TECHNICAL SUBMITTAL

FOAM SYSTEM

G+5P+15 @ Sharjah

BSIOKMFS-310319
INDEX
FOAM SYSTEM 

I. Specification & Compliance ......................................................................................... 1


II. Technical Datasheets and Catalogue
A. DELUGE VALVE (SERIES 769 with Vic-Quick Riser)…………………………………………....... 2
B. Foam Nozzle (V2603)….……………………………………………………………………………………….  3
C. Vertical Bladder Tank ………….……………………………………………………………………..…….  4
D. Ratio Flow Controller (BBT‐RFC_)……………………………………………………………………….  4
E. Aqueous Film‐Forming Foam 3% (TEKNOSOL AF‐1‐3F)…………….…………….…………  5
F. Extinguishant Control Panel (BF‐ECP3DCSM)…….…………………….………………………..  6
G. Heat Detector (B61‐2001)……………………………………………………………………………….…  7
H. Smoke Detector (B61‐1001)………………………………………………………………………………  7
I. Sounder Strobe (B61‐6301)………….……………………………………………………….…………..  8
J. Fire Alarm bell (BF‐AB‐0418)….…………………………………………………………..……………..  8
III. CD Certificates…………………………………………………………………………………………..………….  9
IV. Approval Certificates..…………….………………………………………………………………...………….  10
V. Material Safety Data Sheet ……………..………………………………………………………….………….  11 
VI. Company Profile……………………..……………………………………………………………….…….……….  12
VII. Trade License……………….……………………………………………………………………………..….……  13
I. Specification & Compliance
II. Technical Data Sheets and Catalogue
A. DELUGE VALVE (SERIES 769)
FireLock NXT™ Deluge Valve
Series 769
With Deluge Trim Grooved x Grooved 30.81

Patent Pending

Certifications/Listings:
1 1 1

104d/01
MEA: 248-98-E
See Victaulic Publication 10.01 for more details.

Product Description:

The patent-pending Victaulic Series 769 FireLock NXT


Deluge Valve controls the water supply entry into the
deluge system piping and open sprinklers. The Series
769 is a low differential, latched clapper valve that uses
a unique direct acting diaphragm to separate system
water supplies from deluge pipe sprinkler systems.
1
see page 16-18 for European configurations.

Job/Owner Engineer
System No. Spec Section

Location Paragraph

Contractor Approved

Submitted By Date

Date

victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81


30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
1
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Features: Victaulic Series 769 Deluge Valves feature a high-


strength, low-weight, ductile iron body with pneumatic,
hydraulic, and electric actuation methods. The straight-
through body design provides superior flow and low-
pressure drop. It offers simple access to all internal parts
Clapper Latch for easy maintenance. All internal parts are replaceable.
The valve is painted inside and out to increase corrosion
resistance.
Maintenance and service can be performed from the
installed position. The rubber clapper seal is replaced
Diaphragm
easily without removing the clapper from the valve. The
Assembly body is tapped for main drain and all available trim
Seat Clapper
configurations. The low differential, unique latch and
Seal actuator design of the valve allows the device to be reset
without opening the valve. The low differential design
NOTE: VALVE IS SHOWN ABOVE IN THE “SET” POSITION is not subject to water columns. The system can only
Exaggerated for clarity
Exaggerated for Clarity be installed in a vertical configuration. The valve allows
Note: Valve is shown in the “set” position
the water to operate a water motor alarm and/or electric
pressure alarms, which continue until the flow of water
stops. The valve can be configured for wet pilot, dry pilot
or electrical activation.
The valve is rated to 300 psi/2065 kPa water working
pressure and is factory tested hydrostatically to 600 psi/
4135 kPa for sizes 1 ½ – 8"/40 – 200 mm. VDS trim
configurations are approved to 16 BAR. Other European
trim configurations are approved to 20 BAR. (see page
16-18). Required air pressure is 13 psi/90 kPa.
The Series 769 is available grooved x grooved. Standard
grooved dimensions conform to ANSI/AWWA C606.
Installation Options
The Victaulic Series 769 FireLock NXT Deluge Valve is
available bare, or in the following configurations:
(note: trim kits may be ordered separately)
Pre-trimmed
The pre-trimmed valve comes completely assembled
with all necessary trim components.
Vic-Quick Riser
The Vic-Quick Riser comes completely pre-trimmed and
includes a shut off valve (uses a Series 705W FireLock
Butterfly valve – request publication 10.18; for 1 1/2
and 2"/40 and 50 mm sizes, the Vic-Quick Riser comes
with a Series 728 Ball Valve – request publication 10.17)
for system shut off, pressure switches, and a drain kit
for ease of installation. For complete Vic-Quick Riser
information request publication 30.20.
Series 745 FireLock Fire-Pac (North America only)
The Fire-Pac is a completely pre-assembled fire
protection valve that provides maximum service in a
minimal enclosed space. The unit includes a water
supply shutoff valve, the sprinkler system fire protection
valve, alarm line pressure switches, air supervisory
pressure switches, supervisory pump switches, and
digital pressure gauges that are easily viewed through a
window in the cabinet door.
For complete Fire-Pac information request publication
30.23. Optional accessories ship separately.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Dimensions: The 4"/114.3 mm dry pilot configuration is shown below

1 ½ – 2"/48.3 – 60.3 mm configurations contain ¾"/19 mm drain valves.

2 ½ – 3"/73.0 – 88.9 mm configurations contain 1 ¼"/31 mm drain valves.

4 – 8"/114.3 – 219.1 mm configurations contain 2"/50 mm drain valves.

F
A
B D
*A1
*D1

H K

C *E1
Full Open

Approx.
Weight
Dimensions Each
Actual
Nominal Outside Without With
Size Diameter A A11 B C D D11 E E11 F H J K Trim Trim
inches inches inches inches inches inches inches inches inches inches inches inches inches inches lbs. lbs.
mm mm mm mm mm mm mm mm mm mm mm mm mm mm kg kg
1 1/2 1.900 9.00 16.35 28.50 13.75 12.50 15.00 5.25 8.50 9.25 3.04 9.17 6.98 16.7 43.0
40 48.3 228.60 415.29 723 349 317 381 133 215 234 77.21 232.91 177.29 7.6 19.5
2 2.375 9.00 13.37 28.50 13.75 12.50 15.00 5.25 8.50 9.25 3.04 9.17 6.98 17.0 43.0
50 60.3 228.60 339.60 723 349 317 381 133 215 234 77.21 232.91 177.29 7.7 19.5
2 1/2 2 2.875 12.61 16.50 32.25 13.50 13.50 17.50 5.25 9.00 9.25 3.90 10.50 6.93 41.0 65.0
65 2 73.0 320.29 419.10 819 342 342 444 133 228 234 99.06 266.70 176.02 18.7 29.5
3.000 12.61 16.50 32.25 13.50 13.50 17.50 5.25 9.00 9.25 3.90 10.50 6.93 41.0 65.0
76.1 mm
76.1 320.29 419.10 819 342 342 444 133 228 234 99.06 266.70 176.02 18.7 29.5
3 3.500 12.61 16.50 32.25 13.50 13.50 17.50 5.25 9.00 9.25 3.90 10.50 6.93 41.0 65.0
80 88.9 320.29 419.10 819 342 342 444 133 228 234 99.06 266.70 176.02 18.7 29.5
4 4.500 15.03 19.83 33.50 15.00 15.75 20.50 5.50 9.00 10.75 6.25 9.62 8.46 59.0 95.0
100 114.3 381.76 503.68 850 381 400 520 139 228 273 158.75 244.34 214.88 26.7 43.0
6.500 16.00 22.00 33.75 15.50 16.75 22.00 6.00 8.50 11.25 6.20 9.62 8.84 80.0 116.0
165.1 mm
165.1 406.40 558.80 857 393 425 558 152 215 285 157.48 244.34 224.53 36.2 52.6
6 6.625 16.00 22.05 33.75 15.50 16.75 22.00 6.00 8.50 11.25 6.20 9.62 8.84 80.0 116.0
150 168.3 406.40 560.07 857 393 425 558 152 215 285 157.48 244.34 224.53 36.2 52.6
8 8.625 17.50 23.00 33.50 16.75 19.75 25.25 7.00 8.75 12.75 6.05 9.40 10.21 122.0 158.0
200 219.1 444.50 584.20 850 425 501 641 177 222 323 153.67 238.76 259.33 55.3 71.6
NOTES:
The drawings shown above reflect the dry pilot trim with Series 776 Low-Pressure Actuator. In addition, these dimensions can be applied to hydraulic (wet pilot)
release and electric release trim.

The “A” dimension coupling and the optional sensor switch are not shown for clarity.

Components shown as dotted lines denote optional equipment

1 Measurements denoted with an asterisk take optional equipment into account.

Optional drain connection kit is shown for reference and takeout dimensions.

2 European trim configurations are not available in 2½"/65mm pipe sizes.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Performance:

Hydraulic Friction Loss


The chart below expresses the flow of water at
65ºF/18ºC through a full open valve.

6.0
5.0
4.0
3.0

m
50m

.1m
mm

165
6.1
2"/

0mm
2.0
d7

and
PRESSURE DROP – PSI

an

8"/20
mm

mm
m

m
mm
5m

0m
0

150
"/4

"/6

80

10

6"/

3"/

4"/
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3

0.2

0.1
10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 20,000
800 3,000 8,000
FLOW RATE – GPM

Frictional Resistance
The chart below expresses the frictional resistance of
Victaulic Series 769 FireLock NXT.
Deluge Valve in equivalent feet of straight pipe.

Actual Equivalent
Nominal Outside Length of
Size Diameter Pipe
inches inches feet
mm mm meters
1 1/2 1.900 3.00
40 48.3 0.914
2 2.375 9.00
50 60.3 2.743
2 1/2 2.875 8.00
65 73.0 2.438
3.000 8.00
76.1 mm
76.1 2.439
3 3.500 17.00
80 88.9 5.182
4 4.500 21.00
100 114.3 6.401
6.500 22.00
165.1 mm
165.1 6.706
6 6.625 22.00
150 168.3 6.706
8 8.625 50.00
200 219.1 15.240

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

CV Values: Operation:
CV values for flow of water at +60°F/+16°C through a fully The Victaulic Deluge System utilizes the Series 769
open valve are shown in the table below. Actuated Valve to control the water supply’s entry into
the deluge system’s piping and open sprinklers. The
Formulas for CV values Where: Series 769 Actuated Valve is constructed with a clapper,
ΔP = Q /CV
2 2 Flow Coefficient Cv which has a replaceable rubber face. The clapper makes
Q (Flow) GPM
contact with the valve seat ring, which has access holes
Q = CV × √ΔP
to the intermediate chamber of the valve. The clapper
ΔP (Pressure Drop) psi
is contacted by the latch, which is contacted by the
diaphragm. In the closed position, water supply pres-
sure from upstream of the water supply control valve is
maintained in the diaphragm chamber, which holds the
clapper in the closed position. The water is maintained
Valve Size Full Open
in the diaphragm by one of the system release mecha-
Actual
Nominal Outside nisms (pneumatic, hydraulic or electric). Upon detec-
Size Diameter Flow Coefficient tion of an actuating event of the deluge system, such as
inches inches Cv an actuated pilot sprinkler or heat detection, the water
mm mm Kv supply pressure in the diaphragm chamber is released.
1 1/2 1.900 60 This release allows the latch to move to its open position,
40 48.3 52.0
2 2.375 110
permitting the clapper to pivot freely, thus allowing water
50 60.3 95.0 into the system. Water will flow from all open sprinklers
2 1/2 2.875 180 in the piping. Also, water enters the intermediate cham-
65 73.0 156.0 ber of the valve through the holes in the seat ring. The
3.000 180 water flows from the intermediate chamber to the alarm
76.1 mm
76.1 156.0
line, which activates the system’s alarms. These alarms
3 3.500 200
80 88.9 173.0 continue to sound until the flow of water is stopped.
4 4.500 350 Important Note: If air pressure in a pneumatic
100 114.3 302.8
system is lost, a low air alarm (optional) will activate.
6.500 1000
165.1 mm If air pressure is not restored, the valve will actuate.
165.1 865.0
6 6.625 1000 If a pilot sprinkler in either a pneumatic or hydraulic
150 168.3 865.0 system is damaged, the valve will actuate and water
8 8.625 1500 will flow from all open sprinklers in the deluge system.
200 219.1 1300.0
Water motor alarms and alarm pressure switches will
activate.
Manual Operation
Any time the manual release handle is pulled, water will
be released, and the valve will actuate, thus allowing
water into the deluge system. Water motor alarms and
alarm pressure switches will activate.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Material Specifications:

Body: Ductile iron conforming to ASTM A-536, grade


65-45-12. Ductile iron conforming to ASTM A‑395,
grade 65-45-15, is available upon special request.

