OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1.0 GENERAL
1.1 General
1.2 Design Code & Reference
1.3 Design Method
1.4 Design Data
2.1 BH-01
2.2 BH-02
2.3 BH-04
2.4 BH-05
2.5 BH-06
2.6 BH-08
2.7 BH-09
2.8 BH-10
2.9 BH-11
2.10 DBH-01
2.11 DBH-02
3.0 SUMMARY
40
4.0 STRUCTURAL PILE DESIGN
5.0 CONCLUSIONS
ATTACHMENT
@Seismicisolation
@Seismicisolation
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1.0 GENERAL
1.1 General
For the Olkaria Ⅳ Geothermal Power Plant Project, pile foundation will be needed to support the
buildings and concrete structures depending on sub-soil condition.
The allowable pile capacity was calculated base on soil investigation results which will be submitted
as separate report(Doc No. ZP00700-B2CE-ECG-RPT-0001).
In consideration of sub-soil condition, the various bored pile will be adopted.
1) Pile
2) Concrete
@Seismicisolation
@Seismicisolation
1/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.1 BH-01
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
2/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
3/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
4/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 18.2 1.00 18.2
Cohesive 68.4 1.00 68.4
Cohesive 109.5 1.00 109.5
Cohesive 164.2 1.00 164.2
Cohesive 219.0 1.00 219.0
Cohesive 317.9 1.00 317.9
Cohesive 360.2 1.00 360.2
0 0.0 0.00 0.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1257.4
Ta = ( Tp + Ts ) / FSfriction = 628.7 kN
@Seismicisolation
@Seismicisolation
5/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
6/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
7/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 17.6 kPa
My/cub3 = 139.5
ec/b = 0
Qu/cub2 = 57.0 from the below chart
Qu = 361.2 kN
Hu = 361.2 kN
Ha = Hu / FSlateral = 180.6 kN
@Seismicisolation
@Seismicisolation
8/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 444.7 1663.2 0.04 17.82
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 18.0 419.1 1663.2 0.07 1.01
@Seismicisolation
@Seismicisolation
9/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
10/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.2 BH-02
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
11/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
12/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
13/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 476.8 1.00 476.8
Cohesive 424.2 1.00 424.2
Cohesive 228.1 1.00 228.1
Cohesive 287.4 1.00 287.4
Cohesive 146.0 1.00 146.0
Cohesive 146.0 1.00 146.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1708.4
Ta = ( Tp + Ts ) / FSfriction = 854.2 kN
@Seismicisolation
@Seismicisolation
14/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
15/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
16/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 154 kPa
My/cub3 = 15.9
ec/b = 0
Qu/cub2 = 14.0 from the below chart
Qu = 776.2 kN
Hu = 776.2 kN
Ha = Hu / FSlateral = 388.1 kN
@Seismicisolation
@Seismicisolation
17/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 374.3 1663.2 0.04 15.00
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 15.0 569.5 1663.2 0.07 1.58
@Seismicisolation
@Seismicisolation
18/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
19/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.3 BH-04
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
20/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
21/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
22/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 95.8 1.00 95.8
Cohesive 219.0 1.00 219.0
Cohesive 82.1 1.00 82.1
Cohesive 54.7 1.00 54.7
Cohesive 82.1 1.00 82.1
Cohesive 91.2 1.00 91.2
Cohesive 219.0 1.00 219.0
Cohesive 228.1 1.00 228.1
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1072.0
Ta = ( Tp + Ts ) / FSfriction = 536.0 kN
@Seismicisolation
@Seismicisolation
23/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
24/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
25/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 30.8 kPa
My/cub3 = 79.7
ec/b = 0
Qu/cub2 = 40.0 from the below chart
Qu = 443.5 kN
Hu = 443.5 kN
Ha = Hu / FSlateral = 221.8 kN
@Seismicisolation
@Seismicisolation
26/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 318.6 990.0 0.04 21.46
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 20.0 357.3 990.0 0.07 1.34
@Seismicisolation
@Seismicisolation
27/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
28/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.4 BH-05
-18.0 ~ Cohesive 66
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
29/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
30/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
