Grid Solutions

Multilin F60
Advanced Protection, Control & Automation Protection & Control
for Distribution Feeders • High-impedance fault detection (downed
conductor detection)
The MultilinTM F60 Feeder Protection System provides feeder protection, control, monitoring and metering
• Thermal overload, incipient cable fault and
in an integrated, economical, and compact package.
broken conductor detection
The F60 incorporates a unique and matured algorithm to detect high-impedance faults, such as downed
• Four-shot autorecloser, VT fuse failure
conductor detection. It also provides fast and deterministic execution of programmable logic, which is
detection, and synchronism check
necessary for substation automation applications. Graphical programming tools (Viewpoint Engineer),
supported by a library of logic components, make the F60 simple to use and configure. • Protection and control functionality in one
box, reducing the number of devices
• High density inputs/outputs to support the
Key Benefits control of many switchyard assets – all from
• Advanced and flexible protection and control for distribution feeder applications with unique and one powerful device
secure downed conductor detection backed by many years of field experience
• Integrated large, full color display, for real-time
• Flexible load encroachment allows secure operation during heavy load conditions visualization and control of the protected bay
• Voltage and frequency elements provide load shedding & transfer schemes for increased system
uptime and stability
• Embedded Synchrophasor measurement capabilities (per IEEE® C37.118), eliminating the need for
Advanced Communications
dedicated PMUs and support for synchrophasor multi-cast (per IEC® 61850-90-5) reducing bandwidth • 3 independent Ethernet ports for simultaneous
and communications infrastructure costs & dedicated network connections with
• An integrated large, full color display, provides real-time visualization and control of the protected bay, IEEE 1588 support
via a bay mimic as well as annunciator functionality and graphical visualization of phasors • IEC 61850-9-2LE/IEC 61869* networked or
• Advanced IEC 61850 Ed. 1 and Ed. 2 certified implementation, complete settings via SCL files and IEC61850-9-2 Hardfiber process bus support
comprehensive process bus support (IEC 61850-9-2LE or IEC 61869* or IEC 61850-9-2 Hardfiber) ensures • Direct I/O for secure, high-speed exchange
interoperability, device managing optimization and reduced cost of ownership of data between URs for DTT & pilot-aided
• Routable GOOSE (R-GOOSE) enables GOOSE messages going beyond the substation, which enables wide schemes
area protection and control applications
• Increased network availability via failover time reduced to zero through IEC® 62439-3 “PRP” support Cyber Security
• Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE standard
• CyberSentry™ provides high-end cyber
security aligned to industry standards and
Applications services (NERC® CIP, AAA, Radius, RBAC, Syslog)
• Primary protection and control for feeders on solidly, impedance or resonant (Petersen coil)
grounded systems
Monitoring & Metering
• Busblocking / interlocking schemes
• P&M class synchrophasors of voltage, current,
• Distribution load shedding schemes based on voltage and frequency elements and sequence components
• High-speed fault detection for arc flash mitigation • Advanced recording capabilities with high-
• Throw over schemes (bus transfer scheme applications) capacity event recorder, configurable and
• Backup protection for transmission lines, feeders and transformers extended waveform capture and data logger

• Distributed Generation (DG) interconnect protection , including active and passive anti-islanding • Metering: current, voltage, power, energy,
frequency, and harmonics
F60 Feeder Protection System

Protection and Control F60 - Protection, Metering, Monitoring and Control


As part of the Universal Relay (UR) family, the
F60 features high-performance protection,
expandable I/O options, integrated monitoring
and metering, high-speed communications,
and extensive programming and configuration
capabilities including:

Downed Conductor (Hi-Z) Detection


Fires, injuries, and even fatalities may be caused
by a live downed conductor. Unfortunately,
these high risk incidences often go undetected
by conventional protective relays.