Clapper: Aluminum bronze UNS-C95500

Latch: Aluminum bronze UNS-C95500

Clapper Seal: Peroxide cured EPDM, ASTM D2000

Bushings/Seat O-rings: Nitrile

Springs: Stainless steel (300 Series)

Shafts: Stainless 17-4

Diaphragm: Peroxide cured EPDM with fabric


reinforcement

Bill of Materials
1 Valve Body 12 Cover Plate
2 Clapper 13 Cover Plate Gasket
3 Clapper Seal 14 Cover Plate Bolts*
4 Seal Ring 15 Latch
5 Seal Washer 16 Latch Spring
6 Seal Retaining Ring 17 Latch Shaft Bushing and O-Ring (Qty. 2)
7 Seal Assembly Bolt 18 Diaphragm
8 Bolt Seal 19 Diaphragm Cover
9 Clapper Spring 20 Diaphragm Cover Cap Screws (Qty. 8)
10 Clapper Shaft 21 Latch Shaft
11 Clapper Shaft Bushing and O-Ring (Qty. 2)
20

19

18
17

11

15
21
17

16 1

2 10

3 11

9
13 4
12
5

6
8
14
7

Exaggerated for clarity


* NOTE: The 1½-inch/48.3-mm and 2-inch/60.3-mm valve sizes contain washers under the heads of
the cover plate bolts.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 6
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Trim Package Options: Air Supply Requirements for Dry Pilot Deluge Systems:
1 Pneumatic (Dry Pilot) Release The required air pressure for Series 769 FireLock NXT
Deluge Valves with dry pilot trim is 13 psi/90 kPa,
2 Hydraulic (Wet Pilot) Release regardless of the system supply pressure.
3 Electric Release If multiple Series 769 FireLock NXT Deluge Valves with
Trim packages include all required pipe and fittings. dry pilot trim are installed with a common air supply,
For trim package details and optional accessories, see isolate the systems with a spring-loaded, soft-seated ball
pages 13-15. For European trim and optional accessory check valve to ensure air integrity for each system. Good
details, see pages 16-18. practice is to include a ball valve for isolation and service
of each individual system.
Foam System Option:
The engineer/system designer is responsible for sizing
Black Trim for Foam Systems – If the valve is intended the compressor so that the entire system is charged to
for use in a foam system, black trim must be ordered, the required air pressure within 30 minutes. DO NOT
per NFPA requirements. Specify this requirement on the oversize the compressor to provide more airflow. An
order. oversized compressor will slow down or possibly prevent
Actuators: valve operation.
• Series 776 Low-Pressure Actuator – The Series If the compressor fills the system too fast, it may be
776 Low-Pressure Actuator is pneumatically necessary to restrict the air supply. Restricting the air
actuated and requires only 13 psi/90 kPa minimum supply will ensure that air being exhausted from an open
air pressure, regardless of the system supply sprinkler or manual release valve is not replaced by the
pressure. This actuator allows the system to operate air supply system as fast as it is being exhausted
with a low air or gas pressure of 7 psi/48 kPa.
Request submittal 30.65.
• Series 753-E Solenoid Valve – The Series 753-E
Solenoid Valve is designed for use with systems
that require electrical activation. Request submittal
30.63.
Optional Accessories:
• Series 760 Water Motor Alarm – The Series 760
Water Motor Alarm is a mechanical device that
sounds when a sustained flow of water occurs (such
as with an open sprinkler). Request submittal 30.32.
• Alarm Pressure Switch – Alarm Pressure Switches
are designed to activate electrical alarms and control
panels when a sustained flow of water occurs (such
as with an open sprinkler).
• Air Supply System – The air supply system contains
all components for establishing and maintaining
air in a pneumatic system. The compressor, low-
pressure alarms, ball valves, and required trim are
included in the air supply system.
• Air Compressor (See page 8 for more on the
Victaulic Series 7C7 Compressor Package)
• Air Maintenance Trim Assembly
• Alarm Panels
• Drain Connection Kit

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 7
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Compressor Sizing:

COMPRESSOR REQUIREMENTS
12

20 psi/138 kPa
13 psi/90 kPa
10
REQUIRED FLOW RATE (CFM)

0
1050

1300

1550

1800
300

550

800
50

SYSTEM CAPACITY (in gallons)

Base or Riser-Mounted Compressors: Shop Air or Tank-Mounted Air Compressors:


For base or riser-mounted compressors, the recom- In the event a compressor becomes inoperative, a
mended air pressure of 13 psi/90 kPa is the “on” or properly sized tank-mounted air compressor provides
“low” pressure setting for the compressor. The “off” the greatest protection for systems.
or “high” pressure setting should be 18 psi/124 kPa. When shop air or a tank-mounted air compressor is
Victaulic offers the Series 7C7 Compressor package used, the Series 757 Regulated AMTA must be installed.
for FireLock NXT devices which is riser-mounted and The Series 757 Regulated AMTA provides proper air
pre-set for the FireLock NXT pressure requirements as regulation from the air reservoir to the sprinkler system.
stated above. For information on the Series 7C7 pack-
age, consult publication 30.22. The Series 7C7 Com- For tank-mounted air compressors, the recommended
pressor package is only available in North America. air pressure of 13 psi/90 kPa should be used as the
set point for the air regulator. The “on” pressure of the
When a base or riser-mounted air compressor supplies compressor should be at least 5 psi/34 kPa above the
air to a Series 768 FireLock NXT Dry Valve, it is not set point of the air regulator.
necessary to install the Victaulic Series 757 Regulated
Air Maintenance Trim Assembly (AMTA). In this case,
the airline of the compressor connects to the trim at the
fitting where the Series 757 Regulated AMTA is normally
installed (refer to the applicable trim drawing). If the
compressor is not equipped with a pressure switch, the
Series 757P Air Maintenance Trim Assembly with
Pressure Switch should be installed. For information on
the Series 757 Regulated Air Maintenance Trim
Assembly, see publication 30.35. For information on
the Series 757P Air Maintenance Trim Assembly, see
publication 30.36.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 8
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Series 757 Regulated Air


Maintenance Trim Assembly: NOTICE

• Victaulic recommends a maximum of two Series


769 FireLock NXT Deluge Valves with dry pilot
trim per Series 757 Regulated AMTA.

Bill of Materials
1 1⁄8"/3.2 mm Restrictor
2 Slow Fill Ball Valve (Normally Open)
3 Air Regulator
4 Strainer (100 Mesh)
5 Spring-Loaded, Soft-Seated
Ball Check Valve 1
6
6 Fast Fill Ball Valve (Normally Closed)
2

4
5

Exaggerated for clarity

Series 757P Air Maintenance Trim


Assembly With Pressure Switch: NOTICE

• Victaulic recommends a maximum of two


Series 769 FireLock NXT Deluge Valves with
dry pilot trim per Series 757P AMTA with
Pressure Switch.

Bill of Materials 8
Item Qty. Description
1 1 Restrictor (½-inch NPT) 14
2 1 Strainer (½-inch NPT) 7
3 1 Swing Check (½-inch NPT)
4 1 Slow-Fill Ball Valve 16
(Normally Open)
5 1 Spring-Loaded, Soft-Seated 1
Check Valve 9
6 1 Pressure Switch
7 2 Compression Fitting, Straight 12
(¼-inch NPT x ¼-inch Tube) 5 4
8 1 Copper Tubing (¼-inch OD)
9 11 Close Nipple 13
(½-inch NPT x 1.13) 11
10 1 Nipple (½-inch NPT x 4.00)
11 1 90° Female Elbow (½-inch NPT)
12 4 Female Tee (½-inch NPT)
13 3 Union (½-inch NPT)
14 2 Reducing Bushing
(½-inch NPT x ¼-inch NPT)
15 1 Fast-Fill Ball Valve
(Normally Closed) 3
2
16 1 Pressure Switch Isolation Ball 10
Valve (Normally Open -
Lockable) FROM
COMPRESSOR 15

TO
SYSTEM
Exaggerated for clarity

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 9
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Compressor Requirements:
Settings for Air Supervisory Pressure Switches and
Alarm Pressure Switches
Air supervisory pressure switches are required for dry
systems and must be set according to the following
instructions. NOTE: Switches for Vic-Quick Risers are
pre-set at the factory.
Wire the air supervisory pressure switches to activate a
low-pressure alarm signal. NOTE: In addition, the local
authority having jurisdiction may require a high-pressure
alarm. Contact the local authority having jurisdiction for
this requirement.
Set the air supervisory pressure switches to activate at
2 – 4 psi (14 – 28 kPa) below the minimum air pressure
required, but not lower than 10 psi/69 kPa.
Wire the alarm pressure switch to activate a water flow
alarm.
Set the alarm pressure switch to activate on a pressure
rise of 4 – 8 psi/28 – 55 kPa.

Wet Pilot Line Charts:


Maximum allowable wet pilot line heights for specific
equivalent lengths.
Heights are based on ½" schedule 40 pipe and a ½"
sprinkler.

1½ – 2 inch/48.3 – 60.3 mm
140.0

120.0
300 psi
280 psi
MAXIMUM PILOT LINE HEIGHT (ft.)

100.0 260 psi


240 psi

80.0 220 psi


200 psi

180 psi
60.0
160 psi

140 psi
40.0 120 psi

100 psi

80 psi
20.0
60 psi
20 psi 40 psi

0.0
10 25 50 100 200 300 400 500 1000
LENGTH OF PIPE (ft.)

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 10
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Wet Pilot Line Charts:


Maximum allowable wet pilot line heights for specific
equivalent lengths.
Heights are based on ½" schedule 40 pipe and a ½"
sprinkler.

2½ – 3 inch/73.0 – 88.9 mm (Includes 76.1 mm)


140.0

300 psi
120.0
280 psi

MAXIMUM PILOT LINE HEIGHT (ft.) 100.0 260 psi

240 psi
220 psi
80.0 200 psi
180 psi

60.0
160 psi
140 psi

120 psi
40.0 100 psi

80 psi

60 psi
20.0 40 psi

20 psi

0.0
10 25 50 100 200 300 400 500 1000
LENGTH OF PIPE (ft.)

4 inch/114.3 mm
140.0
300 psi
280 psi
120.0

260 psi
MAXIMUM PILOT LINE HEIGHT (ft.)

100.0 240 psi


220 psi
200 psi
180 psi
80.0

160 psi
140 psi
60.0
120 psi

100 psi
40.0
80 psi

60 psi
20.0
40 psi

20 psi

0.0
10 25 50 100 200 300 400 500 1000
LENGTH OF PIPE (ft.)

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 11
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Wet Pilot Line Charts:


Maximum allowable wet pilot line heights for specific
equivalent lengths.
Heights are based on ½" schedule 40 pipe and a ½"
sprinkler.

6 inch/168.3 mm (Includes 165.1 mm)


250.0

300 psi
280 psi

200.0

MAXIMUM PILOT LINE HEIGHT (ft.)


260 psi
240 psi

150.0
220 psi

200 psi

100.0
180 psi

160 psi

140 psi
50.0 120 psi

100 psi
80 psi
60 psi
40 psi
20 psi
0.0
10 25 50 100 200 300 400 500 1000
LENGTH OF PIPE (ft.)

8 inch/219.1 mm
300.0

225 psi

250.0
200 psi
MAXIMUM PILOT LINE HEIGHT (ft.)

180 psi
200.0
160 psi

140 psi

150.0
120 psi

100 psi

100.0 80 psi

60 psi

50.0 40 psi

20 psi

0.0
10 25 50 100 200 300 400 500 1000
LENGTH OF PIPE (ft.)

