DPX-1 Self Powered Relay: Areva T&D

The document describes the DPX-1 self-powered relay. It provides overcurrent, short circuit, and earth fault protection functions. It uses current transformer inputs and has outputs for tripping circuit breakers or flag indicators. Fault data is stored internally with a time stamp and can be accessed via serial communication. The relay has LED indicators and is designed for compact installation in switchgear panels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
435 views12 pages

DPX-1 Self Powered Relay: Areva T&D

The document describes the DPX-1 self-powered relay. It provides overcurrent, short circuit, and earth fault protection functions. It uses current transformer inputs and has outputs for tripping circuit breakers or flag indicators. Fault data is stored internally with a time stamp and can be accessed via serial communication. The relay has LED indicators and is designed for compact installation in switchgear panels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

DPX-1 Self Powered Relay

AREVA T&D
DPX-1 Self Powered Relay

Contents

1. Introduction

2. Features and Characteristics

3. Product Description

3.1 Operation
3.2 Installation

4. Inputs and Outputs

4.1 Inputs
4.2 Outputs
4.2.1 Impulse Output
4.2.2 Flag Indicator Outputs
4.3 LED

5. Fault Value Memory

6. Communication

6.1 Circuit Breaker Trip Counter

7. Technical data

7.1 Characteristics
7.2 Earth Current Protection
7.3 Settings
7.4 IDMT Characteristics
7.5 Characteristics Curves

8. Product Specific Features

8.1 Earthing

9. Terminal Details

10. System Data

10.1 EMC
10.2 Accuracy
10.3 Common Data
10.4 Ambient Conditions
10.5 Insulation Voltage Withstand

11. Connection Diagram

11.1 Terminal Block


11.2 Connections
11.3 Dimensional Details

2
DPX-1 Self Powered Relay

1. Introduction 3.1 Operation

Areva offers a wide range of CT powered relays which DPX-1 is a high tech and cost optimised protection relay
provide over current, short circuit, instantaneous phase for MV switchboards. Specifically in compact switchboards,
and earth fault functions. DPX is a compact relay specifically the DPX-1 can replace the combination of load break switch.
designed for compact MV switchboards with circuit
breakers. DPX-1 uses CTs with secondary rated for 1A. DPX-1 is provided with four analogue measuring inputs
[Phase current CTs and CBCT]. Setting of parameters is
2. Features & Characteristics done by means of HEX switches.

. CT powered relay. The DPX-1 is provided with an input for remote tripping to
which 110 VAC or 230 VAC can be connected. Tripping is
. O/C, S/C, E/F and E/F High Set protection realised via the electric impulse output even without
presence of phase current.
. DEFT and Inverse characteristics for O/C and
E/F A flag indicator can be installed for signaling occurrence
of trip conditions.
. Impulse output for tripping coil
Pickup activation of the relay is signaled by a bi-color LED
on front panel.
. Impulse output for hand reset type magnetic
flag. (Magnetic flag is not a part of standard
3.2 Installation of the Relay
supply)
The requirements on MS distribution stations with circuit
. Remote Trip input
breakers call for a robust protection relay which is optimized
accordingly and an integral part of the respective
. Fault value memory with Real Time Clock switchboard. DPX-1 with minimal space requirements,
simple but safe wiring, high electromagnetic immunity, and
. Short circuit back-up protection uncomplicated adjustments complies with the highest
demands on a digital protection device.
. Serial communication for remote read-out
on MODBUS RTU By using the three 7mm drill holes, the relay is directly
mounted onto the mounting plate. Please refer to sec 11.3
. Parameter setting by rotary switches dimensional details.