The Hi-Z element in the F60, unique to Multilin,


provides reliable detection of faults caused by
downed conductors. Sophisticated algorithms
developed over the past 20 years, detect
downed conductors, tree branch contacts, and
insulation fault in underground cables. This
unique, field-proven algorithm incorporates
artificial intelligence to maximize dependability.
The F60 offers an integrated protection, control, metering and monitoring package that can directly
Key benefits of Hi-Z detection in the F60:
connect into DCS or SCADA monitoring control systems, such as Viewpoint Monitoring.

Functional Block Diagram

52

79(4)
CLOSE TRIP 81U
Monitoring
81O
50P 50_2 51_2 50BF 51P/V 67P 67_2 32 49 50N 51N 67N/G 50NBF

27P

Transducer 59P
FlexElement™ METERING Inputs

87G 50G 51G 59N

27X 59X 59_2

25
F60 Feeder Protection System

ANSI® Device Numbers & Functions


DEVICE DEVICE DEVICE
FUNCTION FUNCTION FUNCTION
NUMBER NUMBER NUMBER
25 Synchrocheck 50_2 Negative Sequence Instantaneous 59X Auxiliary Overvoltage
27P Phase Undervoltage 51G Overcurrent 59_2 Negative Sequence Overvoltage
27X Auxiliary Undervoltage 51N Ground Time Overcurrent 67N Neutral Directional Overcurrent
32 Sensitive Directional Power 51N Neutral Time Overcurrent 67P Phase Directional
50BF/50BNF(2) Breaker Failure 51P Phase Time Overcurrent 67_2 Negative Sequence Directional Overcurrent
50DD Disturbance Detector 51_2 Negative Sequence Time Overcurrent 79 Automatic Recloser
50G Ground Instantaneous Overcurrent 52 AC Circuit Breaker 81O Overfrequency
50N Neutral Instantaneous Overcurrent 59N Neutral Overvoltage 81U Underfrequency
50P Phase Instantaneous Overcurrent 59P Phase Overvoltage 87G(RFG) Restricted Ground Fault

2 GEGridSolutions.com
F60 Feeder Protection System

Auto-Transfer Scheme Implementation Example It allows the phase overcurrent elements to be


set to see end-of-line phase faults in heavily
loaded feeder applications.

FIBER/COPPER
Over/Under Voltage Protection
CB1 CB2
F60-1 F60-2
The F60 includes the following voltage elements:

• Up to 2 phase undervoltage and 3 phase


overvoltage elements
• 1 auxiliary under/over voltage element
• 1 neutral overvoltage element
The following are some of the key applications
where voltage elements can be used:
TCB1
• Source transfer schemes
CB3 CB4 CB5 CB6
• Load shedding schemes
• Backup capacitor bank protection and
control
• Backup motor protection to prevent
Auto-transfer schemes can be implemented using programmable FlexLogic. Wiring between relays automatic restart
can be eliminated using peer-to-peer communication.
Abnormal Frequency Protection
The F60 offers over and underfrequency
• Reliable detection of faults caused by The F60 allows the use of directional elements
elements to improve network (grid) stability
downed conductors for supervision of ground overcurrent protection
using voltage or frequency-based load
• Fast response to hazardous situations elements and provide sensitive tripping for
shedding techniques. The F60 can be integrated
faults in one direction. Typical application for
• Dependable and secure operation using into a communications network containing
directional overcurrent includes:
artificial intelligence N60 network stability relays to implement
• Detection of arcing faults • Isolation of faulted feeders in ring bus or wide area, intelligent load shedding schemes.
parallel feeder arrangements It also provides backup protection when
• Easy integration by the addition of a Hi-Z
• Prevention of back-feeding utility source fault protecting feeders and other frequency-
module to a new or existing F60 relay
from industrial plant generators sensitive power equipment.
Directional Overcurrent Protection • Sensitive high-speed ground fault protection
Frequency Rate of Change Protection
The F60 also has built-in standard IEEE, IEC, IAC for transformers
and FlexCurves™ overcurrent characteristics Frequency rate of change (df/dt) elements are
For neutral directional sensing, the residual
(TOC), most commonly used for primary and included in the F60 to provide protection against
current of the phase CTs is used as the operating
backup protection in various protective zones. It system disturbances through load shedding
current . For current polarization, a residual
has phase IOC elements with separate outputs and to provide anti-islanding protection for
CT is used to measure zero-sequence current.
for each phase. Each TOC element has the distributed generator interconnections.
For voltage polarization, the calculated or
following programmable characteristics: measured zero-sequence voltage can be used.
Cold Load Pickup
• Pickup current level for trip, alarm, or control The maximum torque angle is programmable.
Two enhanced dual polarization modes use A cold load condition can be caused by a
• Choice of 17 curve shapes (including prolonged outage of the load, by opening the
both current and voltage signals to determine
FlexCurves) and curve multipliers circuit breaker, or by a loss of supply even if the
polarity. “Dual-V” polarization gives priority to
• Instantaneous or linear reset time polarity determined based on voltage while breaker remains closed (cyclic loads like HVAC,
characteristic to coordinate with upstream “Dual-I” polarization gives priority to polarity refrigeration systems). F60 can automatically
transformer damage curves and downstream determined based on current. detect conditions that would lead to cold load
reclosers and fuses pickup and selectively block protection elements
• Voltage restraint to increase sensitivity Load Encroachment for security during feeder energization.