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 12
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Pneumatic Release
(Dry Pilot) Deluge Configuration)
( Trim)

Series 769 FireLock NXT Deluge Valve with


Pneumatic Release (Dry Pilot) Deluge Trim
(Optional Accessories Also Shown)

Bill of Materials From System


Air Feed
1 Series 769 FireLock NXT Deluge Valve
2 FireLock Rigid Coupling (Optional/Sold 15
Separately – Comes Standard when VQR
To Pilot
Assembly is Ordered) Line
3 Water Supply Main Control Valve
19
(Optional/Sold Separately – Comes Standard
16 Location
when VQR Assembly is Ordered)
4 Drain Swing Check Valve A
5 Drip Cup with Cap 14
6 Alarm Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR
5 To Drip
Assembly is Ordered) 20 Cup
7 Series 729 Drip Check Valve Location

8 Diaphragm-Charge-Line Ball Valve A To Drip Cup


Location
(Normally Open) 4 A
13 12
9 3-in-1 Strainer/Check/Restrictor 21
Assembly
10 Series 760 Water Motor Alarm
(Optional/Sold Separately) Note 1
To System
11 Alarm Test Ball Valve 17
12 Diaphragm-Charge-Line Pressure 18 22
Gauge (0-300 psi/0-2068 kPa/0-20.7Bar)
13 Series 749 Auto Drain 9
22
14 Series 776 Low-Pressure Actuator
15 Air Manifold
11
16 Air Supervisory Pressure Switch
(Optional/Sold Separately – Comes Standard
when VQR Assembly is Ordered) 1 10
17 Water Supply Main Drain Valve - Flow Test
18 Water Supply Pressure Gauge
(0-300 psi/0-2068 kPa/0-20.7 Bar)
19 Drain Connection Kit (Optional/Sold
7
Separately – Comes Standard when VQR
Assembly is Ordered) To Drip Cup
2
20 System Main Drain Valve Location
21 Series 755 Manual Pull Station A 6
22 Gauge Valve
8

Exaggerated for clarity


From Water
Supply

Exaggerated for clarity


NOTE 1: Connection point for the Series 75D Water Column Device Kit

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 13
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Hydraulic Release
(Wet Pilot) Deluge Configuration
( Trim)

Series 769 FireLock NXT Deluge Valve with


Hydraulic Release (Wet Pilot) Deluge Trim
(Optional Accessories Also Shown)

Bill of Materials Location


1 Series 769 FireLock NXT Deluge Valve A
16
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered)
3 Water Supply Main Control Valve (Optional/
17 5 To Wet Pilot
Sold Separately – Comes Standard when VQR System
Assembly is Ordered) To Drip Cup
13 Location
4 Drain Swing Check Valve
5 Drip Cup with Cap 4 A 12
6 Alarm Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered)
7 Series 729 Drip Check Valve Note 1 To System
8 Diaphragm-Charge-Line Ball Valve
14 19
(Normally Open) 15
9 3-in-1 Strainer/Check/Restrictor 9
Assembly
10 Series 760 Water Motor Alarm 19
18
(Optional/Sold Separately)
11
11 Alarm Test Ball Valve 10
12 Diaphragm-Charge-Line Pressure
1
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)
13 Series 749 AutoDrain
14 Water Supply Main Drain Valve –
Flow Test
15 Water Supply Pressure Gauge 7 6
(0-300 psi/0-2068 kPa/0-20.7 Bar) To Drip
Cup
16 Drain Connection Kit (Optional/Sold 2 Location
Separately – Comes Standard when VQR
A
Assembly is Ordered) 8
17 System Main Drain Valve
18 Series 755 Manual Pull Station
19 Gauge Valve 3

From Water
Supply

Exaggerated for clarity

NOTE 1: Connection point for the Series 75D Water Column Device Kit

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 14
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

Electric Release Configuration

( Trim)

Series 769 FireLock NXT Deluge Valve with


Electric Release Trim
(Optional Accessories Also Shown)

Bill of Materials Location


1 Series 769 FireLock NXT Deluge Valve A
2 FireLock Rigid Coupling (Optional/Sold 16
Separately – Comes Standard when VQR
Assembly is Ordered) 20
3 Water Supply Main Control Valve (Optional/
Sold Separately – Comes Standard when VQR 18 5
Assembly is Ordered) 13 To Drip
To Drip Cup
4 Drain Swing Check Valve Cup Location
5 Drip Cup with Cap Location
4
A A 12
6 Alarm Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered)
7 Series 729 Drip Check Valve Note 1 To System
8 Diaphragm-Charge-Line
14
Ball Valve (Normally Open) 17
9
15
9 3-in-1 Strainer/Check/Restrictor
Assembly
10 Series 760 Water Motor Alarm 17
19
(Optional/Sold Separately)
11 Alarm Test Ball Valve 11
10
12 Diaphragm-Charge-Line Pressure
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar) 1
13 Series 749 AutoDrain
14 Water Supply Main Drain Valve –
Flow Test
15 Water Supply Pressure Gauge 7 6
(0-300 psi/0-2068 kPa/0-20.7 Bar)
16 Drain Connection Kit (Optional/Sold To Drip Cup
2 Location
Separately – Comes Standard when VQR 8
Assembly is Ordered) A
17 Gauge Valve
18 System Main Drain Valve
19 Series 755 Manual Pull Station 3
20 Series 753-E Solenoid Valve

From Water
Supply

Exaggerated for clarity

NOTE 1: Connection point for the Series 75D Water Column Device Kit

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 15
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

European Deluge Valve Station -


Pneumatic (Dry Pilot) Release Trim

Series 769 FireLock NXT Deluge Valve


(Optional Accessories Also Shown.
Note: Only Vic-Quick Riser configuration is VdS
approved.)

Bill of Materials From System


Air Feed
1 Series 769 FireLock NXT Deluge Valve
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered) To Location To Pilot 15
3 Water Supply Main Control Valve 23 Line
A
(Optional/Sold Separately – Comes 16
Standard when VQR Assembly is Ordered) Location
4 Drain Swing Check Valve
19 B 14
5 Drip Cup with Cap
6 Alarm Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR 13

Assembly is Ordered) 20
To Drip Cup
5 Location
7 Series 729 Drip Check Valve
8 Diaphragm-Charge-Line Ball Valve B 12
(Normally Open – Lockable) 21
9 3-in-1 Strainer/Check/Restrictor 4
Assembly
10 Series 760 Water Motor Alarm To Drip Cup
Note 1 To System Location 22
(Optional/Sold Separately)
11 Alarm Test Ball Valve
B
(Normally Closed – Lockable) 17
9
12 Diaphragm-Charge-Line Pressure 18
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)
13 Series 749 Auto Drain 22
14 Series 776 Low-Pressure Actuator Location
15 Air Manifold A
16 Air Supervisory Pressure Switch 1
(Optional/Sold Separately – Comes
Standard when VQR Assembly is Ordered) 11 8
17 Water Supply Main Drain Valve - Flow Test
18 Water Supply Pressure Gauge 24 10
(0-300 psi/0-2068 kPa/0-20.7 Bar)
19 Drain Connection Kit (Optional/Sold 2

Separately – Comes Standard when VQR


Assembly is Ordered)
7
20 System Main Drain Valve
To Drip Cup
21 Series 755 Manual Pull Station Location
6
3
22 Gauge Valve B
23 Alarm Line Ball Valve
(Normally Open – Lockable)
24 Water Motor Alarm Shutoff Valve
(Normally Open – Lockable)* From Water
Supply

Exaggerated for clarity

NOTE: VicQuick Riser must be specified for VdS approval.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 16
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

European Deluge Valve Station -


Hydraulic (Wet Pilot) Release Trim

Series 769 FireLock NXT Deluge Valve


(Optional Accessories Also Shown.
Note: Only Vic-Quick Riser configuration is VdS
approved.)

Bill of Materials
1 Series 769 FireLock NXT Deluge Valve
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR To Location
Assembly is Ordered) A
3 Water Supply Main Control Valve
20
(Optional/Sold Separately – Comes Location
Standard when VQR Assembly is Ordered) B
4 Drain Swing Check Valve
16
5 Drip Cup with Cap
To Wet Pilot
6 Alarm Pressure Switch (Optional/Sold System
Separately – Comes Standard when VQR 17 13
5
Assembly is Ordered) 12
7 Series 729 Drip Check Valve
8 Diaphragm-Charge-Line Ball Valve
18
(Normally Open – Lockable) 4
9 3-in-1 Strainer/Check/Restrictor
Assembly
10 Series 760 Water Motor Alarm Note 1
To System To Drip 19
(Optional/Sold Separately) Cup
Location
11 Alarm Test Ball Valve 15
(Normally Closed – Lockable) 14
B 9

12 Diaphragm-Charge-Line Pressure
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)
13 Series 749 AutoDrain 19
14 Water Supply Main Drain Valve – Flow Test Location
15 Water Supply Pressure Gauge A
(0-300 psi/0-2068 kPa/0-20.7 Bar) 1
16 Drain Connection Kit (Optional/Sold
Separately – Comes Standard when VQR 11 21
8
Assembly is Ordered)
17 System Main Drain Valve
10
18 Series 755 Manual Pull Station
19 Gauge Valve 2
20 Alarm Line Ball Valve 6
(Normally Open – Lockable)
21 Water Motor Alarm Shutoff 7
Valve (Normally Open – Lockable)*
3
To Drip Cup
Location
B

From Water
Supply

Exaggerated for clarity

NOTE: VicQuick Riser must be specified for VdS approval.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 17
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

European Deluge Valve Station -


Electric Release Trim

Series 769 FireLock NXT Deluge Valve with


(Optional Accessories Also Shown Note:
Only Vic-Quick Riser configuration is VdS approved.)

Bill of Materials
1 Series 769 FireLock NXT Deluge Valve
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR
21 To Location
Assembly is Ordered)
3 Water Supply Main Control Valve A
16
(Optional/Sold Separately – Comes Location
Standard when VQR Assembly is ordered)
B 20
4 Drain Swing Check Valve
5 Drip Cup with Cap
6 Alarm Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR 18
13 12
Assembly is Ordered) 5
7 Series 729 Drip Check Valve
To Drip Cup
8 Diaphragm-Charge-Line Location 19
Ball Valve (Normally Open – Lockable) B
4
9 3-in-1 Strainer/Check/Restrictor
Assembly
Note 1
10 Series 760 Water Motor Alarm (Optional/ To Drip Cup
To System 17 9
Sold Separately) Location
11 Alarm Test Ball Valve B
(Normally Closed – Lockable) 14
12 Diaphragm-Charge-Line Pressure
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)
13 Series 749 AutoDrain
14 Water Supply Main Drain Valve – Flow Test 17 Location
15 Water Supply Pressure Gauge
A
(0-300 psi/0-2068 kPa/0-20.7 Bar) 1
8
16 Drain Connection Kit (Optional/Sold
Separately – Comes Standard when VQR
11
Assembly is Ordered)
17 Gauge Valve 10
18 System Main Drain Valve
22
19 Series 755 Manual Pull Station
2
20 Series 753-E Solenoid Valve
6
21 Alarm Line Ball Valve
(Normally Open – Lockable)
7
22 Water Motor Alarm Shutoff
Valve (Normally Open – Lockable)* 3 To Drip Cup
Location
B

From Water
Supply

Exaggerated for clarity

NOTE: VicQuick Riser must be specified for VdS approval.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 18
victaulic.com | NXT Deluge Valve | Series 769 | Publication 30.81

WARNING

• This product must be installed by an experienced, trained installer, in accordance with


the instructions provided with each valve. These instructions contain important
information.

Failure to follow these instructions may result in serious personal injury, property
damage, or valve leakage.

If you need additional copies of this product literature or the valve installation
instructions, or if you have any questions about the safe installation and use of this
device, contact Victaulic Company, P.O. Box 31, Easton, PA 18044-0031 USA,
Telephone: 001-610-559-3300.

Installation Note
Reference should always be made to the appropriate Installation, Maintenance, and This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Testing Manual included with each shipment of Victaulic products. These manuals are also to be installed in accordance with current Victaulic installation/assembly instructions.
available in PDF format on our website at victaulic.com Victaulic reserves the right to change product specifications, designs and standard
equipment without notice and without incurring obligations.
Warranty
Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks
Victaulic ® and FireLock® are registered trademarks of Victaulic Company.

30.81 4221 Rev G Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 19
...Technical Data Sheets and Catalogue
B. Foam Nozzle
FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS 40.73
V26, K2.8/K5.6 VNIIPO
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS

Pendent Open Foam Nozzle


V2601 and V2603

Model V26 Pendent Foam Nozzles are most typically used with various foam compounds such
as A.F.F.F., Fluoroprotein, Protein and Alcohol type foam liquids for the extin­guishment and/or
control of hydrocarbon based, polar solvents, and other flamma­ble liquid fires.
Model 26 Foam Nozzles are available in both 3⁄8" and 1/2" nominal orifice sizes and have a 1/2"
NPT male thread. The Foam Nozzle is avail­able in the open style for use with deluge systems.
The activation of the deluge valve causes the discharge of foam solution onto the floor in a parabolic
shaped discharge pattern. FOAM NOZZLE

TECHNICAL SPECIFICATIONS: Models: V2601 and V2603


Style: Pendent Foam Nozzle
Nominal Orifice Size: See chart on page 2.
K-Factor: See chart on page 2.
Nominal Thread Size: See chart on pate 2.
Max. Working Pressure: 175 psi/1200 kPa
Min. Recommended Operating Pressure: 
15 psi/103 kPa

Material Specifications
Frame: Bronze
Deflector: Brass
Screw: Brass
Screen Mesh: Stainless Steel
Mounting Plate: Stainless Steel
Retaining Ring: Stainless Steel

Accessories
Installation Wrench:
• Model V26 Foam Nozzle Wrench fits all
V26 Series frames.
Finishes:
• Plain

For cabinets and other accesso­ries refer to


separate sheet.

JOB/OWNER CONTRACTOR ENGINEER


System No._______________________________ Submitted By_____________________________ Spec Sect________________ Para____________
Location_ ________________________________ Date ____________________________________ Approved_ _______________________________
Date ____________________________________

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_C 40.73_
FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS 40.73
V26, K2.8/K5.6
Pendent Open Foam Nozzle
V2601 and V2603

APPROVALS/LISTINGS Orifice Thread Nominal


Model Size Size K-Factor Dimensions
Inches Inches Imperial Inches (Length 5 Width)
mm mm S.I.^ mm
3/8 1/2 2.8
V2601
10 13 4.0 2 1/2 x 3 1/4
1/2 1/2 5.6 64 x 87
V2603
13 13 8.1
‡ Listings and approval as of printing.
^ For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.

