlLogix gateway, without the need for a processor in the gateway chassis, or interface
directly to a ControlLogix controller.
The ControlLogix solution also provides time synchronization capabilities, which is particularly useful in first fault and process
sequencing applications.
7 of 110
Section 1: Creating a Project
Tip Text – The text inside this gray box is supplemental information. This text can include FYIs, useful tips,
and other related information
Objective:
Create a new project
Write ladder logic
Use symbolic tag names
Use the tag monitor/editor
1. Double-click on the Studio 5000 icon on the Desktop to launch Studio 5000 software
Tip - To see what versions of Studio 5000 you have installed on your computer, select About under the
Explore section.
8 of 110
Creating a New Controller Project
In this portion of the lab, you will create an offline project using a CompactLogix controller.
3. When the New Project pop-up is displayed, select Logix and type ‘1769-L36ERM’ in the Search field.
Be sure to choose the correct controller type and revision that matches the equipment at your lab station. Not
choosing correctly will prevent the application from downloading later in the lab
FYI – A name is required. This names both the controller and the default ACD file name. An ACD file is the
file the project is stored in. In this case, the file name is “Intro_Lab_Control_Project.ACD”
9 of 110
6. When the Project Configuration window appears, fill it in as follows:
Select V28
Select No Protection
Add a project description ‘Logix Basics Lab’
Click Finish
The Logix family of controllers in this lab all use Studio 5000 Logix Designer software to configure the
system, but each controller type is set up slightly differently. For example, ControlLogix has more settings
than CompactLogix.
From the New Project window the following fields are being defined for the project.
Controller Type: This is the type of Logix controller you will use. This could be a ControlLogix,
CompactLogix, or SoftLogix controller. Only one programming software package is needed for all Logix
Controllers.
Name: The name of the controller and project.
Revision: Here you are selecting the firmware revision of the project that will be created.
Chassis Type: Select the size of the chassis you will use. This is not applicable for all controller types.
Slot: The slot number where the controller will reside. Some controller types will not require a slot number.
For example, CompactLogix is fixed at slot zero.
Security Authority: Optional, the security server to use for project security.
10 of 110
The Organizer Window appears on the left side of the Studio 5000 window, with a folder called Controller
Intro_Lab_Control_Project. At this time, there is no I/O, tag database, or logic associated with the controller.
We will be adding these later. The following picture points out the various areas.
Controller
Faceplate
Tasks, Programs,
Instructions
and Routines
toolbar
I/O Configuration
Programming
area
Controller Organizer and
Logical Organizer Tabs
The Controller Organizer is a graphical representation of the contents of your controller file. This display
consists of a tree of folders and files that contain all of the information about the programs and data in the
current controller file. The default main folders in this tree are:
- Controller File Name
- Tasks
- Motion Groups
- Add-On Instructions
- Data Types
- Trends
- I/O Configuration
*NOTE: The square containing a ‘+’ or ‘-‘ indicates whether a folder is open or closed. Click on it to expand
or collapse items in the tree display.
11 of 110
The Logical Organizer – This a recent feature of Logix Designer. The Logical Organizer allows code to be
grouped and organized by purpose, instead of by task execution. The code can be organize in a way to
make understanding and troubleshooting the end machine or application easier and faster! This also gives
greater documentation directly inside the Logix Designer application! We’ll cover this more later in the lab.
12 of 110
Adding Ladder Logic to the Main Routine
In this section of the lab you will add code for a simple motor start/stop seal-in circuit. You will experience the ease of
programming with Studio 5000 software. During the labs we will only utilize ladder logic programming, but Logix controllers also
can be programmed using Function Block, Sequential Function Charts, and Structured Text. This allows selection of the
programming language that best fits an application.
1. In the Controller Organizer expand the MainProgram folder by clicking on the +. Once expanded, the
MainProgram will appear as shown below:
13 of 110
2. Double-click the MainRoutine icon and maximize the ladder window if it is not maximized.
This will open the routine editor. An empty rung will already exist as shown below: The red color of the rung and the circled “x”
next to the rung indicate the rung is incomplete.
3. From the instruction toolbar, left click and hold on the Examine On (XIC) instruction.
4. Drag the XIC onto rung 0 until the green dot appears as shown above. Release the mouse button at the location
you wish to place your instruction.
14 of 110
Verify your rung appears like the figure below:
5. From the instruction toolbar left click and hold on the Examine Off (XIO) instruction.
6. Drag the XIO onto rung 0 to the right of the XIC instruction as shown above. Again a green dot will appear to the
right of the XIC instruction indicating where your new instruction will be inserted. Release the mouse button at
the location you wish to place your instruction.
