LM Modbus User Instructions

This document provides instructions for communicating with an LM MODBUS instrument via its RS485/RS232 interface using Modbus protocol. It defines the standard 9600 baud rate communication parameters and data format for reading and writing parameters. These include addresses for items like the primary input value, alarms, offsets, and I/O ranges that can be read or written individually or in blocks depending on the command. Setup values for various factory default parameters are also provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views2 pages

LM Modbus User Instructions

This document provides instructions for communicating with an LM MODBUS instrument via its RS485/RS232 interface using Modbus protocol. It defines the standard 9600 baud rate communication parameters and data format for reading and writing parameters. These include addresses for items like the primary input value, alarms, offsets, and I/O ranges that can be read or written individually or in blocks depending on the command. Setup values for various factory default parameters are also provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

LM MODBUS USER INSTRUCTIONS

1, The instrument RS485/RS232 communication BPS is fixed at 9600 bits/s, start bit=1, data bit=8, stop bit=1,
starting and ending time >5ms.

2, The format of the data reading and writing is same as standard Modbus protocol. Definition as follows:
Request:(eg:01 03 00 62 00 02 65 D5)
01 03 0098(0062H) 0002 26069 (65D5)
ADD COM PV1 Counts CRC
Response: (eg:01 03 04 6D 96 49 F3 71 66)
01 03 04 6D96 49F3 7166
ADD COM Counts PV1 CRC
Return Power: 2 WORD
PV1 = 6D96 49F3=6D96.49F3H= INT 6D96H+ POINT 49F3H=28054+18931/65536=28054.2888
(49F3H=18931 6D96H=28054)
When Max bit is “1”,means negative, viz. sign bit.
Ed96 bit 15=1 is negative,viz.-6D96H

3, When setting parameters, can read multi- parameters; when writing, can write 1 parameter only every time
Please convert the demical part from band 10 to 16 in HEX format.For example,100.5,INT
100=0064h,0.5=0.8000H,therefore 100.5=0064.8000H

4, Commands:
02H: read digital value / discrete I/O parameters
03H: read holding registers parameters
06H: write single holding register parameter value
10H: write multi holding registers parameters value

1
5, Communication parameters:

LM Weighing meter reading and writing parameter


Parameter Data numbers
Factory setting Parameters Function Remark
address (HEX) (bytes)

PV1 0098 (62H) 4 1st input measuring value Read only

90.0 AL1 0000 4 Alarm 1 set value R/W

H: high alarm AM1 0003 2 Alarm 1 mode setting

10.0 AL2 0004 4 Alarm 2 set value R/W

L: Low alarm AM2 0007 2 Alarm 2 mode setting R/W

AL3 0008 4 Alarm 3 set value R/W

AM3 0011 2 Alarm 3 mode setting R/W

AL1 /AL2/AL3 common


H: high alarm HY1 0012 4 R/W
hysteresis value

001 ADD 0015 2 Communication address R/W

PVF 0016 4 Offset value R/W

0.00 USP 0020 4 Adjustment rage R/W

0001 DP 0023 2 Decimal point R/W

UHH 0024 4 Max. Weight value R/W

TRL 0028 4 Low current output R/W

TRH 0032 4 High current output R/W

000 LCK 0035 2 Password R/W

Note: any writing operation to PVF will reset, which is equal to function of RST key in the front panel and terminal
RST.