ORDERING INFORMATION Please specify the following when ordering:

Sprinkler Model Number

K-Factor

Quantity

Sprinkler Finish

WARNING
WARNING
• Always read and understand installation, care, and maintenance
instructions, supplied with each box of sprinklers, before proceeding
with installation of any sprinklers.
• Always wear safety glasses and foot protection.
• Depressurize and drain the piping system before attempting to install,
remove, or adjust any Victaulic piping products.
• Installation rules, especially those governing obstruction, must be
strictly followed.
• Painting, plating, or any re-coating of sprinklers (other than that
supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury
and/or property damage.
The owner is responsible for maintaining the fire protection system and
devices in proper operating condition. For minimum maintenance and
inspection requirements, refer to the current National Fire Protection
Association pamphlet that describes care and maintenance of sprinkler
systems. In addition, the authority having jurisdiction may have
additional maintenance, testing, and inspection requirements that must
be followed.
If you need additional copies of this publication, or if you have any
questions about the safe installation of this product, contact Victaulic
World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031
USA, Telephone: 001-610-559-3300.

VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

40.73_ REV_C
FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS 40.73
V26, K2.8/K5.6
Pendent Open Foam Nozzle
V2601 and V2603

DISTRIBUTION PATTERNS Models V2601


K2.8 Pendent Foam Nozzle Distribution Pattern – Trajectory

8'
2.4 m

6'
1.8 m

4'
1.2 m

2'
0.6 m

0
2' 4' 6' 8' 10' 12' 14'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m

15 PSI
103 kPa

Models V2603
K5.6 Pendent Foam Nozzle Distribution Pattern – Trajectory

8'
2.4 m

6'
1.8 m

4'
1.2 m

2'
0.6 m

0
2' 4' 6' 8' 10' 12' 14'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m

15 PSI
103 kPa

NOTES:
1. Data shown is approximate and can vary due to differences in installation.
2. These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these
specific Victaulic FireLock Automatic Sprinklers. They are provided as information for guidance in
avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for
installation. Refer to the appropriate NFPA National Fire Code and the authority having jurisdiction
for specific information regarding obstructions, spacing limitations and area of coverage requirements.
Failure to follow these guidelines could adversely affect the performance of the sprinkler and will
void all Listings, Approvals and War­ranties.
3. All patterns are symmetrical to the centerline of the waterway.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_C 40.73_
FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS 40.73
V26, K2.8/K5.6
Pendent Open Foam Nozzle
V2601 and V2603

WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.

NOTE This product shall be manufactured by Victaulic Company. All products to be installed in accordance
with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product
specifications, designs and standard equipment without notice and without incurring obligations.

WCAS-7AVMUB

For complete contact information, visit www.victaulic.com


40.73 3181 REV C UPDATED 01/2008
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

40.73
...Technical Data Sheets and Catalogue
C. Vertical Bladder Tank
D. Ratio Flow Controller
BRISTOL FOAM PROPORTIONING UNIT
B LA DDE R TA NK W IT H R AT IO F LOW C ONTROLLE R
UL Listed

Bladder tanks are components of balanced-pressure proportioning


systems, which often are installed on helicopter decks and in small
aircraft hangers, storage facilities, and warehouses.

Bristol UL Bladder Tanks with Ratio Flow Controllers are accurate,


dependable, and provide effective foam fire protection.

FEATURES

 Low Proportioning Losses

 Manual/Automatic Operation

 Horizontal/Vertical Mounting Options

 UL LISTED with AFFF3% 8 AR-AFFF3% Foam Concentrates

 Designed & Constructed as per ASME Sec. VIII Div.1 (Optional -


ASME U Stamped)
Horizontal Bladder Tank
 High reliability and design simplicity minimizes chances of system
failure

Bladder Tank
Orientation Vertical Horizontal
Capacity 200L-15,000L 400-15,000L
SPECIFICATIONS

Design Code ASME Sec.VIII Div.I Latest Edition


Max. Working Pressure 12.06bar (175psi)
Hydrostatic Test Pressure 18.09bar (263psi)
Internal Finishing Coal Tar Epoxy
External Finishing Painted Epoxy Flame Red (RAL 3000)

Vertical Bladder Tank

© Bristol Fire Engineering. All rights reserved. (05/2015)

Bristol Reserves the right to make changes in specifications and discontinue models at any time without prior notice. WWW.BRISTOL-FIRE.COM
BRISTOL FOAM PROPORTIONING UNIT
B LA DDE R TA NK W IT H R AT IO F LOW C ONTROLLE R
UL Listed

Horizontal Bladder Tank

Part No. Part Name Material


1 Foam Vessel Carbon Steel
Foam Bladder Nylon Reinforced Nitrile Rubber
2
(BUNA-N)
Foam Proportioner Carbon Steel with Stainless Steel
3
Intls. / Stainless Steel
COMPONENTS

4 Spool Piece Carbon Steel


5 Foam Piping Stainless Steel
6 Water Piping Carbon Steel
7 Foam Supply Valve Stainless Steel
8 Water Charging Valve Stainless Steel
9 Bladder Vent / Bladder Drain Stainless Steel
10 Vessel Vent / Vessel Drain Stainless Steel
11 Thermal Expansion Relief Valve Copper Alloy / Stainless Steel

Vertical Bladder Tank

© Bristol Fire Engineering. All rights reserved. (05/2015)

Bristol Reserves the right to make changes in specifications and discontinue models at any time without prior notice. WWW.BRISTOL-FIRE.COM
BRISTOL FOAM PROPORTIONING UNIT
B LA DDE R TA NK W IT H R AT IO F LOW C ONTROLLE R
UL Listed

Part No. Part Name Material


1 Body Carbon Steel / Stainless Steel
COMPONENTS

2 Water Nozzle Stainless Steel

3 Foam Nozzle Stainless Steel

4 Drain Valve Stainless Steel

Ratio Flow Controller


Model BBT-RFC2 BBT-RFC3 BBT-RFC4 BBT-RFC6 BBT-RFC8
A (NB) 50 80 100 150 200
B (NB) 25 40 40 50 65
C 1000
SPECIFICATIONS

Nominal Flow Range (L/m) 75-1000 200-3200 400-6200 1000-11500 3000-20000


Proportioning Ratio 3%
Max. Working Pressure 12.06bar (175psi)
Hydrostatic Test Pressure 18.09bar (263psi)
Internal Finishing Coal Tar Epoxy
External Finishing Painted Epoxy Flame Red (RAL 3000)
Flange Drilling As per ANSI B 16.5, 150#, RF
Approval UL Listed with AFFF 3% and AR-AFFF 3x3%

© Bristol Fire Engineering. All rights reserved. (05/2015)

Bristol Reserves the right to make changes in specifications and discontinue models at any time without prior notice. WWW.BRISTOL-FIRE.COM
...Technical Data Sheets and Catalogue
E. Aqueous Film-Forming Foam
AQUEOUS FILM-FORMING FOAM 3%
T EK NOS OL AF -1- 3F
UL 162

I. DESCRIPTION
Teknosol AF-1-3F is superior quality aqueous film-forming foam which can be used at the specified concentration to extinguish fires of non – polar
hydrocarbon fuels. This extinguishing agent is suitable for use with most types of proportioning and discharge equipment. AFFF foam concentrates
are designed for rapid fire knockdown by producing a thin aqueous film which helps to prevent the release of fuel vapors. The foam blanket from
which the film forming liquid drains separates oxygen from the fuel surface, extinguishes the fire and prevents re-ignition. The water content of the
foam provides a cooling effect. The aqueous film type 3% is produced by the fluorocarbon surfactant reducing the surface tension of the foam solu-
tion to a point where the solution can be supported by the surface tension of the fuel. Teknosol AF-1-3F AFFF 3% provides excellent penetrating
and wetting qualities when used on Class A fires also. This is important when extinguishing deep-seated fires in wood, paper, rubber and other
ordinary combustibles.

II. USE
It may be used with Foam Chambers, Air-aspirating and non air-aspirating sprinkler heads or spray nozzles, Standard water fog nozzles for hand
lines, Foam Makers for use with either Floating Roof Storage tanks or Dike/Bund protection systems and monitors, High back pressure foam
makers for subsurface base injection system (hydrocarbon type fuels only). Teknosol AF-1-3F is not compatible with galvanized pipe or fittings in an
undiluted form

III. DOSAGE
Teknosol AF-1-3F should be used as a 3% proportioned solution in fresh or sea water. It may be also used and stored as 3% pre-mix in fresh /
portable water. The correct proportioned or mixture ratio is 3 parts of concentrate and 97 parts of water.

IV. SPECIFICATIONS
Specific gravity @ 20°C 1.02 + 0.05 g / ml Pour Point -1ºC
pH @ 20°C 6.5 - 8.5 Storage temperature 2ºC to 50ºC
Viscosity @ 20ºC < 10 cst Foam Expansion Low > 7
Suspended sediment (v/v) < 0.1 % Foam Drainage 25% 3 - minutes
Freezing point -2°C

V. STORAGE AND HANDLING

When stored in the drums supplied the material has a long shelf life. The minimum and maximum usable temperatures for Teknosol AF-1-3F
concentrate are 2ºC and +50ºC respectively and shelf life should be 10 years when stored in original containers. If inadvertently frozen, thawing will
render the product completely usable.

Teknosol AF-1-3F may be stored in fiber glass, polyethylene or stainless steel containers. For bulk storage, mild steel tanks may be used provided
the internal surface is coated with a protective coating such as epoxy. The use of galvanized material should be avoided for storage vessels and
...Technical Data Sheets and Catalogue
F. Extinguishant Control Panel
EXTINGUISHANT CONTROL PANEL

FEATURES:

 Three detection zones as standard


KM 598387  Any single zone or any combination of zones can be configured
to release

 Configurable first stage sounder delays

 Configurable detection delays

 Zero time delay upon manual release option

 Compatible with I.S. barriers

 Non-latching zone input option to receive signals from other


systems such as aspirating equipment

 Configurable extinguishant duration up to 5 minutes in 5


seconds steps

 Countdown timer shows time remaining until release


BF-ECP3DCSM
 Supports up to seven, four wire status indicators

 Built-in Extract Fan Control

Designed and manufactured to the highest standards in a quality controlled environment and with European EN-12094-1
approvals, the BF-ECP Series extinguishant releasing panel offers outstanding value and performance for small to medium
fixed firefighting installations.

With three detection zones as standard, extinguishant release can be configured to activate from any combination of
detection zone inputs to allow (among other combinations) any two from three type activations such as would be required
for detection in ceiling void, room and floor void applications.

The extensive configuration options of the BRISTOL allow the functionality of the system to be extensively modified while
still complying with the requirements of the controlling standard for the equipment (EN 12094-1, EN54-2 and EN54-4).

The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until
extinguishant release for added user safety.

The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system
status.

With all the electronics mounted on a single easy removable, steel plate BRISTOL panels are both robust and easy to install.
EXTINGUISHANT CONTROL PANEL

Technical Information
Construction 1.2 mm mild sheet steel
IP Rating IP30
Finish Epoxy powder coated
Color-lid and box Red
Color-controls plate and labels RAL 7047 light gray satin
Mains supply 230V AC, 50Hz +10% - 15% (100 Watts maximum)
Mains supply fuse 1.6 Amp ( F1.6A L250V)
Power supply rating 3 Amps total including battery charge 28V +/- 2V
Maximum ripple current 200 millivolts

Battery type Two 12 Volt 7Ah sealed lead acid in series


Battery charge voltage 27.6VDC nominal (temperature compensated)
Battery charge current 0.7A maximum
Battery fuse 20mm, 3.15A glass
Maximum current draw from batteries 3 Amps
Quiescent current of panel in mains fail 0.095A
R0V output Fused at 500mA with electronic fuse
DATA & SPECIFICATIONS

Sounder outputs 21 to 28V DC Fused at 500mA with electronic fuse


Fault relay contact rating 30VDC 1A Amp maximum
Fire relay contact rating 30VDC 1A Amp maximum
Local fire relay contact rating 30VDC 1A Amp maximum
First stage contact rating 30VDC 1A Amp maximum
Second stage contact rating 30VDC 1A Amp maximum
Extract contact rating 30VDC 1A Amp maximum
Zone quiescent current 2mA maximum
Terminal capacity 0.5mm to 2.5mm2 solid or stranded wire
2

Number of detectors per zone Dependent on type


Number of sounders per circuit Dependent on type and current consumption
Detection circuit end of line 6K8 +/- 5% ½ Watt resistor
Monitored input end of line 6K8 +/- 5% ½ Watt resistor
Sounder circuit end of line 10K +/- 5% ¼ Watt resistor
Extinguishant output end of line 1N4004 Diode
No. of detection circuits 3
No. of sounder circuits 2 x 1st Stage, 1 x 2nd Stage
Extinguishant release output Fused at 1 Amp
Extinguishant release delay Adjustable 0 to 60 seconds (in 5 seconds steps)
Extinguishant release duration Adjustable 60 to 300 seconds (in 5 seconds steps)
SIL, AL, FLT, RST inputs Switched -ve, max resistance 100 Ohms
Zone normal threshold 8K Ohms to 1K Ohms
EXTINGUISHANT CONTROL PANEL

Technical Information
Detector alarm threshold 999 Ohms to 400 Ohms
Call point alarm threshold 399 Ohms to 100 Ohms
DATA & SPECIFICATIONS

Short circuit threshold 99 Ohms to 0 Ohms


Head removal condition 15.5 to 17.5 volts
Cabling FP200 or equivalent
Monitored inputs normal threshold 8K Ohms to 1K Ohms
Monitored inputs alarm threshold 999 Ohms to 100 Ohms
Monitored inputs Short circuit threshold 99 Ohms to 0 Ohms
Status unit/Ancillary board connection Two wire RS485 connection
Status unit power output Fused at 500mA with electronic fuse

Programmable Functions Access Level 3


Access Level 2  Sounder Delay
 Test Zone 1 – 3  Coincidence Detection
 Disable Zone 1 – 3  Disable Panel Features
 Disable 1st Stage sounders  Zone Alarm Delays (Detectors)
 Disable Preactivated (1st stage) relay  Zone Alarm Delays (Call Points)
 Disable Activated (2nd stage) relay  Configure Zone for I.S. Barrier use
 Disable Extract Fan output  Zone Short Circuit Alarm
 Disable Manual Release inputs  Zone Non-Latching
 Disable Extinguishant sub-system  Zone Inputs Delay
 Activate sounder Delays  Extinguishant Release Time Delay
 Activate extract output  Extinghuishant Release Duration Timer
...Technical Data Sheets and Catalogue
G. Heat Detector
H. Smoke Detector
DETECTORS
C ONVE NT IONAL DUA L HE AT DE TEC TOR
LPCB Approved, EN 54-5

Photo-electric Smoke Detectors are activated when smoke particles


enter the light path, and some of the light is scattered by reflection
and refraction onto the sensor. The light signal is processed and used 1174b-(cl-3)

to convey an alarm condition when it meets the preset criteria.

