750GPM@15 Bar-Vt-Soft Start PDF
750GPM@15 Bar-Vt-Soft Start PDF
750GPM@15 Bar-Vt-Soft Start PDF
BFV-2484 0 0
Vendor Doc. No.
BFV-FP
Contractor Name:
INTHAR FOR SAFETY, SHARJAH
Project Name:
VERTICAL TURBINE - 750 GPM @ 15 BAR
TECHNICAL SUBMITTAL
3. Accessories:
• Suction and discharge gauge 2
FIRE PUMP
A1. MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends
1
1
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
0 Issued for Approval Najaf Khan Nasser Mansour Nasser Mansour 22-Feb-18
Rev Description Prepared by Checked Approved Date
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 02 0
Vendor Doc. No.
BFV-ED
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 01 0
Vendor Doc. No.
BFV-VDI
Contractor Name:
Project Name:
BFV-2484 02 0
Vendor Doc. No.
BFV-ED
Contractor Name:
INTHAR FOR SAFETY, SHARJAH
Project Name:
VERTICAL TURBINE - 750 GPM @ 15 BAR
EQUIPMENT DESCRIPTION
A1. MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge 1
b. Fuel meter GERAND venture type model K-500-6" Grooved ends 1
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 02 0
Vendor Doc. No.
BFV-ED
Contractor Name:
Project Name:
VERTICAL TURBINE - 750 GPM @ 15 BAR
C. JOCKEY PUMP 1
Q = 20 GPM H=15 BAR
bristol/RV Pump RV410-16 , 7HP, 415V 5HP 3PH 50HZ
1 . Automatic jockey pump contoller.
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 03 0
Vendor Doc. No.
BFV-SVL
Contractor Name:
A1.
SUB-VENDORS LIST
MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge 1
b. Fuel meter GERAND venture type model K-500-6" Grooved ends 1
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 03 0
Vendor Doc. No.
BFV-SVL
Contractor Name:
Project Name:
SUB-VENDORS LIST
BFV-2484 04 0
Vendor Doc. No.
VDSC-4001
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 05 0
Vendor Doc. No.
VDCSD-5001
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 06 0
Vendor Doc. No.
VDED-6001
Contractor Name:
Project Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Engine Data Sheet Basic Engine Model:
Kirloskar Oil Engines Limited KFP6R-UF25
Laxmanrao Kirloskar Road Reference Number : EDS - UF25 - 00
Khadki, Pune - 411003 (India)
Revision Date : 13.02.2014
Rev. Number : 01
General Engine Data
Engine Manufacturer.……………………………… KOEL
Ignition Type……………………………………….. Compression (Diesel)
Number of Cylinders………………………………. 6
Bore and Stroke - in.(mm)………………………… 4.13 x 4.92 (105 x 125)
Displacement - in.3 (L)……………………………. 395.4 (6.48)
Compression Ratio……………………………….. 17.6 : 1
Valve per cylinder - Intake………………………… 1
Exhaust……………………… 1
Combustion System………………………………. Direct Injection
Engine Type………………………………………… In-Line, 4 Stroke Cycle
Aspiration…………………………………………… Turbocharged, Aftercooled
Firing Order…………………………………………. 1-5-3-6-2-4
Charge Air Cooling Type…………………………… Raw Watercooled
Rotation(Viewed from Flywheel end) - Clockwise.. Not Available
Counter-Clockwise……….. Standard
Engine Crankcase Vent System…………………… Open
Installation Drawing…………………………………. 6H.2583.00.00
Continued……
Page 1 of 3
Electric System - DC
System Voltage (Nominal)………………………….. 12 V
Battery Capacity for Ambients above 320F (00C)
Voltage (Nominal)…………………………. 12 V
Qty. per Battery Bank…………………….. 1
Heater System
Jacket Water Heater……………………………….. Standard
Wattage (Nominal)………….. 2000
Voltage - AC, 1P……………. 240
Continued……
Page 2 of 3
Induction Air System 1760 2100 2200 2350 2600
Air Cleaner Type……………………………………. Dry
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. of Water (kPa)….. 10 (2.5) at 1760 rpm and 20 (5) at 2600 rpm
Clean Air Cleaner - in. of Water (kPa)… 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min)………………. 298.6(8.5) 389.4(11) 428(12.1) 456(12.9) 542.7(15.4)
0 0
Air Temperature(At Engine Inlet) - F ( C)***……. 113(45) Max. Allowable
Lubrication System
2
Oil Pressure(Normal) - lb./in. (kPa)………………. 36.26 to 72.52 (250 to 500)
Oil Temperature(In Pan) - 0F (0C) (max.)………….. 230 - 248 (110 - 120)
Oil Pan Capacilty, High - L………………………… 15
Low - L…………………………. 13.5
Total Oil Capacity with filter - L…………………….. 17
Page 3 of 3
Engine Instrumentaion Panel Engine Model (FM/UL)
KFP4R-UF07 KFP4R-UF15
panel data sheet KFP6R-UF25
Kirloskar Oil Engines Limited
Application : Fire Fighting Pump set
Page 1 of 1
Engine Materials & Construction Basic Engine Model:
Kirloskar Oil Engines Limited KFP6R-UF25
Laxmanrao Kirloskar Road, Revision Date: 25.06.09
Khadki, Pune - 411003 (India) Reference No.: EMC - UF25 - 00
Air Cleaner Cylinder Head
Type : Dry type Type : Integral Type
Material : Pleated Paper Material : Gray CI- Grade FG260
Housing : Enclosed Cylinder Liners
Type : Wet Liner
Crankshaft Material : Gray CI- Grade FG150
Material : 39 Cr 5 V Valves
Type of Balance : Balance weight attached Type : Poppet
Page 1 of 1
Engine Performance Curve Basic Engine Model :
Kirloskar Oil Engines Limited KFP6R-UF25
Laxmanrao Kirloskar Road Revision Date : 25.06.2009
Khadki, Pune - 411003 (India) Curve Number : EPC - UF25 - 00
250
Engine Power Output
240
Engine Speed Power
RPM HP 230
1760 169 220 225
NGINE POWER (HP)
2100 191
210 203
2200 196
200
2350 203 191
196
2600 225 190
EN
180
170
169
160
150
1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700
ENGINE SPEED(RPM)
1 . Power Curves shown above represent gross engine performance capabilities obtained and corrected in
accordance with SAE J1349 conditions of 29.61 in Hg (100 kPa) barometric pressure [300 ft. (91.4 m)
altitude], 77 oF (25 oC) inlet air temperature with No. 2 diesel fuel
2 . The engine can be operated without changing the fuel setting up to 300 ft. (91.4 m) altitude and up to 77
o o
F (25 C) ambient temperature. To operate at high altitudes, the fuel rate of the engine should be
adjusted to limit performance by 3% per 1,000 ft. (305 m) above 300 ft. (91.4 m) altitude. To operate at
high ambient temperatures, the fuel rate of the engine should be adjusted to limit performance by 1%
per 10 oF above 77 oF (2% per 11 oC above 25 oC).
Page 1 of 1
Engine Specification Basic Engine Model:
Kirloskar Oil Engines Limited KFP6R-UF25
Laxmanrao Kirloskar Road Khadki, Reference Number : ES - UF25 - 00
Pune - 411003 (India) Revision Date : 13.02.2014
Rev. Number : 01
Number of Cylinders……………………………….. 6
Aspiration…………………………………………….. Turbocharged, Aftercooled
Rotation *…………………………………………….. Counter - Clockwise
Engine Weight - lb (kg)…………………………. 1946 (883)
Compression ratio………………………………….. 17.6 : 1
3
Displacement - in. (L)………………………………. 395.4 (6.48)
Engine Type………………………………………….. 4 Stroke Cycle - Inline Construction
Bore & Stroke in. (mm)……………………………… 4.13 x 4.72 (105 x 120)
Installation Drawing………………………………….. 6H.2583.00.00
Wiring Diagram……………………………………… 4H.1364.22.0.00
Engine Series……………………………………….. R Series
* Ratation viewed from Flywheel end
A deduction of 3 percent from engine power rating at standard SAE conditions shall be made for
diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m).
A deduction of 1 percent from engine power corrected to standard SAE conditions shall be made
for diesel engines for every 10 0 F (5.6 0 C) above 77 0 F (25 0 C) ambient temperature.
Page 1 of 1
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 07 0
Vendor Doc. No.
