Climatix™ C600

HVAC&R controller
POL648.x0, POL688.x0, POL69x.x0

Climatix C600 controllers for heating, ventilation, air conditioning and refrigeration
equipment.

Freely programmable modular controllers


21, 27 and 29 physical inputs / outputs per controller
Integrated stepper motor outputs with failsafe behavior (UPS)
Integrated local or remote HMI
Standard USB service connection for tool access
Ethernet port for local/remote servicing and Climatix IC connectivity
SD card interface with for applications, firmware download, and archiving
Physical input/output extension using extension modules
Third-party integration using the built-in RS-485 interfaces for Modbus RTU
Networking over the process bus
Communication module connectivity for additional BACnet IP, BACnet MS/TP,
M-bus, LON and OPC
Operating temperature range: -40...70 degree Celsius

A6V10990076_en_a Building Technologies


2016-10-17
Application and features

Field of application
Climatix products are designed for use in heating, ventilation, air conditioning and
refrigeration machines and provide a broad range of control and monitoring functions.
The number and type of I/Os on the controller and extension modules are optimized for
these application types.

Modular design
The product range is of modular design and primarily comprises controllers and various add-
on I/O and communication modules. Different HMIs can be connected to the controllers,
either directly (local HMI) or via the network (remote HMI).

Freely programmable
The Climatix controllers are freely programmable using a powerful graphical software tool
(SAPRO). A number of defined inputs/outputs (analog or digital) plus freely programmable
I/O channels make it possible to create a host of applications with or without additional
modules.

Communications
On-board communication interfaces complete the scalable and intelligent control system.
Additional communication modules can be added to the system in accordance with
integration requirements.

Topologies
Modbus RS-485
Master/slave
BACnet MS/TP

Peripheral Bus

System integration

User Interface

Process Bus

via Ethernet Modbus RS-485


Tools, IP integration Master/slave

via USB
Service interface, tools

2
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Design

The Climatix C600 product range consists of three controller types with 21, 27, and 29
physical inputs and outputs.
The design and configuration of the inputs/outputs and interfaces are conceptually equal for
all controller types.
The controllers are available with and without integrated HMI.
The following figures display the three basic types, each with integrated HMI.

POL648 - 21 inputs and outputs

3
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
POL688 - 27 inputs and outputs

POL69x - 29 inputs and outputs

4
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Additional interfaces on the bottom of the devices

Type Stock number Inputs Outputs HMI,


integrated
POL648.10/STD S55396-C481-A100 3 UI, 8 UIO, 4 DI 6 relays
POL648.80/STD S55396-C488-A100 3 UI, 8 UIO, 4 DI 6 relays Yes
POL688.10/STD S55396-C881-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs
POL688.80/STD S55396-C888-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs Yes
POL698.10/STD S55396-C981-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs, 2 stepper motors
POL698.80/STD S55396-C988-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs, 2 stepper motors Yes
POL69U.10/STD S55396-C991-A100 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs, 2 stepper motors (UPS)
POL69U.80/STD S55396-C998-A400 3 UI, 8 UIO, 6 DI 8 relays, 2 triacs, 2 stepper motors (UPS) Yes

5
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Input/output signal types

POL648 - Input/output configuration


X9 X10 X11 X1 X2 X3 X4 X5 X6 X7 X8 D1 D2 DU1 DU2
N N N N N N N N N N N DI DIp DG DG
Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni
Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt
DI DI DI R R R R R R R R
V in V in V in V in V in V in V in V in
mA in mA in mA in mA in mA in mA in mA in mA in
DIx DIx DIx DIx DIx DIx DIx DIx
V out V out V out V out V out V out V out V out
mA out mA out DV DV DV DV
VM VM

DS DS DO DO DO DO
Q1 Q2 Q3 Q4 Q5 Q6

POL688 - Input/output configuration


X9 X10 X11 X1 X2 X3 X4 X5 X6 X7 X8 D1 D2 DU1 DU2
N N N N N N N N N N N DI DIp DG DG
Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni
Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt
DI DI DI R R R R R R R R
V in V in V in V in V in V in V in V in
mA in mA in mA in mA in mA in mA in mA in mA in
DIx DIx DIx DIx DIx DIx DIx DIx
V out V out V out V out V out V out V out V out
mA out mA out DV DV DV DV
VM VM

DS DS DO DO DO DO DO DO DT DT DA DA
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 DO1 DO2 DL1 DL2