. Inverse characteristics can be individually 4. Inputs and Outputs


selected for phase and earth fault
4.1 Inputs
3. Product Description
The analog input signal of the conductor currents are fed
The DPX-1 is a CT-powered protection relay with inverse to the protective device via separate input transformers at
time and definite time protection characteristics. terminal numbers 17, 18, 19, 20, 21 and 22 respectively.
The continuously measured current values are galvanically
DPX-1 provides following protection functions: isolated, analog filtered and finally fed to the analog/digital
converter.
. 3 phase definite time over current and short- There are two optionally selectable terminals CBCT1 and
circuit protection with variable tripping times CBCT2 for use with a Core Balance Current Transformer.
(ANSI 50/51) CBCT doesn’t energize the DPX-1. Earth current can also
be measured with CBCT using holomgreen arrangement.
. 3 phase over current protection with
selectable inverse time characteristics and 4.2 Outputs
definite time short-circuit current element
(ANSI 50/51) 4.2.1 Impulse Output

. Definite time and inverse time earth over Tripping coil receives 50ms pulses as long as adequate
current protection by internal calculation excitation is present. The repetition rate of pulses depends
(ANSI 50N/51N). on the energy consumed by the trip coil and the fault current
level.

TRIP Energy = 0.2Ws@24V DC

3
DPX-1 Self Powered Relay

4.2.2 Flag indicator output

An output similar to above but with less energy is provided


for operating a magnetic flag.

TRIP Energy = 0.02Ws@24V DC

4.3 LED

A bicolor LED indication is provided in the front panel of


the relay DPX-1. The two colors are green and red. Green
flashing indicates the healthy state of relay. Applying of Ext
DC supply or applying of current grater than 0.495A starts
the green flashing this green flashing incorporates the
watchdog feature of relay as a check of its internal processor
healthiness. Red flashing indicates the Phase/ earth fault
pickup and steady red indicates trip on phase / earth fault.

5. Fault value memory

A fault value memory with real time clock stamp is


integrated in the relay DPX-1, where data of the last fault Figure: DR1
occurrence is stored. The stored information can be read
out via the Data Retrieval Device DR1 or through PC
interface on MODBUS. The following fault information is
available. DPX1 supports External MODBUS communication on RS485
with following settings.
· The protective element causing the trip or an
externally triggered trip. Baud rate : 9600 baud
Parity : Even
· Values of the trip current in the individual phases Stop Bit : 1 bit
and earth fault current. Data Bit : 8 bit data
Remote Address : 1-32(settable through
· Time and date stamp of the trip PC with default factory
setting of 2 )
6. Communication
All parameters of DPX-1 relay can be accessed through
DPX-1 serially communicates with data retrieval device type “MODBUS” using external RS485 to RS232 converter.
DR1/DR2. DR1 is an externally powered unit housed in a
DIN standard 96 x 96 mm flush mounting enclosure, while
DR-2 is a +9V battery powered unit housed in a DIN
standard 72x72mm. Both can be used for data /fault 6.1 Circuit Breaker Trip Counter
retrieval. DR-1 has additional four relays which can be
used for annunciation. DR1/2 is wired to DPX-1 on RS485 DPX-1 maintains a counter for running count of the number
port. DR1 has a RS232 port on the front panel and of times a circuit breaker has been tripped. DPX1
supporting software for connection to a PC. Ext supply of permanently stores this number in its EEPROM. DPX1 can
+12V is required for DPX-1 communication with DR-1/ maintain maximum upto 65535 trip counts in its internal
DR-2 . DR-1/DR-2 is not a part of the standard supply, it is memory after that counter gets automatically reset. This
an accessory. information is accessible through MODBUS / PC front end
software/DR1/DR2. Similarly one can also reset this count
through MODBUS / PC front end software / DR1/DR2.

4
DPX-1 Self Powered Relay

7. Technical Data

7.1 Characteristics

Hex switches are provided for parameter setting.