FEATURES

 Filter designed in both software and hardware enhance anti-


interference ability

 PCB board inside is sealed with full protection

 Use thermal sensor with high sensitivity, enhance quick


response to variation of temperature

 Talented design of structure without a single screw

 Compatible with wide range of conventional panel or interface

Conventional Dual Heat Detector — B61-2001


Operating Voltage 9VDC ~ 28VDC
Quiescent Current ≤60uA
Alarm Current 10mA ≤I ≤ 50mA
LED indicator Red, flashing every 2s ~ 4s when standby; Illuminating when alarm fire
Remote indicator output 10kΩ resistor is required
SPECIFICATIONS

Power-Up Time ≤ 10s


Class A1R
Wiring Method Polarized two-wire
Ingress Protection Rating IP32
Temperature -10⁰C ~+ 55⁰C
Humidity ≤95%, non-condensing
Dimension Diameter: 100mm, Height: 43mm (w/out base)
Weight About 120g
DETECTORS
C ONVE NT IONAL OPT IC A L S MOK E D ETE CTOR
LPCB Approved, EN 54-7

Optical Smoke Detector are activated when smoke particles enter


the light path, and some of the light is scattered by reflection and
refraction onto the sensor. The light signal is processed and used to 1174a-(cl-3)
convey an alarm condition when it meets the preset criteria.

FEATURES

 Intelligent drift compensation to the variation of external


environment (temperature, humidity, dust, static)

 Can accurately detect the chronic fire happened in 24 hours

 Intelligent algorithm and judgment, warning reminder for dirty


and cleaning

 Filter designed in both software and hardware, enhance the


ability of anti-interference

 PCB board inside is sealed with full protection

 Unique chamber design for protection against dust, insects and


other external interferences

 Talented design of structure without a single screw

 Compatible with a wide range of conventional panel or interface

Conventional Optical Smoke Detector — B61-1001


Operating Voltage 9VDC ~ 28VDC
Quiescent Current ≤60uA
Alarm Current 10mA ≤I ≤ 50mA
LED indicator Red, flashing every 2s ~ 4s when standby; Illuminating when alarm fire
SPECIFICATIONS

Remote indicator output 10kΩ resistor is required


Power-Up Time ≤ 10s
Wiring Method Polarized two-wire
Ingress Protection Rating IP32
Temperature -10⁰C ~+ 55⁰C

Humidity ≤95%, non-condensing


Dimension Diameter: 100mm, Height: 43mm (w/out base)
Weight About 120g
...Technical Data Sheets and Catalogue
I. Sounder Strobe
J. Fire Alarm Bell
ALARM DEVICES
C ONVE NT IONAL S OU ND ER STROB E
LPCB Approved, EN54-3

FEATURES

 Alert Sound and flash combined in one unit


1174c-(cl-3)
 A select of 16 different tones

 Using ultra bright LEDs as source for light indication

 Fully synchronized operating frequencies and LED beacon

 Low power consumption

 Plug-in structure design for easy installation

 Compatible with a wide range of conventional panel or interface

Conventional Sounder Strobe — B61-6301


Operating Voltage 20VDC ~ 28VDC
Alarm Current ≤35mA
SPECIFICATIONS

Flashing Frequency 1.4 x (1± 20%) Hz


Ingress Protection Rating IP21C
Temperature -10⁰C ~ + 50⁰C
Humidity ≤95%, non-condensing
Dimensions (LxWxH): 152mm x 91mm x 49.5mm
Weight About 210g
ALARM DEVICES
F IRE A LA R M BE LL
EN54, LPCB Approved

Bristol Fire Alarm Bells have low power consumption and long
operating life.

FEATURES

 Electricity insulating base

 Can accept 2.5mm terminal cables

 Fitted with 2 series diodes for fault monitoring

EN54 AE 50203154 0001


506e-(cl-2)

MODEL BF-AB-0418
Voltage 24VDC
Current 25mA
Sound Output 93dB @ 1m
SPECIFICATIONS

Movement Motor, Pinion and Striker


Movement Feature DC Motor, Acetral Gear Wheel,
Steel Striker
Material Steel Plate
Base Plate Molded Black Polycarbonate
Dimensions Ø6‖ (152mm) x 58mm (H)
Weight ≈850g
III. CD Certificates
• -
;._ . , , , , ,

Ill <.· .
i
~~~~~~~~~~~
K36 =~-' ill ~.)
2018 • • . -:11 ~
-~J---

19 - 19 :~l~I~~

~.:i · t?i.Jll tUW.U <a.oL::.tt O.Jl.:i)'I - -• -• -- -


United Arab Em irates
88869 529724 . , . t .-: ....
ea~~->: ___ ~..)>-_ _.=-_
.:J\ ~\

- - - - -- - - - -
Ministry of I nterior - _ft......:31 u~ ~I ~ .1ll:.. ~_>ill ~\...a ~I
DCD General Directorate
~->---11 u l.,.>--l=i

12282 :'-;-1.~ 04-3414748 04-3472900 Uri~\ ~f--..-.9..;


Tel .: 009714 261 1111 -- · -- - - -- -
Fax : 009714 26 12449 L....s~1w1.J 1¥

P.O. Box 11377 Dubai


United Arab Emirates
ameed@c~r~dex.com ~.J_jiS.l'Jl J.J~I/ c9yJI

f2018/11_
/2_6_~ f2012/04/12 t~...J~ ~L___:i
k 1t
t;_;l. j 31 o~I o~'il.J~IJLJI JJ£:.
Emergency • ~, .•... ~::t\J$ 3 LJ:!' ll ~~I J~
U:! ~
0 0
-,.

997
www.dcd.gov. ae
'"

~~~~~~.:~~21~
_ 6__.I =~Y1' ~_)
.__K3
.__2_0_1s__.I =~Y1' ~

.;. ..... -::w., • ~·;:; -


(19 - 7) I =~'Y1' ~~
- ..
,.- <?~·t-'!l
~-- -

l~~~~~~~~L
~---~---~-~
~~~~~~~~-'j,~~
Special Svstem Water Control Valves. Deluge Type
10378 VLFI.
2018/10/12 UL-USA VICTAULIC Models: ·769,
EX5197
<,r.~ -~..i.t1 t~.JJS a..w1 ;.J1~~1 Sizes: 1-112, 2, Z-112, 76.1 mm, 3, 4, 6, 165.1 mm and 8 in,
Rated Pressure: 300 psi, ~
United Arab Emirates Installation: Vertical
Ministry of Interior
DCD General Directorate Special System Water Control Valves. Deluge Type .. '
...;

1. Models: 869E,
Sizes: 1-112, 2, 2-112, 3, 4, 6 and 8 in,
Tel.: 009714 2611111 Rated Pressure: 250 psi, ..· -
VLFI. Installation: Vertical and Horizontal.
Fax : 009714 2 61 2449 2018/10112 10378 UL-USA VICTAULIC 2. Models: 869Y, ~
EX5197
Sizes: 3, 4, 6, 8 and 10 in,
P.O. Box 11377 Dubai Rated Pressw:e: 365 psi, 1 ~.-
United Arab Emi r ates Installation: Vertical and Horizo ntal. li .•
3. Models: 869, I!
Sizes: 1-112, 2,2-112, 3, 4, 6, ~ and 10 in, :... ,_
Rated Pressure: 300 psi,
Installation: Verticaland Horizontal.
ts.) 'J't--....b._._.
tt
Emergency :~

997
www.dcd.gov.ae
• -
;._ . , , , , ,

Ill <.· .
i
~~~~~~~~~~~
K36 =~-' ill ~.)
2018 • • . -:11 ~
-~J---

19 - 19 :~l~I~~

~.:i · t?i.Jll tUW.U <a.oL::.tt O.Jl.:i)'I - -• -• -- -


United Arab Em irates
88869 529724 . , . t .-: ....
ea~~->: ___ ~..)>-_ _.=-_
.:J\ ~\

- - - - -- - - - -
Ministry of I nterior - _ft......:31 u~ ~I ~ .1ll:.. ~_>ill ~\...a ~I
DCD General Directorate
~->---11 u l.,.>--l=i

12282 :'-;-1.~ 04-3414748 04-3472900 Uri~\ ~f--..-.9..;


Tel .: 009714 261 1111 -- · -- - - -- -
Fax : 009714 26 12449 L....s~1w1.J 1¥

P.O. Box 11377 Dubai


United Arab Emirates
ameed@c~r~dex.com ~.J_jiS.l'Jl J.J~I/ c9yJI

f2018/11_
/2_6_~ f2012/04/12 t~...J~ ~L___:i
k 1t
t;_;l. j 31 o~I o~'il.J~IJLJI JJ£:.
Emergency • ~, .•... ~::t\J$ 3 LJ:!' ll ~~I J~
U:! ~
0 0
-,.

997
www.dcd.gov. ae
K36 I =~Y1' ~.)
201s I =~yi1 4.l....
I (19 - 1s) I :~1yi1 .')~

o ~ I A::i.>=!I CilJl.o,..1 a!J.l . ~..lfiil~ .ow.;. ' ii\S_,JJ ~ . - ~I ~ ,


- -~ "'~ ~ ....,-. . -~.~:£-.~ ~s: . ~
~,.---~; - • ~-""'!' - · -_,;;.- -:.
-~r-l • '<'-"°"!' -~-- - - --. ~---=-- -' ..
;. 1 ~ 1 OJIJJ
~:;ll >.# .. . "- ~jl\•. I ~. • ,•~;,:l..<.ll : <i , . ~ -
- •;- -: . --
;: .f
4 I

- ·-
<:r..:i - t,?i..ill t~..1.11 ~WI o.;l.:i)'I I FOAM EQUIPMENT ! ; '°'. .
VERTICAL AND HORIZONTAL BLADDER TANKS ' - -~-
Un i ted Arab Emira t es WITH RATIO FLOW CONTROLLERS ".
I· '
Min i stry of I nterior I.,<·. -
- 53-3963 GAL CAPACITY ASME BLADDER TANKS FOR
DCD General Directorate GHXV. VERTICAL AND HORIZONTAL INSTALLATION FOR
2019/02/05 17921 . INDIA UL BRISTOL 31
~
EX26946 USE WITH THE FOLLOWING RATIO CONTROLLERS: .-
1 MODEL :BBT-RFC2-2" ratio controller ..
2 MODEL :BBT-RFC3--3" ratio controller
-
Tel.: 009 7 1 4 261111 1
3 MODEL :BBT-RFC4-4" ratio controller
Fax: 009 7 14 2612449 - - 4 MODEL :BBT-RFC6-6" ratio controller -----
5 MODEL :BBT-RFC8-8" ratio controller I·.