6
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
POL69x Input/output configuration
X9 X10 X11 X1 X2 X3 X4 X5 X6 X7 X8 D1 D2 DU1 DU2 M4/3
N N N N N N N N N N N DI DIp DG DG SMv
Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni Ni
Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt Pt
DI DI DI R R R R R R R R
V in V in V in V in V in V in V in V in
mA in mA in mA in mA in mA in mA in mA in mA in
DIx DIx DIx DIx DIx DIx DIx DIx
V out V out V out V out V out V out V out V out
mA out mA out DV DV DV DV
VM VM

DS DS DO DO DO DO DO DO DT DT DA DA SMc
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 DO1 DO2 DL1 DL2 M1/2

Key

Signal type Short name Description


Analog inputs N NTC10…100k
Ni Ni1000
Pt Pt1000
R 0…2.5 k
V in DC 0…10 V
mA in 4…20 mA
Digital inputs DIx Potential-free
DI Potential-free
DIp Potential free, 300 Hz
DG Active, 24 V (AC/DC)
DA Active, AC 230 V
Analog outputs V out DC 0…10 V
mA out 4…20 mA
VM PWM
Digital outputs DV DC 24 V
DS Relay, NO/NC
DO Relay, NO
DT Triac
Stepper motors SMv Voltage controlled, bipolar or unipolar
SMc Current controlled PWM, bipolar

7
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Technical data

Housing and weight

Housing

Color Base plate: Pigeon blue (RAL 5014)


Housing: Light gray (RAL 7035)
Dimensions See "Dimensions [ 30]"

Weight

Type Weight
POL648.10/xxx 453 g
POL648.80/ xxx 492 g
POL688.10/ xxx 468 g
POL688.80/ xxx 506 g
POL698.10/ xxx 552 g
POL698.80/ xxx 593 g
POL69U.10/ xxx 611 g
POL69U.80/ xxx 652 g

Packaging for POL69x 119 g


Packaging POL648 and POL688 95 g

Battery compartment for back-up battery


Permissible battery type: BR2032

Processor and memory

Processor

Main processor Cortex M4 NXP LPC4337JET256 (136 kB RAM, 1 MB Flash)


Subprocessor Cortex M3 NXP LPC1763FBD100 (64 kB RAM, 256 kB Flash)

Storage

SDRAM 64 MB
Flash 64 MB

8
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Power data

Power, T8
Operating voltage
POL648, POL688 AC 24 V -20%...+20%; DC 24 V ±10%
POL698, POL69U AC 24 V -15%...+20%; DC 24 V ±10%
Frequency 45…65 Hz
Protection class III (SELV / PELV)
UL Class 2
External fuse in the supply line max. 4 A non-renewable fuse or circuit breaker, type
B, C or D
Power consumption,
without connected extension modules
POL648, POL688 39 VA / 24 W
POL698, POL69U 60 VA / 43 W
Current consumption AC, without extension modules
POL648, POL688 max. 1.6 A @ AC 24 V
POL698, POL69U max. 2.5 A @ AC 24 V
Current consumption DC, without extension modules
POL648, POL688 max. 1.0 A @ AC 24 V
POL698, POL69U max. 1.8 A @ AC 24 V
Current consumption AC, for extension modules*
POL648, POL688 max. 2.4 A @ AC 24 V
POL698, POL69U max. 1.5 A @ AC 24 V
Current consumption DC, for extension modules*
POL648, POL688 max. 3.0 A @ DC 24 V
POL698, POL69U max. 2.2 A @ DC 24 V

* For calculation, see Q3900

9
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Inputs/outputs

Universal inputs (T1)


Analog inputs X9, X10, X11
Typical sensor Range Resolution Accuracy
NTC10k / NTC100k 500 …670 k < 43 @ 10 k ± 215 @ 10 k
< 856 @ 100 k ± 2996 @ 100 k
Ni1000 / Pt1000 740 …2000 < 560 m @ 1100 ± 2250 m @ 1100

Universal inputs (T1)


Digital inputs X9, X10, X11
0/1 digital signal (binary) For potential-free inputs
Sensing voltage/current Typical DC 18 V / 7 mA
Contact resistance Max. 200 (closed)
Min. 50 k (open)

Universal I/Os (T2, T3)