Switch Setting Parameter

1 I> Characteristics for O/C

2 I> Pick-up value of phase O/C

3 tI> Tripping time of the definite time


over current element or time
multiplier of the inverse time
characteristic

4 I>> Pick-up value of the phase S/C


element

5 tI>> Tripping time of the short-circuit


element

6 IE > Characteristic for E/F

7 IE> Pick-up value of the definite time


Earth O/C element

8 tIE> Tripping time of the definite time earth


over current element or time
multiplier of Earth O/C element

9 IE>> Pick up value of E/F high set

10 tIE>> Tripping time of the definite time Earth


High Set element

7.2 Assignment of terminals

The protection relay DPX-1 is equipped with 22 screw-


type plug in terminals. For Details see section 9 terminal
details.

5
DPX-1 Self Powered Relay

7.3 Setting Ranges and Steps

HEX - Switch 1

HEX 1 0 1 2 3 4 5 6 7 8 9 A B C D E F
CHAR DEFT N- V- E- L- RI- x x x x x x x x x x
INV INV INV INV INV

I>: HEX - Switch 2

HEX 3 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 0.5 0.6 0.7 0.8 0.9 1 1.15 1.3 1.4 1.5 1.6 1.8 2 2.25 2.5 Exit

tI>: HEX – Switch 3

HEX 3 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.04 1 2 3 4 5 6 8 10 15 30 60 120 180 240 300
(DEFT)
Factor 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10
“a”

I>>: HEX – Switch 4

HEX 4 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 Exit

tI>> : HEX – Switch 5

HEX5 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.04 0.07 0.1 0.15 0.2 0.25 0.3 0.4 0.6 0.8 1.0 1.4 1.8 2.2 2.6 3.0

HEX - Switch 6

HEX 6 0 1 2 3 4 5 6 7 8 9 A B C D E F
CHAR DEFT N- V- E- L- RI- x x x x x x x x x x
INV INV INV INV

IE>: HEX – Switch 7

HEX 7 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.2 1.4 1.6 2.0 2.5 Exit

tIE>: HEX – Switch 8

HEX 8 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.06 0.1 0.2 0.4 0.6 1 2 4 6 10 20 40 60 100 200 300
(DEFT)
Factor 0.05 0.07 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 6 8 10
“a”

6
DPX-1 Self Powered Relay

IE>>: HEX – Switch 9

HEX 9 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 10 Exit

tIE>> : HEX – Switch 10

HEX10 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.03 0.04 0.05 0.06 0.08 0.1 0.15 0.20 0.25 0.3 0.4 0.6 0.8 1 1.5 2

7.4 Calculation formula for IDMT characteristics

Normal Inverse:

Very Inverse:

Extremely Inverse:

Long time inverse:

RI- Inverse:

t= 1 .a[s]
0.339 – 0.236

{ IsI }

7
DPX-1 Self Powered Relay

Figure 4 : DEFT Figure 6: RI-INV

8
DPX-1 Self Powered Relay

8. Product Specific Features

8.1 Earthing

The fourth terminal (PE) of the top terminal block is the central earth connection point of the protection system.

9. Terminals Details

Terminal Terminal Description Details


No. Name
1 E Earth
2 N Neutral
3 110 V Remote trip Input 110V AC
4 230 V Remote trip Input 230V AC
5 P1 RS 485 Comm (Positive)
6 N1 RS 485 Comm (Negative)
7 GND Ext Supply GND
8 +12 V Ext Supply +12 V
9 TF+ Trip Flag (+ ve)
10 TF- Trip Flag (- ve)
11 TC- Trip Coil (- ve)
12 TC+ Trip Coil (+ ve)
13 E1 CT Inter Connection
14 CS2 CT Inter Connection
15 CBCT2 CBCT2
16 CBCT1 CBCT1
17 B2 B phase
18 B1 B phase
19 Y2 Y phase
20 Y1 Y phase
21 R2 R phase
22 R1 R phase