P.O. Box 11377 Dubai


United Arab Em i ra t es
--
,e:'tJ • 2013;,:...i1505\e< ~ ~.~fli!Jl .:.t...,;. e@'J.,:.,,; 2017 ;,:...i Gl3l i§,i .s;ljJ!J ool>-<,)!) ,.,l\ iJ.::..1.~,..,;3.,.1 ,,.; ~ :<.i,1,;..o , ~_, ,..,_,.;..n e full<...i.n;;i.." ll Je c:..ue,,..;.s,n a .21
. i j...I ~ ~~ -.:.1,jYsJ\ wtJ~ Jf µ...pµ.. >&,;; f '& 1~ 'i1 ~,J.."11 Ci!t 0§~i ~Ab .u
~""""'h ~ lilJ'-""1_,.!! .:.L>o...nU..O, .,..s.p.;.s,,D,~ .22

ls..JIJ t, 1 ! • •J!!l clO C:.. .HI<&.>?~~ .:.u.,ii , ,.; °'""'"


,,i ,mUa...,.iyt=-gl:J fli.:.!l :w.n •.:lh1 f:J,,i .23
'1;:?11 , ~IJI <&,Al •~ .:;.;;_.ip....!1 ~'1,t:!:!! , )<.J . J.,.&lliJ-'il clOC:.._,.:l..lJJ;..:;..J!.:.i......J..oolH' .µ,.i.l\ .sJ...s&jill jl.>!lsrt>- ,,.;:.Jlf§:J! i; l:l lf>I~<s_,.:Jt ,.l<>.,.,.. .24

Emergency

997
www. d c d.gov. a e
III. Approval Certificate

Kitemark Licence
No. KM 598387

This is to certify that: Bristol Fire Engineering


PO Box 74582
Dubai
UAE

Holds Kitemark Licence Number: KM 598387

In respect of:
BS EN 54-2 and BS EN 54-4 and BS EN 12094-1 Electrical Automatic Control and Delay
Devices for Gas Extinguishing Systems, Fire Panel and Power Supply Equipment

This issues the right and Licence to use the Kitemark in accordance with the Kitemark Terms and Conditions
governing the use of the Kitemark, as may be updated from time to time by BSI Assurance UK Ltd (the
"Conditions"). All defined terms in this Licence shall have the same meaning as in the Conditions.

The use of the Kitemark is authorized in respect of the Product(s) detailed on this Licence provided at or from the
above address.

For and on behalf of BSI:


Gary Fenton, Global Assurance Director

First Issued: 30/05/2013 Latest Issue: 30/05/2013

Page 1 of 3
First Issued: 30/05/2013 Latest Issue: 30/05/2013

Page 1 of 3

This Licence remains the property of The British Standards Institution and shall be returned immediately upon request.
To check its validity telephone +44 (0)845 080 9000
Information and contact: BSI, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP. Tel: +44 845 080 9000.
BSI Assurance UK Limited, registered in England under number 7805321, at 389 Chiswick High Road, London, W4 4AL, UK.
A member of the BSI Group of Companies.
No. KM 598387

BS EN 12094-1:2003, BS EN 54-2:1997 and BS EN 54-4:1998 + A1

Model Reference Type


BF-ECP3DCSM Class A, Single Area Fire Extinguishing Control Panel Surface Mountable
BF-ECP3DCFM Class A, Single Area Fire Extinguishing Control Panel Flush Mountable
Certified for use with Apollo series 30, 60 & 65, Fulleon, Hochiki, Nittan, Notifier and MorleyIAS ECO1000, KAC
fire detection and alarm products and MTL778ac and MTL5061 intrinsically safe barriers.

Options with requirements


Certified with the following options with requirements from BS EN 54 Part 2:1997

Output to fire alarm devices (clause 7.8)


Delays to outputs (clause 7.11)
Test condition (clause 10)

Certified with the following options with requirements from BS EN 12094-1:2003

Delay of extinguishing signal (clause 4.17)


Signal representing the flow of extinguishing agent (clause 4.18)
Monitoring of the status of components (clause 4.19)
Emergency hold device (clause 4.20)
Control of flooding time (clause 4.21)
Manual only mode (clause 4.23)
Triggering signals to equipment within the system (clause 4.24)
Triggering signals to equipment outside the system (clause 4.26)
Activation of alarm devices with different signals (clause 4.30)

First Issued: 30/05/2013 Latest Issue: 30/05/2013

Page 2 of 3

This Licence remains the property of The British Standards Institution and shall be returned immediately upon request.
To check its validity telephone +44 (0)845 080 9000
Information and contact: BSI, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP. Tel: +44 845 080 9000.
BSI Assurance UK Limited, registered in England under number 7805321, at 389 Chiswick High Road, London, W4 4AL, UK.
A member of the BSI Group of Companies.
No. KM 598387

BS EN 12094-1:2003, BS EN 54-2:1997 + A1:2006 and BS EN 54-4:1997 + A1:2003 & A2:2006

Model Reference Type


BF-ECP2Z1A Class A, Two zone, single area extinguishing control panel
BF-ECP4Z1A Class A, Four zone, single area extinguishing control panel
BF-ECP4Z2A Class A, Four zone, two area extinguishing control panel
BF-ECP8Z1A Class A, Eight zone, single area extinguishing control panel
BF-ECP8Z2A Class A, Eight zone, two area extinguishing control panel
BF-ECP8Z3A Class A, Eight zone, three area extinguishing control panel
BF-ECP8Z4A Class A, Eight zone, four area extinguishing control panel
Certified for use with Apollo series 30, 60 & 65, Fulleon, Hochiki, Nittan, Notifier and MorleyIAS ECO1000, KAC
fire detection and alarm products and MTL778ac and MTL5061 intrinsically safe barriers.

Options with requirements


Certified with the following options with requirements from BS EN 54 Part 2:1997

Output to fire alarm devices (clause 7.8)


Delays to outputs (clause 7.11)
Test condition (clause 10)

Certified with the following options with requirements from BS EN 12094-1:2003:

Delay of extinguishing signal (clause 4.17)


Signal representing the flow of extinguishing agent (clause 4.18)
Monitoring of the status of components (clause 4.19)
Emergency hold device (clause 4.20)
Control of flooding time (clause 4.21)
Manual only mode (clause 4.23)
Triggering signals to equipment outside the system (clause 4.26)
Emergency abort device (clause 4.27)
Activation of alarm devices with different signals (clause 4.30)

First Issued: 30/05/2013 Latest Issue: 30/05/2013

Page 3 of 3

This Licence remains the property of The British Standards Institution and shall be returned immediately upon request.
To check its validity telephone +44 (0)845 080 9000
Information and contact: BSI, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP. Tel: +44 845 080 9000.
BSI Assurance UK Limited, registered in England under number 7805321, at 389 Chiswick High Road, London, W4 4AL, UK.
A member of the BSI Group of Companies.
Certificate of Product Approval
Certificate Number: 1174c-(cl-3) Issue: 01

Bristol Fire Engineering LLC


Al Quoz Industrial Area 3
P O Box 74582
Dubai
United Arab Emirates

is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix
having complied with the requirement(s) of the standards as detailed below:

Products Standards
Audible Warning Devices EN 54-3:2001 + A1:2002 + A2:2006
B61-6301

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

Martin McCullagh 25 August 2016 25 August 2016


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and are
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

BF1278B Rev. 0.7 Page 1 of 2 © BRE Global Ltd, 2016


Appendix to Certificate No: 1174c-(cl-3) Issue: 01
Bristol Fire Engineering LLC
Certified LPCB
Description
Product Ref.No.

B61-6301 Conventional Type A Sounder Strobe (B61-4101 Base) 1174c/01


Notes:
1. Meets the requirements of EN 54-3 and approved at the following tones:
1) Tone 01, 2400Hz – 2900Hz @ 3 Hz
2) Tone 10, 500Hz – 1200Hz x 3, 3.5s on / 0.5s off

2. The strobe function is not included within the scope of this approval

Base:
B61-4101 Base

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

Martin McCullagh 25 August 2016 25 August 2016


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and are
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

BF1278B Rev. 0.7 Page 2 of 2 © BRE Global Ltd, 2016


Certificate of Product Approval
Certificate Number: 1174b-(cl-3) Issue: 01

Bristol Fire Engineering LLC


Al Quoz Industrial Area 3
P O Box 74582
Dubai
United Arab Emirates

is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix
having complied with the requirement(s) of the standards as detailed below:

Products Standards
Heat Detectors EN 54-5:2000 + A1:2002
B61-2001

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

Martin McCullagh 25 August 2016 25 August 2016


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and are
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

BF1278B Rev. 0.7 Page 1 of 2 © BRE Global Ltd, 2016


Appendix to Certificate No: 1174b-(cl-3) Issue: 01
Bristol Fire Engineering LLC
Certified LPCB
Description
Product Ref.No.

B61-2001 Conventional Heat Detector (B61-4001 base) 1174b/01


Note:
1. Meets the requirements of EN 54-5: 2000 at class A2R

Base:
B61-4001 Base

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

Martin McCullagh 25 August 2016 25 August 2016


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and are
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

BF1278B Rev. 0.7 Page 2 of 2 © BRE Global Ltd, 2016


Certificate of Product Approval
Certificate Number: 1174a-(cl-3) Issue: 01

Bristol Fire Engineering LLC


Al Quoz Industrial Area 3
P O Box 74582
Dubai
United Arab Emirates

is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix
having complied with the requirement(s) of the standards as detailed below:

Products Standards
Smoke Detectors EN 54-7:2000 + A1:2002 + A2:2006
B61-1001

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

Martin McCullagh 25 August 2016 25 August 2016


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and are
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

BF1278B Rev. 0.7 Page 1 of 2 © BRE Global Ltd, 2016


Appendix to Certificate No: 1174a-(cl-3) Issue: 01
Bristol Fire Engineering LLC
Certified LPCB
Description
Product Ref.No.

B61-1001 Conventional Optical Smoke Detector (B61-4001 base) 1174a/01


Note:
1. Meets the requirements of EN 54-7: 2000 at default sensitivity setting only

Base:
B61-4001 Base

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

Martin McCullagh 25 August 2016 25 August 2016


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and are
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

BF1278B Rev. 0.7 Page 2 of 2 © BRE Global Ltd, 2016


8/16/2016 VIHU.EX6098 ­ Nozzles, Fixed Spray, Foam

VIHU.EX6098
Nozzles, Fixed Spray, Foam

Page Bottom

Nozzles, Fixed Spray, Foam

See General Information for Nozzles, Fixed Spray, Foam

VICTAULIC CO EX6098
4901 KESSLERSVILLE RD
EASTON, PA 18040­6714 USA

Discharge Discharge
SIN Angle Deg Coefficient K

V2601 180 2.8

V2603 180 5.6

Refer to the individual foam concentrate Listings for operating limitations with specific combinations of foam concentrates and spray nozzles.

Last Updated on 2001­03­13

Questions? Print this page Terms of Use Page Top

© 2016 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow­Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow­Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non­
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VIHU.EX6098&ccnshorttitle=Nozzles,+Fixed+Spray,+Foam&objid=1075… 1/1
Deluge Sprinkler Systems
Deluge sprinkler systems have open sprinklers or open spray nozzles and are used where it is desirable to discharge water through
all of the system's sprinklers or nozzles simultaneously. Prior to discharge there is no water in the sprinkler piping. The water supply is
held back by a control valve which is operated manually or automatically by the actuation of a fire detection system. The fire detection
system is required to be one of the following types: wet pilot sprinkler line, dry pilot sprinkler line, hydraulic rate-of-rise, pneumatic
rate-of-rise or electric. Compatible FM Approved Release Control Panels for use with electric release deluge sprinkler system(s) are
listed under RELEASE CONTROL PANEL COMPATIBILITY.

Automatic sprinklers are used on wet or dry pilot sprinkler lines. The dry pilot sprinkler line may also require a dry pilot actuator
depending upon the type of automatic water control valve. When required, only the compatible dry pilot actuator noted in the sprinkler
system listing shall be used in FM Approved systems.

Electrically operated deluge sprinkler systems are FM Approved on a component basis. Only the major, compatible components noted
in the sprinkler system listing shall be used in an FM Approved system. FM Global installation acceptance may stipulate that only
heat-actuated fire detection devices be used. Acceptance criteria by other jurisdictional authorities may vary.
Deluge sprinkler systems are FM Approved as complete systems. Only the listed components for a specific manufacturer shall be
used in an FM Approved system.

Series 769
Series 769 Firelock NXT Deluge Valves with Dry Pilot Line Pneumatic Release. Sizes 1 1⁄2, 2, 2 1⁄2, 3, 4, 6 and 8 in. NPS.
Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim
components consist of the following:
• Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve; Series 729 alarm line Drip Check Valve
• Series 768 alarm line 3-Way Ball Valve for alarm/test/of
• Series 768 dry pilot line Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.
Optional system components include:
• Regulated pilot line Air Maintenance Trim Assemblies
• Series 757 or 757-P (with pressure switch) Air Maintenance Devices • System Sensor EPS10-2 alarm line pressure switch
• System Sensor EPS40-2 pilot line system air pressure supervisory switch
• Series 755 Manual Pull Station
• Series 760 Water Motor Alarm
• Series 705W water supply butterfly shutoff valve.
• Series 765 water supply butterfly shutoff valve.
Series 769 Firelock NXT Deluge Valves with Wet Pilot Line Hydraulic Release. Sizes 1 1⁄2, 2, 2 1⁄2, 3, 4, 6 and 8 in. NPS. Grooved
inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components
consist of the following:
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 729 alarm line Drip Check Valve
• Series 768 alarm line 3-Way Ball Valve for alarm/test/off
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.
Optional system components include:
• System Sensor EPS10-2 alarm line pressure switch
• Series 755 Manual Pull Station
• Series 760 Water Motor Alarm
• Series 705W water supply butterfly shutoff valve.
• Series 765 water supply butterfly shutoff valve.
Series 769 Firelock NXT Deluge Valve with Electric Release. Sizes 1 1⁄2, 2, 2 1⁄2, 3, 4, 6 and 8 in. NPS. Grooved inlet and grooved
outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:
• Series 753-E normally closed solenoid valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 729 alarm line Drip Check Valve
• Series 768 alarm line 3-Way Ball Valve for alarm/test/off
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.
Optional system components include:
• System Sensor EPS10-2 alarm line pressure switch
• Series 755 Manual Pull Station

© 2007-2016 FM Approvals. All rights reserved. 1 of 2


• Series 760 Water Motor Alarm
• Series 705W water supply butterfly shutoff valve.
• Series 765 water supply butterfly shutoff valve.
The 1 1⁄2, 2, 2 1⁄2, 3, 4, and 6 inch and 76.1 and 165.1 mm NPS Deluge Sprinkler Systems are available factory assembled in the
Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system components and accessories, and requires only the
connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical
power supply. The Series 745 Fire-Pacs may be connected to a System Sensor PDRP-2001 fire alarm control panel.

