1. General
NVF2G-series inverters are high-efficiency open-loop vector
inverter researched and developed independently by our
company. It has the features of high starting torque (0.5 Hz, 1.5
times of rated torque), strong overload capacity, flexible and
convenient operation and forward PID and reverses PID, etc.
This series of inverter can be divided into mini type, general type
(heavy load) and fan and water pump type (light load), with the
functions of strong load adaptability, stable and reliable
operation and automatic energy-saving operation, etc. This
product can be widely applied to electric drive field and
automation control field, such as papermaking, textile, water
supply, municipal administration, food, concrete, chemical
industry, printing and dyeing, metallurgy, mine and plastic
machinery.
PLC
MODBUS
Programmable digital input: Mini type: 5-route; General type, fan and water pump type: 6-route
Programmable analog quantity input: AI1: (0-10)V input; AI2: (0-10)V or (0/4-20)mA; AI1 + AI2
Peripheral
Open collector output: 1-route output
interface
Relay output: Mini type: 1-route output; General type, fan and water pump type: 2-route output
Analogue output: For 2-route output, (0-10)V or (0/4-20)mA (mini type; 1-route) can be selected
Torque boost: Automatic torque boost; Manual torque boost of 0.1% - 30.0%
Dynamic braking: Built-in or external brake unit, external connection with brake resistance
DC braking: Start and stop are selectable separately; motion frequency (0-10)Hz, brake current (0-150)% , actuation time
(0.0-50.0)s
Jog control: Jog frequencyrange: (0-400)Hz, time for jog acceleration and deceleration (0.1-3600.0)s
Multistage speed operation: Multistage speed operation can be achieved through the built-in simple PLC or controlling
Ope rat ion multi-function terminal.
fun ction s an d
feat ur es Automatic voltage regulation (AVR): When the network voltage changes, it can keep the output voltage stable automatically
Automatic current limit: To automatically limit the current during the operation to prevent fault and tripping due to frequent
overcurrent
Built-in PID controller: It can constitute a closed-loop control system conveniently
Self-defined JOG function key: The JOG key can be set as jog operation or switch from forward and reverse operation
Protection functions: It can provide over 20 kinds of fault protection functions: overcurrent, overvoltage, undervoltage,
overheating, default phase, overload, PID disconnection and other protection functions
Technical Starting torque: Non-PG vector control: 0.5 Hz /150% (Rated torque)
features Speed regulation ratio: Non-PG vector control: 1: 100; V/F control: 1:50
Speed control precision: (non-PG vector control): ±0.5% maximum speed
Carrier frequency (1-15) kHz
Temperature: The inverter should be used at an ambient temperature of -10℃ to +40℃ and derated by 1% per 1℃ when it is
over 40℃
Humidity: Relative air humidity of the operation environment ≤ 90%, without moisture condensation
Altitude: The inverter can achieve the rated power when installed below the altitude of 1000m. It should be derated by 10%
Operation
per 1000m when over 1000m.
environment
Impact and vibration: The inverter should not be dropped to the ground or subjected to sudden impact. It should not be
installed in places where vibration may occur.
Electromagnetic radiation: The inverter should not be installed adjacent to electromagnetic radiation protection
Air pollution: The inverter should not be installed in places with air pollution, such as dust or corrosive gas atmosphere
Circuit
Contacto r
breaker +2
+1 B
B
-
R
R U U
Power S
S V V
input T
T W
W
M
Motor grounded
Inverter ground Main circuit terminals
connection
Control circuit terminals
Multi-f unctio n input 1 X1 AO1 Multi-function analog
Multi-f unctio n input 2 X2 quantity output
(0 ~ 10) V or (0/4 ~ 20) mA
Multi-f unctio n input 3 X3
Multi-f unctio n input 4 X4
AO2 Multi-function analog
Multi-f unctio n input 5 X5 quantity output
Multi-f unctio n input 6
GND
GND (0 ~ 10) V or (0/4 ~ 20) mA
X6
COM
COM
protocol COM
AO1 and AO2 connecting with the analog signal meter of DC 0V-10V or
AO1,AO2 Output terminal of analog signal 0/4mA-20mA can be used for indicating the operation frequency,
output current, output voltage, etc.
25
73.5(W1)
63
15.6
RUN/PRGF/R LOC/REMFAULT Hz A V
111.5
93
JOG - +
SHIFT
< <
PRG SET
RUN STOP
H1
H
W1 4×d D1
W D
NVF2G-11/TS4~37/PS4
4×d
W D W1
H
H1
D1
NVF2G-37/TS4~75/PS4
4×d
W D W1
H
H1
D1
NVF2G-75/TS4~NVF2G-315/PS4
W D W1 W1 6×d
H1
H
D1
1. To improve or restrain the aberration rate of the voltage of power grid and current waveform due to
DC electric reactor the pulse current generated at the charging and discharging of filter capacitor;
2. To reduce the amount of harmonic and increase the power supply quality of the power grid.
1. It can control the pumping voltage of bus bar and has certain protective function to the inverter;
Brake units 2. When frequent braking is needed, it can increase the braking capacity of inverter.
It can consume the mechanical energy generated during braking as the thermal energy through
Braking resistance
brake resistance to reduce the deceleration time of drive system of the inverter.
When the operation panel of inverter is needed to be installed on the door sheet of control cabinet
Keyboard support plate
or needed remote control of operation cabinet, it shall be installed through keyboard support plate.
Display extension cord It is used as extension cable when using remote monitoring or pulling out the operation panel.
Selection of braking accessories AC input electric reactor AC output electric reactor DC electric reactor
Inverter Braking resistance
Configuration
Configuration
Configuration
conditions of Rated Rated Rated (mH )
Inductance Inductance
the braking Resistance Power curr ent curr ent Configuration current
(mH) (mH) Inductance
NVF2G-□/□□□ unit (10% value (Ω) (W ) (A) (A) (A)
braking ratio)
0.4/TD2 220 80 2.4 4.6 2.4 4.5 — —
0.75/TD2 St andar d 220 80 4.5 2.4 4.5 2.3 — —
int er nal
1.5/TD2 100 260 7 1.6 7 1.5 — —
conf igurat ion
2.2/TD2 of br aki ng uni t 70 260 11 1 11 0.9 — —
3.7/TD2 40 390 18.5 0.6 18 0.5 — —
Corresponding
physical diagram
of each accessory
Improved type
Inverter
Company code
When ordering, you shall select the needed model and specification according to the illustration of model and implication:
For example:
single-phase 220V series: NVF2G-0.75/TD2
3-phase 380V general type: NVF2G-45/TS4
3-phase 380V fan and water pump type: NVF2G-55/PS4