Shear Strength of RC Jacketed Interior Beam-Column Joints Without Horizontal Shear Reinforcement
Shear Strength of RC Jacketed Interior Beam-Column Joints Without Horizontal Shear Reinforcement
Shear Strength of RC Jacketed Interior Beam-Column Joints Without Horizontal Shear Reinforcement
The interior joint shear strength of nonductile frames strengthened RESEARCH SIGNIFICANCE
with reinforced concrete (RC) jackets, but with no new joint shear RC jacketing without dowel anchors between the new and
hoops and no dowel anchors installed into the new and old old concrete interface, which is different from the conventional
concrete interface, was investigated experimentally. Seven one- construction method, was adopted to retrofit beam-column
way interior beam-column joint subassemblages were tested under joints with no horizontal joint shear reinforcement.
quasistatic cyclic loading to observe the joint shear strength and
Experimental tests were performed to observe the seismic
overall frame performance. The test measurements are also used to
verify two of the analytical models used for predicting the horizontal
behavior of the jacketed frames. Relative slip that occurred
shear strength of jacketed joints without horizontal joint shear between the new and old concrete in the joint area was
reinforcement. The results show that the RC jacketed scheme is measured to evaluate its influence on the overall seismic
able to efficiently rehabilitate nonductile frames with very poor performance of the jacketed frames. The other purpose of the
joint details. An empirical equation for calculating the joint shear study was to compare the shear strengths of the as-built and
strength of RC jacketed frames is proposed in this study. strengthened joints measured and computed using two
predicted models.7,8
Keywords: interior beam-column joints; jacketing; joint shear strength;
seismic behavior; shear degradation. ASSESSMENT OF JOINT SHEAR STRENGTH
A primary interest of the authors is beam-column joints
INTRODUCTION without horizontal shear reinforcement, which belong to the
More than 90% of the reinforced concrete (RC) buildings class of substandard reinforcing details. This means that the
in Taiwan, especially low-rise RC dwellings, are constructed joint’s shear strength cannot be predicted by the equations
by the cast-in-place concrete method. Unlike precast concrete, specified in ACI 318-05.1 In this study, the softened strut-
cast-in-place concrete buildings are more subject to the and-tie model7 and shear degradation model8 are then
incorporation of substandard reinforcing details1,2 such as adopted as alternative options for computing the behavior of
substandard seismic hooks in the transverse reinforcement of substandard joints.
columns or beams, or no transverse reinforcement (beam
bars or horizontal hoops and ties) passing through the Softened strut-and-tie model
beam-column joint core. During the 1999 Taiwan Chi-Chi The softened strut-and-tie model7 was based on the
earthquake, it was found that in addition to base column shear concept that, after the beam and column bars passing through
failure, there were many joint shear damages in RC buildings.2 the joint have deteriorated, the concrete of the diagonal strut
The reason for this type of failure was mainly due to low mechanism may become a major contributor to the joint
concrete strength and no transverse joint reinforcement. shear strength, as presented in Fig. 1.
Several retrofitting techniques, including the use of concrete A jacketed joint as shown in Fig. 1 is assumed as a newly
jackets, bolted steel plates, and fiber-reinforced polymer constructed joint to calculate the joint shear strength when
(FRP) sheets, have been suggested in the literature3-6 for the softened strut-and-tie model is used. To evaluate the
structural upgrading. Among these retrofitting techniques, diagonal concrete strength, the so-called diagonal strut force
the application of RC jacketing to columns has been the most Cdn needs to be evaluated (refer to Fig. 1 and Eq. (1)). That
widely adopted in Taiwan after the 1999 earthquake. This is is, the coefficient K for the beneficial effect of horizontal and
because concrete jacketing is more consistent with as-built vertical reinforcement passing through the jacketed joint
RC structures than the other retrofit materials, so that core and the joint concrete softened coefficient ζ are needed.
deficiencies in columns and beam-column joints can be
more easily strengthened by the RC jacketing. As well, the Cdn = Kζ fcj′ Astr (1)
retrofitting scheme is simple and, thus, more economical,
than other retrofitting schemes. where K is the index calculated from the horizontal and
In this study, as-built and RC jacketed interior beam- vertical reinforcement passing through the jacketed joint
column joint subassemblages that have no horizontal joint core, and ζ is the concrete softened coefficient
hoops are tested to verify the seismic performance of the
poor beam-column joints strengthened with RC jackets. The
effect of the floor slab was not considered in the research. ACI Structural Journal, V. 106, No. 2, March-April 2009.