VDCD-7001
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Project:
Customer:
Engineer:
Pump Manufacturer:
Contents:
• Data Sheets
• Dimensional Data
• Wiring Schematics
• Field Connections
Note: The drawings included in this package are for controllers covered under our standard offering.
Actual AS BUILT drawings may differ from what is shown in this package.
October 2013
Technical Data
GPD Diesel Fire Pump Controller
Standard
Ambient □ 5°C to 40°C / 41°F to 104°F
Temperature Optional
Rating □ 5°C to 50°C / 41°F to 122°F
□ 5°C to 55°C / 41°F to 131°F
AC
□ 120V / 1ph / 60hz
□ 208V to 240V / 1ph / 50-60hz
DC
□ 12VDC
General
□ 24VDC
Grounding system • Negative
• Two independent fully automatic
Battery chargers • 10A continuous charge
• 500mA trickle charge
• Battery 1 & Battery 2 voltage
Electrical Reading • Battery 1 & Battery 2 charging amperage
• Charging mode
• Continuous system pressure display
Pressure Reading
• Cut-in and Cut-out pressure setting
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events can be stored in memory for up to 5 years
Event Recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
October 2013 2
Technical Data
GPD Diesel Fire Pump Controller
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing connection 1/2” Female NPT
Pressure sensing • Drain connection 3/8”
• Rated for 0-500psi Working pressure (calibrated at 0-300psi)
• Externally mounted with protective cover
Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)
Visual only
• Periodic test • Cranking Cycle
• Engine run
• Main switch in HAND • Main switch in OFF
• Main switch AUTO
• Pump room temperature ( F or oC)
o
SPDT-8A-250V.AC
• Engine run (2x) (1x field re-assignable)*
• Common controller trouble
• Charger #1 & Charger #2 failure • Pressure line failure
• Common engine trouble
• High engine temperature • Battery #1 & battery #2 failure • Overspeed
• Fail to start • DC failure • Fail when running
Remote Alarm • Fuel injection malfunction** • Loss of continuity (starter) #1 and/or #2 • Low oil pressure
Contacts • ECM selector switch in alternate position***
• Common pump room alarm (field re-assignable)*
• Low fuel level • Low suction pressure • Water reservoir low
• High fuel level • Low pump room temperature • Water reservoir empty
• Fuel tank leak • High pump room temperature • AC Failure
• H-O-A selector switch in AUTO (field re-assignable)*
• H-O-A selector switch in OFF or HAND
• Free (field programmable)*
• Embedded micro-computer with software PLC logic
• 4.2” color touch screen (HMI technology)
ViZiTouch
• Upgradable software
Operator Interface
• Expandable storage
• Multi-language
*Except if option C13 is ordered. Tornatech reserves the right to use any of these four alarm points for special specific application requirements
**Applicable to electronic engines only.
*** Applicable to electronic engines only. Alarms when ECM selector switch on the engine is in alternate mode.
October 2013 3
Technical Data
GPD Diesel Fire Pump Controller
• Hand-Off-Auto
Selector Switch
• Behind lockable and breakable cover
• Start on pressure drop
Automatic Start
• Remote start signal from automatic device
• Crank 1 and Crank 2 start pushbuttons
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• 6 consecutive cycle attempts
Crank Cycle • 3 X 15s crank from battery 1 or 2 alternatively
Operation • 15s rest in between each crank attempt
• Manual with Stop pushbutton
Stopping
• Automatic after expiration of minimum run timer ***
• Minimum run timer ***(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic
October 2013 4
Technical Data
GPD Diesel Fire Pump Controller
A1 Periodic test alarm contact (Form C-SPDT) Delayed automatic start on AC power failure
C14
(factory set at 15 minutes)
A2 Overspeed alarm contact (Form C-SPDT)
C15 Low zone pump control function
A3 Low oil pressure alarm contact (Form C-SPDT)
C16 Medium zone pump control function
A4 High coolant temperature alarm contact (Form C-SPDT)
C17 High zone pump control function
A5 Failure to start alarm contacts alarm contact (Form C-SPDT)
Lockout/interlock circuit from equipment installed inside the
A6 Battery 1 & 2 failure alarm contact (2 x Form C-SPDT) C19
pump room
A7 Charger 1 & 2 failure alarm contact (2 x Form C-SPDT) Pressure transducer and run test solenoid valve for fresh
D4
A8 AC failure alarm contact (Form C-SPDT) water rated for 0-500PSI (for calibration purposes only)
System overpressure alarm contact (For engines with PLD) Pressure transducer and run test solenoid valve for sea
A9 D6
(Form C-SPDT) water rated for 0-500PSI
A11 Extra controller trouble alarm contact (Form C-SPDT) D7A Low fuel level float switch supplied as separate item (1-1/4”)
A12 Extra engine trouble alarm contact (Form C-SPDT) D7B Low fuel level float switch supplied as separate item (1-1/2”)
Additional engine alarm contact (Form C-SPDT) D8A High fuel level float switch supplied as separate item (1-1/4”)
Ax
(specify function) D8B High fuel level float switch supplied as separate item (1-1/2”)
B1 Low fuel level alarm contact (Form C-SPDT) D9A Anti-condensation heater & thermostat
B2 Water reservoir level low alarm contact (Form C-SPDT) D9B Anti-condensation heater & humidistat
B3 Water reservoir empty alarm contact (Form C-SPDT) D9C Anti-condensation heater & thermostat & humidistat
B4 Low pump room temperature alarm contact (Form C-SPDT) Low suction pressure transducer for fresh water rated at
D11
B5 High fuel level alarm contact (Form C-SPDT) 0-300PSI with visual indication and alarm contact
Low suction pressure transducer for sea water rated at
Low system (discharge) pressure alarm contact D11A
B6 0-300PSI with visual indication and alarm contact
(Form C-SPDT)
D12 Tropicalization
B7 Low suction pressure alarm contact (Form C-SPDT)
D25 Mounting stand
B8 Pump on demand alarm contact (Form C-SPDT)
D25A Mounting stand SST- 304 painted
B9 Fuel tank leak alarm contact (Form C-SPDT)
D25B Mounting stand SST- 304 brushed finish
B10 Main relief valve open alarm contact (Form C-SPDT)
D25C Mounting stand SST- 316 painted
B11 Flow meter loop valve open alarm contact (Form C-SPDT)
D25D Mounting stand SST- 316 brushed finish
B12 Water reservoir level high alarm contact (Form C-SPDT)
D26 Combined low and high fuel level float switch (1-1/4”)
B13 High pump room temperature alarm contact (Form C-SPDT)
D26A Combined low and high fuel level float switch (1-1/2”)
Additional pump room alarm contact (Form C-SPDT)
Bx D27 Fuel level probe (1-1/4”) Level indication
(specify function)
C5 CE Mark with factory certificate D28 Field programmable I/O board - 8 Input / 5 output
C6 Nickel – Cadmium battery chargers D29 Field programmable I/O board - 8 Input / 10 output
Engine block heater circuit (same voltage as battery charger Redundant pressure transducer for fresh water rated for
C7 D30
primary) 0-500PSI (calibrated at 0-300PSI)
Redundant pressure transducer for sea water rated for
Foam pump application w/o pressure transducer and run D31
C8 0-500PSI (calibrated at 0-300PSI)
test solenoid valve
D32 Modbus RTU provision
Non pressure actuated controller w/o pressure transducer
C9
and run test solenoid valve D32A Modbus TCP/IP provision
C13 Louver activation circuit (battery power specific) D33 Window kit for operator interface
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
October 2013 5
Technical Data
GPD Diesel Fire Pump Controller
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
October 2013 6
Technical Data
GPD Diesel Fire Pump Controller
3
1
4 5 6 7
8
9 10
11
1 2
12 13
14
?
October 2013 7
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 08 0
Vendor Doc. No.
VDSC-8001
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 09 0
Vendor Doc. No.
VDCSD-9001
Contractor Name:
Project Name:
VERTICAL TURBINE - 750 GPM @ 15 BAR
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 10 0
Vendor Doc. No.
