DPX-1 Self Powered Relay: Areva T&D
DPX-1 Self Powered Relay: Areva T&D
AREVA T&D
DPX-1 Self Powered Relay
Contents
1. Introduction
3. Product Description
3.1 Operation
3.2 Installation
4.1 Inputs
4.2 Outputs
4.2.1 Impulse Output
4.2.2 Flag Indicator Outputs
4.3 LED
6. Communication
7. Technical data
7.1 Characteristics
7.2 Earth Current Protection
7.3 Settings
7.4 IDMT Characteristics
7.5 Characteristics Curves
8.1 Earthing
9. Terminal Details
10.1 EMC
10.2 Accuracy
10.3 Common Data
10.4 Ambient Conditions
10.5 Insulation Voltage Withstand
2
DPX-1 Self Powered Relay
Areva offers a wide range of CT powered relays which DPX-1 is a high tech and cost optimised protection relay
provide over current, short circuit, instantaneous phase for MV switchboards. Specifically in compact switchboards,
and earth fault functions. DPX is a compact relay specifically the DPX-1 can replace the combination of load break switch.
designed for compact MV switchboards with circuit
breakers. DPX-1 uses CTs with secondary rated for 1A. DPX-1 is provided with four analogue measuring inputs
[Phase current CTs and CBCT]. Setting of parameters is
2. Features & Characteristics done by means of HEX switches.
. CT powered relay. The DPX-1 is provided with an input for remote tripping to
which 110 VAC or 230 VAC can be connected. Tripping is
. O/C, S/C, E/F and E/F High Set protection realised via the electric impulse output even without
presence of phase current.
. DEFT and Inverse characteristics for O/C and
E/F A flag indicator can be installed for signaling occurrence
of trip conditions.
. Impulse output for tripping coil
Pickup activation of the relay is signaled by a bi-color LED
on front panel.
. Impulse output for hand reset type magnetic
flag. (Magnetic flag is not a part of standard
3.2 Installation of the Relay
supply)
The requirements on MS distribution stations with circuit
. Remote Trip input
breakers call for a robust protection relay which is optimized
accordingly and an integral part of the respective
. Fault value memory with Real Time Clock switchboard. DPX-1 with minimal space requirements,
simple but safe wiring, high electromagnetic immunity, and
. Short circuit back-up protection uncomplicated adjustments complies with the highest
demands on a digital protection device.
. Serial communication for remote read-out
on MODBUS RTU By using the three 7mm drill holes, the relay is directly
mounted onto the mounting plate. Please refer to sec 11.3
. Parameter setting by rotary switches dimensional details.
. Definite time and inverse time earth over Tripping coil receives 50ms pulses as long as adequate
current protection by internal calculation excitation is present. The repetition rate of pulses depends
(ANSI 50N/51N). on the energy consumed by the trip coil and the fault current
level.
3
DPX-1 Self Powered Relay
4.3 LED
4
DPX-1 Self Powered Relay
7. Technical Data
7.1 Characteristics
5
DPX-1 Self Powered Relay
HEX - Switch 1
HEX 1 0 1 2 3 4 5 6 7 8 9 A B C D E F
CHAR DEFT N- V- E- L- RI- x x x x x x x x x x
INV INV INV INV INV
HEX 3 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 0.5 0.6 0.7 0.8 0.9 1 1.15 1.3 1.4 1.5 1.6 1.8 2 2.25 2.5 Exit
HEX 3 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.04 1 2 3 4 5 6 8 10 15 30 60 120 180 240 300
(DEFT)
Factor 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10
“a”
HEX 4 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 Exit
HEX5 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.04 0.07 0.1 0.15 0.2 0.25 0.3 0.4 0.6 0.8 1.0 1.4 1.8 2.2 2.6 3.0
HEX - Switch 6
HEX 6 0 1 2 3 4 5 6 7 8 9 A B C D E F
CHAR DEFT N- V- E- L- RI- x x x x x x x x x x
INV INV INV INV
HEX 7 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.2 1.4 1.6 2.0 2.5 Exit
HEX 8 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.06 0.1 0.2 0.4 0.6 1 2 4 6 10 20 40 60 100 200 300
(DEFT)
Factor 0.05 0.07 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 6 8 10
“a”
6
DPX-1 Self Powered Relay
HEX 9 0 1 2 3 4 5 6 7 8 9 A B C D E F
x IS 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 10 Exit
HEX10 0 1 2 3 4 5 6 7 8 9 A B C D E F
Time(s) 0.03 0.04 0.05 0.06 0.08 0.1 0.15 0.20 0.25 0.3 0.4 0.6 0.8 1 1.5 2
Normal Inverse:
Very Inverse:
Extremely Inverse:
RI- Inverse:
t= 1 .a[s]
0.339 – 0.236
{ IsI }
7
DPX-1 Self Powered Relay
8
DPX-1 Self Powered Relay
8.1 Earthing
The fourth terminal (PE) of the top terminal block is the central earth connection point of the protection system.
9. Terminals Details
10.1 EMC
9
DPX-1 Self Powered Relay
Interference immunity against line conducted interference quantities induced by high-frequent fields
DIN EN 61000-4-6 [04/97]
Class 3 (0.15-230 MHz) 10 V/m
Interference immunity against surge voltage
DIN EN 61000-4-5 [09/96] within a current circuit 2 kV
Class 4 current circuit to earth 4 kV
Measuring of the radio interference voltage
DIN EN 55011 [10/97] Limit. value class B
Measuring of the radio interference radiation
DIN EN 55011 [10/97] Limit. value class B
10.2 Accuracy
Tripping times with prefault : DMT: + 3% of the setting value & absolutely +20 ms
IMT: Accuracy as per IEC-255-3 (2 x In to 20 x In)
For VINV / NINV:+ 5% or + 20 msec which ever is higher
For EINV/LI-INV/RI-INV : + 7.5% or + 20 msec which ever is
higher
Pickup Accuracy: + 3%
Frequency: 50 Hz ± 2 Hz / 60Hz ± 2 Hz
Thermal load capacity: Continuously : 2.5 x In
1s 60 x In
10s 20 x In
Dynamically current withstand 250 x In (half wave)
Dropout Ratio : > 95%
Burden 2 VA
Ext. Aux. Supply +12V DC Range +7V to +14V DC
10
DPX-1 Self Powered Relay
Class of protection
Relay housing IP 40
Electronics IP 65
Terminals IP 20
11.2 Connections
R
R
Y
Y
B
B
N
N
E1 E1 E1
11
11.3 Dimensional Details.