Special attention will be given to the design of RC jacketing MS No. S-2007-297 received August 14, 2007, and reviewed under Institute publication
policies. Copyright © 2009, American Concrete Institute. All rights reserved, including the
or the assessment of shear strength of the as-built and making of copies unless permission is obtained from the copyright proprietors. Pertinent
discussion including author’s closure, if any, will be published in the January-February
concrete jacketed beam-column joints. 2010 ACI Structural Journal if the discussion is received by September 1, 2009.
ACI member Kai Hsu is a PhD Student in the Department of Civil Engineering at
NCU. His research interests include the analytical study on the behavior of reinforced
concrete structures.
Astr = as × bs (3)
Fig. 1—Diagonal strut mechanism for interior joint with
where as is the depth of the diagonal strut (refer to Fig. 1). reinforced concrete jacketing.
2 2
as = ac + ab (4) A j f cj′ = A 1 f c1′ + A 2 f c2′ (7)
where bs is the width of diagonal strut, and ac is the width of where fcj′ is the effective concrete strength at the jacketed
the compression zone in a column adjacent to a joint.9 joint core, Aj is the effective area of shear in the jacketed
joint, A1 is the gross existing area, A2 is the area of column
jacket included in the joint shear area, fc1′ is the strength of
a c = ⎛ 0.25 + 0.85 -------------⎞ h c
N
⎝
(5) concrete at the joint in the existing column, and fc2′ is the
A g f cj′ ⎠
jacketed concrete strength at the joint.
The horizontal shear strength Vjh obtained from Cdn in Eq. (1)
where ab is the width of the compression zone in a beam now becomes
adjacent to a joint.
Vjh = Cdncosθ (8)
ab = hb /5 for satisfying Eq. (6c) (6a)
θ = tan–1(lv /lh) (9)
ab = hb /3 for not satisfying Eq. (6c) (6b)
the parameters θ, lv, and lh are depicted in Fig. 1.
∑ ∑
1 A numerical example that illustrates a calculation
M nc ≥ ( 6/5 ) M nb (6c)
procedure using the aforementioned equations is presented
in the Appendix.*
where N is the axial force on the column; Ag is the gross
section area of the column; hc is the overall depth of the Joint shear degradation model
column; hb is the overall depth of the beam; ΣMnc is the sum The shear strength of the interior beam-column joint,
of nominal flexural strengths of jacketed columns, evaluated especially a joint with substandard reinforcing details or
at the faces of the joint; and ΣMnb is the sum of nominal flexural without horizontal shear reinforcement, such as is described
strengths of beams, evaluated at the faces of the joint. in the study, can be evaluated using the aforementioned
Equation (6a), proposed by the original model,7 evaluates softened strut-and-tie model, but this method may be too
the approximate effective depth of the beam compression zone complex for routine design use. To overcome this problem,
when the plastic hinging occurs at the beams adjacent to the the authors used the joint shear degradation model8,10 to
joint face. For the case different from the aforementioned, predict the horizontal joint shear strength of RC jacketed
however, Eq. (6b) proposed by the authors can be used. In beam-column joints.
the study, the shear strength of a jacketed interior joint The original shear degradation model proposed by Park10
without transverse reinforcement in joint core is evaluated, included column shear and joint shear degradation. The
as shown in Fig. 1. The parameters possibly affecting the complete joint shear degradation model as shown in Fig. 2
nominal diagonal compressive strength Cdn are the coefficient was demonstrated. This can be used for the seismic assessment
for the beneficial effect of the tie forces, K, and the effective of RC moment-resisting frames. The imposed ductility
area of the diagonal strut, Astr .