VEED-E1001
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Horizontal A.C. Motors
Open Dripproof Enclosure Fire Pump Motors
Horsepower: 1 – 500 HP
Speed Range: 1800 – 3600 RPM
Rated Voltages: 200 through 575 Voltage at 60 Hz
Frame Sizes: 143T – 5012
Insulation: Class F insulation with Class B
temperature rise at service factor
Enclosure: Open Dripproof (ODP)
Efficiency Level: Energy Efficient (IE2) and
NEMA Premium®† Efficient (IE3)
For fire pump applications per NFPA®† 20 where contaminants are minimal
On January 1, 1998, all fire pump manufacturers were required NFPA®†: National Fire Protection Association
to have motors UL Listed specifically for Fire Pump applications.
A worldwide leader in providing fire, electrical, and life safety to
At that time, we released the UL Listed Fire Pump Motor line.
the public since 1986, the mission of the international nonprofit
Fire Pump Motors were designed per UL-1004A (currently
NFPA®† is to reduce the worldwide burden of fire and other
UL-1004-5) and met the NFPA 20 “Standard for the Installation
hazards on the quality of life by providing and advocating
of Stationary Pumps for Fire Protection.”
scientifically-based consensus codes and standards, research,
training and education. NFPA®† membership totals more than
U.S. MOTORS® brand ODP fire pump products are fully
75,000 individuals from around the world and more than 80
compliant with federal motor efficiency requirements as
national trade and professional organizations.
described in the Energy Independence and Security Act of 2007
also known as EISA. All fire pump motors provide necessary For more information, go to www.nfpa.org
identifying nameplate data.
• Class F insulation, Class B temperature rise • Inverter duty 10:1 variable torque
at 1.15 service factor (60Hz) • 50 Hertz voltages
®†
• 40°C Ambient, NEMA Design B performance • 50°C ambient
on 60Hz Sine Wave Power • C and D flanges
• Rolled steel frame 143-320, Cast iron frame 360-5012 • Special paint
• Aluminum end shields 143-250, Cast iron end shields 320-5012 • Space heater
• Premasked Mylar nameplate 143-320, Stainless steel 360-5012 • Winding and bearing thermal protection
• Regreaseable bearings 180 Frame & Larger
• Double shielded bearings 140-400, Open On 440 Frame & larger
• Internal bearing caps 400 Frame & Up
• Lifting provisions 210 Frame & Larger
• Catalog models suitable for Wye-Delta Start 250-445 Frame
• Dual voltage catalog models suitable
for Part Winding Start (PWS) on low voltage
• 230/460 & 575 Volt catalog models comply with NRCan
Standards
• 230/460V catalog models dual nameplated for 190/380V 50Hz,
Next lower horsepower
• Oversized connection diagram, Catalog models “CE” Mark
on nameplate
• Vertical “JP” closed coupled pump catalog models (140-365)
with drip cover
Warranty Information
Refer to the U.S. MOTORS® website (usmotors.com) for the most up-to-date warranty information.
All Nidec Motor Corporation products shall carry the limited warranty of 12 months from the date of installation, not to exceed 18
months from date of manufacture as specified in Section 5 of Nidec Motor Corporation’s Terms and Conditions of Sale except those
specifically listed below, or noted within individual product family pages within this catalog.
For additional information, please refer to our Full Line Standard Motor Catalog (FL600)
or contact your Nidec Motor Corporation representative.
† All marks shown within this document are properties of their respective owners.
8050 W. Florissant Avenue | St. Louis, MO 63136
Nidec Motor Corporation, 2015; All Rights Reserved. U.S. Motors® is a registered trademark of Nidec Motor Corporation.
Nidec Motor Corporation trademarks followed by the ® symbol are registered with the U.S. Patent and Trademark Office. Phone: 888-637-7333 | Fax: 866- 422-7758
Model Number:
Status: PUB
Motor Type: FR
Frame: 445
MPI: 147730
HP: 200.00
POLES: 4
VOLTS: 415
HZ: 50
SERVICE FACTOR: 1.15
EFFICIENCY (%):
S.F. 94.6
FULL 95.0
3/4 95.9
1/2 95.9
1/4 94.2
POWER FACTOR (%):
S.F. 83.9
FULL 83.3
3/4 80.1
1/2 71.7
1/4 50.1
NO LOAD 2.7
LOCKED ROTOR 25.8
AMPS:
S.F. 301.0
FULL 262.0
3/4 203.0
1/2 151.0
1/4 110.0
NO LOAD 92.6
LOCKED ROTOR 1724.0
NEMA CODE LETTER G
NEMA DESIGN LETTER B
FULL LOAD RPM 1480
NEMA NOMINAL EFFICIENCY (%) 95.0
GUARANTEED EFFICIENCY (%) 94.1
MAX KVAR 56.6
AMBIENT (°C) 50
ALTITUDE (FASL) 3300
SOUND PRESSURE (DBA @ 1M) 67.0
TORQUES:
BREAKDOWN{% F.L.} 200
LOCKED ROTOR{% F.L.} 100
FULL LOAD{LB-FT} 709.0
SAFE STALL TIME-HOT (SEC) 13
NEMA Nominal and Guaranteed Efficiencies are up to 3,300 feet above sea level and 25 ° C ambient.
Nidec trademarks followed by the ® symbol are registered with the U.S. Patent and Trademark Office.
http://nmcmotor.com/CIMWebViewer/CIMWebViewerPerfData.asp?MI=1 6/25/2014
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 11 0
Vendor Doc. No.
VECD-E2003
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Project:
Customer:
Engineer:
Pump Manufacturer:
Contents:
• Data Sheets
• Dimensional Data
• Wiring Schematics
• Field Connections
Note: The drawings included in this package are for controllers covered under our standard offering.
Actual AS BUILT drawings may differ from what is shown in this package.
July 2016
Technical Data
Model GPS Electric Fire Pump Controller
3L3 1M
T3
From normal
3L2
incoming power through
Disconnecting Means 3L1
T2
T1
M
(IS/CB)*
CR4
1M
3L1
GPS
3L2 Soft Starter
Across-the-lin
600 e starting
July 2016 2
Technical Data
Model GPS Electric Fire Pump Controller
Shortcircuit 200V to 208V 220V to 240V 380V to 416V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating HP (kw)
� Standard 100kA
5-150 (3.7 - 110) 5-200 (3.7 - 147) 5-300 (3.7 - 220) 5-450 (3.7 - 335) n/a
� Optional 150kA
� Standard 50kA 200 (147) 250 (184) 350 - 450 (257 - 335) 500 (373) 5-500
� Optional 100kA n/a n/a n/a n/a (3.7- 373)
Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
Service Entrance
Suitable as service entrance equipment
Rating
Locked Rotor • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current
July 2016 3
Technical Data
Model GPS Electric Fire Pump Controller
**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.
***Can only be used if approved by the AHJ
July 2016 4
Technical Data
Model GPS Electric Fire Pump Controller
Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 15014
A Tobalski Watkins Affiliate
Company
Mounting
Rigid base and wall mounting
details
Seismic
Building Test Seismic AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria Parameters
SDS z/h IP
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016
1.0
0.1
0.1 1.0 10.0
Frequency, f (Hz)
Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
• OSHPD Special Seismic Certification Preapproval (OSP)
July 2016 5
Technical Data
Model GPS Electric Fire Pump Controller
A4 Flow switch provision C20 Manual start alarm contact (Form C-SPDT)
Foam pump application w/o pressure transducer and run C21 Deluge valve start alarm contact (Form C-SPDT)
A8
test solenoid valve C22 Remote automatic start alarm contact (Form C-SPDT)
A9 Low zone pump control function C23 Remote manual start alarm contact (Form C-SPDT)
A10 Middle zone pump control function C24 High pump room temperature alarm contact (Form C-SPDT)
A11 High zone pump control function Second set of standard alarm contacts (Form C-SPDT)
C25
Non-pressure actuated controller w/o pressure transducer (Typical for city of Los Angeles and Denver)
A13
and run test solenoid valve Additional visual and alarm contact
Cx
Lockout/interlock circuit from equipment installed inside the (specify function) (Form C-SPDT)
A16
pump room Low suction pressure transducer for fresh water rated at
D1
Built in alarm panel (120V.AC supervisory power) providing 0-300PSI with visual indication and alarm contact
indication for: Low suction pressure transducer for sea water rated at
B11 • Audible alarm & silence pushbutton for motor run, phase D1A
0-300PSI with visual indication and alarm contact
reversal, loss of phase.
