Reference Performance Test Description: Project - JIYEH Power Plant, Location - Beruit, Lebanon
Reference Performance Test Description: Project - JIYEH Power Plant, Location - Beruit, Lebanon
Applicable Standards :
The "Reference" performance test shall be in accordance with CIMAC
recommendations and corrected to the Facilities designed condition. All the
correction Curve will be as the original OEM acceptance test.
For DE and generator ASME PTC 17
For STG ASME PTC 6.2
HRSG ASME PTC 4.1
Condensor ASME PTC 30.1
Other measurements :
Air intake temp. @ all engines oil bath filter by Electronic thermometer.
Coolant inlet temp. before CAC @ all engines for reference only.
Charge air inlet temperature before engine by existing / installed meter.
Ambient pressure @ T/C @ oil bath filter by Precision pressure guage.
Cummulative measurement of KWHr for average production calculation.
Fuel oil sample collection for all engines after 100 % load test for analysis.
Power factor at generator terminals.
Documentation submission :
Before the test for review and approval
Performance Test procedure