To calculate the jacketed joint strength, where there are two
*The Appendix is available at www.concrete.org in PDF format as an addendum to
different concrete strengths contained in the joint core, it is the published paper. It is also available in hard copy from ACI headquarters for a fee
necessary to evaluate an effective concrete strength3 as follows equal to the cost of reproduction plus handling at the time of the request.
EXPERIMENTAL PROGRAM
Description of test units
A total of seven one-way interior beam-column joint units
were constructed and tested. Figure 3 and Table 1 show the
Fig. 2—Horizontal joint shear degradation model for interior dimensions of the units and the details of the reinforcement.
beam-column joints. The as-built jacketed units (Ko-JI1 and Ho-JI1) are typical of
the construction used in old RC low-rise buildings in
shown in Fig. 2 is defined in terms of the curvature ductility Taiwan. The main deficiency is that there was no horizontal
factor φu/φy in the beam plastic hinges at the faces of the joint shear reinforcement in the joint, as shown in Fig. 3(a)
column. Hakuto et al.8 performed a series of testing on beam- and (b). This might lead to the occurrence of premature shear
column joints without transverse reinforcement in the joint core failure in the joint.
to verify the maximum joint shear strength and the trend for the Two series of beam-column joint subassemblages (Ko series
shear strength degradation under cyclic loading. That is, Fig. 2 and Ho series) are discussed in this paper. All units,
is confirmed by the Hakuto’s experimental results. including the retrofitted units, were cast in the horizontal
The aforementioned results, however, did not include the plane. RC jacketing 100 mm (3.94 in.) in thickness was taken
effect of column axial load on the joint shear strength. To into account.
study the axial load effect, Park’s10 equation was then For all jacketed units, the Ko units were designed to
adopted to the evaluation of the shear strength of RC jacketed illustrate the joint shear failure mode, whereas the Ho units
interior beam-column joints, as depicted in Eq. (10). were designed to illustrate flexural hinging mode at the beam
ends. The purpose of the Ko units was to examine the effect
N of new-to-old concrete interfacial slippage on the jacketed
v jh = k f cj′ 1 + ------------------- (10) joint shear strength.
A j k f cj′ All the jacketed units except Ko-JI2 were cast in two pours
to simulate a normal construction procedure of the retrofit
where k = 1.0 for interior beam-column joints (MPa) [k = work. The dowels were not anchored into the new-to-old
12.0 for interior beam-column joints (psi)]; and Aj is the concrete interface in the retrofit scheme. Ko-JI2, however,
effective area of the joint core. was cast in one pour to simulate the jacketed concrete with
The equation was derived assuming the joint shear enough dowel anchors as an ideal interfacial bond condition
strength is reached at the stage of initial diagonal tension and to serve as a standard with which Ko-JIR1 was
compared. The purpose of the aforementioned was to retrofitted with the proposed concrete jacketing. The shear
observe the bond slippage effect on joint shear strength. failure of the prototype Unit Ho-JI1 would occur, whereas
Units Ko-JI1 and Ko-JIR2 were subjected to an axial Units Ho-JIR1 and Ho-JIR2 rehabilitated with RC jacketing
column loading of 0.14fc′ Ag. This was to simulate the real could expect the failure with a mode of strong column and
condition for the low-rise buildings with a small gravity load weak beam. Dowels were not used to anchor the new-to-old
onto the columns. The comparison between the columns concrete interface similar to Units Ko-JIR1 and Ko-JIR2.