Pressure transducer and run test solenoid valve for fresh
• Pilot lights for loss of phase & supervisory power available D5
water rated for 0-500PSI (for factory calibration purposes only)
Built in alarm panel same as B11 but 220-240VAC
B11B Pressure transducer and run test solenoid valve
supervisory power D5D
for sea water rated for 0-500PSI
High motor temperature c/w thermoster relay and alarm
B19A D10 Omit mounting feet (when applicable)
contacts (Form C-SPDT)
High withstand rating for (normal power section)
High motor temperature c/w PT100 relay and alarm D13
B19B • 208V to 480V = 150kA • 600V = 100kA
contacts (Form C-SPDT)
D14 Anti-condensation heater & thermostat
Ground fault alarm detection c/w visual indication and alarm
B21
contact (Form C-SPDT) D14A Anti-condensation heater & humidistat
C1 Extra motor run alarm contact (Form C-SPDT) D14B Anti-condensation heater & thermostat & humidistat
C4 Periodic test alarm contact (Form C-SPDT) D15 Tropicalization
C6 Low discharge pressure alarm contact (Form C-SPDT) D18 CE Mark with factory certificate
C7 Low pump room temperature alarm contact (Form C-SPDT) D26 Modbus with RTU frame format and RS485 connection
C10 Low water reservoir level alarm contact (Form C-SPDT) Motor heater connection (external single phase power
D27
source and heater on/off contact)
High electric motor temperature alarm contact
C11
(Form C-SPDT) Motor heater connection (internal single phase power
D27A
source and heater on/off contact)
High electric motor vibration c/w visual indication and alarm
C12
contact (Form C-SPDT) D28 Customized drawing set
Pump on demand / automatic start alarm contact D34 Field programmable I/O board - 8 Input / 5 output
C14
(Form C-SPDT)
D35 Field programmable I/O board - 8 Input / 10 output
C15 Pump fail to start alarm contact (Form C-SPDT)
Redundant pressure transducer for fresh water rated for
D36
C16 Control voltage healthy alarm contact (Form C-SPDT) 0-500PSI
Flow meter valve loop open c/w visual indication and alarm Redundant pressure transducer for sea water rated for
C17 D36A
contact (Form C-SPDT) 0-500PSI
High water reservoir level c/w visual indication and alarm D37 Window kit for operator interface
C18
contact (Form C-SPDT)
C19 Emergency start alarm contact (Form C-SPDT)
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
July 2016 6
Technical Data
Model GPS Electric Fire Pump Controller
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
July 2016 7
Technical Data
Model GPS Electric Fire Pump Controller
3
1
4 5 6 7 8
8
9
10
11 12
13
?
July 2016 8
Electric Fire Pump Controller Model: GPS
Dimensions Built to the latest edition of the NFPA 20 standard
39 3/8" [999]
38 3/8" [976]
21 3/4" [552] 36" [914]
See Notes
69 1/8" [1756]
68" [1727]
65 7/8" [1675]
62" [1576]
40" [1016]
Sensing Line Connection - 1/2 " F.NPT
38" [965]
10" [255]
Voltage / Power Table Normal
11 5/8" [294]
11" [279]
Power and
16" [406]
Motor Leads
Voltage Min HP Max HP Entrance
IS CB
1L3 3L3 CT3 1M*
1L2 3L2 CT2
1L1 3L1 CT1
CR5
White
White
White
White
Black
Black
Black
Black
Red
17
ST 1M 64 66 68
SA 65 67 69
TB14
3 2
To J45 3L1 CR4 3L2
To J57 To J76
SSS
1M-1 1M
14 14
Motor J19 J18 1M-2
11 11
Running 1M-3 1M-4
12 12
1M CR4
14 12
Power J40
Available 11
TB1
J36 11
CR4-1
CR4-2
CR4
12 14
3L1 3L2
14 12
Phase J42
Reversal 11
TB2
J38 11
CR5-1
CR5-2
CR5 H1 H2
12 14
XTR4
14 (+)
Common J37 J14
Pump Room 11
TB3 AI4-IN 44 X2 X1
Alarm 12 (-)
120V
Common
Motor
14
J39 J15
(+)
CR5
11 AI3-IN 50 47
Trouble TB4
12 (-)
46
Pressure
47
14
J41 J16
(+) Red
White
PT1 transducer
CR4
49
Instant 11
TB5 PT1-IN
type 0-5V
Stop 46 Black
12 (-)
J17
(+)
PT2-IN
A1 1 A2
(-)
J8
LS1* LS1-1
J1
21 P1
LS1-2
22 J11
23
REMOTE Temperature
MANUAL START 24 P1 Probe 1
J6
LOCKOUT
25
8 TM1
26
7
REMOTE J1* 27
6
69 VIZITOUCH
AUTOMATIC START 28
29
J25
J76
5
68
67
MAIN BOARD
DELUGE J2* 4 J3
VALVE 30 66 To CT1-2-3 P2
3
WATER RESERVOIR 31 65
2 Red Red + -
LOW 32 64 J16 (+) AB1
1 Black
(-)
33
Black
34
J53 2
35
1
J14 J13
36
198
COM
COM
COM
COM
COM
COM
COM
COM
GND
24V
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
37 3L3
7
195 SSS FAULT
38
6
5
J57 4
3L2
To 3L1-2-3
3
2
3L1
1
I/O RELAY BOARD
Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
* REMOVE JUMPER TO USE THIS FEATURE * Contact closed when Emergency Start is in ON position Contact manufacturer for "As Built" drawing.
3 Phases
Bonding Incoming Power
Ground
Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3 (Use Copper Conductors Only)
Bending
Space 5 " (127 mm) 8 " (203 mm)
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250)
220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250)
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)
600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)
Bending
Space 12 " (305 mm) 16 " (406 mm)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (300 to 500) 1x (500) 2x (4/0 to 500) 2x (250 to 500) 2x (400 to 600) -------- -------- -------- -------- -------- --------
220 to 240 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
2x (400 to 500)
380 to 416 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (300 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (500 to 600) 2x (600) --------
2x (400 to 500)
440 to 480 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)
600 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)
Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
Wiring Size for motor connection for Models GPA, GPR & GPS (AWG or MCM). TERMINALS T1 - T2 - T3 (Use Copper Conductors Only)
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0) 1x (4/0 to 300)
220 to 240 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0)
380 to 416 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)
440 to 480 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (3 to 1/0)
600 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x ( 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (300) 2x (2/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (400 to 600) -------- -------- -------- -------- -------- --------
220 to 240 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
380 to 416 1x (1/0 to 3/0) 1x (3/0) 1x (250 to 300) 1x (300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (400 to 500) 2x (500 to 600) 2x (600)
440 to 480 1x (1 to 2/0) 1x (2/0 to 3/0) 1x (3/0) 1x (4/0 to 300) 2x (1/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)
600 1x (3 to 1/0) 1x (1 to 2/0) 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (300) 2x (350 to 500)
Notes:
1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC
Gnd L1 L2 L3 Gnd L1 L2 L3 (Canada) or local code.
IS IS 2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or
motor nameplate.
2M 1M 2M 1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC
Gnd Gnd
T7 T8 T9 T1 T2 T3 T6 T4 T5 T1 T2 T3 sequence.
5 - Field wiring and lug sizes base on copper conductors only.
Do not use aluminium conductors.
M M
Bending
Space 5 " (127 mm) 8 " (203 mm)
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250)
220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250)
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)
600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)
Bending
Space 12 " (305 mm) 16 " (406 mm)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (300 to 500) 1x (500) 2x (4/0 to 500) 2x (250 to 500) 2x (400 to 600) -------- -------- -------- -------- -------- --------
220 to 240 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
2x (400 to 500)
380 to 416 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (300 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (500 to 600) 2x (600) --------
2x (400 to 500)
440 to 480 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)
600 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)
Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
Wiring Size for motor connection for Models GPP, GPW & GPY (AWG or MCM). TERMINALS T1 - T2 - T3 - T4 - T5 - T6 - T7 - T8 - T9 (Use Copper Conductors Only)
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (2 to 3/0) 1x (1 to 3/0)
220 to 240 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0)
380 to 416 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0)
440 to 480 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2)
600 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (1/0 to 300) 2x (3/0 to 350) -------- -------- -------- -------- -------- --------
220 to 240 1x (1/0 to 3/0) 1x (3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (4/0 to 350) -------- -------- -------- -------- --------
380 to 416 1x (4 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 350) 2x (4/0 to 350) --------
440 to 480 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300) 2x (3/0 to 350) 2x (4/0 to 350)
600 1x (6 to 2) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (250 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300)
MOTOR RUN
Normally open J19 - 14 23
Closes to alarm Manual Close to start pump
Motor J25
Running Normally closed J19 - 11 Start 24
Opens to alarm J19 - 12
Lockout
Normally closed J40 - 14 25
Lockout Close to block start
Power Opens to alarm J25
TB1
Available Normally open J40 - 11 Signal 26
(Fail Safe) Closes to alarm J40 - 12
Automatic Start
Remote
Normally open J42 - 14 Automatic Open to start pump 27
Phase Closes to alarm J1 J25
If used, remove jumper J1 28
TB2
Normally closed J42 - 11 Start
Reversal
Opens to alarm J42 - 12
(RE-ASSIGNABLE)
Normally open
Motor Closes to alarm
J39 - 14
Field Connections for External Devices
TB4
Normally closed
Trouble
Opens to alarm
J39 - 11
J39 - 12
(I/O board)
Terminals Wire Size:
12 - 24 AWG
0.5 Nm
Flow / Zone
Flow / Zone
Start / Stop Close to signal alarm 33
J25
Signal 34
BFV-2484 12 0
Vendor Doc. No.
