Loop Checking Basic Procedure
Loop Checking Basic Procedure
Electrical Instrumentation
5. If a transmitter exists in a loop, the output signals equivalent to 0%, 50% and 100% of the
range of the instrument will be generated in manual mode (dummysignals) to verify the
function of the loop, such as variable zero variation of the transmitters or by connecting the
standard DC current generator or the retaining nozzle and the fin in the pilot of the pneumatic
transducers.
6. Connect a known precision source to the primary field transmitter. The assimilation of the
measured variable is applied to the transmitter for reading at zero, half scale and full scale,
according to the instructions recommended by the manufacturer. Note in the PLC system that
the indication is shown as simulated. Also note on the MMI screens (ManMachine Interface)
on the PC. You must indicate the appropriate actions in Screen and Alarm Screens
7. If there is a local controller mounted in a loop, the signal to verify the operation of the
valve will be generated manually using the manual operation device in the controller before
the automatic operation check. An automatic operation check will be performed by changing
the setpoint of the controller.
8. Control loop: Place the controller in manual mode and simulate the signal of the process
variable from 0%, 25%, 50%, 75% and 100% of the scale and note on the monitor that the
process variable indication shows signals assimilated. Return the process variable to 0%,
place the controller in automatic mode, set P.B. 100%, restart the time and derived to
Minimum adjustment with 50% set point and make sure the controller is an indirect action.
Simulate the process variable signal 0%, 25%, 50%, 75% and 100%, observe and record all
the findings
9. For pressure switches and level interrupters, their contact must be made manually and / or
interrupted to guarantee the corresponding responses of the instrument.
For thermocouple loops, check the burn characteristics by disconnecting the cables, and
confirm that the polarity of the thermocouple extension leads is maintained when they are
reconnected. To assist in the identification of the thermocouple extension cables, the
following guidance is provided.
(1) The negative extension cables are always colored in red as in the PER ANSI C96.1.
(2) For the K-type thermocouple (Chromel / alumel), the negative cable is slightly magnetic.
It has a lower resistance in ohms / feet for the same size cable.
(3) For R type thermocouple (copper alloy / nickel copper), the negative wires are softer than
the positive wire.11.For the loops of the resistance temperature detector (RTD), check the
function of all the instruments and control valves in the circuit by connecting the resistor
approximately 120 ohm in the terminal heads, and visually verify the correct connections
when closing the terminal heads.