The majority of distribution systems are either The load encroachment function in the F60
Wattmetric Ground Fault Protection
solidly grounded or grounded through a low provides the capability to manage load growth
impedance. Fast fault clearance is required in feeders. The load encroachment element can A sensitive wattmetric zero-sequence directional
due to the ground fault impact. The following be set for the feeder’s expected maximum load, function can be used on isolated or resonant
functions are incorporated in the F60 to provide reducing the likelihood of false tripping for load (Petersen coil) grounded, low-resistance
secure ground protection: conditions while maintaining dependability to grounded and solidly grounded systems to
trip for legitimate faults. detect ground faults.
• Neutral IOC and TOC
• Ground IOC and TOC

GEGridSolutions.com 3
F60 Feeder Protection System

This function determines the presence and For time synchronization purposes, this Process • Does not introduce new cyber security
direction of ground faults by measuring the bus module can become an IEEE 1588 slave concerns
value and direction of zero-sequence power. clock (61850-9-3 profile) or a 1588 Grand Master Visit the HardFiber System product page on the
This flexible element responds to power derived clock which removes the need of external time GE Grid Solutions website for more details.
from zero-sequence voltage and current in a sources connected to the process bus network.
direction specified by the element characteristic
angle. Power can be selected as active, reactive,
Customers who may not be using GE MU devices, Advanced Automation
could use MU from other vendors. Interoperability
or apparent . Therefore, the element may The F60 incorporates advanced automation
with MU from other vendors is expected when
be used to sense either forward or reverse features including powerful FlexLogic
they comply to the mentioned standards.
ground faults. programmable logic, communication, and
SCADA capabilities that far surpass what is found
Autorecloser IEC 61850-9-2 HardFiber in the average feeder relay. The F60 integrates
Two autoreclose elements are provided for use Process Bus seamlessly with other UR relays for complete
with distribution lines in three-pole tripping system protection, including the unit and auxiliary
The IEC 61850 Process Bus module is designed
schemes with up to two breakers. Up to four transformers, and balance of plant protection.
to interface with the Multilin HardFiber System,
selectable recloser “shots” are possible prior to
allowing bi-directional IEC 61850 fiber optic
locking out. Any of the autoreclose elements FlexLogic
communications. The HardFiber System is
can be dynamically blocked or unblocked by FlexLogic is the powerful UR-platform
designed to integrate seamlessly with existing
other elements or user logic. This way they can programming logic engine that provides the
UR applications, including protection functions,
coordinate with the F60 protection setting groups. ability to create customized protection and
FlexLogic, metering and communications.
control schemes, minimizing the need and
Synchronism Check The Multilin HardFiber System offers the associated costs of auxiliary components and
The F60 provides six synchrocheck elements that following benefits: wiring. With 1024 lines of FlexLogic, the F60
monitor voltage difference, phase angle difference • Communicates using open standard can be programmed to provide the required
and slip frequency taking the CB closing time into IEC 61850 messaging tripping logic along with custom scheme logic
account to ensure proper breaker closure as per for auto transfer schemes (main-tie-main),
• Drastically reduces P&C design, installation
user requirement. Any of the six synchrocheck load shedding based on frequency, voltage
and testing labor by eliminating individual
elements can be dynamically blocked or copper terminations and communication, loop restoration schemes,
unblocked by other elements or user logic. This other remedial action schemes and dynamic
• Integrates with existing F60’s by replacing
way they can coordinate with the F60 protection setting group changes.
traditional CT/VT inputs with the IEC 61850
setting groups.
Process Bus module