31/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 410.5 1.00 410.5
Cohesive 123.2 1.00 123.2
Cohesive 273.7 1.00 273.7
Cohesive 150.5 1.00 150.5
Cohesive 155.1 1.00 155.1
Cohesive 127.7 1.00 127.7
Cohesive 205.3 1.00 205.3
0 0.0 0.00 0.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1446.0
Ta = ( Tp + Ts ) / FSfriction = 723.0 kN
@Seismicisolation
@Seismicisolation
32/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
33/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
34/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 132 kPa
My/cub3 = 18.6
ec/b = 0
Qu/cub2 = 17.0 from the below chart
Qu = 807.8 kN
Hu = 807.8 kN
Ha = Hu / FSlateral = 403.9 kN
@Seismicisolation
@Seismicisolation
35/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 325.0 1663.2 0.04 13.03
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 18.0 482.0 1663.2 0.07 1.16
@Seismicisolation
@Seismicisolation
36/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
37/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.5 BH-06
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
38/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
39/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
40/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 54.7 1.00 54.7
Cohesive 177.9 1.00 177.9
Cohesive 127.7 1.00 127.7
Cohesive 246.3 1.00 246.3
Cohesive 191.6 1.00 191.6
Cohesive 146.0 1.00 146.0
Cohesive 232.6 1.00 232.6
Cohesive 191.6 1.00 191.6
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1368.5
Ta = ( Tp + Ts ) / FSfriction = 684.2 kN
@Seismicisolation
@Seismicisolation
41/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
42/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
43/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 17.6 kPa
My/cub3 = 139.5
ec/b = 0
Qu/cub2 = 58.0 from the below chart
Qu = 367.5 kN
Hu = 367.5 kN
Ha = Hu / FSlateral = 183.7 kN
@Seismicisolation
@Seismicisolation
44/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 345.6 1663.2 0.04 13.85
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 20.0 456.2 1663.2 0.07 1.02
@Seismicisolation
@Seismicisolation
45/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
46/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.6 BH-08
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
47/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
48/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
49/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 205.3 1.00 205.3
Cohesive 164.2 1.00 164.2
Cohesive 136.8 1.00 136.8
Cohesive 205.3 1.00 205.3
Cohesive 191.6 1.00 191.6
Cohesive 155.1 1.00 155.1
Cohesive 219.0 1.00 219.0
Cohesive 146.0 1.00 146.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1423.2
Ta = ( Tp + Ts ) / FSfriction = 711.6 kN
@Seismicisolation
@Seismicisolation
50/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
51/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
52/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 66 kPa
My/cub3 = 37.2
ec/b = 0
Qu/cub2 = 25.0 from the below chart
Qu = 594.0 kN
Hu = 594.0 kN
Ha = Hu / FSlateral = 297.0 kN
@Seismicisolation
@Seismicisolation
53/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 326.8 1663.2 0.04 13.10
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 20.0 474.4 1663.2 0.07 1.06
@Seismicisolation
@Seismicisolation
54/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
55/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.7 BH-09
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
56/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
57/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
58/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 232.6 1.00 232.6
Cohesive 109.5 1.00 109.5
Cohesive 173.3 1.00 173.3
Cohesive 232.6 1.00 232.6
Cohesive 155.1 1.00 155.1
Cohesive 182.5 1.00 182.5
Cohesive 287.4 1.00 287.4
0 0.0 0.00 0.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1373.0
Ta = ( Tp + Ts ) / FSfriction = 686.5 kN
@Seismicisolation
@Seismicisolation
59/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
60/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
61/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 74.8 kPa
My/cub3 = 32.8
ec/b = 0
Qu/cub2 = 22.0 from the below chart
Qu = 592.4 kN
Hu = 592.4 kN
Ha = Hu / FSlateral = 296.2 kN
@Seismicisolation
@Seismicisolation
62/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 346.4 1663.2 0.04 13.89
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 18.0 457.7 1663.2 0.07 1.10
@Seismicisolation
@Seismicisolation
63/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
64/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.8 BH-10
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
65/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