FYI - If you place an instruction in the wrong location on a rung, simply click and hold on the instruction and
drag it to the correct location.
15 of 110
7. From the instruction toolbar, left click and hold on the Output Energize (OTE) instruction.
8. Drag the OTE onto rung 0 to the right of the XIO instruction as shown above. Again a green dot will appear to the
right of the XIO instruction indicating where the OTE instruction will be inserted. Release the mouse button at the
location you wish to insert the instruction.
16 of 110
We will now add a branch around the XIC instruction.
17 of 110
11. Left-click and hold on the blue highlighted part of the branch and drag your selected leg of the branch to the
left side of the XIC instruction.
12. Place the branch over the green dot and release the mouse button.
13. From the instruction toolbar, left click and hold on the XIC instruction.
14. Drag the XIC onto your newly created branch until the green dot appears and release the mouse button.
18 of 110
Verify that the entire rung appears like the figure below. If it does not, use what you have learned to make it match.
15. Save the program by clicking on the Save icon on the toolbar. This will save the program in the default
directory, which is C:\Users\LabUser\Documents\
As you can see the free form editing in Studio 5000 can help speed development. You do not have to place
an instruction and tie an address to it before you add the next instruction.
19 of 110
Creating Tags for the Ladder Code
In this section of the lab you will create the tags needed for the program. In older traditional PLCs, a physical memory address
identifies each item of data, for example N7:0. In Logix controllers, there is no fixed numeric format. Tags are used instead and
can be given any name.
Continue to use the project already open. We will create 3 tags for the program: Motor_Start, Motor_Stop, and Motor_Run.
1. First create the tag Motor_Start. To do this, right click on the ? of the first XIC instruction. It will be highlighted
blue. Select New Tag.
20 of 110
A New Program Parameter or Tag window will appear.
Creating a Tag - When you create a tag there are several attributes for a tag. The main attributes we are
interested in for this lab are as follows:
Usage: Defines a Local Tag or a Parameter Tag. We will use Local.
Type: Defines how the tag operates within the project
Base: Stores a value or values for use by logic within a project
Alias: A tag that represents another tag
Produced: Send data to another controller
Consumed: Receive data from another controller
Alias For: Only applies when the tag “type” is Alias. Defines the tag which the alias tag will reference.
Data Type: Defines the type of data that the tag stores. Example: Boolean, Integer, Real, String, etc.
Parameter Connection: Shows and allows selection of the parameter connected to this tag.
Scope: Defines how the data is accessed in the project. It is either controller scoped, global data
accessible throughout the controller or program scoped, data accessible for a specific program.
External Access: Defines the access external applications (HMIs) will have with the tag.
Read/Write: External application can read and write to the tag.
Read Only: External application can only read the tag.
None: External application cannot read the tag or write to the tag
Style: Display the tag value has Binary, Octal, Decimal, or Hex.
Constant: If checked, that tag cannot be changed programmatically.
Sequence: Allows Equipment Phase input/output tags to be used with FactoryTalk Batch Server.
Open Configuration: Opens the configuration wizard for complex tags (MSGs, PIDs, etc)
Open Parameter Connection: Opens the Connection Configuration window.
21 of 110
2. Enter the name “Motor_Start” and fill in the remaining fields as shown below.
Make sure the scope of the tag is MainProgram.
22 of 110
4. Right click on the “?” of the XIO instruction and select New Tag.
23 of 110
Verify the rung appears like the figure below:
7. Right click on the ? of the OTE instruction and select New Tag.
24 of 110
9. Click Create to accept and create the tag.
Your rung should now appear as shown below:
For the XIC instruction in the branch we do not have to create a tag. You will use the tag Motor_Run.
10. Left click and hold the mouse button over the tag Motor_Run on the OTE instruction.
11. Drag the Motor_Run tag to the XIC instruction until a green dot appears next to the “?” and release the mouse
button.
25 of 110
The rung should now appear as shown below. Notice the “X” next to rung zero has disappeared and that the rung color is now
blue. This indicates that the rung passes auto verification and no errors are present.
Studio 5000 software verifies each rung automatically to make programming easier!
12. Prior to verifying the project, open the error window by going to the View menu and choosing Errors.
26 of 110
13. Verify the program by clicking on the Verify Controller icon on the toolbar.
You will see if there are any errors in the status window.
This is useful to locate errors or incomplete rungs in larger projects that may have hundreds or thousands of
rungs!
27 of 110
14. Close the MainRoutine by clicking the “X” located at the top right corner of the screen.
16. Save the program by clicking on the Save icon on the toolbar.
The tag database of Logix versus a traditional PLC’s fixed memory addresses help you create self-
documenting code. This means you do not have to use address descriptions or symbols to make code easy
to read.