Company Name: Victaulic Company


Company Address: 4901 Kesslersville Rd, Easton, Pennsylvania 18040, USA
Company Website: http://www.victaulic.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved

© 2007-2016 FM Approvals. All rights reserved. 2 of 2


Indicating Valves, Butterfly or Ball Type
Design features provide a dependable visible indication of the open position even at a distance. If excessive force is applied to the
handle, weakness-joints will break so as to preserve correct orientation between indicator and valve position. Valve and indicator
parts are so designed that they can be assembled only one way, always to give correct indication. All FM Approved indicating valves
turn clockwise to shut. They are small, lightweight, and, because of a resilient seat, are easy to operate. They are not subject to
sticking or dropped gates. They are not recommended for throttling service. Unless otherwise noted in the listing, these valves have
175 psi (1205 kPa) rated working pressure.

Model Nos. BR-HPG-300, BR-HPW-300, BR-DG 175, BR-DW 175, BR-FF-TH, BR-FF-G

Rated Working
Nominal Pipe
Model Number Product Type Pressure, Remarks
Size, mm
psi (kPa)

Butterfly Valve, 2 ½ , 3, 4, 6 300


BR-HPG-300 a, b, c
Grooved Ends (65 ,80, 100, 150) (2070)

Butterfly Valve, 2 ½, 3, 4, 6 300


BR-HPW-300 a, b, c
Wafer Style (65 ,80, 100, 150) (2070)

Butterfly Valve, 2 ½, 3, 4, 6, 8 175


BR-DG 175 a, b, c
Grooved Ends (65, 80, 100, 150, 200) (1205)

Butterfly Valve, 2 ½, 3, 4, 6, 8 175


BR-DW 175 a, b, c
Wafer Body (65, 80, 100, 150, 200) (1205)

Butterfly Valve, 1, 1 ¼, 1 ½, 2, 2 ½ 175


BR-FF-TH a, b, c
Threaded Ends (25, 32, 40, 50, 65) (1205)

Butterfly Valve, 2, 2 ½ 175


BR-FF-G a, b, c
Grooved Ends (50, 65) (1205)

Remarks:
a. Available with dual supervisory switches.
b. FM Approved for indoor and outdoor service.
c. FM Approved for aboveground installations only.

Company Name: Bristol Fire Engineering LLC


Company Address: P.O. Box 74582, Dubai, United Arab Emirates
Company Website: http://www.bristol-fire.com
New/Updated Product Listing: No
Listing Country: United Arab Emirates
Certification Type: FM Approved

© 2007-2013 FM Approvals. All rights reserved. 1 of 1


HLXS.EX16012
Butterfly Valves

Page Bottom

Butterfly Valves

Se e Ge ne ra l Inform a tion for Butte rfly Va lve s

BRISTOL FIRE ENGINEERING L L C EX16012


AL Q UO Z INDUSTR IAL AR EA 3
PO BO X 74582
DUBAI, UNITED AR AB EMIR ATES

Pressure
Rating, psig Indicator Supervisory
Model Size, NPS Body Type (Bar) Post Switch*

Butterfly valve

"BR -DW 175" 2.5, 3, 4, 6, 8 Ductile Iron W a fe r 175 (12) — I

"BR -DG 175" 2.5, 3, 4, 6, 8 Ductile Iron Groove d End 175 (12) — I

"BR -HPW -300" 2.5, 3, 4, 6, 8 Ductile Iron W a fe r 300 (21) — O

"BR -HPG-300" 2.5, 3, 4, 6, 8 Ductile Iron Groove d End 300 (21) — O

"BR -FF-TH" 1, 1.25, 1.5, 2 Thre a de d Bronze 175 (12) — —

"BR -FF-G" 2, 2.5 Groove d End Bronze 175 (12) — O


* I = Indoor insta lla tion; O = O utdoor insta lla tion

Last Upda te d on 2013-09-03

Q ue stions? Print this page Te rm s of Use Pa ge Top

© 2013 UL LLC

W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.

The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.

UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
2/14/2016 GHXV.EX26946 ­ Proportioners, Foam Concentrate

GHXV.EX26946
Proportioners, Foam Concentrate

Page Bottom

Proportioners, Foam Concentrate

See General Information for Proportioners, Foam Concentrate

BRISTOL FIRE ENGINEERING L L C EX26946
AL QUOZ INDUSTRIAL AREA 3
PO BOX 74582
DUBAI, UNITED ARAB EMIRATES

BLADDER TANK AND RATIO­FLOW CONTROLLER INVESTIGATED TO UL 162

53 ­ 3963 gal capacity ASME for vertical and horizontal installation.

Following are equivalent length valves for the controllers (Models BBT­RFC2, BBT­RFC3, BBT­RFC4, BBT­RFC6, BBT­RFC8) based on a
roughness factor of 130 and schedule 40 steel pipes:

Model Equivalent Length Ft

BBT­RFC2 22.0

BBT­RFC3 17.5

BBT­RFC4 29.3

BBT­RFC6 24.9

BBT­RFC8 23.0

Refer to the individual foam concentrate Listings for operating limitations with specific combinations of foam concentrates and proportioners.

Last Updated on 2015­10­20

Questions? Print this page Terms of Use Page Top

© 2016 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow­Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow­Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non­
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=GHXV.EX26946&ccnshorttitle=Proportioners,+Foam+Concentrate&… 1/1
7/5/2017 GFGV.EX27032 - Foam Liquid Concentrates

GFGV.EX27032
Foam Liquid Concentrates
Page Bottom

Foam Liquid Concentrates

See General Information for Foam Liquid Concentrates

BRISTOL FIRE ENGINEERING L L C EX27032


AL QUOZ INDUSTRIAL AREA 3
PO BOX 74582
DUBAI, UNITED ARAB EMIRATES

TeKnoSol AF-1-3R, nominal 3 percent Aqueous Film Forming Foam, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

FireMaster AR-2-3X6R, nominal 3 percent and 6 percent Alcohol Resistant Aqueous Film Forming Foam, +20 F minimum storage and use
temperature. Hydrocarbon fuels at 3 percent. Polar solvent fuels at 6 percent.

FireMaster AR-2-1X3, nominal 1 percent and 3 percent Alcohol-Resistant Aqueous Film Forming Foam, +20 F minimum storage and use
temperature. Hydrocarbon fuels at 1 percent. Polar solvent fuels at 3 percent.

TeKnoSol AF-1-1U, nominal 1 percent Aqueous Film Forming Foam, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

TeKnoSol AF-1-3U, nominal 3 percent Aqueous Film Forming Foam, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

TeKnoSol AF-1-6U, nominal 6 percent Aqueous Film Forming Foam, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

FireMaster AR-2-3X3U, nominal 3 percent Alcohol Resistant Aqueous Film Forming Foam, +35 F minimum storage and use temperature.
Hydrocarbon fuels at 3 percent. Polar solvent fuels at 3 percent.

EkoSol FF-3-1, nominal 1 percent Synthetic Foam, +35 F minimum storage and use temperature. Hydrocarbon fuels at 1 percent.

EkoSol FF-3-3X6, nominal 3 percent and 6 percent Synthetic foam, +35 F minimum storage and use temperature. Hydrocarbon fuels at 3
percent. Polar solvent fuels at 6 percent. Fresh water use only. Not suitable for use with sea water solutions.

TeKnoSol AF-1-3LF, nominal 3 percent Aqueous Film Forming Foam, +35F minimum storage and use temperature. Hydrocarbon fuels only.

TeKnoSol AF-1-3F, nominal 3 percent Aqueous Film Forming Foam, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

TeKnoSol AF-1-6B, nominal 6 percent Aqueous Film Forming Foam, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

TeKnoSol AF-1-1B, nominal 1 percent Aqueous Film Forming Foam, +35 F min storage and use temperature. Hydrocarbon fuels only.

BlazeMaster FP-1-3, nominal 3 percent, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

BlazeMaster FP-1-6, nominal 6 percent, +35 F minimum storage and use temperature. Hydrocarbon fuels only.

BlazeMaster FP-2-3, nominal 3 percent Film Forming Fluoroprotein Foam, +20 F min storage and use temperature. Hydrocarbon fuels only.

BlazeMaster FP-2-6, nominal 6 percent Film Forming Fluoroprotein Foam, +20 F min storage and use temperature. Hydrocarbon fuels only.

AquaFreeze AF-1-3, nominal 3 percent Aqueous Film Forming Foam, -20 F min storage and use temperature. Hydrocarbon fuels only.

FireMaster AR-2-3x3B, nominal 3 percent Alcohol Resistant Aqueous Film Forming Foam, +35 F min storage and use temperature. Hydrocarbon
fuels at 3 percent. Polar solvent fuels at 3 percent.

FireMaster AR-2-3x6F, nominal 3 or 6 percent Alcohol Resistant Aqueous Film Forming Foam, +35 F min storage and use temperature.
Hydrocarbon fuels at 3 percent. Polar solvent fuels at 6 percent.

EkoSol AF-1-3, nominal 3 percent Aqueous Film Forming Foam, +35 F min storage and use temperature. Hydrocarbon fuels only.

EkoSol ARAF-1-3x3, nominal 3 percent Alcohol Resistant Aqueous Film Forming Foam, +35 F min storage and use temperature. Hydrocarbon
fuels at 3 percent. Polar solvent fuels at 3 percent.

BlazeMaster ARFP-1-3x3, nominal 3 percent Alcohol Resistant Film Forming Fluoroprotein Foam, +35 F min storage and use temperature.
Hydrocarbon fuels at 3 percent. Polar solvent fuels at 3 percent.

FireMaster AR-2-1x3B, nominal 1 or 3 percent Alcohol Resistant Aqueous Film Forming Foam, +35 F min storage and use temperature.
Hydrocarbon fuels at 1 percent. Polar solvent fuels at 3 percent.

Foam concentrates for use with the following equipment.

TeKnoSol AF-1-3R, 3 PERCENT

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=GFGV.EX27032&ccnshorttitle=Foam+Liquid+Concentrates&ob… 1/12
IV. Material Safety Data Sheet
MATERIAL SAFETY DATA SHEET
T EK NOS OL AF -1- 3F ( A FF F 3 % )

Section 1. IDENTIFICATION
Product Name BRISTOL TEKNOSOL AF-1-3F (AFFF 3%)
Common Name AFFF 3%
CAS No. N/A
Chemical Name N/A
Chemical Family Mixture
Supplier Bristol Fire Engineering LLC
Al Quoz Industrial Area 3,
Supplier Address
P.O. Box 74582, Dubai, UAE
Contact No. Tel.: +971 4 3472426 / Fax: +971 4 347 2363

Section 2. COMPOSITION
Acute Toxicity
Ingredient CAS No. WT. % AGCIH TLV
Data
Proprietary mixture of Flurosurfactants,
Hydrocarbon surfactant, Inorganic salts and N/A N/A N/A NDA
DM Water
Hexylene Glycol (2 Methylpentane, 2-4-diol) 107-41-5 10% N/A NDA

Section 3. HAZARD IDENTIFICATION


Threshold Limit Value (TLV): None established by ACGIH or OSHS
ROUTES OF ENTRY
Eye Contact May cause mild transient irritation.
Skin Contact May Cause mild transient irritation and /or dermatitis
Inhalation Inhalation is not anticipated to be a problem
Irritating to mucous membranes large oral doses could product
Ingestion
narcosis
SINGS AND SYMPTOMS
Acute Over exposure Irritation of the eyes, skin and mucous membranes.
Chronic Over exposure Delayed kidney injury possible liver damage.
Medical Conditions Aggravated by exposure: Diseases of the kidney and liver.
Chemical listed as carcinogen or potential
National Toxicology Programme: No. I.A.R.C. Monograph No. OSHA: No.

© Bristol Fire Engineering. All rights reserved. (2017)

WWW.BRISTOL-FIRE.COM
MATERIAL SAFETY DATA SHEET
T EK NOS OL AF -1- 3F ( A FF F 3 % )

Section 4. FIRST AID MEASURES


Eye contact Flush with large amounts of water, if irritation persists, seek medical attention
Skin Contact Wash with soap and water; if irritation persists, seek medical attention
Inhalation Remove victim to fresh air, Seek medical attention if discomfort persists
If patient is conscious, given large amounts of water and induce vomiting, seek
Ingestion
medical help
If other symptoms persist seek medical advice and treat symptomatically

Section 5. FIREFIGHTING MEASURE


No specific measures required as this product is a fire-extinguishing medium

Section 6. ACCIDENTAL RELEASE MEASURE


Personal precautions: Avoid contact with skin, eyes and clothing. Do not breathe mists, aerosols.
Personal protection: Wear protective clothing specified for normal operations.
Clean-up methods - Small Absorb or contain liquid with sand, earth or spill control material. Shovel up spillage: and
place in a labeled, sealable container for subsequent safe disposal.

