Factorytalk Linx Getting Results Guide
Factorytalk Linx Getting Results Guide
Factorytalk Linx Getting Results Guide
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by
suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer,
the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated
with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this
manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to
personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Important: Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be
present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous
temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc
Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work
practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of contents
Chapter 1
Chapter 2
Chapter 3
Start FactoryTalk Linx and Start FactoryTalk Administration Console .................................................................. 25
FactoryTalk Administration Console user interface components........................... 25
explore the user interface
Add FactoryTalk Linx to the FactoryTalk application .............................................. 26
Explore the FactoryTalk Linx Communication Setup editor................................... 27
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Chapter 8
Use FactoryTalk Linx with For Windows Server 2008 and Windows 7 operating systems................................. 53
Dual-channel 1784-PKTX(D) driver .................................................................... 53
RSLinx Classic
For all the supported operating systems......................................................................... 54
1784-PKTX driver ..................................................................................................... 54
Serial-DF1 driver (RS232 DF1 devices) ................................................................ 54
1784-PCIC(S) driver................................................................................................. 54
Chapter 9
Use FactoryTalk Linx with Select RSLinx Edition in Studio 5000 Logix Designer............................................... 55
Select an RSLinx edition in ControlFLASH ............................................................... 55
Studio 5000 Logix Designer
The Network Browser....................................................................................................... 56
and ControlFLASH Configuring drivers in the Network Browser............................................................... 56
Search criteria for a device ........................................................................................ 57
Perform a search.................................................................................................. 57
Search filters ........................................................................................................ 58
Operators ............................................................................................................. 59
Upload and register an EDS file .............................................................................. 59
Upload and register an EDS file in the Network Browser ......................... 59
Register EDS files using the EDS Hardware Installation Tool ................. 61
Considerations when uploading and registering EDS files ........................ 62
What is EDS Hardware Installation Tool .................................................... 63
Bridge across networks .............................................................................................. 63
Add a bridge......................................................................................................... 63
Edit a bridge ......................................................................................................... 64
Delete a bridge..................................................................................................... 64
Copy and paste items to a list in a bridge configuration ............................. 65
Delete an item in a list in a bridge configuration ......................................... 65
Add New dialog box .......................................................................................... 66
Add New dialog box settings ............................................................................ 66
Chapter 10
Install FactoryTalk Linx with Comparing different installation methods ................................................................... 73
Use unattended installation ............................................................................................. 74
command line syntax
Perform unattended installation ............................................................................. 74
Parameters.................................................................................................................... 74
Examples....................................................................................................................... 76
Use silent installation for FactoryTalk Linx .msi file .................................................. 76
Before you begin ......................................................................................................... 76
Rockwell Automation x64 driver package ............................................................ 77
Install certificates ........................................................................................................ 78
Perform silent installation ........................................................................................ 79
Uninstall FactoryTalk Linx.............................................................................................. 80
Glossary
Index
About this publication The Getting Results Guide provides you with information on installing,
navigating, and using FactoryTalk Linx.
Important: The Getting Results Guide is included as a PDF (portable document format) file on your
FactoryTalk Services installation DVD. This file must be viewed using the Adobe Acrobat
Reader software.
Intended audience
Find additional information
Legal notices
Find additional information For additional information about FactoryTalk Linx, consult the following
resources:
Help The Help includes overview, procedural, screen, and reference information for the
product. The Help contains these basic components:
Overview topics
Quick-start topics
Step-by-step procedures
Dialog box descriptions
From the Start menu, select Programs > Rockwell Software >
FactoryTalk Tools > FactoryTalk Help > FactoryTalk Linx Help.
Release Notes The electronic Release Notes provide a list of the hardware and software that is
necessary to use FactoryTalk Linx effectively and a list of known anomalies,
anomalies fixed, and new features that are available in the current release.
The Release Notes are available from the FactoryTalk Services installation DVD.
The Release Notes for all FactoryTalk components, including FactoryTalk Linx,
are available from the FactoryTalk Help. FactoryTalk Help can be launched from
FactoryTalk Administration Console or from the Windows Start menu as
described in the previous section.
Knowledgebases The Rockwell Automation Customer Support Center offers an extensive online
database that includes frequently asked questions and the latest patches. The
Knowledgebase web page leads to a comprehensive, searchable database of support
information for all Rockwell Automation products.
Technical support Questions concerning installation and use of FactoryTalk Linx software are
handled by the Rockwell Automation Customer Support Center. The center is
staffed Monday through Friday, except on U.S. holidays, from 8 a.m. to 5 p.m.
Eastern time zone for calls originating within the U.S. and Canada.
To reach the Customer Support Center, call 440-646-3434 and follow the
prompts. For calls originating outside the U.S. or Canada, locate the number in
your country by visiting http://support.rockwellautomation.com/contact
information.
When you call, you should be at your computer and be prepared to provide the
following information:
Training programs Rockwell Automation offers a wide range of training programs, from regularly
scheduled classes to custom-tailored classes conducted at your site.
