FMM-1, FMM-101, FZM-1 & FDM-1: General

The document describes four different monitor modules - FMM-1, FMM-101, FZM-1, and FDM-1 - that are available for Notifier's intelligent control panels. The modules can monitor circuits of dry contact devices or power and monitor circuits of two-wire smoke detectors. Each module type has different features and applications.

Uploaded by

Carlos Misano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
320 views4 pages

FMM-1, FMM-101, FZM-1 & FDM-1: General

The document describes four different monitor modules - FMM-1, FMM-101, FZM-1, and FDM-1 - that are available for Notifier's intelligent control panels. The modules can monitor circuits of dry contact devices or power and monitor circuits of two-wire smoke detectors. Each module type has different features and applications.

Uploaded by

Carlos Misano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

FMM-1, FMM-101,

FZM-1 & FDM-1


Monitor Module
Intelligent/Addressable Devices

General
Four different monitor modules are
available for Notifier’s intelligent control
panels for a variety of applications. Monitor
modules supervise a circuit of dry-contact
input devices, such as conventional heat
detectors and manual call points, or
monitor and power a circuit of two-wire
smoke detectors.

FMM-1 Monitor Module FMM-1, FZM-1, FDM-1


Is a standard-sized module that supervises
a circuit of dry-contact input devices.

The FMM-1 Monitor Module is intended for


use in intelligent, two-wire systems, where
the individual address of each module is
selected using the built-in rotary switches.
It provides either a two-wire or four-wire
fault-tolerant Initiating Device Circuit (IDC) FMM-101
for normally-open-contact fire alarm and
supervisory devices. The module has a Applications
panel-controlled LED indicator. The FMM-1
can be used to replace MMX-1 modules in Use to monitor a zone of four-wire smoke
existing systems. detectors, manual call points, waterflow
devices, or other normally open
Features dry-contact alarm activation devices. May
also be used to monitor normally-open
• Built-in type identification automatically supervisory devices with special
identifies this device as a monitor supervisory indication at the control panel.
module to the control panel.
• Powered directly by two-wire SLC loop. FMM-101 Mini Monitor Module
No additional power required.
• High noise (EMF/RFI) immunity. Is a miniature monitor module a mere
• Direct-dial entry of address: 01 – 159 on 3.302 cm (H) x 6.985 cm (W) x 1.270 cm (D)
FlashScan loops; 01 – 99 on CLIP loops. that supervises a circuit of dry-contact
• LED flashes green during normal input devices. Its compact design allows
operation (this is a programmable the FMM-101 to often be mounted behind
option) and latches on steady red to the device it monitors.
indicate alarm.
• Compatible with FlashScan® and CLIP
protocol systems

Page 1 of 4 DOC-02-040
The FMM-101) Mini Monitor Module can full zone of conventional detectors back to
be installed in a single-gang junction box the control panel. All two-wire detectors
directly behind the monitored unit. Its being monitored must be compatible with
small size and light weight allow it to be the module.
installed without rigid mounting. The
FMM-101 is intended for use in intelligent, Features
two-wire systems where the individual
address of each module is selected using • Supports compatible two-wire smoke
rotary switches. It provides a two-wire detectors.
initiating device circuit for • High noise (EMF/RFI) immunity.
normally-open-contact fire alarm and • Direct-dial entry of address: 01 – 159 on
security devices. The FMM-101 can be used FlashScan loops; 01 – 99 on CLIP loops.
to replace MMX-101 modules in existing • LED flashes during normal operation; this
systems. is a programmable option.
• LED latches steady to indicate alarm on
Features command from control panel.