66/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
67/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 314.7 1.00 314.7
Cohesive 191.6 1.00 191.6
Cohesive 100.4 1.00 100.4
Cohesive 219.0 1.00 219.0
Cohesive 219.0 1.00 219.0
Cohesive 164.2 1.00 164.2
Cohesive 219.0 1.00 219.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1427.8
Ta = ( Tp + Ts ) / FSfriction = 713.9 kN
@Seismicisolation
@Seismicisolation
68/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
69/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
70/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 101.2 kPa
My/cub3 = 24.3
ec/b = 0
Qu/cub2 = 18.0 from the below chart
Qu = 655.8 kN
Hu = 655.8 kN
Ha = Hu / FSlateral = 327.9 kN
@Seismicisolation
@Seismicisolation
71/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 327.5 1663.2 0.04 13.13
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 18.0 475.9 1663.2 0.07 1.15
@Seismicisolation
@Seismicisolation
72/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
73/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.9 BH-11
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
74/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
75/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
76/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 246.3 1.00 246.3
Cohesive 219.0 1.00 219.0
Cohesive 100.4 1.00 100.4
Cohesive 191.6 1.00 191.6
Cohesive 164.2 1.00 164.2
Cohesive 155.1 1.00 155.1
Cohesive 328.4 1.00 328.4
0 0.0 0.00 0.0
0 0.0 0.00 0.0
0 0.0 0.00 0.0
sum = 1405.0
Ta = ( Tp + Ts ) / FSfriction = 702.5 kN
@Seismicisolation
@Seismicisolation
77/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
78/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
79/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 79.2 kPa
My/cub3 = 31.0
ec/b = 0
Qu/cub2 = 23.0 from the below chart
Qu = 655.8 kN
Hu = 655.8 kN
Ha = Hu / FSlateral = 327.9 kN
@Seismicisolation
@Seismicisolation
80/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 368.5 1663.2 0.04 14.77
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 18.0 468.3 1663.2 0.07 1.13
@Seismicisolation
@Seismicisolation
81/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
82/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.10 DBH-01
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
83/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
84/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
85/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 150.5 1.00 150.5
Cohesive 123.2 1.00 123.2
Cohesive 109.5 1.00 109.5
Cohesive 287.4 1.00 287.4
Cohesive 73.0 1.00 73.0
Cohesive 228.1 1.00 228.1
Cohesive 273.7 1.00 273.7
Cohesive 155.1 1.00 155.1
Cohesive 287.4 1.00 287.4
Cohesive 209.8 1.00 209.8
sum = 1897.6
Ta = ( Tp + Ts ) / FSfriction = 948.8 kN
@Seismicisolation
@Seismicisolation
86/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
87/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
88/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 48.4 kPa
My/cub3 = 50.7
ec/b = 0
Qu/cub2 = 30.0 from the below chart
Qu = 522.7 kN
Hu = 522.7 kN
Ha = Hu / FSlateral = 261.4 kN
@Seismicisolation
@Seismicisolation
89/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 445.0 1663.2 0.04 17.84
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 25.0 632.5 1663.2 0.08 1.19
@Seismicisolation
@Seismicisolation
90/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
91/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2.11 DBH-02
Note: 1) "Cohesive" = clay or plastic sily, "Cohesionless" = sand, gravel or non-plastic silt
2) For cohesionless soil, we couldn't carry out unit weight tests because sampling of
cohesionless soil is very difficult. Therefore, we use typical soil properties in a natural
state and conservartively select soil type.
@Seismicisolation
@Seismicisolation
92/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
a) Cohesive soil
su = average undrained shear strength between the base of the pile and
an elevation 2B below the base
b) Cohesionless soil
where, N60 = average SPT blow count between the base of the pile and
an elevation 2B below the base for condition which approximately
60 percent of the potential energy of hammer is transferred
a) Cohesive soil
fmax = α x su
b) Cohesionless soil
fmax = β x σ'v
@Seismicisolation
@Seismicisolation
93/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
94/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
1)
qmax (uplift) = 0
Note: 1) qmax should be taken as zero for uplift loading unless experience or load testing at
the construction site can show that suction between the bottom of the drilled shaft
and the soil can be predicted reliably or the drilled shaft has a bell.