VJPD-3002
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
2013
.08
RV,RVA
Vertical Multistage Centrifugal Pump
50Hz
Product introduction Vertical Multistage Centrifugal Pump
outer sleeve
fasten bolt
Impellers
hydraulic stack
Position 1 position 2 position 3 Position4
Viscosity
pump body
The pumping of liquids with densities or kinematic visc-
osities higher than those of water will cause a consider-
Base
able pressure drop, a drop in the hydraulic performance
and a rise in the power consumption.
In such situations the pump should be fitted with a larger
motor, if in doubt, contact.
Motor
RVA and RV are fitted with a totally enclosed Fig.3 Relationship between motor output (P2)
fan-cooled 2-pole three-phase standard motor. and temperature
From 0.37kW to 2.2kW, are also available with P2
single-phase motor.(1*220-230V/240V). [%]
100
Motor Protection 90
Single-phase motor have a built-in thermal overload switch. 80
Three-phase motors must be connected to a motor 70
protective circuit breaker according to local regul- 60
ations. 50
20 25 30 35 40 45 50 55 60 65 70 75 80
Ambient temperature o
t[ C]
Ambient temperature: maximum+40 , if the ambient 1000 2250 3500 m
temperature exceeds +40 , or the pump is installed Example:
at an altitude exceeding 1000 meters, the motor must From the Fig.3, the pump is installed at an altitude exc-
not be fully loaded due to the risk of overheating. eeding altitude 3500 meters, P2 will decrease to 88%,
Overheating may result from excessive ambient tem-
if the ambient temperature is up to 70 , P2 will decrease
peratures or the low density and consequently low
to 78%.
cooling effect of the air.
In such cases ,it may be necessary to use a motor with
a higher rated output.
5
Construction Vertical Multistage Centrifugal Pump
RV1,2,3,4,5 RVA1,2,3,4,5
1 1
2 2
3 3
4 4 15
5 13 5 13
6 12 6 12
7 7
8 11 8 11
9 9
10 10
14
1 Motor 1 Motor
3 Pump head Cast iron EN-JL1030 ASTM25B 3 Pump head Cast iron EN-JL1030 ASTM25B
8 Hydraulic stack S.S 1.4301 AISI304 8 Hydraulic stack S.S 1.4301 AISI304
10 Pump body Cast iron EN-JL1030 ASTM25B 10 Pump body S.S 1.4301 AISI304
12 Outer sleeve S.S 1.4301 AISI304 12 Outer sleeve S.S 1.4301 AISI304
6
Operating and inlet pressures Vertical Multistage Centrifugal Pump
Operating range of the shaft seal Fig.4 Operating range of standard shaft seals
The operating range of the shaft seal depends on P[bar]
operating pressure, pump type, type of shaft seal 35
and liquid temperature.The range shown in fig 4. 30
Applies to clean water and water with glycol liquids. 25
H H
20 Q
Q HQUE HQUE
15 U U
E HQUV HQUV E
10
5
0
-40 - 20 0 20 40 60 80 1 00 1 20 1 40
t[ oC]
10
Selection and sizing Vertical Multistage Centrifugal Pump
14
Performance Curve RV10-50Hz
0 4 8 12 16 20 24 28 32 36 40 44 48 52 Q(US.GPM)
0 4 8 12 16 20 24 28 32 36 40 44 Q(IMP.GPM)
P H
(kPa) (m) H
-22
2200 RV10 (ft)
220 50Hz
700
-20
2000
200
-18
1800 600
180
-16
1600 160
50Hz
-14 500
1400 140
-12
1200 120 400
-10
1000 100
-9
300
-8
800 80
-7
-6
600 60 200
-5
-4
400 40
-3
100
-2
200 20
-1
0 0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10 11 12 13 Q(m 3/h)
P 2 (kW) Eta(%)
0.40 80
Eta
0.30 60
P2
0.20 40
0.10 20
0.00 0
0. 0 1. 0 2. 0 3. 0 4. 0 5. 0 6. 0 7. 0 8. 0 9. 0 10 11 12 13 Q(m 3/h)
NPSH NPSH
(m) (f t)
4.0
12
3.0 9
2.0 6
NPSH
1.0 3
0.0 0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10 11 12 13 Q(m 3/h)
38
Technical Data RV10-50Hz
Performance table
Power Q
Model P 2(kW) (m 3/h) 2.0 4.0 6.0 8.0 10 12 14
RV10-2 0.75 23 22 20 18 16 13 10
RV10-3 1.1 33 32 31 28 25 21 16
RV10-4 1.5 43 42 40 37 32 27 20
RV10-5 2.2 53 51 48 44 39 32 24
RV10-6 2.2 62 61 58 53 46 38 28
RV10-7 3.0 73 72 67 61 54 43 32
RV10-8 3.0 H 83 81 78 71 62 51 37
(m)
RV10-9 3.0 93 91 87 81 71 59 42
20.5 X18 -
G1/2 23
RV10-9 576 293 848 177 116 63
4- 13.5
188 215
RV10-16 821 390 1211 300 275 210 100
280 256
RV10-18 881 390 1271 300 275 210 125
39
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 13 0
Vendor Doc. No.
VJPCD-4001
Contractor Name:
JOCKEY PUMP
3. Accessories:
• Suction and discharge gauge 2
A1.
CONTROLLER DATA
MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge 1
b. Fuel meter GERAND venture type model K-500-6" Grooved ends 1
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Project:
Customer:
Engineer:
Pump Manufacturer:
Contents:
• Data Sheets
• Dimensional Data
• Wiring Schematics
• Field Connections
Note: The drawings included in this package are for controllers covered under our standard offering.
Actual AS BUILT drawings may differ from what is shown in this package.
November 2014
M
Technical Data
Model JP3 Jockey Pump Controller
JP3
November 2014 2
Technical Data
Model JP3 Jockey Pump Controller
November 2014 3
Technical Data
Model JP3 Jockey Pump Controller
A4 Elapsed time meter (time totalizer) L01 Other language and English (bilingual)
A5 Motor run alarm contact L02 French
A6 Loss of power alarm contact L03 Spanish
A7 Overload or short circuit alarm contact L04 German
A7A Overload pilot light L05 Italian
D12 CE Mark c/w externally mounted wetted parts L06 Polish
D13A Externally mounted wetted parts L07 Romanian
D14 Export packing for 1 controller L08 Hungarian
D18 Audible alarm L09 Slovak
D19 Anti-condensation heater and thermostat L10 Croatian
D20 Anti-condensation heater and humidistat L11 Czech
D21 Tropicalization L12 Portuguese
D22 Phase reversal / failure pilot light and alarm contact L13 Dutch
D23 Controller power healthy pilot light and alarm contact L14 Russian
Pump failure via current sensing relay with pilot light and dry L15 Turkish
D24
alarm contact
L16 Swedish
D25 Low zone pump control function
L17 Bulgarian
D26 Mid zone pump control function
L18 Thai
D27 High zone pump control function
L19 Indonesian
D28 Selector switch in auto alarm contacts
L20 Slovenian
D29 Selector switch in off alarm contacts
D30 Motor heater circuit
Service entrance rated - 100kA short circuit withstand rating:
• 120V/1ph (0.5hp max.)
• 240V/1ph (1hp max.)
D32 • 200V-208V - 60hz (2hp max.)