• Built-in type identification automatically Applications


identifies this device as a monitor
module to the control panel. Use the FZM-1 to monitor a zone of
• Powered directly by two-wire SLC loop. two-wire smoke detectors.
No additional powerrequired.
• High noise (EMF/RFI) immunity. FDM-1 Dual Monitor Module
• Direct-dial entry of address: 01 – 159 on
FlashScan loops; 01 – 99 on CLIP loops. Is a standard-sized dual monitor module
• Tinned, stripped leads for ease of wiring. that monitors and supervises two
independent two-wire dry-contact
Applications initiating device circuits (IDCs) at two
separate, consecutive addresses in
Use to monitor a single device or a zone of intelligent, two-wire systems.
four-wire smoke detectors, manual call
The FDM-1 automatically assigns itself to
points, waterflow devices, or other
two addressable points, starting with the
normally-open dry-contact devices. May
original address. For example, if the
also be used to monitor normally-open
FDM-1is set to address “26”, then it will
supervisory devices with special
automatically assign itself to addresses “26”
supervisory indication at the control panel.
and “27”.
FZM-1 Interface Module NOTE: “Ones” addresses on the FDM-1 are
0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the
Is a standard-sized module that monitors first address, and terminals 8 and 9 use
and supervises compatible two-wire, 24 the second address.
volt, smoke detectors on a circuit.
The FZM-1 Interface Module is intended
Features
for use in intelligent, addressable systems,
• Supports compatible two-wire smoke
where the individual address of each
detectors.
module is selected using built-in rotary
• High noise (EMF/RFI) immunity.
switches. This module allows intelligent
• LED flashes during normal operation; this
panels to interface and monitor two wire
is a programmable option.
conventional smoke detectors. It transmits
• LED latches steady to indicate alarm on
the status (normal, open, or alarm) of one
command from control panel.

Page 2 of 4 DOC-02-040
Applications
It provides two independent two-wire initiating device circuits (IDCs) at two separate,
consecutive addresses. It is capable of monitoring normally open contact fire alarm and
supervisory devices; or either normally open or normally closed security devices.

SPECIFICATIONS

FMM-1

Nominal Operating Voltage: 15 to 32 VDC.

Maximum Current Draw: 5.0 mA (LED on).

Average Operating Current: 350 μA (LED flashing),


1 communication every 5 seconds, 47k EOL.

Maximum IDC Wiring Resistance: 40 ohms.

EOL Value: 47K ohms.

Temperature range: 0°C to 49°C.

Humidity range: 10% to 93% noncondensing.

FMM-101

Nominal Operating Voltage: 15 to 32 VDC.

Average Operating Current: 350 μA, 1 communication every 5 seconds,


47k EOL; 600 μA Max. (Communicating,
IDC Shorted).

Maximum IDC Wiring Resistance: 40 ohms.

Maximum IDC Voltage: 11 Volts.

Maximum IDC Current: 400 μA.

EOL Value: 47K ohms.

Temperature range: 0°C to 49°C.

Humidity range: 10% to 93% noncondensing.

Page 3 of 4 DOC-02-040
FZM-1

Nominal Operating Voltage: 15 to 32 VDC.

Maximum Current Draw: 5.1 mA (LED on).

Maximum IDC Wiring Resistance: 25 ohms.

Average Operating Current: 300 μA, 1 communication and 1 LED flash


every 5 seconds, 3.9k eol.

EOL Value: 3.9K ohms.

External supply voltage


(between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple
voltage: 0.1 Vrms maximum. Current: 90 mA
per module maximum.

Temperature range: 0°C to 49°C.

Humidity range: 10% to 93% noncondensing.

FDM-1

Normal Operating Voltage Range: 15 to 32 VDC.

Maximum Current Draw: 6.4 mA (LED on).

Average Operating Current: 750 μA (LED flashing).

Maximum IDC Wiring Resistance: 1,500 ohms.

Maximum IDC Voltage: 11 Volts.

Maximum IDC Current: 240 μA

EOL Value: 47K ohms.

Maximum SLC Wiring Resistance: 40 Ohms.

Temperature Range: 0° to 49°C.

Humidity Range: 10% to 93% (non-condensing).

© 2009 by Honeywell International Inc. All rights reserved.


Unauthorised use of this document is strictly prohibited.

This document is not intended for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information contact your nearest Notifier Sales Office or Distributor
www.notifier.com.au

Page 4 of 4 DOC-02-040