Qs Ts
Soil type ψ
(kN) (kN)
Cohesive 82.1 1.00 82.1
Cohesive 54.7 1.00 54.7
Cohesive 45.6 1.00 45.6
Cohesive 136.8 1.00 136.8
Cohesive 146.0 1.00 146.0
Cohesive 191.6 1.00 191.6
Cohesive 342.1 1.00 342.1
Cohesive 173.3 1.00 173.3
Cohesive 287.4 1.00 287.4
Cohesive 246.3 1.00 246.3
sum = 1706.0
Ta = ( Tp + Ts ) / FSfriction = 853.0 kN
@Seismicisolation
@Seismicisolation
95/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Note: 1) Determine the general soil type within the critical depth below the grond FHWA-HI-97-013
surface (about 4 or 5 pile diameters). Chapter 9
1)
where, ϕ = Internal friction angle correleted by Ozaki's equation
0.5
Note: 1) ϕ = ( 20 N ) + 15
@Seismicisolation
@Seismicisolation
96/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
2) Pile parameters
a) Stiffness factor
0.20 0.00 -1
η = (Kh / EI) = m for Cohesionless soil,
b) Length factor
@Seismicisolation
@Seismicisolation
97/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5) Soil parameters
cu = 26.4 kPa
My/cub3 = 93.0
ec/b = 0
Qu/cub2 = 45.0 from the below chart
Qu = 427.7 kN
Hu = 427.7 kN
Ha = Hu / FSlateral = 213.8 kN
@Seismicisolation
@Seismicisolation
98/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
where, Qwp = load carried at the pile point under working load condition
Qws = load carried by frictional resistance under working load condition
Ap = area of cross section of pile
L = length of pile
Ep = modulus of elasticity of the pile material
ξ = coefficient which will depend on the nature of the distribution of the unit
friction resistance along the pile shaft
conservatively, 0.5
Settlement of Pile Caused by the Load at the Pile Tip (Vesic, 1977)
D Qwp qp se(2)
Borehole Cp
(mm) (kN) (kN/m2) (mm)
Design-N 600 435.5 1663.2 0.04 17.46
Settlement of Pile Caused by the Load Transmitted along the Pile Shaft (Vesic, 1977)
L Qws qp se(3)
Borehole Cs
(m) (kN) (kN/m2) (mm)
Design-N 25.0 568.7 1663.2 0.08 1.07
@Seismicisolation
@Seismicisolation
99/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
100/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
3.0 Summary
The allowable pile capacities for Olkaria IV Power Plant project are summarized as follows.
Cooling
BH-01 18.0 863.8 628.7 180.6
Tower(1)
Cooling
BH-10 18.0 803.5 713.9 327.9
Tower(2)
Cooling
BH-11 18.0 836.8 702.5 327.9
Tower(2)
Cooling
BH-06 20.0 801.8 684.2 183.7
Tower(1)
Steam
DBH-01 25.0 1077.6 948.8 261.4
Turbine BD.
Steam
DBH-02 25.0 1004.2 853.0 213.8
Turbine BD.
@Seismicisolation
@Seismicisolation
101/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Reinforcement bars in pile are designed to be followed as the basic requriement in BS 8110,
and to resist axial force, bending moment and tension stress.
Alowing for eccentricity of loading due to deviations during construction, BS 8110, Part 1
the untimate axial load should not exceed the value of N given by: Clause 3.8.3
N = 0.45 x fcu x Ac + 0.95 x As x fy
fcu = 25 N/mm2
fy = 460 N/mm2
Ac = 282,743 mm2
As = 2,827 mm2
The rebar shall be designed for this Article requirement plus seismic action
Assume H-force on the Pile : 150.0 kN
Horizontal load on pile : 160.7 kN
(due to construction allowances)
B.M produced by eccentricity : 60.0 kN-M
@Seismicisolation
@Seismicisolation
102/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
103/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Nc M Φ
σ at 5 M = ± ×
Ac 1 2
3 6
800 × 10 63.455 × 10 × 600
= 2
±
π/4 × 600 6361725124 × 2
5.82 2 -0.16 2
= N/mm Or N/mm
As per BS 8004 Article 7.4.4.3.1:
these stresses are < 0.25 fcu or 10 N/mm2
From the above results it can be inferred that stresses in the concrete are acceptable
if 5 m long steel is used. However we are providing for full length steel.