Analog inputs X1…X8
Type Range Resolution Accuracy
NTC10k (@ 10 k ) 100 …760 k < 43 ± 215
NTC100k (@ 100 k ) 100 …1280 k < 437 ± 2166
Ni1000 (@ 1100 ) 100 …3800 < 396 m ± 1980 m
Pt1000 (@ 1100 ) 100 …3800 < 378 m ± 1890 m
Resistance input 0 …2500 < 1000 m < 4000 m
Input DC 0…5 V, 0…5 V < 1 mV < 25 mV @ 5 V
ratiometric sensor
Input resistance: > 100 k
Input DC 0...10 V 0…10 V < 1 mV < 50 mV @ 10 V
Input resistance: > 100 k
Input 0...20 mA 0…20 mA <1 A < 120 A @ 20 mA
Input resistance: < 500

10
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Universal I/Os (T2, T3)
Digital inputs X1…X8
0/1 digital signal (binary) For potential-free inputs
Sensing voltage/current Typical DC 24 V / 6 mA
Contact resistance Max. 200 (closed)
Min. 50 k (open)

Universal I/Os (T2, T3)


Analog outputs X1…X8
Type Range Resolution Accuracy
Output DC 0…10 V 0…10 V < 11 mV < 124 mV @ 10 V
Output current: Max. 1 mA (short-circuit proof)
Capacitive load: < 200 nF

Universal I/Os (T2, T3)


Analog outputs X1, X2
Type Range Resolution Accuracy
Output 0...20 mA 0…20 mA < 22 A < 243 A @ 20 mA
Input resistance: < 500

Universal I/Os (T2, T3)


DC outputs, e.g. for relay control X5…X8
Switching voltage Typical DC 24 V
Switching current Max. 25 mA

Universal I/Os (T2, T3)


PWM outputs X5, X6
Output voltage (high) DC 8…12 V
Output voltage (log) DC 0…1 V
Output current Max. 10 mA
PWM frequency 0.5…2.5 kHz
NOTICE! Default settings is 500 Hz
Sampling ratio 0…100 %
Resolution 0.5 %

NOTICE

The following applies to all inputs or inputs/outputs (X1…X11):


Can be configured via software
System zero is the reference potential
Maximum contact voltage: DC 24 V
Overvoltage protection: Up to 40 V
Resolution and accuracy are indicated at 25 °C ambient temperature.

11
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Supply power for active /
ratiometric sensors with 5 V, 24 V, 2 x 2 outputs (T2, T3)
Sensor power output for active sensors
Output voltage DC 24 V (-25 %…15 %)
Output current Max. 2 x 40 mA (short-circuit proof)
Reference potential System zero
Reference voltage output for ratiometric measurements
NOTICE! Not designed for sensors with pulse-like energy demand.
Output voltage DC 5 V (±2.5 %)
Output current Max. 2 x 20 mA (short-circuit proof)

Digital inputs (T4)


Digital inputs, potential-free D1, D2
D1 D2
0/1 digital signal (binary) For potential-free contacts For potential-free contacts or pulse
measurements
Configurable with firmware
Sensing voltage/ DC 24 V / 8 mA
current
Contact resistance Max. 200 (closed)
Min. 50 k (open)
Pulse frequency Max. 60 Hz Max. 60 Hz
Pulse measurement Max. 18,000 pulses/min.

Digital inputs (T5)


24 V active digital inputs DU1, DU2
0/1 digital signal (binary) Galvanically separated voltage input
Nominal voltage AC 24 V (-20 %…+20 %)
DC 24 V (±10 %)
Input current 8 mA @ DC 24 V
Pulse frequency Max. 5 Hz

Digital inputs (T13)


115…230 V active digital inputs DL1, DL2
0/1 digital signal (binary) Galvanically separated voltage input
Nominal voltage AC 115 V…230 V (-15 %…+10 %)
Input current < 1 mA @ 230 VAC
Frequency range 45…65 Hz
Pulse frequency Max. 5 Hz
Dielectric strength:
Insulation on low voltage 2900 V