10. System Data

10.1 EMC

Interference immunity against discharges of static electricity


DIN EN 60255-22-2 [05/97] Air discharge 8 kV
DIN EN 61000-4-2 [03/96] contact discharge 6 kV
Class 3
Interference immunity against high-speed transient interference quantities
DIN IEC 60255-22-4 [10/93] power supply, mains inputs ±4 kV, 2.5 kHz
DIN EN 61000-4-4 [03/96] other inputs and outputs ±2 kV, 5 kHz
Class 4
Interference immunity against 1 MHz burst disturbance tests
DIN EN 60255-22-6 [11/94] differential mode 2.5 kV, 1 MHz
DIN IEC 60255-22-1 [05/91] common mode 1 kV, 2 s
Interference immunity against surge immunity test
DIN EN 61000-6-2 [03/00] 4 kV/2 kV
DIN EN 61000-4-5 [09/96]
Interference immunity against high-frequent electromagnetic fields
DIN EN 61000-4-3 [08/97] 10 V/m
Class 3
Interference immunity against magnetic fields of energy based frequency
DIN EN 61000-4-8 [05/94] continuously 100 A/m
Class 5 3s 1000 A/m

9
DPX-1 Self Powered Relay

Interference immunity against line conducted interference quantities induced by high-frequent fields
DIN EN 61000-4-6 [04/97]
Class 3 (0.15-230 MHz) 10 V/m
Interference immunity against surge voltage
DIN EN 61000-4-5 [09/96] within a current circuit 2 kV
Class 4 current circuit to earth 4 kV
Measuring of the radio interference voltage
DIN EN 55011 [10/97] Limit. value class B
Measuring of the radio interference radiation
DIN EN 55011 [10/97] Limit. value class B

10.2 Accuracy

Tripping times with prefault : DMT: + 3% of the setting value & absolutely +20 ms
IMT: Accuracy as per IEC-255-3 (2 x In to 20 x In)
For VINV / NINV:+ 5% or + 20 msec which ever is higher
For EINV/LI-INV/RI-INV : + 7.5% or + 20 msec which ever is
higher

Pickup Accuracy: + 3%

Tripping time without prefault Standard time + ( <100 msec)

Technical data subject to change without notice!

10.3 Common Data

Frequency: 50 Hz ± 2 Hz / 60Hz ± 2 Hz
Thermal load capacity: Continuously : 2.5 x In
1s 60 x In
10s 20 x In
Dynamically current withstand 250 x In (half wave)
Dropout Ratio : > 95%
Burden 2 VA
Ext. Aux. Supply +12V DC Range +7V to +14V DC

10.4 Ambient Conditions

Vibration and continuous vibration test


DIN EN 60255-21-1 [05/96] 1/2 gn
Class 2
Shock and continuous shock test
DIN EN 60255-21-2 [05/96] 10/20 gn
Class 2
Test Ad: Cold
DIN EN 60068-2-1 [03/95] Temperature -40°C
Period of stress 16 h
Test Bd: Dry heat
DIN EN 60068-2-2 [08/94] Temperature +85°C
Rel. humidity <50%
Period of stress 72 h
Test Ca: Humid heat (constantly)
DIN IEC 60068-2-3 [12/86] Temperature +40°C
Rel. humidity 93%
Period of stress 56 d
Test Db : Humid heat (cyclic)
DIN IEC 60068-2-30 [09/86] Temperature +70°C
Rel. humidity 95%
Cyclen (12 + 12-hours) 2

10
DPX-1 Self Powered Relay

Class of protection
Relay housing IP 40
Electronics IP 65
Terminals IP 20

10.5 Insulation voltage withstand

Test of withstand alternating IEC 60255-5 2.5 kV


voltage for 1 min:
Test of lightning surge voltage IEC 60255-5 5 kV
1.2/50 μs, 0.5 J

11. Connection Diagram

11.1 Terminal Block

11.2 Connections

R
R

Y
Y

B
B

N
N

E1 E1 E1

11
11.3 Dimensional Details.

All Dimensions are in mm.

Weight : 1kg (Approx.)


Dimensions (W x H x T) : 125×222×41mm