Section 7. HANDLING AND STORAGE


No Special Handling techniques required and Store in original container.

Section 8. EXPOSURE CONTROLS, PERSONAL PROTECTION


Eye Protection: Wear Side-Shield Safety Glasses.
Skin Protection: Wear Gloves.
Respiratory Protection: Use dust Respirator if needed.

Section 9. PHYSICAL & CHEMICAL CHARACTERISTICS

Boiling point: 97°C

Vapor pressure (mm hg) Not determined

Solubility in water 100%

Appearance and Odor Clear Mild Sweet

Flash point None to boiling

Specific Gravity 1.01

Ph 7.5 ± .5

Percent Volatile Approx. 90

Reactivity in water Unreactive

Special Fire Fighting Procedure None, this is an extinguishing agent

© Bristol Fire Engineering. All rights reserved. (2017)

WWW.BRISTOL-FIRE.COM
MATERIAL SAFETY DATA SHEET
T EK NOS OL AF -1- 3F ( A FF F 3 % )

Section 10. STABILITY AND REACTIVITY


Stability: Stable
Conditions to avoid: N/A
Incompatibility: Reactive metals, electrically energized equipment, strong, any material reactive with water.
Hazardous Polymerization: Will not occur.
Hazardous Decomposition Products: None know but oxides of sulfur and nitrogen may be formed

Section 11. TOXICOLOGICAL INFORMATION


Eye Irritation: (Rabbits) mild irritant
Skin Irritation: (Rabbits) minimal irritant Inhalation toxicity: Not evaluated
Inhalation toxicity: Not evaluated
Sensitization: Not evaluated
Teratology: Not evaluated
Mutagenicity: Not evaluated
Reproduction: Not evaluated
Acute oral effect (rats): Not evaluated

Section 12. ECOLOGICAL INFORMATION


Persistence/Degradability: Biodegradable.
Bioaccumulation: Bioaccumulation is unlikely to occur due to metabolism and excretion.

Section 13. DISPOSAL CONSIDERATION


Dispose in accordance with local, state, and federal regulation. Discharge to waste treatment plants only with per-
mission.

Section 14. TRANSPORTATION INFORMATION


Label for conveyance: No Transport Warning Sign Required

Section 15. REGULATORY INFORMATION


All ingredients are on the TSCA Inventory
No Components are reportable under SARA Title III, Sec 313
No Components are priority pollutants listed under the U.S. Clean Water Act Section 307 (2) (1) priority Pollu-
tants list. (40 CFR 401.15)
No Components are reportable under CERCLA.

Section 16. OTHER INFORMATION

NFPA Hazard Ratings HMIS Identification System

1 Health Hazard Rating 1

0 Flammability Rating 0
0 Instability / Reactivity 0

© Bristol Fire Engineering. All rights reserved. (2017)

WWW.BRISTOL-FIRE.COM
V. Company Profile
Firefighting Solutions Provider
www.bristol-fire.com

BRISTOL Fire Engineering, part of the Concorde – Corodex Group (CCG), was
established in 1974 as a leading manufacturer of high quality Fire Fighting
Systems and Equipments. BRISTOL was one of the first fire fighting companies
to receive an ISO 9001 certification in the Middle East, placing a great emphasis
on achieving international and Third party approvals in all our product range
such as (Kite Mark, LPBC, UL listing and FM Approval). In addition, all our
products carry Civil Defense approvals in the market we operate in.

We are continuously working on adding new technologies to our product range


so we can meet the ever changing customer needs.

Our range of experience expands to all category projects from residential,


commercial, healthcare, Industrial and educational.

Integrity and Quality are ingrained in BRISTOL name. For over three decades,
Bristol related companies have consistently performed complex projects on
time and within the budget while never compromising quality.

BRISTOL’s complete in house staff consists of fire fighting specialist engineers,


project executive staff, professional services & maintenance teams and it
ensures that end users receive a total solution rather than merely a product.

Product range

• Fire Alarm & Detection System


• Fire Suppression systems (Novec 1230, FM200,CO2,Water Mist, Kitchen
Hood & Inert gas)
• FOAM System /FOAM Concentrate
• Fire Sprinkler systems
• Fire Pumps
• Fire and Rescue trucks
• Hydrant valves /Nozzles and accessories
• Wet / Dry riser components (Fire Hose reel ,Landing Valves ,PRV etc.. )
• Fire Extinguishers ( Wet Chemical, Dry Chemical Powder
/CO2/Foam/Water Harleton)
• Fire Doors
Concorde-Corodex Group

Group Profile

The Concorde- Corodex Group, a part of M.H Al Mana Group of Companies, is


one of the Middle East region’s pioneering providers of fire protection, water
purification, wastewater treatment and environmental services. Established in
1974, the company has evolved to become the largest group to offer a diverse
portfolio of products and services like a complete kit of water treatment services,
fire fighting equipment and marine & industrial chemical cleaning to name a few.

Looking to meet the continuously changing demands and requirements from


customers across various industry verticals, the Concorde – Corodex Group has
diversified itself into 17 individual companies--each excelling in their respective
field of expertise and operating as an independent entity. Collectively, all
subsidiary companies continue to consolidate the Concorde – Corodex Group
market leadership in the Middle East region, with assets worth over USD 90
million.

CCG’s core values have been the cornerstone of what define us and what we
stand for. They are excellence, innovation, environment stewardship, and health
& safety.

All business units of Concorde-Corodex Group are registered companies with


Quality, Environment, Occupational Health and Safety Management Systems
(QHSEMS) in compliant to international standards such as ISO 9001:2008, ISO
14001:2004 and OHSAS 18001:2007.

Our Team
From relatively small team, Concorde-Corodex Group has vastly grown in size.
Presently, we have 920 total employees, amongst which are 322 Engineers,
Specialists, Chemists and other Technical Professionals.
Mission Statement

We, the Concorde-Corodex Group, are committed to provide quality products


and services.

In pursuit of this commitment in serving the consumers, we shall adopt sound


trade and industrial policies as well as regulations provided by the government.

We shall provide timely and world class services that answer our clients'
business needs for Design, Manufacturing, Servicing and Trading.

In the same way we relate with our clients, so shall we relate with each other as
we promote an internal environment that foster professional growth.

In the attainment of this mission and for love of this country, we bind ourselves to
be the highest standards of competence, integrity and dedication.

Vision Statement
We are committed to deliver world class products in various business activities in
the fields of Designing, Manufacturing, Servicing and Trading.

We shall actively provide innovative and effective services to the consumers, with
customers' delight as our measure of success.

As we move toward this direction, we shall endeavor to become leader in


providing total quality service in the field.

We are group of highly capable, skilled and dedicated people with creative and
noble ideas committed to build an organization we can be proud of.

We shall triumph in a work environment that upholds the highest distinction in


excellence professionalism, integrity and harmony.

In essence, we shall always strive to be a provider of true service worthy of


consumer’s trust as we meet the challenges of the ever changing consumer
needs.

International Operating offices:

• U.A.E. (Head corporate office and manufacturing facility)


• Winnipeg, Canada
• London, UK
• Khartoum, Sudan
• Doha, Qatar
• Muscat, Oman
• Jeddah, K.S.A
• Amman, Jordan

UAE Operating Offices:

• Abu Dhabi
• ICAD Mussafa
• Khalidiya
• Dubai
• Al Quoz
• Al Awir
• Sheikh Zayed
• Sharjah
• Al Ain
• Ras Al Khayma

Core Activities
ƒ Water Purification / Treatment Systems
ƒ Sewage Treatment Plants
ƒ Vacuum Sewer Systems
ƒ Operation & Maintenance
ƒ Electromechanical Services
ƒ Marine and Industrial Chemical Cleaning
ƒ Fire Fighting Equipments and Systems
ƒ Fire Protection and Safety
ƒ Machine Tools and Engineering Equipment
ƒ Scientific & Laboratory Equipment
ƒ Oilfield Equipment
ƒ Industrial Gases
ƒ Welding Equipment
ƒ Vehicle Manufacturing Division

Quality Policy

Concorde-Corodex Group is a professional company devoted to build a strong


customer relation base to deliver a wide range of quality products. With a history
of service excellence that has evolved through the decades, our organization
leads a Group of Companies/ Business Operating Units, incorporating a variety
of business activities in the fields of Designing, Manufacturing, Servicing and
Trading.
We at CCG have committed ourselves to provide and exceed our customers’
expectations and contractual requirements through:

Employee: We recognize our employees as the most valuable asset of the


organization. On the basis of merit hiring the right incumbent for the right
position, we value their skills and knowledge and we lead, motivate and empower
them through a working environment that advances our business objectives.

Products/Services: Our objective is to provide products or services that meets


or exceeds customer’s satisfaction. We deliver to customer the right product or
service at the right time at the right quantity, quality and price.

Processes: We have implemented ISO 9001:2008 to define and control our


processes and ensure that they are conforming with the set policies. Our aim is
to reach to the most efficient way of carrying out the tasks to enhance our
business relations with customers.

Customers: Customer Satisfaction is recognized as the number one priority in


our organization as our success is directly linked to the satisfaction of the
customer towards his final output of the quality of our product and services.

CCG is an enterprise that retains a tradition of integrity and is on the path to


expand and continually improve in line with the market trends.

Environmental Policy
We, at Concorde-Corodex Group, are committed to provide quality products and
services in a manner that ensures a safe and healthy workplace for our
employees and minimizes our potential impact on the environment. We will
operate in compliance with ISO 14001: 2004 and all relevant environmental
legislations and will strive to use pollution prevention and environmental best
practices in all we do.
We are committed to continually improving our environmental performance
using the following measures:

1. The control of emissions and discharges consequential upon our


Operations to ensure these has minimal detrimental effect upon the
environment.
2. The control of odour, noise and litter to eliminate or minimize the
effects on surrounding areas.
3. To optimize raw materials usage and conversion efficiencies including
the rework and/or recycling of scrap.
4. To seek to reduce the consumption of materials, fuel & energy used in our
operations.
5. Compliance with environmental legislation and regulations.
6. To take into account the concerns of interested parties such
as regulators, shareholders, suppliers, employees and the public.
7. To communicate this policy to all members of the organization and
ensure all are trained in their respective environmental responsibilities.
8. To make this Environmental Policy available to customers and the public
on demand.
The introduction and implementation of this Policy is a commitment of
CCG Management and a shared responsibility of all our employees.

This policy will be reviewed annually as part of the company’s overall


Environmental Management review system.

Occupational Health and Safety (OHS) Policy


Concorde-Corodex Group is committed to prevent injury and ill health by
providing safe and healthy working conditions for all its employees and to ensure
that work done does not affect adversely the health and safety of others.

CCG strives for continual improvement in Occupational Health and Safety


(OH&S) management and performance through consultation and participation of
employees.

To achieve this, the following work policy is hereby issued:

ƒ Provide adequate control of the Health and Safety risks arising from our
work activities.
ƒ Consult with our workers and volunteers on matters affecting their Health
and Safety, including work related stress.
ƒ Provide and maintain safe plant and equipment.
ƒ Ensure safe handling and use of substances.
ƒ Provide training, information, instruction and supervision for workers to
ensure that they are aware of their individual OH&S obligations.

All works will be carried out in accordance with the requirements of OHSAS
18001:2007 and other relevant Health & Safety laws, Acts, Regulations, Codes
of Practice and Guidance Notes and ensure compliance to applicable laws where
the company subscribes to.

Management and supervisory staff have the responsibility for implementing this
policy throughout the company and must ensure that health and safety are
always given priority in planning day-to-day supervision of work.

This policy will be reviewed periodically and will be available to interested parties.
Group Members
• Concorde Trading Co, Abu Dhabi
For everything water related
• Concorde Agencies Est, Abu Dhabi
Fire protection and automation system
• Concorde Technical Est, Abu Dhabi
Fire Protection, Water and Wastewater Treatment, and Environmental
Specialists
• Corodex Trading Co, Dubai
For everything water related
• Corodex Agencies Est, Dubai
Fire protection and automation system
• Corodex Industries, Dubai
Water Purification and Wastewater Treatment Specialists
• Corodex Marine, Dubai
Step ahead in chemical cleaning
• Corodex Electromechanic, Dubai
Bringing Engineering Solutions to Life Vacuum Sewerage System Water
and Wastewater
Treatment Systems
• Bristol Fire Engineering, Dubai
Everything Fire Related
• Al Jaddaf Electromechanical, Abu Dhabi
Fire Protection, Water and Wastewater Treatment, and Environmental
Specialists
• EFLO International, United Kingdom
Wastewater Treatment Specialists
• Bristol Gases, Dubai
Industrial Gases
• Dubai Industrial Gases, Sharjah
Industrial Gases