12
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Outputs

Relay outputs T9…T11


Q1, Q2 (T9, T10) and Q3…Q8 (T10, T11)
Relay: Type, contact Q1, Q2, monostable, NO/NC
Q3…Q8, monostable, NO
Switching voltage AC 12 V…250 V (45…65 Hz)
DC 12 V…30 V
Nominal current (resistive) Max. AC 4 A / DC 3 A
Nominal current (inductive) Max. 3 A (cos 0.6)
Maximum switch-on current 10 A (for 1 sec)
Minimum current 10 mA @ AC/DC 12 V
1 mA @ AC 230 V
Contact life Switchings: 100,000 @ 4 A resistive
50,0000 @ 300 mA resistive
100,000 @ 2 A inductive
Dielectric strength:
Insulation on low voltage 2900 V
External fuse supply line max. 6.3 A non-renewable fuse or
circuit breaker, type B, C or D

Triac outputs (T12)


DO1, DO2
Switching voltage AC 19…250 V
Switching current (resistive) Max. 500 mA / Min. 30 mA
Maximum switch-on current 1.5 A (for 1 sec)
Cos Phi 1…0.8
Dielectric strength:
Insulation on low voltage 2900 V
External fuse supply line max. 2.0 A non-renewable fuse or
circuit breaker, type B, C or D

NOTICE

The following applies for relay and triac outputs:


Do not mix SELV / PELV and mains power on the same terminal block.
Use external protection circuits for inductive loads.
The outputs are not fused internally. An external fuse is required.

13
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Stepper motor control
SMc (T16) SMv (T7)
Principle Current controlled PWM Voltage controlled
Uni/bipolar Bipolar Unipolar or bipolar mode can be
configured over software
Modes Half or full step mode can be configured over software
LED displays Two green LEDs indicate movement and
state of the stepper motor control
Switching capacity Max. 7.2 W Max. 9 W
Overall switching power Max. 12 W
Output voltage Max. DC 24 V Max. DC 12 V
Output current Max. 600 mA Max. 375 mA
Peak current Max. 800 mA Max. 550 mA
Overcurrent protection n/A > 0.8…2 A
Speed 0…500 steps/half steps per second
Thermal warning 150 °C…180 °C 120 °C…170 °C
Capacitive load Max. 2 nF
Line length Max. 10 m
Uninterruptible power supply: Energy cells: > 140 Ws
UPS Charge time: < 180 s
(POL69U only)
The EEV failsafe behavior can be set over software
Protection Overcurrent Overcurrent
Overtemperature Overtemperature
Undervoltage Under and overvoltage
Notice The outputs are not protected against incorrect 24 V wiring

14
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Interfaces

The device interfaces are depicted in "Design [ 3]".

Interface Symbol/ Use Technical data


Location
Service/tool T-SV Engineering and commissioning USB 2.0 device
interface SAPRO and SCOPE tool Plug: Type Micro-B
Data rate: 1.5 Mbps and 12 Mbps.
Off-the-shelf USB cable (not included)
NOTICE! No galvanic separation to ground.
USB host T-SP Auxiliary energy via USB Plug: Type A
Supply of USB powered WLAN routers Provides supply current of max. 500 mA
NOTICE! No galvanic separation to ground.
NOTICE! The interface currently does not provide
communications.
SD card left, from Loading and archiving Cards: SD, SDHC
top Load application programs Memory card size: 128 MB up to 32 GB
Download the firmware File system: FAT16, FAT32
See SCOPE online help CAUTION! Switching off the controller during a read/write
action may result in a loss of data.
HMI interface T-HI Commissioning and operation Plug: RJ45, screened
Climatix HMIs Communication: RS485 (Modbus)
Power: 24 V, max. 100 mA
Compatible cables are included with the HMIs
Ethernet T-IP Engineering and commissioning Plug: RJ45, screened
SAPRO and SCOPE tool Interface type: 10Base-T and 100BASE-TX, IEEE
Cloud services 802.3 compatible
Climatix IC integration Bitrates: 10/100 Mbps
Integration Auto sensing
Modbus, BACnet IP or OPC Multiple, simultaneous connections are possible
Touch panels when using a switch

via Modbus IP or IP

Process bus T15 Process bus Type: KNX TP1, galvanic isolation.
Connection of CLIMATIX controllers and Baud rate: 9.6 kbps
room units Bus power: 50 mA
KNX-LTE, PL-Link Bus load: 5mA
Short-circuit proof