Breaker Failure and Control


The F60 provides the required elements to
perform two independent breaker failure
functions. The F60 can provide independent
breaker failure protection for both breakers Topologies:
on a feeder with a breaker-and-a-half or ring PRP Start Station Bus
bus terminal. The relay also provides for the Hot-Stanby
control of one or two breakers from faceplate
pushbuttons, remote communications or
contact inputs. A breaker position can be
indicated by LEDs on the faceplate. Integrated Station and
Process bus (available)

IEC 61869* and 61850-9-2LE


Process Bus Topologies: Process Bus:
HSR ring -9-2LE or 61869* SV
Three UR process bus modules enable
communicating to Merging Units “MU” that PRP start IEEE 1588 Grand Master or
P-2-P Process Bus slave 61850-9-1 GOOSE
comply to either IEC 61869* standard or
IEC 61850-9-2LE technical report. MUs connect
to the primary asset and translate analog signals
and digital status/commands to standard
sample values “SV” data and GOOSE messages. Mergin units

Flexibility for connecting to different network size


and topology is granted through 100Mbps and/
Conventional or
or 1Gbps Ethernet port support, plus IEC 62439 Optical CT/VTs
PRP or HSR standard redundancy, plus Star, Ring
and Point-to-point network support.

4 GEGridSolutions.com
F60 Feeder Protection System

Scalable Hardware • Oscillography Cyber Security – CyberSentry UR


- Supports IEEE C37.111-1999/2013,
The F60 is available with a multitude of I/O CyberSentry UR enabled UR devices deliver full
IEC 60255-24 Ed 2.0 COMTRADE standard
configurations to suit the most demanding cyber security features that help customers to
- 64 digital & up to 40 analog channels
application needs. The expandable modular comply with NERC CIP and NIST® IR 7628 cyber
- Events with up to 45s length
design allows for easy configuration and future security requirements.
upgrades. • Data Logger and Disturbance Recording
- 16 channels up to 1 sample/cycle/channel This software option delivers the following core
• Flexible, modular high density I/O covering a broad features:
• Fault Reports
range of input signals and tripping schemes
- Powerful summary report of pre-fault and
• Types of digital outputs include trip- fault values AAA Server Support (Radius/LDAP)
rated Form-A and Solid State Relay (SSR) Enables integration with centrally managed
• Extensive breaker info (continuous coil
mechanically latching, and Form-C outputs authentication and accounting of all user
monitor, arcing current, operating time,
• RTDs and DCmA inputs are available to operation counter for asset management) activities and uses modern industry best
monitor equipment parameters such as practices and standards that meet and exceed
The very high sampling rates and large amount
temperature and pressure NERC CIP requirements for authentication and
of storage space available for data recording
password management.
in the F60 can eliminate the need for installing
Monitoring and Metering costly stand-alone recording equipment.
Role Based Access Control (RBAC)
The F60 includes high accuracy metering and
Advanced Device Health Diagnostics Efficiently administrate users and roles within
recording for all AC signals. Voltage, current,
UR devices. The new and advanced access
and power metering are built into the relay The F60 performs comprehensive device health
functions allow users to configure up to five
as a standard feature. Current and voltage diagnostic tests at startup and continuously
roles for up to eight configurable users with
parameters are available as total RMS during run-time to test its own major functions
independent passwords. The standard “Remote
magnitude, and as fundamental frequency and critical hardware. These diagnostic tests
Authentication Dial In User Service” (Radius) is
magnitude and angle. The F60 also measures monitor for conditions that could impact security
used for authentication.
up to the 25th harmonic on voltage and current, and availability of protection, and present device
suitable for power quality applications. status via SCADA communications and front
Event Recorder (Syslog for SEM)
panel display. Providing continuous monitoring
Fault and Disturbance Recording and early detection of possible issues help Capture all cyber security related events within
improve system uptime. a SOE element (login, logout, invalid password
The advanced disturbance and event recording
attempts, remote/local access, user in session,
features within the F60 can significantly reduce • Comprehensive device health diagnostic settings change, FW update, etc), and then
the time needed for postmortem analysis of performed at startup
serve and classify data by security level using
power system events and creation of regulatory
• Monitors the CT/VT input circuitry to validate standard Syslog data format. This will enable
reports. Recording functions include:
the integrity of all signals integration with established SEM (Security Event
• Sequence of Event (SOE) Management) systems.
- 1024 time stamped events

