Transformer Details

Project Reference: Hamad Women's Hospital Job Number: ELEC-0001

Document No: Created On: 11/26/2018 Rev Date: 4/9/2020

Created By: SWAMINATHAN GNANESWARAN Revised By: VAIBHAV KANTHE Revision: REV-A

Transformer Id No: TX-F (EXISTING)

Transformer Name:

Transformer Details: Active: Yes

Transformer Rating Transformer (A) Primary Secondary

Rating (kVA): 1000 Rating (A) 52.5 1333.4

Impedance (%) 6.39 Load (A) 24.5 621.6

Supply Voltage:

Supply Voltage (V) Primary Secondary

Three Phase 11000 433 Supply frequency: 50 Hz


Single Phase 6350 250

Voltage Drop Settings:

Load Type Lighting Other Limits set to: User Defined

Voltage Drop 5.0 % 5.0 %


Limit
3 Phase 21.65 V 21.65 V

1 Phase 12.5 V 12.5 V

Fault Level Data:

Short-circuit (Pscc) Earth Fault (Ief)


Transformer Fault Data
kA PF kA PF Impedance (Ze)

Transformer Fault Contribution (A) 20.24 0.20 20.24 0.20 0.0124

Fault Through Main Cable (B) 20.24 0.20 20.24 0.20 0.0124

Fault at Board (C) 18.33 -- 16.15 -- --

Protection: Manufacturer: Terasaki Type: AR216S


Family: ACB standard Device Rating (A): 1600

RCD: 1,600,000.00
mA RCD Adjustment: N/A

Network Load Data:

Diversified Load L1 L2 L3

Current: Each Transformer / Total (A) 621.57 / 621.57 621.57 / 621.57 621.57 / 621.57

Power Factor 0.8 0.8 0.8

Connected Load L1 L2 L3

Current: Each Transformer / Total (A) 621.57 / 621.57 621.57 / 621.57 621.57 / 621.57

Power Factor 0.80 0.8 0.8

Absorbed Power kW kVAr kVA

Connected Load: : Each Transformer / Total 373.2 / 373.2 279.4 / 279.4 466.2 / 466.2

Network Conductor Energy Loss (W): At Design Current = 3874 Fully Loaded = 4398.1

Project: Hamad Building Construction - LVP-03 (1) - Copy.p18x Page 1 of 1 Printed on: 4/10/2020
Created using: v2018.0.0.661 BS 7671:2018 - Al Bidda Switchgear © 1996-2018 Trimble Inc.