with and without the axial loading discusses the influence of Note that the longitudinal and transverse reinforcement of
the axial column loading on the behavior of the jacketed jacketing around columns for both Ko series and Ho series
beam-column joints. units were designed according to ACI 318-05.1 Transverse
The Ho series units were used to verify the seismic reinforcement in the jacketed joints was not arranged as
performance of nonductile concrete beam-column joints mentioned previously. Thus, the shear strengths of all jacketed
joints without transverse reinforcement were examined by Figure 5 shows the sequence of the applied horizontal
the softened strut-and-tie model and joint shear degradation loading. Two cycles of horizontal loading to ±0.5Hn and
model described previously. ±0.75Hn were initially applied, defined as the load control
cycles. The variable Hn was the lateral load at the top of the
Test setup column associated with reaching the theoretical flexural
The beam-column joint test specimens were subjected to strength in the critical sections of the beams or columns,
seismic loading using the loading system shown in Fig. 4(a). whichever was least. This was calculated using the
The ends of the members of the subassemblage coincided conventional compressive stress block for concrete with an
with the midspan and midheight points of the investigated extreme fiber concrete compressive strain of 0.003 and the
building frame. Cyclic horizontal loading was applied to the measured material strengths. For prediction of the strengths
top end of the columns using a double acting hydraulic jack. of the tested specimens, no strength reduction factor was
In the test, a constant column axial load of 0.14fc′ Ag was applied. The yielding displacement Δy for all test units was
applied to test Units Ko-JI1 and Ko-JIR2, which were also calculated by extrapolating the measured horizontal
subjected to step-by-step horizontal cyclic loading. The displacement at 0.75Hn linearly to Hn. After the load reached
other test units sustained only horizontal cyclic loading Hn, displacement was used to control the loading. The test
without column axial loading. specimens were subjected to two cycles of displacement to a
δj – δj ′ ⎛ 1 -⎞ Ko series units
γ j = ---------------
- tan α + ------------ (12)
2l j ⎝ tan α j ⎠ The Ko series units were designed to illustrate joint shear
failure (refer to Fig. 6 to 9). In the as-built Unit Ko-JI1, with
a constant column axial load of 0.14fc′ Ag , the column shear
where δj and δj′ are the changes in the lengths of the diagonal started degrading when the maximum column shear reached
AB and A′B′, respectively; lj is the initial length of the diagonal 134 kN (30.1 kips), and the drift ratio was 2%. With this drift
in the joint core; and αj is the angle of the initial diagonal to ratio, shear pinching developed due to the occurrence of joint
the horizontal axis. shear failure.
Meanwhile, of special concern is the observation of bond In the retrofitted Unit Ko-JI2, without column axial
slippage in the area of the new-to-old concrete interfacial loading, a maximum column shear of 321 kN (72.2 kips),
joint area of the jacketed units, as shown in Fig. 4(b). The equivalent to the column shear stress 0.23 f cj′ MPa
difference between two measured shear strains in jacketed (2.8 f cj′ psi), was attained and maintained until reaching a
and as-built concrete joint core is then discussed to observe 3% drift ratio to the negative cycle after which shear
the possibility of the jacket bond slippage. pinching began. Note that Unit Ko-JI2 was similar to the
jacketed Unit Ko-JIR1, but was cast monolithically to repre-
Material properties sent a retrofitted frame with perfect bonding at the interface
Table 2 contains a summary of the mechanical properties between the new and old concrete. This means that there was
no effect of interfacial bond slippage on the joint shear
of the concrete and reinforcing steel used to construct the
strength and deformation. For the retrofitted Unit Ko-JIR1,
prototype and retrofitted Ko series and Ho series units. To the maximum column shear stress was 0.23 f cj′ MPa
measure the concrete strengths, three cylinders 150 mm (2.8 f cj′ psi), attained at approximately a 3% drift ratio.