Communications
The F60 provides advanced commun-ications
technologies for remote data and engineering
access, making it easy and flexible to use and
Fiber LAN, single
or redundant, for integrate into new and existing infrastructures.
Source Direct support for fiber optic Ethernet provides
added security
high-bandwidth communications allowing
CB1 for low-latency controls and high-speed
file transfers of relay fault and event record
information. The available three independent
Fault 1 Ethernet ports, redundant Ethernet option
CB2 and the embedded managed Ethernet switch
provide the means to create fault tolerant
communication architectures in an easy,
cost-effective manner without the need for
CB3 intermediary communication hardware.

The F60 supports the most popular industry


standard protocols enabling easy, direct
Fault 2
integration into DCS and SCADA systems.

Reverse zone interlocking protection. By using the IEC 61850/GOOSE or hi-speed direct I/O capability
blocking signals can be transferred upstream, allowing for minimal coordination delays. Fast clearance
can be provided for Fault 1 while still maintaining coordination for Fault 2.

GEGridSolutions.com 5
F60 Feeder Protection System

• IEC 61850 Ed. 1 and Ed. 2 Station Bus, • Configures GE Systems based on IEC 61850 LAN Redundancy
IEC 61850-2-2LE / IEC 61869* networked or using universal 3rd party tools
Substation LAN redundancy has been traditionally
IEC 61850-9-2 HardFiber Process Bus, and • Multicast IEEE C37.118 synchrophasor accomplished by reconfiguring the active network
IEC 61850-90-5 PMU over GOOSE support data between PMU and PDC devices using topology in case of failure. Regardless of the type
• DNP 3.0 (serial & TCP/IP) IEC 91850-90-5 of LAN architecture (tree, mesh, etc), reconfiguring
• Ethernet Global Data (EGD) • R-GOOSE enable customer to send GOOSE the active LAN requires time to switchover, during
• IEC 60870-5-103 and IEC 60870-5-104 messages beyond the substation, which which the LAN is unavailable. UR devices deliver
enables WAPC and more cost effective redundancy as specified by PRP-IEC 62439-3,
• Modbus RTU, Modbus TCP/IP communication architectures for wide area which eliminates the dependency on LAN
• HTTP, TFTP, SFTP and MMS file transfer applications reconfiguration and the associated switchover
• IEEE1588 and redundant SNTP for time time. The UR becomes a dual attached node
Direct I/O Messaging
synchronization that transmits data packets over both main and
Direct I/O allows for the sharing of high-speed redundant networks simultaneously, so in case
• PRP as per IEC 62439-3
digital information between multiple UR of failure, one of the data packets will reach the
• Supports Routable GOOSE (R-GOOSE) relays via direct back-to-back connections or receiving device with no time delay.
multiplexed through a standard DS0 multiplexer
Interoperability with Embedded
channel bank. Regardless of the connection Multi-Language
IEC 61850 Ed. 1 and Ed. 2
method, direct I/O provides continuous UR devices support multiple languages: English,
The new IEC 61850 implementation in the UR real-time channel monitoring that supplies French, Russian, Chinese, Turkish, German,
Family positions GE as an industry leader in this diagnostics information on channel health. Polish and Japanese. These language options
standard. Direct I/O provides superior relay-to-relay are available on the front panel, in the EnerVista
• Implements, user selectable, Ed. 1 and Ed. 2 communications that can be used in advanced setup software, and in the product manuals.
of the standard across the entire UR Family interlocking, generation rejection and other Easily switch between English and an additional
special protection schemes. language on the local displays without
• Provides full relay setting management via
standard SCL files (ICD, CID and IID) • Communication with up to 16 UR relays uploading new firmware.
• Enables automated relay setting in single or redundant rings rather than
management using 3rd party tools through strictly limited to simplistic point-to-point
standard file transfer services (MMS and SFTP) configurations between two devices