28 of 110
Monitoring/Editing Tags
In this section of the lab, we will review the Tag Monitor/Editor in Studio 5000. The concept of Controller, Parameter, and
Program Local tags will be covered.
29 of 110
The tag Monitor/Editor window appears. Notice in the lower left corner of the window two tabs labeled Monitor Tags and Edit
Tags as shown below.
30 of 110
Notice that there are no tags present even though you just created three tags. These tags were created at the Program
Scope.
Notice a field in the upper left corner of the Tag Editor window labeled Scope. Earlier in the lab we talked
briefly about Controller and Program scoped tags. Currently the selection is Intro_Lab_Control_Project,
which will show controller scoped tags.
31 of 110
Data scope defines where you can access tags.
Controller-scoped tags are accessible by all programs. Parameters and Local Tags are accessible only by
the code within a specific program; Isolate portions of a machine or different stations into separate programs.
This lets you do the following:
- Provide isolation between programs and equipment phases
- Prevent tag name collisions
- Improve the ability to reuse code
Data Scoping
When you create a tag, you define it either as a controller tag (global data) or a program tag for a specific
program (local data).
Local tags are isolated from other programs. Routines cannot access the Local tags of another program.
Thus you can re-use Local tag names across multiple programs.
32 of 110
3. Click on the down arrow for the Scope selection box.
The Tag Editor now has switched views to the program level and you see the tags you created earlier.
5. Close the Tag Editor by pressing the “X” located at the top right corner of the tag editor.
33 of 110
Section 2: Configuring I/O
We will now configure I/O for the project. To communicate with I/O modules you must add modules to the I/O Configuration
folder (also referred to as the I/O tree).
Objective:
This part of the lab covers adding 1769 I/O using the equipment at your lab station. For this lab we will add the following I/O
modules for your lab station.
34 of 110
Adding CompactLogix I/O
You will continue to use the project already open.
7. In the I/O Configuration Folder, right click on 1769 Bus and select New Module.
8. The Select Module Type window appears. Type “IQ6” in the search box.
35 of 110
9. Select the 1769-IQ6XOW4 module and click Create
36 of 110
10. The new module window appears. Enter the Name Digital_Card_1 and Slot 1 parameters as shown below.
11. Click on the Change... Button and change the Series to A. Notice the revision changes to 1. Click OK.
Note: Some of the demos have series B modules. Compatible module keying will allow earlier profile version to work with
newer modules.
12. Click YES on the Change Module Definition Warning that pops up.
37 of 110
13. The properties window should now appear as follows.
Electronic Keying – Keying determines what checks are performed between the controller configured I/O tree
and the module before an I/O connection is made. This helps guard against improper operation by verifying
the hardware matches with what is configured.
The following data is read and compared:
Vendor, Product Type, Catalog Number, Major Revision, Minor Revision.
The user may select one of the following module keying options during the initial module configuration:
- Exact Match – All of the parameters described above must match or the inserted module will reject the
connection.
- Compatible Module – The module determines if the settings are compatible. Generally, the IO module
checks the Module Type, Catalog Number, and verifies the revision of the hardware is equal to or
greater than that configured.
- Disable Keying – No keying used at all. This is not typically used.
Connection -- Input only modules use “Data”. Modules that include outputs use “Output”.
Data Format -- Determines the data structure for the tags that are associated with the module. With the
modules in this lab, the format is integer.
38 of 110
14. Click on the Connection tab to observe the Requested Packet Interval data. We will leave the default at 20
milliseconds.
16. In the Select Module Type window, type in “IF4” into the filter box and select the 1769-IF4XOF2 module.
Note: Do not select the module with “F” at the end, I.E. do not select 1769-IF4XOF2F (which is shown above as
1769-IF4FXO....). This is a different module then shown in the rack and will give a mismatch error if
selected. If this module is selected, it will need to be deleted to put in correct module.
39 of 110
17. Click on Create. The new module window appears.
40 of 110
21. Click on the Output Configuration tab.
23. Click OK
41 of 110
Viewing the CompactLogix I/O Tags
Now that we have configured I/O modules in the project, let’s take a look how that information is presented in Studio 5000.
Notice by looking in the upper left corner of the tag editor that Controller Scope is selected. All I/O module tags are created in the
Controller Scope. Modules that reside within the controller chassis are called “Local”.
42 of 110
FYI - I/O Address Format
43 of 110
The above entries are tag structures for the modules you added. They contain more tags than are actually
displayed. Note the + sign next to the tag name, this indicates that you can expand the tag structure to see
more information.