15
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Interface Symbol/ Use Technical data
Location
Third-party bus T6, T14 Connect field devices Plug: 3-pin connection for all interfaces
e.g. variable speed drive, fan coil RS-485 (EIA-485) interface
controller Galvanically separated (T6 only)
Touch panels Data rate: max. 9.6…115 kBaud (can be set over
via RS485 software)
Building automation system Maximum connectable devices: Up to 31 devices
Modbus RTU Bus termination (can be set over software):
BACnet MS/TP (T6 only) 120 + 1 nF (T6 only)
Bus polarization (can be set over software):
680 / 680
NOTICE! The baud rate must be adapted to match the
cable length.
Peripheral bus Right side Extension inputs/outputs Plug connection (see "Accessory [ 21]")
Connection of I/O modules Maximum number of I/O modules: 31
Addresses 1…31, 0 not used
Please note "Power data [ 9]".
NOTICE! Not internally fused. Use an external fuse at 4 A
in the power supply line.
Communication Left side Extending communications and integration Plug connection (see "Accessory [ 21]")
interface Connect communication modules Maximum number of communication modules: 2
Voltage / current: DC 5 V / max. 670 mA
Short-circuit proof

Wire lengths

Interface Wire lengths


Ethernet Max. 100 m
Process bus Overall length: Max. 1,000 m
Between 2 nodes: max. 700 m (as per KNX specification)
Peripheral bus Overall length: Max. 30 m
Voltage drop off on 0 V wire: 1.5 V
Third-party bus Overall length: Max. 1,000 m @ 9.6kBaud
Max. 500 m @ 9.6kBaud between 2 nodes
Total 40 m stub lines; 1 stub line max. 20 m
Service interface Max. 3 m
Signal wiring Max. 80 m
NOTICE! Restriction: X9…X11 on NTC10k, NTC100k: max. 30 m

16
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Cable types

Interface Specification
Ethernet Always screened:
100Base-TX, cable category 5
10Base-T, cable category 4
Process bus Shielded, twisted pair: 0.5…1.5 mm2 (as per KNX specification)
Peripheral bus 4-wire (2 wires as twisted pair), shielded, if >3 m
Third-party bus 2 or 3-wire, twisted, shielded, if >3 m
Signal lines Wire: 0.5…2.5 mm2
(Inputs/outputs) Stranded wire (twisted, terminating sleeves required): 0.5…1.5 mm2
Stripping lengths:
– 7 mm for screw terminals (MVSTBW)
– 10 mm for spring cage terminals (FKCT)

NOTICE

Installation of connections as per:


Load
Local regulations
Applicable installation documents

17
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Conformity

Ambient conditions and protection classification


Classification as per EN 60730
Operation of automatic controller Type 1
Degree of pollution 2
Overvoltage category III
Design type Device suited for use with equipment of safety classes I and II
Degree of protection of housing to EN 60529 IP20
Climatic ambient conditions
Transport (in transport packaging) Class 2K3
as per EN 60721-3-2 Temperature -25...70 °C
Air humidity: 5…90 % (non-condensing)
Operation per EN 60721-3-3 Class 3K7
Average ambient temperature: 45 °C
Temperature:
– POL6x8: -40...70 °C
– POL69U: -40°C…60 °C
Air humidity: 5…90 % (non-condensing)
Air pressure: Minimal 700 hPa
(corresponds to a maximum 3000 m above sea level)

Restrictions: Temperature range POL6x8 with 1 communication module: -40 °C…65 °C


POL6x8 with 2 communication modules: -40 °C…60 °C
LCD reliability range: -20 °C…60 °C
Process bus reliability range: -25 °C…70 °C
Mechanical ambient conditions
Transport to EN 60721-3-2 Class 2M2
Operation per EN 60721-3-3 Class 3M2
NOTICE! Screw fix the devices if continuously exposed to resonance frequency.
NOTICE! Comply as well with the Mounting Instructions "A6V10990056".

Standards, directives and approvals


Product standard EN 60730-1
Automatic electronic controls for household and similar use
Electromagnetic compatibility For residential, commercial, and industrial environments
EU conformity (CE)
RCM conformity
UL Approbation UL916, UL873. http://database.ul.com
Federal Communications Commission FCC CFR 47 Part 15 Class B
CSA-Approbation C22.2
EAC
RoHS-China
Environmental compatibility The product environmental declaration () contains data on environmentally
compatible product design and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal).

18
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Functions

LED indicators "BSP" and "BUS"

LED Color Flash response Function


BSP Red/green Changes at 1 Hz Software update mode:
Download application or new firmware
Green Continuous Application loaded and operational
Orange Continuous Application loaded but not operational
Orange Flashing, 50 ms on / 1000 ms off Application not loaded
Red Flashing at 2 Hz Firmware error
Red Continuous Hardware fault
BUS The application sets the response and function. Additional notes are available in the SAPRO online help.