@Seismicisolation
@Seismicisolation
104/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
For fcu 25 2
= N/mm
Anchorage length = 32 × 20 = 640 mm
We propose 640 mm into the pile cap
8) Lateral Reinforcement:
As previously shown lateral reinforcement is not required for shear considerations,
however buckling should be investigated. Euler’s theory gives the minimum force
for buckling as
2
π EI
F = 2
eK
6
where E = Young’s modulus for steel = 200 × 10 kN/m2
4
π×Φ
I = Moment of Inertia of the bar = = 7.854E-09 M4
64
eK = Free length to be examined hereunder:
Refer to attached sketches on following page.
Thus eK = I / 2= 200 / 2= 100 mm
Minimum Force for Buckling is
2
π EI
F = 2
= 1,550 kN
eK
For this condition, the compressive stress in the bar is
F
= = 4,935 N/mm2 , where Φb = 20 mm
π / 4 Φb2
@Seismicisolation
@Seismicisolation
105/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Alowing for eccentricity of loading due to deviations during construction, BS 8110, Part 1
the untimate axial load should not exceed the value of N given by: Clause 3.8.3
N = 0.45 x fcu x Ac + 0.95 x As x fy
fcu = 25 N/mm2
fy = 460 N/mm2
Ac = 282,743 mm2
As = 2,827 mm2
The rebar shall be designed for this Article requirement plus seismic action
Assume H-force on the Pile : 150.0 kN
Horizontal load on pile : 160.7 kN
(due to construction allowances)
B.M produced by eccentricity : 60.0 kN-M
@Seismicisolation
@Seismicisolation
106/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
107/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Nc M Φ
σ at 5 M = ± ×
Ac 1 2
3 6
800 × 10 63.455 × 10 × 600
= 2
±
π/4 × 600 6361725124 × 2
5.82 2 -0.16 2
= N/mm Or N/mm
As per BS 8004 Article 7.4.4.3.1:
these stresses are < 0.25 fcu or 10 N/mm2
From the above results it can be inferred that stresses in the concrete are acceptable
if 5 m long steel is used. However we are providing for full length steel.
@Seismicisolation
@Seismicisolation
108/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
For fcu 25 2
= N/mm
Anchorage length = 32 × 20 = 640 mm
We propose 640 mm into the pile cap
8) Lateral Reinforcement:
As previously shown lateral reinforcement is not required for shear considerations,
however buckling should be investigated. Euler’s theory gives the minimum force
for buckling as
2
π EI
F = 2
eK
6
where E = Young’s modulus for steel = 200 × 10 kN/m2
4
π×Φ
I = Moment of Inertia of the bar = = 7.854E-09 M4
64
eK = Free length to be examined hereunder:
Refer to attached sketches on following page.
Thus eK = I / 2= 200 / 2= 100 mm
Minimum Force for Buckling is
2
π EI
F = 2
= 1,550 kN
eK
For this condition, the compressive stress in the bar is
F
= 2
= 4,935 N/mm2 , where Φb = 20 mm
π / 4 Φb
@Seismicisolation
@Seismicisolation
109/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Alowing for eccentricity of loading due to deviations during construction, BS 8110, Part 1
the untimate axial load should not exceed the value of N given by: Clause 3.8.3
N = 0.45 x fcu x Ac + 0.95 x As x fy
fcu = 25 N/mm2
fy = 460 N/mm2
Ac = 282,743 mm2
As = 2,827 mm2
The rebar shall be designed for this Article requirement plus seismic action
Assume H-force on the Pile : 150.0 kN
Horizontal load on pile : 160.7 kN
(due to construction allowances)
B.M produced by eccentricity : 60.0 kN-M
@Seismicisolation
@Seismicisolation
110/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
111/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Nc M Φ
σ at 5 M = ± ×
Ac 1 2
3 6
800 × 10 63.455 × 10 × 600
= 2
±
π/4 × 600 6361725124 × 2
5.82 2 -0.16 2
= N/mm Or N/mm
As per BS 8004 Article 7.4.4.3.1:
these stresses are < 0.25 fcu or 10 N/mm2
From the above results it can be inferred that stresses in the concrete are acceptable
if 5 m long steel is used. However we are providing for full length steel.