• Increases the number of Logical Devices and • Connect to standard DS0 channel banks
data mapped to them, GOOSE messages through standard RS422, G.703 or
from up to 64 remote devices, and reports IEEE C37.94 interfaces or via direct fiber optic
to support different organizational needs for connections
data transfer and reduce dependency on • No external or handheld tester required to
generic logical nodes provide channel diagnostic information

Power System Troubleshooting


The F60 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events, increase uptime and
reduce loss of production.

Analyze feeder faults and disturbances using both analog and digital power
Record the operation of the internal F60 elements and external connected system quantities that are measured and recorded up to a rate of 64 samples
devices with 1ms time-stamped accuracy to identify the Sequence of per cycle.
Operation of station devices during faults and disturbances.

6 GEGridSolutions.com
F60 Feeder Protection System

EnerVista Software Viewpoint UR Engineer User Interface


The EnerVista suite is an industry-leading set Viewpoint UR Engineer is a set of powerful The F60 front panel provides extensive local
of software programs that simplifies every tools that allows the configuration and testing HMI capabilities. The local display is used for
aspect of using the F60 relay. The EnerVista of GE relays at a system level in an easy-to- monitoring, status messaging, fault diagnosis,
suite provides all the tools to monitor the status use graphical drag-and-drop environment . and device configuration. User-configurable
of the protected asset, maintain the relay, and Viewpoint UR Engineer provides the following messages that combine text with live data can be
integrate information measured by the F60 into configuration and commissioning utilities: displayed when user-defined conditions are met.
DCS or SCADA monitoring systems. Convenient • Graphical Logic Designer A 7” color, graphic HMI is optionally available that
COMTRADE and SOE viewers are an integral part allows users to have customizable bay diagrams
• Graphical System Designer
of the UR setup software included with every UR with local monitoring of status, values and control
relay, to carry out postmortem event analysis and • Graphical Logic Monitor
functionality. The alarm annunciator panel
ensure proper protection of system operation. • Graphical System Monitor provides the configuration of up to 96 signals
(alarms and status) with full text description.
EnerVista Launchpad Viewpoint Maintenance
EnerVista Launchpad is a powerful software Viewpoint Maintenance provides tools that
package that provides users with all of will create reports on the operating status of
the setup and support tools needed for the relay, simplify the steps to download fault
configuring and maintaining Multilin products. and event data, and reduce the work required
The setup software within Launchpad allows for cyber security compliance audits. Tools
for the configuration of devices in real-time available in Viewpoint Maintenance include:
by communicating using serial, Ethernet , or • Settings Security Audit Report
modem connections, or offline by creating
• Device Health Report
setting files to be sent to devices at a later time.
• Single-Click Fault Data Retrieval
Included in Launchpad is a document archiving
and management system that ensures critical EnerVista Integrator
documentation is up-to-date and available when
EnerVista Integrator is a toolkit that allows
needed. Documents made available include:
seamless integration of Multilin devices into
• Manuals new or existing automation systems. Included in
• Application Notes EnerVista Integrator is:

• Guideform Specifications • OPC/DDE Server

• Brochures • Multilin Drivers

• Wiring Diagrams • Automatic Event Retrieval

• FAQ’s • Automatic Waveform Retrieval

• Service Bulletins

Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use and LED indicators 7” large color graphic HMI
full-featured monitoring and data recording
software package for small systems. Viewpoint 8 user
Monitoring provides a complete HMI package programmable
with the following functionality: pushbuttons

• Plug-&-Play Device Monitoring


• System Single-Line Monitoring & Control
• Annunciator Alarm Screens
• Trending Reports
• Automatic Event Retrieval 10 side screen
• Automatic Waveform Retrieval pushbuttons

GEGridSolutions.com 7
F60 Feeder Protection System

Typical Wiring

A B C

52

CONNECTION

F 5a

F 6a

F 7a

F 5a

F 6a

F 7a

F 8a

F 1a

F 1b

F 2a

F 2b

F 3a

F 3b

F 4a

F 4b
F 5c

F 6c

F 7c

F 5c

F 6c

F 7c

F 8c

F 1c

F 2c

F 3c

F 4c
VX
VB

VC

VB

VC
VA

VA

VX

IG5

IG1
VB

VC

VB

VC

IG
VA

VA

IA5

IA1

IB

IC
IA

IC5

IC1
IB5

IB1
8L/8M
H7a 6B I H1a TC 1
H7c H1 H1b
V
H8a H1c
H8c I H2a
H7b H2 H2b
V
H2c
H8b SURGE
H3a
H3 H3b TC 2
H3c
H4a
Digital Energy H4 H4b
Multilin H4c
H5a
H5
F60
H5b
H5c
H6a
H6 H6b
H6c
W5a 6A I W1a
W5c W1 W1b
V
W6a W1c
W6c I W2a
W5b W2 W2b
V
W2c
W7a
W3a
W7c
W3 W3b
W8a
W3c
W8c
W4a
W7b
W4 W4b
W8b SURGE W4c
6C P1a
P1 P1b
U1a
6D

U1c P1c
U2a P2a
P2 P2b
U2c
U1b P2c
P3a
U3a P3 P3b
U3c P3c UR COMPUTER
U4a P4a
U4c 1 1 8
P4 P4b
U3b TXD 2 2 3 RXD
P4c
RXD 3 3 2 TXD
U5a P5a
4 4 20
U5c P5 P5b
SGND 5 5 7 SGND
U6a P5c
6 6 6
U6c P6a
P6 7 7 4
U5b P6b
8 8 5
U7a P6c
9 9 22
U7c P7a
P7 P7b
U8a
U8c P7c CONNECTOR
CONNECTOR
U7b P8a
P8 P8b
U8b SURGE RS-232
P8c
DB-9
B1b M1a
CRITICAL
1

(front)
6K

B1a FAILURE M1 M1b


B2b M1c
DC B3a M2a
B3b OUTPUT M2 M2b
B5b HI M2c
CONTROL
B6b LO POWER M3a
B6a M3 M3b
B8a SURGE This diagram is based on
M3c
B8b FILTER M4a the following order code:
M4 M4b F60-HG4-HLH-F8L-H6B-M6K-
M4c
M5a P6C-U6D-W6A
* Optic
Fibre Tx1 10BaseFL
NORMAL M5 M5b This diagram provides an
Rx1
M5c
Tx2 10BaseFL COM example of how the device is
Rx2
ALTERNATE
1
M6a
M6 M6b wired, not specifically how to
Shielded 10BaseT M6c wire the device. Please refer
Remote M7a
Device D1a
RS485 M7 M7b to the Instruction Manual for
D2a
M7c additional details on wiring
D3a com
M8a based on various configurations.
D4b M8 M8b
D4a IRIG-B
Input M8c
Co-axial BNC