27. Expand and explore the tags for the I/O modules by clicking the +.
• :C - Configuration tags hold the module configuration and are designated by a “:C” in the tag name.
• :I - Input tags have “:I” in the tag name.
• :O - Output tags have a “:O” in the name.
28. Save the program by clicking the Save icon in the toolbar.
Aliasing
An Alias tag lets you create one tag that represents another tag.
Both tags share the same value
When the value of one of the tags changes, the other tag reflects the change
Use Aliases in the following situations:
-Program logic in advance of wiring diagrams
-Assign a descriptive name to an I/O device
-Provide a simpler name for a complex tag
-Use a descriptive name for an element of an array
44 of 110
29. From the Controller Organizer double click on MainRoutine.
In the last part of the lab we added I/O modules to the project. Now it’s time to Alias the tags in the program to the I/O Modules.
This will connect the ladder logic to real world I/O points. All three Motor tags will be aliased to points on the 1769-IQ6XOW4
module.
30. Right click on the tag Motor_Start and select Edit ‘Motor_Start’ Properties.
45 of 110
The Tag Properties window for Motor_Start will appear. Currently the tag is defined as a Base tag.
31. Select Alias as a type and notice that the Tag Properties window changed.
46 of 110
33. Uncheck the Show Program tags checkbox to deselect Program Scoped Tags.
The view on the screen will change to view only your Controller Scoped Tags
47 of 110
When you select 0 from the tag browser the window will close. Tag Properties will now appear as follows:
Motor_Start will now be aliased to Local:1:I.Data.0, which is the first input point on the 1769-IQ6XOW4 module.
37. Click OK to close and apply the changes to the tag Motor_Start.
Motor_Start has been Aliased to Local:1:I.Data.0. This means that the tags are equivalent to one another in code. It is much
easier to understand Motor_Start than Local:1:I.Data.0.
38. Using the previous steps, alias the remaining two tags.
Motor_Stop = Local:1:I.Data.1
Motor_Run = Local:1:O.Data.0
48 of 110
39. When you are finished the ladder code should appear as follows:
40. Save the program by clicking on the Save icon on the toolbar.
49 of 110
Section 3: Connecting Your Computer to the Controller
Objective:
In this lab, we will learn to configure a driver in RSLinx Classic communications software. We will complete the following steps:
Launch RSLinx Classic communications software
Configure a communications driver
1. Double click on the RSLinx icon on the Desktop to launch RSLinx software to bring up the RSLinx Classic
Gateway window.
The Configure Drivers dialog appears. There may already be a driver configured on this lab. However, we are going to create a
new driver. RSLinx Classic allows multiple drivers to be used.
50 of 110
3. From the Available Driver Types pull-down menu, choose EtherNet/IP Driver then click on the Add New
button.
4. Change the name of the driver from AB_ETHIP-1 (or AB_ETHIP-2) to AB_ETHIP-LAB as shown and click OK
5. Choose “Browse Local Subnet” and the “Intel” network driver as shown. Click OK.
51 of 110
6. Exit the Configure Driver Dialog by clicking on OK.
FYI - In RSLinx you will notice two different Ethernet drivers listed: EtherNet/IP Driver and Ethernet
devices. In general, you should use the newer EtherNet/IP driver. It will automatically scan for any
EtherNet/IP compatible devices on the network. A few older Rockwell Ethernet products cannot be found
using this driver. The older Ethernet devices driver works with all Rockwell Ethernet products, but it will only
scan for IP addresses that you manually tell it to search for. You can have both types of drivers and/or
multiple instances of each type active in RSLinx at the same time if needed.
7. If no drivers are shown the software background is grey, click the RSWho icon in the toolbar. Otherwise
move on to the next step.
52 of 110
The Rockwell Software RSLinx Gateway - [RSWho - 1] screen appears.
8. Expand the AB_ETHIP-LAB, Ethernet driver to see the Ethernet module with IP 192.168.1.7
This is the RSLinx driver we will use in Studio 5000 Logix Designer to download to the Logix controller in the next section.
FYI - RSWho
The RSWho screen is actually a RSLinx network browser interface, which allows you to view all of your
active network connections.
The left pane of this display is the Tree Control, which shows networks and devices in a hierarchical view.
When a network or device is collapsed, as indicated by the + sign, you can click on the + sign or double click
on the network or device icon to expand the view and begin browsing. When a network or device is
expanded, as indicated by the - sign, you can click on the - sign or double click on the network or device icon
to collapse the view.
The right pane of the RSWho display is the List Control, which is a graphical representation of all of the
devices present on a selected network.