@Seismicisolation
@Seismicisolation
112/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
For fcu 25 2
= N/mm
Anchorage length = 32 × 20 = 640 mm
We propose 640 mm into the pile cap
8) Lateral Reinforcement:
As previously shown lateral reinforcement is not required for shear considerations,
however buckling should be investigated. Euler’s theory gives the minimum force
for buckling as
2
π EI
F = 2
eK
6
where E = Young’s modulus for steel = 200 × 10 kN/m2
4
π×Φ
I = Moment of Inertia of the bar = = 7.854E-09 M4
64
eK = Free length to be examined hereunder:
Refer to attached sketches on following page.
Thus eK = I / 2= 200 / 2= 100 mm
Minimum Force for Buckling is
2
π EI
F = 2
= 1,550 kN
eK
For this condition, the compressive stress in the bar is
F
= = 4,935 N/mm2 , where Φb = 20 mm
π / 4 Φb2
@Seismicisolation
@Seismicisolation
113/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Alowing for eccentricity of loading due to deviations during construction, BS 8110, Part 1
the untimate axial load should not exceed the value of N given by: Clause 3.8.3
N = 0.45 x fcu x Ac + 0.95 x As x fy
fcu = 25 N/mm2
fy = 460 N/mm2
Ac = 282,743 mm2
As = 2,827 mm2
The rebar shall be designed for this Article requirement plus seismic action
Assume H-force on the Pile : 150.0 kN
Horizontal load on pile : 163.3 kN
(due to construction allowances)
B.M produced by eccentricity : 75.0 kN-M
@Seismicisolation
@Seismicisolation
114/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
115/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Nc M Φ
σ at 5 M = ± ×
Ac 1 2
3 6
1000 × 10 63.455 × 10 × 600
= 2
±
π/4 × 600 6361725124 × 2
6.53 2 0.54 2
= N/mm Or N/mm
As per BS 8004 Article 7.4.4.3.1:
these stresses are < 0.25 fcu or 10 N/mm2
From the above results it can be inferred that stresses in the concrete are acceptable
if 5 m long steel is used. However we are providing for full length steel.
@Seismicisolation
@Seismicisolation
116/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
For fcu 25 2
= N/mm
Anchorage length = 32 × 20 = 640 mm
We propose 640 mm into the pile cap
8) Lateral Reinforcement:
As previously shown lateral reinforcement is not required for shear considerations,
however buckling should be investigated. Euler’s theory gives the minimum force
for buckling as
2
π EI
F = 2
eK
6
where E = Young’s modulus for steel = 200 × 10 kN/m2
4
π×Φ
I = Moment of Inertia of the bar = = 7.854E-09 M4
64
eK = Free length to be examined hereunder:
Refer to attached sketches on following page.
Thus eK = I / 2= 200 / 2= 100 mm
Minimum Force for Buckling is
2
π EI
F = 2
= 1,550 kN
eK
For this condition, the compressive stress in the bar is
F
= = 4,935 N/mm2 , where Φb = 20 mm
π / 4 Φb2
@Seismicisolation
@Seismicisolation
117/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
5.0 CONCLUSIONS
2) Pile Reinforcement
2) Pile Reinforcement
2) Pile Reinforcement
2) Pile Reinforcement
@Seismicisolation
@Seismicisolation
118/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
119/124
@Seismicisolation
@Seismicisolation
120/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
@Seismicisolation
@Seismicisolation
121/124
PROJECT : OLKARIA Ⅳ GPP
Modulus of Elasticity
Interval Modulus of
Sample No. & Type
Angle of Internal
Interval Angle of
Internal Friction
Sampler Type
Elasticity
Friction
SPT-N
Borehole From To
122/124
OLKARIA IV GEOTHERMAL POWER PLANT
REV. A
TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE
Att h
Attachment-3:
t 3 Pil
Pile Drawing
D i
@Seismicisolation
@Seismicisolation
123/124
@Seismicisolation
@Seismicisolation
124/124