IRIG-B
Co-axial BNC Output

Minimum 832769A5.CDR

X W V U T S R P N M L K J H G F D B
6 6 6 6 6 8 9 1
Inputs/ Inputs/ Inputs/ Inputs/
outputs outputs outputs outputs Inputs/ CT/VT CPU Power
PROVIDED
* * * * outputs Supply

8 GEGridSolutions.com
Ordering
F60 - * ** - H * * - F ** - H ** - M ** - P ** - U ** - W ** For Full Sized Horizontal Mount
Base Unit F60 Base Unit
CPU E RS485 + RS485 (IEC 61850 option not available)
J RS485 + multimode ST 100BaseFX
K RS485 + multimode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
T RS485 + three multimode SFP LC 100BaseFX. Req FW v7xx or higher
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT.
Req FW v7xx or higher
V RS485 + three SFP RJ45 100BaseT. Req FW v7xx or higher
W RS485 + two 100BaseFx Eth, Multimode ST + one 10/100BaseT Eth, RJ-453
Software Options1 00 No Software Options
03 IEC 61850
06 PMU
07 IEC 61850 + PMU
A0 CyberSentry Lvl 1. Req UR FW 7.xx or higher
B0 IEEE 1588. Req UR FW 7.xx or higher
C0 PRP
D0 IEEE 1588 + CyberSentry. Req UR FW 7.xx or higher
M0 IEC 61850 + PMU + 61850-90-5
Mount / Coating H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface E 7” Graphical display, USB front port & programmable pushbuttons - Multi-Language (FW 7.6x or higher)
F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
H Enhanced Polish Front Panel3
O Enhanced Polish Front Panel with User-Programmable Pushbuttons3
Z Enhanced Japanese Front Panel3
X Enhanced Japanese Front Panel with User-Programmable Pushbuttons3
Power Supply2 H 125 / 250 V AC/DC
H RH 125/250 V AC/DC with redundant 125/250 V AC/DC power supply
L 24 - 48 V (DC only)
CT/VT DSP 8F Standard 4CT/4VT
8G Sensitive Ground 4CT/4VT
8H Standard 8CT
8J Sensitive Ground 8CT
8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
8R 8R Sensitive Ground 8CT w/ enhanced diagnostics
8Z HI-Z 4CT (high impedance fault detection)
IEC 61850 Process Bus4, 5 81 8 Port IEC 61850 Process Bus Module
85 -9-2LE & 61869* Process Bus, 2 x 1000BaseF
86 -9-2LE & 61869* Process Bus, 4 x 1000BaseF + 4 x 100BaseFx
87 -9-2LE & 61869* Process Bus, 4 x 100BaseFx
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
6W 6W 6W 6W 6W 30 Contact Inputs - Pin Terminals3
6X 6X 6X 6X 6X 18 Form-A (No Monitoring) Outputs - Pin Terminals3
Transducer I/O 5C 5C 5C 5C 5C 8 RTD Inputs
5E 5E 5E 5E 5E 4 dcmA Inputs, 4 RTD Inputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, singlemode, ELED, 1 Channel
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, singlemode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
76 IEEE C37.94, 820 nm, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
Ordering Note: 
1. To view all the options available for L90, please visit GE’s On-Line Store
http://store.gedigitalenergy.com/viewprod.asp?model=F60
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be
same type. Maximum 2 per chassis GEGridSolutions.com
3. Option available soon
4. Process bus module requires empty slots next to it. IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
5. Conventional DSP and Process Bus modules cannot run simultaneously trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Footnote: * Upcoming release Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General
Electric Company. GE reserves the right to make changes to specifications of products described at
any time without notice and without obligation to notify any person of such changes.
Copyright 2018, General Electric Company. GEA-12595J(EN)