53 of 110
Section 4: Downloading the Project from the Computer to the Controller
Objective:
Power supply
1769-L36ERM
CompactLogix
Controller
Built in DLR
Ethernet ports
(5370 series
controllers) Analog input and
output
1769-IF4XOF2
1769-IQ6XOW4 Combination Analog
Combination Digital Input Input/Output Module
Output Module
54 of 110
Downloading the Project to the Controller
In this section of the lab you will download the project.
55 of 110
3. Expand the AB_ETHIP-LAB driver and select the 1769-L36ERM controller by clicking on it.
4. Click Download. You will be asked to verify the download. Click Download again.
The project will then begin to download to your controller.
56 of 110
If your controller was in the RUN mode prior to the download, you may be prompted to return to the RUN
mode. If asked select YES.
5. When the following prompt appears, click Yes to change the controller mode to Remote Run.
At this point you will be online with the controller and the status LEDs on the controller faceplate in your project will mimic the
LEDs on your controller. In this case the green color represent run mode. Blue would signify program mode. Grey means not
connected to a controller.
57 of 110
Section 5: Testing Your Logic Program
Objective:
I/O Mapping
For the lab there are a group of push buttons on the Demo Box. The push buttons are mapped as follows:
Motor_Start = DI0
Motor_Stop = DI1
Motor_Run = DO0
Switching the Controller into Run Mode and Testing the Program
1. If not already in run mode, click the Controller Faceplate and select Run Mode.
58 of 110
The controller will go into run mode. This can be verified by looking at the Run LED on the controller. It should now illuminate
green. It can also be verified through Studio 5000 by viewing the controller faceplate.
2. From the Controller Organizer expand the MainProgram by clicking on the “+”.
You will now see the ladder logic. Notice the green power rails on both sides of the ladder. This indicates you are online and the
routine is executing.
59 of 110
Notice that the XIO instruction Motor_Stop is green. This means that this instruction is in the ‘true’ or ‘on’ state. This is because
the Motor_Stop Pushbutton is not pressed.
This correlates to the XIO instruction for Motor_Stop. Notice the instruction is no longer green because the instruction is no
longer true.
60 of 110
6. Verify that output DO0 (Motor_Run) stays illuminated when you release pushbutton DI0 (Motor_Start).
The ladder logic you have just written is a simple 3-wire control or motor start/stop seal-in circuit.
7. Press pushbutton DI1 (Motor_Stop) and verify that output DO0 (Motor_Run) turns off.
61 of 110
Section 6: Adding Logic and Tags Online
Objective:
In this lab we will explore online editing. You will:
Add a MOV instruction
Add a timer to the logic and its execution will be based on the motor running
Add ladder logic to reset the timer when the motor is stopped.
62 of 110
3. Use the scroll buttons if necessary to scroll to the Move/Logical instruction group tab in the instruction toolbar.
Under the Move/Logical category tab, click and drag a MOV instruction to the new rung.
4. Double click the ‘?’ by the source in the MOV instruction and select Local:2:I.Ch0Data by double-clicking the tag.
You might have to scroll down to find the Channel data tags.
63 of 110
5. Double click the ‘?’ by the destination. Select Local:2:O.Ch0Data by double-clicking the tag.
64 of 110
Adding a Timer to the Logic
7. Select rung 0. Right click in the blue highlighted area to the left of rung zero and select Start Pending Rung
Edits.
The rung with the lower case ‘i’s on the power rails is the rung you will perform the edits on.
65 of 110
9. From the Instruction Toolbar click on the Timer/Counter tab, click the Timer On (TON) icon
A timer is inserted into the code to the right of the OTE instruction.
In Studio 5000 Logix Designer you can string output instructions together in series. Branches are not
required.
66 of 110
10. On the timer instruction right click in the blue area next to the word Timer and select New Tag.
The New Tag window appears. Notice that the Data Type is already set to TIMER. This is because you are creating a tag in the
timer instruction.
67 of 110
12. Verify that the tag has been created in the timer instruction as shown below:
13. Double-click on the 0 in the timer instruction next to the word Preset.
In Logix the Timer Preset is a 32-bit DINT which means the maximum value for your timers can be:
2,147,483,647
15. Press Enter. The TON instruction should now appear as shown below.
The Preset value is now 32767 milliseconds (= 32.767 seconds). Leave the accumulated value set to zero. You are now ready
to verify the edits you made.
68 of 110
16. Click on the Finalize All Edits icon
69 of 110
The ladder editor will now appear as follows:
19. Verify that DO0 (Motor_Run) illuminates and the Timer instruction starts incrementing.
21. Verify that DO0 turns off and the Timer resets.
70 of 110
Section 7: Creating and Running a Trend
Objective:
In this lab we will explore the built-in trending capabilities of Studio 5000.