• 220V-240V - 60hz (3hp max.)
• 380V-416V - 50hz - 60hz (5hp max.)
• 440V-480V - 60hz (5hp max.)
Service entrance rated - 65kA short circuit withstand rating:
• 120V/1ph (0.5hp max.)
• 240V/1ph (1hp max.)
D33 • 200V-208V - 60hz (3hp-15hp max.)
• 220V-240V - 60hz (515hp max.)
• 380V-416V - 50hz - 60hz (7.5hp - 40hp max.)
• 440V-480V - 60hz (7.5hp-40hp max.)
Service entrance rated - 42kA short circuit withstand rating:
D34
• 600V - 60hz (7.5hp max.)
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
November 2014 4
Technical Data
Model JP3 Jockey Pump Controller
3 2
4 7
HAND AUTO
5
8
November 2014 5
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
NYC
Dpt of Building
Approved
FU1 DS
B B
D 1L1 3L2 5L3
XTR1
F C
2T1 4T2 6T3
Underwriters
Laboratories Inc.
LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX
NYC
C C
Main Disconnect
G
ON
Y
OFF
HAND G G
AUTO
C1 OL1
G DS
B E
D D
PT1
DANGER
Rating
E Label E
Standard Internal Layout
3
8 "[9] x4
Sensing Line
Connection
1/4 " M.NPT
F F
Dimension*
Maximum Motor Horsepower Dimension Enclosure Dimension Door Dimension Anchor
200-208V 220-240V 380-416V 440-480V 575-600V AXBXC DXE FXG
G 10- "X12- "
G
3HP 3HP 7.5HP 7.5HP 10HP
5HP 5HP 10HP 10HP 15HP 10- "X12- "
10HP 10HP 20HP 20HP 25HP 10- "X12- "
20HP 20HP 40HP 50HP 50HP
25HP 30HP 50HP 60HP 60HP TBD TBD TBD
A
H H
Notes:
- Standard NEMA: NEMA 2
- Standard Paint : Textured Red RAL 3002. - Drawing for information only.
I - All Dimensions are in Inches [Millimeters] Manufacturer reserves the right to modify this drawing without notice. I
Projection
- Use Watertight Conduit and Connector Only. Contact manufacturer for "As Built" drawing.
- Protect Equipment Against Drilling Chips. -*Dimension may change depending on option required. Consult Factory for exact
- Door Swing Equal to Door Width dimensions.
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
NYC
Dpt of Building
Approved
L1 L2 L3
Green
White
Black
Red
B W G R 5 S HAND G G AUTO
J5
FU1 XTR1
PsOut-
PsOut+
PsIn-
PsIn+
J9
H2 X1 3
C C
H1 X2 J8
1
RESET
G
"IPD+" J19
A2
OUT2
OUTPUT ON A1
A2
F5 OUT1
A1
24Vdc
D J2 J3 J1 D
24Vac 24Vac
A2 A1
3 1 22 8
OL1
E 14 13 9 A1 A2 E
C1
F F
G OL1 G
H H
C1
G
T1 T2 T3
I I
P1 - Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
NYC
Dpt of Building
Approved
3 Phases
Incoming Power
Bonding Ground
C C
L1 L2 L3
DS
C1
T1 T2 T3
D D
M
E E
Line Terminals (L1,L2,L3,GND)
Maximum Motor Horsepower
Wire Size Copper Only Torque Wire Size Ground Copper Only
200-208V 220-240V 380-416V 440-480V 575-600V
7.5HP 10HP 15HP 20HP 15HP #14 AWG - #8 AWG 1.8 Nm #14 AWG - #2 AWG
10HP 10HP 20HP 25HP 25HP #12 AWG - #4 AWG 1.8 Nm #14 AWG - #2 AWG
F 15HP 15HP 25HP 30HP 40HP #4 AWG - #1/0 AWG 5.65 Nm #6 AWG - #2 AWG F
I I
0 1 2 3 4 5 6 7 8
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 14 0
Vendor Doc. No.
VGBD-5001
Contractor Name:
Project Name:
VERTICAL TURBINE - 750 GPM @ 15 BAR
RIGHT ANGLE
• Suction and discharge gauge 2
A1.
GEAR BOX DRIVE
MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends
1
1
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
T.M.
1/4X 1/a
~
1/a .876 10-32 13/a 9132
2 3/4 2.751 5
/s x 5/15 3fs -16 3 3/4 9132
500A 16 6 3la 3.124 'l4x% 42M 36:V. 4334 38 45% 3834 23 13.500 34 2411 1}{, 131is +25}2 14'!<0 %-11-NC 3 % % 1"'As 4Y2 2% % 7% 7% 2~s
600A 16 6 3~ 3.749 :V.x ~s 42:V. 36:V. 4334 38 45% 3834 23 13.500 34 2411 1}{, 131is +25¥. 14'!<0 %-11-NC 3 % % 1"'118 4Y2 2% % 7% 7% 2~s
750A 18 6 3% 3.749 :V.x ~. 48 41% 50 42 50 42o/1s 23 13.500 34 24¥. 1}{, 131is +26"A 14'!<0 %-11-NC 3 1 1 1"'118 6 2:V. "A 834 834 2~s
1000G 21 8 4 3.998 1xY2 62 )' 50 34 6234 50 34 6234 5034 28% 22.000 34 3011 1 34 '"As 36:V. 26 "A-10-NC 3% % % 25As 634 3% % 8 8Y2 2 15As
t"XA" dimensions shown apply to 1:1 and speed increasing ratios only. Request certified drawing for others.
*Models 300 and 350 furnished with external heat exchanger.
**Contact factory for maximum coupling bore for Fig. 2 or Fig. 3 rotation with 1:2 or 1:3 ratio.
RATIOS AND ROTATIONS: The ratio of a drive is defined as the ratio of the horizontal input speed to vertical output speed. For example, a 2:1 ratio would have a
horizontal speed of twice the vertical speed. There are four rotational schemes available as shown in figures 1, 2, 3, and 4. Figure 1 is denoted as standard rotation.
Figures 2, 3, and 4 are special rotation, being manufactured only on order, and are not subject to cancellation without charge for completed parts.
JIF'
Vertical Shaft Percent of Percent of Vertical Shaft Percent of Percent of
R.P.M. Rated Horsepower Thrust Capacity R.P.M. Ratad Horsepower Thrust Capacity
430 37% 160% *2000 107% 96%
580 46% 145% *2200 112% 93%
690 52% 137% *2400 117% 90%
HORIZONTAL • CW 720 53% 135% *2600 122% 88%
VERTICAL • CCW 870 61% 126% *2800 128% 86%
960 65% 122% *3000 134% 84%
1160 75% 115% *3460 146% 80%
1460 88% 106% *3600 150% 79%
1760 100% 100%
* Cooling coils should be specified for models 40, 60A, and BOA operating at speeds
HORIZONTAL • CCW HORIZONTAL· CCW above 1760 rpm. Consult with the factory on all applications when the vertical speeds
VERTICAL • CCW VERTICAL • CW
exceed 1760 rpm. Maximum allowable cooling water pressure for cooling coils is 100 psi
CW - Clockwise; CCW - Counterclockwise. and heat exchanger is 150 psi.
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 15 0
Vendor Doc. No.