LED indicators (green) "O" and "C" for stepper motor control

LED "O" (open) LED "C" (close) Status


Off Off Valve is not moving
On Off Valve is fully open (if referenced*)
Off On Valve is fully closed (if referenced*)
Off Flashing, 250 ms on / 250 ms off Valve is closing
Flashing, 250 ms on / 250 ms off Off Valve is opening
Off Flashing, 50 ms on / 450 ms off Valve moving to the close-failsafe position
Flashing, 50 ms on / 450 ms off Off Valve moving to the open-failsafe position
Flashing, 250 ms on / 250 ms off Flashing, 250 ms on / 250 ms off Error

* "If referenced" means a reference deployment was made. So that the program knows the position of the valve

19
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Download button
Along with an SD card, the download button provides a simple and fast method for loading
firmware and application files to the controller without additional tools.

Additional information on the download button is available in the SCOPE tool online help.

Integrated HMI (for ".80" controller types)


See "Design [ 3]".
An integrated HMI provides the following operating elements:
Turn/press button
Alarm button
Info button
ESC button
The LCD has blue background lighting.

Real-time clock
Backup without battery: 3 days
Backup with battery: 4 years

The Mounting and installation instructions (A6V10990056) illustrate how to install or replace
the backup batters for the real-time clock.

Data Matrix Code (DMC)


The controller has a Data Matrix Code (DMC).
You can scan the code using a code reader app. The result is a text string that, for example,
can be helpful on service calls. Example:
1PS55396-C488-A100+31PPOL648.80/STD+S160908Z0000000005+23S00-A0-03-EB-01-
04+3C3WSZHI-2J7SM-ETMN7-I3LO4-VDVNX
The text string is subdivided into code letters:
1P: Siemens stock number (SSN); fixed
31P: Siemens device type (ASN); fixed
S: Date (YYMMDD), series, serial number, variable
23S: MAC address (hex); variable
3C: Climatix IC activation code (password); variable

20
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Order data

Climatix controllers

Type Stock number Description


POL648.10/STD S55396-C481-A100 Climatix C600 controller
POL648.80/STD S55396-C488-A100 Climatix C600 controller with HMI
POL688.10/STD S55396-C881-A100 Climatix C600 controller
POL688.80/STD S55396-C888-A100 Climatix C600 controller with HMI
POL698.10/STD S55396-C981-A100 Climatix C600 controller with EEV drivers
POL698.80/STD S55396-C988-A100 Climatix C600 controller with HMI, EEV drivers
POL69U.10/STD S55396-C991-A100 Climatix C600 controller with EEV drivers, UPS (failsafe)
POL69U.80/STD S55396-C998-A400 Climatix C600 controller with HMI, EEV drivers, UPS (failsafe)

Accessory

Siemens accessories

Type Stock number Designation


POL064.85/STD Terminal set POL648, screw connection
POL064.86/STD Terminal set POL648, spring return
POL068.85/STD Terminal set POL688, screw connection
POL068.86/STD Terminal set POL688, spring return
POL069.85/STD Terminal set POL69x, screw connection
POL069.86/STD Terminal set POL69x, spring return

PHOENIX CONTACT accessories, www.phoenixcontact.com

Phoenix cable connector

Phoenix type Description


ZEC 1,0/ 4-LPV-3,5 GY35AUC2CI1 Printed circuit board connector,
Board-to-Board to connect I/O modules
ZEC 1,0/ 4-ST-3,5 GY35AUC1R1,4 Printed circuit board connector,
Board-to-Board to connect I/O modules
ZEC 1,0/10-LPV-3,5 GY35AUC2CI1 Printed circuit board connector,
Board-to-Board for connecting COM modules

21
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Phoenix terminal plug
The following overview of compatible types assist you in selecting and ordering the Phoenix
type:

Controller connectors Compatible Phoenix connector types Color


T1 1 x 5 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray
T2 1 x 8 pos - MVSTBW, FKCVW or FKCT 2,5/8-ST Gray
T3 1 x 8 pos - MVSTBW, FKCVW or FKCT 2,5/8-ST Gray
T4 1 x 3 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray
T5 1 x 3 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray
T6 1 x 3 pos - MCVW 1.5/ 3-ST-3,5 Green
T7 1 x 5 pos - MVSTBW, FKCVW or FKCT 2,5/5-ST Gray
T8 1 x 2 pos - MVSTBW, FKCVW or FKCT 2,5/2-ST Orange
T9 1 x 3 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray
T10 1 x 7 pos - MVSTBW, FKCVW or FKCT 2,5/7-ST Gray
T11 1 x 6 pos - MVSTBW, FKCVW or FKCT 2,5/6-ST Gray
T12 1 x 3 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray
T13 1 x 3 pos - MVSTBW, FKCVW or FKCT 2,5/3-ST Gray
T14 1 x 3 pos - MCVW 1.5/ 3-ST-3,5 Green
T15 1 x 2 pos - MCVW 1.5/ 2-ST-3,5 Green
T16 1 x 5 pos - MVSTBW, FKCVW or FKCT 2,5/5-ST Gray

22
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Product documentation

Document ID Title Description


A6V10990076 Datasheet C600 Climatix Functions, use, technical data, terminal concept, and
controller dimensions for the C600 controller product range
A6V10990056 Installation C600 Climatix Mounting and wiring the Climatix controller
controller
M3910 Climatic mounting Connecting extension modules. Power variants.
instructions
Q3900en Climatix range The section "Connecting the extension modules" is important
with sample calculations for permissible pass-through current
Q3993en EMC design guidelines Notes on EMC, especially for panel design

Notes

Safety: National regulations

CAUTION

National safety regulations


Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.

Engineering: Panel

WARNING

Risk of electric shock caused by unintentional contact with electrical connections


Touching powered connections (over 42 Volt) can result in serious injury.
Install the device in a protective housing (preferably a panel).
A key or tool is required to open the protective housing.
AC 230 V cable must be double insulated versus safety extra-low voltage (SELV)
cables.

Installation

WARNING

No internal line protection for supply lines to external consumers


Risk of fire and injury due to short-circuits!
Adapt the line diameters as per local regulations to the rated value of the installed fuse.

23
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
WARNING

Electric shock on plug-in terminal blocks


The distance to parts potentially under power is very small when using plug-in terminal
blocks.
Ensure the device is not connected to power before using plug-in terminals.

Disposal

The device is considered an electronics device for disposal in terms of


European Directive 2012/19/EU and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Dispose of empty batteries in designated collection points.

24
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Connection terminals

POL648.10, POL648.80

POL648.10

POL648.10

Slot Terminal Description


T1 X9, X10, X11 Universal inputs
M System zero
T2 X1, X2, X3, X4 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T3 X5, X6, X7, X8 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T4 D1, D2 Digital inputs (potential-free)
M System zero
T5 DU1, DU2 24 V active digital input
DG Reference potential 24V active digital input
T6 A2+, B2-, REF2 Third-party bus, RS-485
NOTICE! Galvanically separated
T8 24V Power AC 24V / DC 24V
0V System zero
T9 Q11 NO contact Q1 (normally closed)
Q12 Wiring Q1
Q14 NO contact Q1 (normally open)
T10 Q21 NO contact Q2 (normally closed)
Q22 Wiring Q2
Q24 NO contact Q2 (normally open)

25
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Slot Terminal Description
Q33 Wiring for Q3
Q34 NO contact Q3 (normally open)
Q43 Wiring Q4
Q44 NO contact Q4 (normally open)
T11 Q53 Common wiring for Q5 and Q6
Q54, Q64 NO contacts for Q5 and Q6 (normally open)
T14 A1+, B1-, REF1 Third-party bus, RS-485
NOTICE! Not galvanically separated
T15 CE-, CE+ Process bus (based on KNX TP1)

26
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
POL688.10, POL688.80

POL688.10

POL688.10

Slot Terminal Description


T1 X9, X10, X11 Universal inputs
M System zero
T2 X1, X2, X3, X4 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T3 X5, X6, X7, X8 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T4 D1, D2 Digital inputs (potential-free)
M System zero
T5 DU1, DU2 24 V active digital input
DG Reference potential 24V active digital input
T6 A2+, B2-, REF2 Third-party bus, RS-485
NOTICE! Galvanically separated
T8 24V Power AC 24V / DC 24V
0V System zero
T9 Q11 NO contact Q1 (normally closed)
Q12 Wiring Q1
Q14 NO contact Q1 (normally open)
T10 Q21 NO contact Q2 (normally closed)
Q22 Wiring Q2
Q24 NO contact Q2 (normally open)
Q33 Wiring for Q3
Q34 NO contact Q3 (normally open)