This will be done online with the program from the previous Lab.
Trending
Basic Trending in Studio 5000 allows you to view data sampled over a time period in a graphical display.
Data is sampled at a periodic rate that is configurable from 10 milliseconds to 30 minutes. Studio 5000 will
allow you to create a trend and save it as part of your project file.
Basic Trending has these constraints: you can trend data elements of type BOOL, SINT, INT, DINT, and
REAL, you are limited to sampling eight unique data elements in a single trend.
1. From the Controller Organizer, right click on Trends and select New Trend.
71 of 110
2. In the Name field enter ‘My_Trend’’.
3. Click Next.
The New Trend Add/Configure Tags window appears.
This will allow the trend to monitor the input from AI0
72 of 110
5. Let’s also trend the timer accumulator value. The timer the tag was created in the Program Scope, so we must
select the MainProgram tags as shown below:
7. Select Timer.ACC and then click the Add button. This will add the tag Timer.ACC to the Tags To Trend list.
73 of 110
8. Click on Finish.
The Trend window will now appear.
9. Right click on the Trend graph background and select Chart Properties.
74 of 110
10. Click on the X-Axis tab.
11. Change the Chart time range - Time span from Second(s) to Minute(s).
13. Start the trend by clicking on the RUN button located toward the upper left of the Trend dialog box.
75 of 110
14. Press the DI1 pushbutton then push the DI0 and watch the trend capture the data of the Timer.ACC.
15. Try turning the AI0 input and verify that you see the trend recording the input:
By default, each tag will be independently scaled to its observed min/max values. If desired, the scaling
options can be changed under the chart properties - Y axis tab.
There are also other options in the trend properties such as a start and stop trigger and pen colors.
16. When you are finished investigating the trend, click Stop and close the trend window.
76 of 110
Section 8: (Optional) Creating and Using User Defined Types (UDT)
Objective:
This lab section covers creating and using custom data structures.
Create a User Defined Type (UDT)
Create a tag from a UDT
Use the tag in an instruction
Use the tag monitor/editor to see the tag
1. Right click DataTypes in the Controller Organizer and select New Data Type…..
77 of 110
A new Data Type window will appear.
3. Fill in the description field with “Holds gallons and the equivalent in liters” as shown.
78 of 110
5. Double click the Data Type field on the same row and type in REAL
6. Follow the same steps to enter the next row for “Liters” and REAL as shown.
7. Click Apply.
79 of 110
9. Double click on Parameters and Local Tags under the MainProgram as shown to open the tag window.
11. On the blank row, fill in “Gallons_to_Liters” for the tag Name.
12. On the same row, select “Gallons_to_Liters” for the Data Type as shown and click OK.
13. Click on a different row or tag to make sure the tag is accepted. The data type column for the Gallons_to_Liters
tag will turn grey when it is accepted.
80 of 110
Add the UDT tag to an instruction
15. Make sure the End rung is highlighted. Click on the insert rung icon to create a new rung.
16. Find the Compute/Math tab on the instruction tool bar and click on the MUL instruction.
81 of 110
17. Double click on the “?” in the Source A field of the MUL (multiply) instruction and select the
Gallons_to_Liters.Gallons tag.
Note: the Gallons_to_Liters tag will need to be expanded to select the Gallons member.
18. Fill in ‘3.785’ for source B (the conversion constant to convert gallons to liters).
19. Double click on the “?” in the destination field and select the Gallons_to_Liters.Liters tag as shown.
82 of 110
20. Click on the finalize edits button and click on Yes to accept the changes.
Notice that the values of the tags are shown on the instruction. The multiply instruction converts the number in gallons to
liters.
21. Click on the number 0 just below gallons, type “34” or any desired value, and press enter. Notice that the Liters
value updates automatically.
83 of 110
Monitoring UDT Tags
22. Double click the Parameters and Local Tags under the MainProgram and expand the Gallons_to_Liters tag.
Notice the values are also shown here. Make sure to select the Monitor Tags tab.
23. The values for gallons can be modified directly in the monitor screen by changing the value in the Value column.
Change the gallons value and watch that liters updates to corresponding value.
The UDT allows associated data to be stored under a single main tag instead of using completely separate
tags. This makes it easier to keep track of data and keep it more organized. The UDT name itself can
document what the data is for.
84 of 110
Section 9: (Optional) Using Periodic Tasks
Objective:
In this lab, we will learn to add and configure a periodic task and add a program and routine with some logic. This will also be
done while online with the controller. It will be shown that multiple tasks are running.