VACC-6001
Contractor Name:
A1. ACCESSORIES
MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge 1
b. Fuel meter GERAND venture type model K-500-6" Grooved ends 1
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Air Release Valves
Installation Dimensions
WATER AIR RELEASE VALVES
Inlet Outlet Model CWP Dimensions A
Orifice Size
Size Size Number PSI A B
1/2” NPT 1/2” NPT 15A*• 175 1/16” 4 3/4” 5 1/4”
3/4” NPT 1/2” NPT 15A.2*• 175 1/16” 4 3/4” 5 1/4”
1” NPT 1/2” NPT 15A.3*• 175 1/16” 4 3/4” 5 1/4”
B
1” NPT 1/2” NPT 22.3*• 175 3/32” 5 1/8” 6”
1/2” - 3/4” NPT 1/2” NPT 22.4*• 175 3/32” 5 1/8” 6”
1/2” NPT 1/2” NPT 22.7*• 300 1/16” 5 1/8” 6”
1/2” - 1” NPT 1/2” NPT 22.9* 300 1/16” 5 1/8” 6”
3/4” - 1” NPT 1/2” NPT 25.5* 150 1/8” 6 1/8” 7” 15A - 50HP
3/4” - 1” NPT 1/2” NPT 25.6* 300 3/32” 6 1/8” 7” Air Release Valve
1” NPT 1/2” NPT 38* 150 3/16” 7” 10”
1” NPT 1/2” NPT 38HP* 500 1/8” 7” 10”
2” NPT 1/2” NPT 38.2* 150 3/16” 7” 10”
A
1” NPT 1/2” NPT 38.5* 300 5/32” 7” 10”
2” NPT 1/2” NPT 38.6* 300 5/32” 7” 10”
2” NPT 1” NPT 45* 150 23/64” 9 1/2” 12 1/4”
2” NPT 1” NPT 45HP* 400 3/16” 9 1/2” 12 1/4”
B
3” NPT 1” NPT 45.2* 150 23/64” 9 1/2” 12 1/4”
2” NPT 1” NPT 45.5* 300 7/32” 9 1/2” 12 1/4”
3” NPT 1” NPT 45.6* 300 7/32” 9 1/2” 12 1/4”
2” NPT 1” NPT 50* 500 7/32” 10 7/8” 13” 61
2” NPT 1” NPT 50HP* 1000 1/8” 10 7/8” 13” Air Release Valve
6” 125lb Flg 1” NPT 61* 150 1” 18 3/4” 22”
*NSF/ANSI 61 Certified •UL Listed/FM Approved
13
Air Release Valves
Operational Highlights:
• Maintains system flow efficiency
• Releases unwanted air pockets during system operation
• Protects system against air related surges
Product Features:
• Unconditionally guaranteed stainless steel floats
• Stainless steel 316 internal trim
• Resilient seating for positive shutoff
• Performance proven for over 40 years
• Non-clog design eliminates backwashing
Optional Accessories:
Clean Water* Wastewater
• Vacuum check (prevents inflow of air)
• Outlet hood with screen (prevents debris from entering valves)
• Ball and plug isolation valves (allows valve maintenance)
• Inflow Preventer on outlet (stops flood water and resulting
contamination from entering pipeline)
• Backwash kit (for severe wastewater applications)
*
MATERIALS OF CONSTRUCTION
COMPONENT STANDARD OPTIONAL
Cast Iron ASTM A126 Class B Ductile Iron ASTM A536 Grade 65-45-12
Body and Cover
< 300 psig Stainless Steel ASTM A351 Grade CF8M
12
Well Service Air Valves
Installation Dimensions
A
100ST - 103ST
Well Service Air Valves with
Well Service Air Valve with Regulated-Exhaust Device Dual Port Throttling Device
Dimensions A
Inlet Outlet Model CWP
Size Size Number PSI A B
4” 125lb Flg 4” NPT 104SS 150 11 1/2” 22 3/4”
4” 250lb Flg 4” NPT 154SS 300 11 1/2” 22 3/4”
6” 125lb Flg 6” NPT 106SS 150 14” 28 1/2” B
6” 250lb Flg 6” NPT 156SS 300 14” 28 1/2”
8” 125lb Flg 8” NPT 108SS 150 17 1/4” 35 5/16”
8” 250lb Flg 8” NPT 158SS 300 17 1/4” 35 5/16”
10” 125lb Flg 10” 125lb Flg 110FSS 150 20 1/4” 40 1/16”
10” 250lb Flg 10” 125lb Flg 160FSS 300 20 1/4” 40 1/16” 104SS - 162FSS
12” 125lb Flg 12” 125lb Flg 112FSS 150 24” 44 5/16” Well Service Air Valves
with Regulated-Exhaust Device
12” 250lb Flg 12” 125lb Flg 162FSS 300 24” 44 5/16”
Typical Applications
Fire Protection System Service
Using the Model 55L in a fire
protection system or other closed
type system, prevents pressure CLA-VAL 90-42AS
90-21
build-up whenever line pressure
exceeds the setting of the spring.
The valve will relieve excess Model 55L
pressure to atmosphere preventing
damage to the distribution network.
CLA-VAL 90-42
90-21
Specifications 55L Basic Valve Dimensions (In Inches)
Size 1/2" & 3/4" Threaded
Temperature Range Water, Air: to 180°F Max.
Materials
Body & Cover: Cast Bronze ASTM B62
Stainless Steel ASTM A743-CF-16Fa 1.75
Trim: Brass & Stainless Steel 303
Rubber: Buna-N® Synthetic Rubber
3.50
When Ordering, Please Specify
1. Catalog No. 55L 4.50
2. Valve Size
3. Adjustment Range Desired 0 to 75 and 20 to175 psi design
4. Optional Materials
Application
Fluid medium which does not clog connection port or
corrode copper alloy. Specifically designed for the fire
sprinkler industry.
Sizes
4" (100 mm)
Accuracy
+ 3/2/3% of span (ASME B40.1 Grade B)
Ranges
0/80 PSI retard to 250 PSI (Air)
0/300 PSI (Water)
Working Range
Steady: 3/4 of full scale value
Fluctuating: 2/3 of full scale value
Short time: full scale value
Operating Temperature
Ambient: -40°F to 140°F (-40°C to 60°C)
Media: max. 140°F (+60°C)
Temperature Error
Additional error when temperature changes from reference
temperature of 68°F (20°C) +0.4% for every 18°F (10°C)
rising or falling. Percentage of span.
Standard Features
Connection
Material: copper alloy
Lower mount (LM)
1/4" NPT limited to wrench flat area
Bourdon Tube
Material: copper alloy
C-type Order Options (not all options are UL or FM approved)
Brass threaded or press fit restrictor
Movement Cover ring
Copper alloy Glass window
Black painted steel case
Dial Stainless steel case
White aluminum with stop pin. Black and red markings Special case colors
Special connections limited to wrench flat area
Pointer Nickel plated connection
Black aluminum- non- adjustable Custom dial layout
Other pressure scales available:
Case Bar, kPa, MPa, Kg/cm 2 and dual scales
Black polycarbonate DIN standards
Window
Snap-in clear polycarbonate
Approvals
UL Listed (UL-393)
Factory Mutual Approved
APM 111.10SP
(APM 01.01.4)
Dimensions:
A* NOMINAL SIZE
THE MEASURE OF
Total Performance TM
Ordering Information:
State computer part number (if available) / type number / size /
range / connection size and location / options required. WIKA Instrument Corporation
1000 Wiegand Boulevard
Specifications given in this price list represent the state of engineering at the time of printing.
Modifications may take place and the specified materials may change without prior notice Lawrenceville, Georgia 30043-5868
Tel: 770-513-8200 Fax: 770-338-5118
05/01 http://www.wika.com e-mail: [email protected]
MODEL
50B-4KG-1
Fire Protection Pressure Relief Valve
• U.L. Listed / U.L.C. Listed
LLED B
LAB Y
ULC
U N D E R W RIT
CANADA
OF
R
• Factory Mutual Approved
S
S E
LAB RI
O R AT O
2050B-4KG1 (Angle)
C V Factor Where:
Formulas for computing CV Factor, Flow (Q) and Pressure Drop ( P): C V = U.S. (gpm) @ 1 psi differential at 60 F water
2 or
Q Q = (l/s) @ 1 bar (14.5 PSIG) differential
CV = Q = CV P P= C at 15 C water
P V
d = inside pipe diameter of Schedule 40 Steel Pipe (inches)
K Factor (Resistance Coefficient) 4
The Value of K is calculated from the formula: K = 894d f = friction factor for clean, new Schedule 40 pipe
(U.S. system units) Cv 2 (dimensionless) (from Cameron Hydraulic Data,
Model Flow Chart (Based on normal flow through a wide open valve)
40
Pressure Drop — psi
30
20
10
8
6
4
3
1
1 3 5 10 20 30 40 60 80 100 200 500 1000 2000 5000 10,000 20,000 50,000 100,000
BFV-2484 16 0
Vendor Doc. No.
CERT
Contractor Name:
Project Name:
VERTICAL TURBINE - 750 GPM @ 15 BAR
A1. CERTIFICATES
MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge 1
b. Fuel meter GERAND venture type model K-500-6" Grooved ends 1
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
QYZS.EX3971 - Pump Controllers, Fire Page 1 of 3
QYZS.EX3971
Pump Controllers, Fire
Page Bottom
Fire Pump Controllers: Model AF, AFP, AFR, AFY, ATF, ATR, ATP or ATY followed by C or N, followed by additional suffixes. All of the above
controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:
-160, -250
160, -250
The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the normal power source side is determined by the transfer switch as indicated below:
The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.