27
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Slot Terminal Description
Q43 Wiring Q4
Q44 NO contact Q4 (normally open)
T11 Q53 Common wiring for Q5 and Q6
Q54, Q64 NO contacts for Q5 and Q6 (normally open)
T12 C Actuator voltage AC 24..230V
DO1, DO2 Switching output 0.5A, triac
T13 DL1, DL2 115...230V active digital input
DN Reference potential 115...230V active digital input
T14 A1+, B1-, REF1 Third-party bus, RS-485
NOTICE! Not galvanically separated
T15 CE-, CE+ Process bus (based on KNX TP1)

28
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
POL698.10, POL69U.10, POL698.80, POL69U.80

POL698.10

POL698.10 or POL69U.10

Slot Terminal Description


T1 X9, X10, X11 Universal inputs
M System zero
T2 X1, X2, X3, X4 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T3 X5, X6, X7, X8 Universal inputs/outputs
M System zero
+5V 5V reference power
+24V 24V sensor power
T4 D1, D2 Digital inputs (potential-free)
M System zero
T5 DU1, DU2 24 V active digital input
DG Reference potential 24V active digital input
T6 A2+, B2-, REF2 Third-party bus (RS-485)
NOTICE! Galvanically separated
T7 +12V Stepper motor control, M4/3
M4-, M4+, M3-, M3+ Voltage controlled
unipolar / bipolar
Unipolar Control of motor windings
0V
Bipolar Control of motor winding
0V/12V
T8 24V Power AC 24V / DC 24V
0V System zero
T9 Q11 NO contact Q1 (normally closed)
Q12 Wiring Q1
Q14 NO contact Q1 (normally open)
T10 Q21 NO contact Q2 (normally closed)
Q22 Wiring Q2
Q24 NO contact Q2 (normally open)
Q33 Wiring for Q3
Q34 NO contact Q3 (normally open)

29
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Slot Terminal Description
Q43 Wiring Q4
Q44 NO contact Q4 (normally open)
T11 Q53 Common wiring for Q5 and Q6
Q54, Q64 NO contacts for Q5 and Q6 (normally open)
Q73 Common wiring for Q7 and Q8
Q74, Q84 NO contacts for Q7 and Q8 (normally open)
T12 C Actuator voltage AC 24..230V
DO1, DO2 Switching output 0.5A, triac
T13 DL1, DL2 115...230V active digital input
DN Reference potential 115...230V active digital input
T14 A1+, B1-, REF1 Third-party bus, RS-485
NOTICE! Not galvanically separated
T15 CE-, CE+ Process bus (based on KNX TP1)
T16 COM Not connected internally Stepper motor control, M1/2
M1-, M1+, M2-, M2+ Control of motor winding Current controlled
0V/24V bipolar

Dimensions

POL648 and POL688 (all dimensions in mm)


180.0

4.5 171.0

Bottom view POL648 and POL688 (POL688 depicted here)

30
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
168.5

124.2
74.0
4.5

Front view POL648 and POL688 (POL688 depicted here)

31
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
7.5

4.5

( 3.0 )

110.0

134.9
45.0
35.3

5.5

43.0

72.0

83.5

86.5

Side view POL648 and POL688

32
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
113.0

56.5
125.7 4.9 4.9

114.4

4.9 4.9

42.5

93.5

Rear view POL648 and POL688

POL698 and POL69U (all dimensions in mm)

243.0

4.5 234.0

Bottom view POL698 and POL69U

33
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
231.5

124.2
74.0
4.5

Front view POL698 and POL69U

34
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
7.5

4.5

( 3.0 )

134.9
110.0
35.3

45.0

5.5

43.0

72.0

83.5

86.5

Side view POL698 and POL69U

35
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
170.5

4.9 4.9

125.7
114.5

4.9 4.9
88.0
( 5.5 )
176.0

Rear view POL698 and POL69U

Issued by © Siemens Switzerland Ltd, 2016


Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies
36
Siemens A6V10990076_en_a
Building Technologies 2016-10-17
Document ID A6V10990076_en_a
Edition 2016-10-17