(5.91 in.) in diameter and 300 mm (11.81 in.) in height were From the comparison of maximum column shear stress
cast for each pour. The cast concrete cylinders were tested on (normalized by f cj′ ) and corresponding drift ratio between
the same date as the unit was loaded. The mean value of the Ko-JI2 and Ko-JIR1, they behaved in a similar manner. It
three cylinders was taken, as shown in Table 2. The tensile was believed that the different interfacial bond conditions for
strengths of three 1000 mm (39.4 in.) long samples for each Ko-JI2 and Ko-JIR1 did not affect the column and horizontal
diameter of deformed reinforcement were also measured and joint shear strengths. The only different result for both
the average value of the three reinforcing bar samples adopted. testing units found is the crack patterns, shown in Fig. 7(b)
Fig. 6—Hysteresis loops and failure mode for test unit Fig. 7—Hysteresis loops and failure mode for test unit
Ko-JI1: (a) hysteresis loops; and (b) cracking observed at Ko-JI2: (a) hysteresis loops; and (b) cracking observed at
end of testing. (Note: 1 in. = 25.4 mm; 1 kip = 4.45 kN.) end of testing. (Note: 1 in. = 25.4 mm; 1 kip = 4.45 kN.)
and 8(b). That is, Ko-JI2 is damaged uniformly through the Ho series units
joint core, whereas the cracking of Ko-JIR1 is likely to occur The Ho series units were designed to confirm the seismic
at the new concrete in the joint core. performance of nonductile beam-column joints rehabilitated
In the retrofitted Unit Ko-JIR2 with an axial load of with RC jacketing. The jacketing scheme was similar to that
0.14fc′ Ag (refer to Fig. 9) the same maximum column shear of the Ko series in that dowel anchors were not used at the
as Ko-JIR1 was obtained, but earlier shear degradation was new-and-old concrete interface. It can be seen in Fig. 10 to
generated at a drift ratio of approximately 2%. The differ- 12 that the as-built Unit Ho-JI1 was loaded to joint shear
ence in shear degradation between Ko-JIR1 (started at 3% failure whereas the jacketed Units Ho-JIR1 and Ho-JIR2
drift ratio) and Ko-JIR2 (started at 2% drift ratio) could be were damaged by the occurrence of flexural hinging at the
due to the effects of axial compressive loading on the new- ends of beams. In other words, the RC jacketing scheme
and-old concrete interfacial bond. This caused slippage to proposed in this study can improve nonductile frames with
occur at an earlier drift ratio. Unlike Ko-JIR1, a cracking joint shear failure, ensuring that code requirements1 for
pattern formed in Ko-JIR2 consisting of diagonal tensile strong column and weak beam modes are met.
cracks at the joint core. Spalling off of newly cast concrete at The difference between the concrete jacket strengths of
the joint core was also found, similar to Ko-JIR1. Ho-JIR1 and Ho-JIR2, with normal and higher concrete
Fig. 9—Hysteresis loops and failure mode for test unit Fig. 11—Hysteresis loops and failure mode for test unit
Ko-JIR2: (a) hysteresis loops; and (b) cracking observed at Ho-JIR1: (a) hysteresis loops; and (b) cracking observed at
end of testing. (Note: 1 in. = 25.4 mm; 1 kip = 4.45 kN.) end of testing. (Note: 1 in. = 25.4 mm; 1 kip = 4.45 kN.)
19.8% is larger than SDM with 12.6%. That is, the SDM
predictions of the as-built and jacketed joint shear strengths
are more stable than those attained using SSTM. In addition,
the joint shear strength predicted by the SDM in Eq. (10) is
more convenient for engineers to use as it is easier to calculate.
Thus, the SDM is more practical for joint shear strength
evaluation.