All of the above controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:
-100, -160
The controllers provided with automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the entire controller is determined by the transfer switch as indicated below:
The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.
Models FPA, FPP, FPR, FPS, FPV, FPW, FPY, VPA, VPR, and VPS may be followed by additional suffixes. The withstand ratings are as follows:
file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QYZS.EX3971... 6/11/2014
QYZS.EX3971 - Pump Controllers, Fire Page 2 of 3
OPTIONAL
VOLTAGE STANDARD HIGH
Model ATG or VPG. The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering high fault
currents. The withstand rating of the normal power side is the same as the withstand ratings of controllers without transfer switches. The
withstand rating of the alternate power side is determined by the transfer switch as indicated by the following tables:
40 40 — — — 65,000
— — 60 75 — 25,000
— — — — 100 18,000
Withstand
Rating Specific**
Transfer 200-208V 230-240V Withstand
Switch 50/60 Hz 50/60 Hz Time Rating
(A) Max HP Max HP (A) (Cycles) (A)
Withstand Rating
Transfer 600V Specific Withstand
Switch 60 Hz Time Rating
(A) Max HP (A) (Cycles) (A)
Model ATU: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Same as withstand rating of controller without transfer switch.
Model FPL, GPL: Limited Service controllers with withstand ratings as follows:
Short Circuit Withstand Ratings of Limited Service Controllers Without Transfer Switches
OPTIONAL
VOLTAGE STANDARD HIGH
Model LTG, GLG: Automatic transfer switch for connection to a generator set.
Model LTG: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Withstand rating only applies when the generator
120 30 25,000
file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QYZS.EX3971... 6/11/2014
QYZS.EX3971 - Pump Controllers, Fire Page 3 of 3
120 30 18,000
Model LTU: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Same as withstand rating of controller without transfer switch.
Model LTG: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Withstand rating only applies when the generator set is protected
Withstand Rating
Transfer 200-480 V Specific Withstand
Switch A Max HP A Time Rating A
Withstand Rating
Transfer 600 V Specific Withstand
Switch A Max HP A Time Rating A
Model LTU: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Same as withstand rating of controller without transfer switch.
Models CPA, CPP, CPR, CPS, CPV, CPW, CPY, may be followed by additional suffixes. The withstand ratings are as follows:
Model CPU - The controllers provided with automatic transfer switches are suitable for use on circuits capable of delivering high fault currents.
The withstand rating of the normal power side and the alternate power side is the same as the withstand ratings of controllers without transfer
switches.
Model CPU
Short circuit withstand rating for alternate power circuit with transfer switch (RMS
Symmetrical)
High
V Standard (optional)
Fire pump controllers, Models GPA, GPP, GPR, GPS, GPV, GPY and GPW.
© 2014 UL LLC
When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment
database for additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2014 UL LLC".
file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QYZS.EX3971... 6/11/2014
CERTIFICATE OF COMPLIANCE
Certificate Number 20140708-E158750
Report Reference E158750-19940223
Issue Date 2014-JULY-08
Only those products bearing the UL Listing Mark for the US and Canada should be considered as
being covered by UL's Listing and Follow-Up Service meeting the appropriate requirements for US
and Canada.
The UL Listing Mark for the US and Canada generally includes: the UL in a circle symbol with “C” and
“US” identifiers: the word “LISTED”; a control number (may be alphanumeric) assigned by UL;
and the product category name (product identifier) as indicated in the appropriate UL Directory.
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus
Page 1 of 1
QXZF.EX5189 - Fire Pump Motors Page 1 of 1
QXZF.EX5189
Fire Pump Motors
Page Bottom
Number Rated
Model FL Service of Ins Prot. Ambient
No. Output Volts Amps Factor Poles Speeds RPM Phases Class Type (°C) CCN
(+) - Motors have also been evaluated as inverter duty (PRHJ) motors.
(v) - Voltage range details: 190, 200, 208, 230, 380, 400, 415, 460, 575, 660 or 208-230/460.
© 2014 UL LLC
When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment
database for additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2014 UL LLC".
file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QXZF.EX5189... 6/11/2014
10/1/2014 QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps
QYLU.EX6155
Internal-combustion Engines for Driving Stationary Fire Pumps
Page Bottom
See General Information for Internal-combustion Engines for Driving Stationary Fire Pumps
Rated
No. of Rated Speed
Model Cylinders HP (rpm)
JU4H-UF10 4 41 1760
4 51 2100
4 55 2350
JU4H-UF12 4 55 2350
4 59 2600
JU4H-UF14 4 55 2350
4 59 2600
4 70 2800
4 71 3000
JU4H-UF20 4 60 1760
4 67 2100
4 72 2350
JU4H-UF22 4 72 2350
4 75 2600
JU4H-UF24 4 72 2350
4 75 2600
4 80 2800
4 83 3000
JU4H-UF30 4 64 1760
4 79 2100
4 85 2350
JU4H-UF32 4 85 2350
4 85 2600
JU4H-UF34 4 85 2350
4 85 2600
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+… 1/8
10/1/2014 QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps
4 104 2800
4 115 3000
JU4H-UFH8 4 63 1470
4 73 1760
JU4H-UFH0 4 73 1760
4 88 2100
4 98 2350
JU4H-UFH2 4 98 2350
4 99 2600
JU4H-UF40 4 94 1760
4 105 2100
4 106 2350
4 106 2600
JU4H-UF50 4 79 1470
4 110 1760
4 130 2100
4 127 2350
4 127 2600
4 139 2600
4 145 2800
4 145 3000
JU4H-UF58 4 79 1470
4 110 1760
6 360 2100
6 410 1760
6 280 2100
6 286 2350
6 144 2100
6 148 2350
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+… 2/8
10/1/2014 QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps
JU6H-UFD2 6 148 2350
6 148 2600
JU6H-UF30 6 94 1470
6 140 1760
6 160 2100
6 160 2350
6 160 2600
6 160 2600
6 160 2800
6 175 3000
6 149 1760
6 175 1760
6 207 2100
6 200 2350
6 200 2600
6 183 1760
6 183 1760
6 210 2100
6 210 2350
6 210 2600
6 216 2600
6 216 2800
6 216 3000
6 200 1760
6 200 1760
6 240 2100
6 240 2350
6 240 2600
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+… 3/8
Vendor Ref. No. Doc. Seq. No. Revision No.
BFV-2484 17 0
Vendor Doc. No.
BFV-CO/PRO
Contractor Name:
C. JOCKEY PUMP 1
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2. Automatic jockey pump controller, suitable for 2HP
fghgh
Fire Pumps
Bristol: A History & Future.
In 1971, seven emirates joined forces to create the United Arab Emirates, with the goal of becoming a growing leader on an international
scale. The UAE’s focus has always been the safety of its land and people, BRISTOL was established in support of that same vision.
BRISTOL FIRE ENGINEERING, part of the Concorde – Corodex Group, is the leading fire-fighting and fire protection nmanufacturer in the
Middle East and has been unsurpassed in innovative fire-fighting solutions for more than 44 years.
We have been steadfast in our developments and have grown to become pioneers in the industry for unmatched quality and dependability,
longstanding commitment and unwavering dedication.
Our headquarters and manufacturing facility started in the UAE’s Emirate of Dubai, producing world-class fire-fighting systems and equipment
in cooperation with international know-how and technology with a grand vision to expand globally.
We strive to continue to adopt the highest international and national standards in line with the UAE’s goal to become the safest country in the
world.
BRISTOL was one of the first fire-fighting companies in the Middle East to receive an ISO 9001 certification, placing great emphasis on
achieving local and international approvals on product certifications such as Kite Mark, LPBC, UL listing, and FM approval. Moreover, Bristol
is certified to of ISO 14001 and OHSAS 18001.
We focus on innovation by means of continual research and development of advanced fire-fighting solutions, ensuring we not only meet, but
exceed the demands of our rapidly changing market.
For decades, we have been proudly supplying various government entities and sectors such as the oil and gas, commercial, and industrial
industries across the globe with world-class equipment and services.
BRISTOL has been serving Middle Eastern, African, Asian, and European markets for more than three decades with a vision to expand further.
Paving the road towards safety for more than four decades, and counting: BRISTOL.