1. In the Controller Organizer, right click on Tasks and select New Task.
The New Task window appears. In this window we can configure the properties of a task.
85 of 110
2. Fill in the Window as shown.
Name – ‘My_Periodic_Task_50ms’.
Type - Periodic.
Period – ‘50.000’ ms
3. Click OK.
Logix controllers have three task types: Continuous, Periodic, and Event.
Continuous – Runs at the lowest priority of any task and can be interrupted by other tasks. The continuous
task is designated by a folder with a circular arrow. There can be a maximum of 1
continuous task.
Periodic – Executes at regular intervals and can be assigned different priorities. It is designated by a circular
blue clock symbol. There can be multiple periodic tasks.
Event – Triggers on specific events. This allows code to execute as quickly as possible
when some event happens. For example, a counting instruction can quickly be executed whenever a
photeye turns on to get an accurate count of parts.
4. Right click on the My_Periodic_Task_50ms folder, select Add and then select New Program….
86 of 110
Tasks are divided into programs. Whenever a new task is added, a new program also needs to be created.
Multiple programs are allowed in each task, and the programs execute in order one at a time whenever the
task executes. Programs allow the code in a task to be visually organized in large applications.
7. Right click on the My_Push_Buttons_Program folder and select Add and New Routine.
Routines are where the code resides. Different kinds of language routines can be created. The Logix
platform supports Ladder, Function Block Diagram, Structured Text, and Sequential Function Chart as the
types of routines that can be created.
87 of 110
8. Fill in the window as shown.
Name – ‘My_Push_Buttons_Routine’
Description – ‘<Any desired description.>’
Type – Ladder Diagram
In Program or Phase –My_Push_Buttons_Program.
Assignment – None.
9. Click OK.
88 of 110
10. Right click on My_Push_Buttons_Program folder and select Properties.
89 of 110
The controller organizer should look like the following with an “I” indicating the main routine. There is only one main routine for
each program. Only the main routine runs by default. If no routine is select as the main routine, then no routines will execute.
JSR (Jump To Subroutine) instructions are used to call other routines.
14. Double click on the My_Push_Buttons_Routine to open the routine. It should look like the following.
15. Create the following two rungs using the lessons previously learned. Use input point 2 to drive output 2 and
input point 3 to drive output 3 as shown.
90 of 110
16. Click on the Finalize All Edits in Program button -> Yes to accept the changes.
17. Try pushing the DI2 and DI3 buttons. They should light up while pressed.
Notice that the motor start and stop buttons still work as they did before. This demonstrates that both
programs are running! The controller is running two tasks, one as “continuous”, and another as a 50ms
periodic task.
Note: Notice the ability to make many kinds of changes while the controller is running and controlling.
We did these changes while online with a ‘live’ controller that was currently controlling our ‘machine’.
91 of 110
Section 10: (Optional) Creating an AOI (Add On Instruction)
Objective:
In this lab, an AOI instruction will be added to the project. AOI’s cannot be created or modified online (although they can be
imported online). The AOI will be created offline, code added, and downloaded to the controller to see it execute.
1. In the Logix Designer window, click the save icon -> yes to save the project and tag values, then Go Offline.
2. In the Controller Organizer, right click on Add-On Instructions folder and select New Add-On Instruction.
92 of 110
The New Add-On Instruction window appears.
4. Click OK.
The Add-On Instruction Definition window appears. In this window we can configure the properties of the AOI.
The Parameters tab is where the inputs and outputs of the instruction are defined.
The Local Tags tab contain tags that are only used by the AOI for internal storage.
93 of 110
6. Fill in the following two parameters as shown below.
My_Signal_Input -- Input -- BOOL -- check Required (Req).
My_Signal_Output -- Output -- BOOL -- check Required (Req).
The required checkbox indicates a tag will need to be filled in on the instruction.
The usage INPUT means the AOI will operate on a copy of the tags data. OUTPUT means the AOI will copy the result
to the tag. There is also an INOUT usage, this passes tag by reference, and the tag is read from and written to directly
while the AOI executes.
7. Click Apply.
94 of 110
9. Add an XIC instruction with the tag My_Signal_Input and add two timers to a rung. The rung should appear as
follows.
10. Enter the tag name ‘Timer1’ into the first timer.
11. Right click on Timer1 and select New Local Tag ‘Timer1’ as shown
12. Click OK on the New Add-On Instruction Parameter or Local Tag window that appears.
95 of 110
13. For Timer1, set the Preset to 500 and the Accum to 0 as shown
14. Now add Timer2 to the remaining TON instruction and create it as a local tag as well.
16. Also add an XIO instruction of Timer2.DN as shown after the XIC My_Signal_Input instruction.
17. Add a second rung with an XIC of Timer1.DN and an OTE instruction of My_Signal_Output as shown.
We have finished creating the AOI definition and logic! We will now add the AOI into the program to have
it flash a light.