To use the SDM for designing RC jacketed interior beam-
column joints without joint transverse reinforcement in as-
built and jacketed joint cores, the effect of the column axial
load presented in Eq. (10) is discussed. The measured joint
shear enhancement due to the effect of column axial load by
comparing Ko-JIR1 and Ko-JIR2, as shown in Table 4, is an
11% increase (from 0.97 f cj′ to 1.08 f cj′ ), which is lower
than the predicted one of 32% increase (from 1.00 f cj′ to
1.32 f cj′ ). The limited test results suggest that it is noncon-
servative to include the full predicted axial column load
effect for the jacketed interior joint. Thus, it is recommended
for reasons of safety that the effect of column axial load not
be considered in the evaluation of the jacketed joint shear Fig. 14—Details of reinforced concrete jacketing scheme:
strength. That is, Eq. (13) is adopted at present. (a) front view of jacketed frame in joint area; (b) sectional
view of jacketed beam-column joint; and (c) section view of
vjh = k f cj′ (13) jacketed column.
6 An example of test specimen Ko-JIR2 was taken to perform the calculation. Fig. A1 shows
7 the related parameters for the model calculation. 100mm jacket thickness was adopted in this
8 case. The nominal flexural strengths of the jacketed columns and beams adjacent to joint
9 faces are Mnc = 493 kN-m and Mnb = 443 kN-m, respectively. Mnc was obtained from the
10 flexural analysis on the section 500mmx500mm with as-built and jacketed column
11 longitudinal bars. Mnb was calculated assuming the tensile beam bars stressed to 1.25 fy.
13 According to Eq.(7),
15 Then,
18
hb
22 ab = = 500 / 3 = 167 mm (Eq. (6c) is not satisfied) from Eq.(6b)
3
as = ac + ab = 249 mm
2 2
23 from Eq.(4)
20
1 Astr = as × bs = 249 × 500 = 124,500 mm2 from Eq.(3)
5 The stiffness ratios between the horizontal and vertical tie are computed as follows:
10 In this case, no transverse reinforcement passing horizontally through the joint core.
11 Fyh = 0
12 6-D25 of prototype column bars passing vertically through the joint core.
15 [ ] [ ]
k h = 1 / 1 − 0.2(γ h + γ h ) = 1 / 1 − 0.2(0.333 + 0.3332 ) = 1.097
2
16 [ ] [ ]
k ν = 1 / 1 − 0.2(γ ν + γ ν ) = 1 / 1 − 0.2(0.333 + 0.3332 ) = 1.097
2
22
21
1 k h = 1 + (k h − 1) Fyh / F h = 1 + (1.097 − 1) × 0 / 468 = 1.000 ≤ k h ; Ok!
6 Cdn = Kζf cj′ Astr = 1.097 × 0.52 × 28 × 124500 × 10 −3 = 1989 kN from Eq.(1)
1406 × 103
V jh
10 ν jh = = = 5.62 MPa
Aj 500 × 500
ν jh
11 = 1.06
f cj′
12
14 To design jacket thickness of as-built Ko-JI1, the demand for imposing horizontal joint
15 shear V ju is estimated by assuming the failure mode of strong column and weak beam. That is
2 M nb 2 M nb 2 × 443 2 × 443
17 V ju = − = − = 1855 kN
jd b Lv 0.4 2.46
18 where,
19 M nb = beam flexural strength was calculated when the tensile beam bars were stressed to
20 1.25 f y = 443 kN
22
1 Lv = column height = 2.46m
1855 × 10 3
= 350562 mm , assuming f cj′ = 28 MPa
2
3 A jreq =
1.0 × 28
23
lh=400
N
300
6-D25
4-D25
lv=400
500
hb
4-D25
beam
4-D25
N
N = 0.14f'cjAg
100 300 100
prototype f'c = 32 MPa
hc = bs = 500 jacketing f'c = 25 MPa
effective f'cj = 28 MPa
D10, fy = 554 MPa
D25, fy = 533 MPa
6-D25(prototype)
Note:
1 in = 25.4 mm
100mm thick 1 kip = 4.45 kN
RC jacketing 1 ksi = 6.895 MPa
500
300
Unit: mm
4-D25(jacketing)
jacketed column
41
V jv
Fv = γ vV jv
V jh
− D = γ d Cd
Fh = γ hV jh
Fh F
Cd = − D + + v
cos θ sin θ
Fig. A2 Strut-and-tie idealization7
42