96 of 110
AOI’s allow logic to be embedded into a single instruction. This allows new custom instructions to be tailored to the
specific application. This also allows code to be easily reused between applications since AOI’s can be imported and
exported.
19. Click and drag the My_Signal_Light Instruction folder from the tree to the rung as indicated by the next two
pictures.
97 of 110
20. Enter ‘My_Signal_Light_Tag’ into the My_Signal_Light field.
The local tag being created is called the AOI’s backing tag. This is the tag the AOI uses to store its status and local tag
values.
98 of 110
23. Add Local:1:I.Data.4 as the input tag, and Local:1:O.Data.1 as the output tag
25. Toggle the DI4 input switch and watch what happens to the DO1 light.
Every time the DI4 input switch is on (turned right), the DO1 light blinks at a 500 millisecond rate.
AOI’s allow code to be encapsulated into a single instruction. This allows common code and functionality to be clearly
defined and easily reused. The AOI can be reused as many times as desired. Each AOI should typically have a unique
backing tag.
Congratulations! You have Completed Section 10. Please move on to Section 11.
99 of 110
Section 11: (Optional) Using Logical Organizer
Objective:
The Logical Organizer will be used in this lab to group the code to model the demo box. This will demonstrate how the Logical
Organizer can be used to group code regardless of the layout of the Controller Organizer. In this case, we will model it after our
machine, the demo box. The Logical Organizer allows programs to be grouped in any manner desired, but grouping them by
machine physical or logical function is typical.
By default, all of the programs in the Controller Organizer are shown as an ungrouped list. Only the programs, and not the
tasks, are shown. We can use the organizer to group the programs. We will typically use a “folder” object to group the
programs.
100 of 110
2. To add a new folder, right click on the Logical Model folder -> Add -> New Folder
Notice that we can also add programs here as well as in the Controller Organizer. If we add a program here, the configure
window will allow us to pick which Controller organizer task the program is scheduled in.
4. Click and drag the MainProgram onto My_Demo_Box so that the MainProgram is grouped under the
My_Demo_Box folder.
101 of 110
5. Do the same for My_Push_Buttons_Program to associate with My_Demo_Box.
Notice that the two programs we are using to run the demo box are now grouped together. Anyone looking at the Logical
Organizer will have a better idea that both programs are being used to run the demo box.
6. Click on the Controller Organizer and notice that the programs and tasks haven’t changed.
Notice that the two programs we are using to run the demo box are now grouped together. Anyone looking at
the Logical Organizer will have a better idea that both program are being used to run the demo box. In
general, the organizer is used to group the program code to model the physical or logical application.
Congratulations! You have Completed Section 11. Please move on to Section 12.
102 of 110
Section 12: (Optional) Using Studio 5000 Help
Objective:
In this lab we will explore the extensive online Help system in Studio 5000. Feel free to look and poke around as desired.
Instruction Help
103 of 110
The following window will appear.
2. Click on the instruction links on the left (for example, Alarm Instructions), then click on an instruction icon to
locate its description, details about its parameters, and related instructions along with examples on how to use
the instruction.
Alternately, pressing the F1 key while an actual instruction in ladder code is highlighted will also bring up the
help for that instruction.
104 of 110
Viewing I/O Module Wiring Diagrams
6. Select a topic to display from the list such as, Wiring Diagram.
105 of 110
7. Click Display to view the wiring diagram for this module. Note you may need to maximize your screen.
8. When you are finished viewing the wiring diagram close the display window.
106 of 110
Using Start Pages
9. From the Help pull down menu select Quick Start which is one of the three tabs available from the Start
Page.
Organizes various resources intended to accelerate the customer’s ability to use the software and to locate relevant
information
Provides Getting Started and My First Project media clips and tutorials to assist new users
Provides easy navigation to Studio 5000 sample projects Rockwell Automation specific and those involving other vendors
107 of 110
Learning Center Tab
Targets customers wanting to learn or explore how to use the software beyond just getting started reduces learning curve
and helps increase productivity.
108 of 110
Resource Center Tab
Targets a customer looking for additional information or support
Provides links to download sites for software, firmware, EDS files, etc.
Provides links to Support sites Knowledgebase, Technical Bulletins, Sample Code
Provides links to Online books installed to the PC with Studio 5000.
109 of 110
Copyright© 2015 Rockwell Automation, Inc. All rights reserved.