If you would like more information about these training programs, visit the
Rockwell Automation site on the Web or contact the Rockwell Automation
Training Coordinator. The Web address and telephone numbers appear on the
back cover of this document.
Consulting services Rockwell Automation provides expert consulting and turnkey implementations
for making optimal use of Rockwell Software products. Please contact your local
representative for more information.
You can view the Rockwell Automation End-User License Agreement ("EULA")
by opening the License.rtf file located in your product's install folder on your hard
drive.
Trademark Notices
Other Trademarks
Microsoft, SQL Server, Windows, and Windows Server are registered trademarks
of Microsoft Corporation in the United States and other countries.
Intel and Intel Core are registered trademarks of the Intel Corporation in United
States and other countries.
All other trademarks are the property of their respective holders and are hereby
acknowledged.
Warranty
This product is warranted in accordance with the product license. The product’s
performance may be affected by system configuration, the application being
performed, operator control, maintenance, and other related factors. Rockwell
Automation is not responsible for these intervening factors. The instructions in
this document do not cover all the details or variations in the equipment,
procedure, or process described, nor do they provide directions for meeting every
possible contingency during installation, operation, or maintenance. This
product’s implementation may vary among users.
This document is current as of the time of release of the product; however, the
accompanying software may have changed since the release. Rockwell Automation,
Inc. reserves the right to change any information contained in this document or
the software at any time without prior notice. It is your responsibility to obtain the
most current information available from Rockwell when installing or using this
product.
Environmental compliance
What is FactoryTalk Linx? FactoryTalk® Linx™ is a FactoryTalk® Live Data server and communications service
designed to deliver control system information from Allen-Bradley® control
products to the Rockwell Automation FactoryTalk® software portfolio and
Studio5000® design software. While FactoryTalk Linx can communicate with
most Allen-Bradley Programmable Logic Controllers (PLC®) and many other
control products, it is specifically optimized to work with Logix 5000™
Programmable Automation Controllers (PAC) using EtherNet/IP. This gives the
fastest data rates and capacity possible, while minimizing the impact on
automation networks and control system operation. FactoryTalk Linx provides a
scalable solution that can support small applications running on a single computer
with a single controller, to large distributed and even redundant data server
configurations communicating with many controllers.
Shortcuts. A shortcut is a name that stands for the device you want to
connect to, and the data that device contains. The communication path
associated with the shortcut tells the application where to find that data.
Starting with version 5.90.00, reads Logix 5000 tag extended properties (e.g.
@Min, @Max, @Description).
Starting with version 5.90.00, removes Logix 5000 tag requests when their
external access is switched to no access in Logix Designer, and the tags can be
removed from the controller while it is operating.
Starting with version 5.90.00, permits communications to specific Logix
5000 shortcuts to be inhibited to reduce the impact of Logix 5000
controllers that are disabled or off-line
Starting with version 6.00.00, provides access to Logix 5000 tag based alarm
attributes (e.g. @Alarm…)
Offers a variety of communication drivers and routing options.
Supports Local applications (also called stand-alone applications) for
smaller systems, and Network applications (also called distributed
applications) for larger systems.
Starting with version 6.00.00, enables the configuration of two redundant
shourtcut paths to a single Logix 5000 controller to support high availability
systems that desire to retain communications when a path through a
network becomes disabled.
Starting with version 6.00.00, permits configuration of two shourtcut paths
to the primary and secondary Logix 5000 controllers in a redundant
ControlLogix revision 31.5x system to retain communications when a
redundancy switchover occurs.
Supports FactoryTalk Security to provide a means for system administrators
to control access to resources (such as applications or areas) or the ability to
perform tasks, such as read and write, in the automation system using
FactoryTalk Security.
In conjunction with FactoryTalk Linx Gateway, provides standard OPC
connectivity into the FactoryTalk system for third-party products. For more
information about FactoryTalk Linx Gateway, refer to the FactoryTalk
Linx Gateway Help.
Overview of basic concepts It is important to understand some basic concepts about FactoryTalk and
FactoryTalk Linx before you begin working with FactoryTalk Linx within the
FactoryTalk Administration Console. For more detailed information about
FactoryTalk, refer to the FactoryTalk Help.
FactoryTalk Services Platform 0Formerly known as FactoryTalk Automation Platform, the FactoryTalk Services
Platform is an underlying architecture and set of services that Rockwell
Automation software products build upon.
FactoryTalk Directory
FactoryTalk Live Data
FactoryTalk Diagnostics
FactoryTalk Administration Console
FactoryTalk Directory FactoryTalk Directory allows products to share a common address book, which
finds and provides access to plant-floor resources, such as data tags and graphic
displays.
FactoryTalk Live Data FactoryTalk Live Data manages connections between FactoryTalk products and
data servers. It reads values from, and writes values to, OPC-DA servers (Open
Platform Communications - Data Access) and Live Data servers on behalf of
client software products, such as FactoryTalk View and FactoryTalk Transaction
Manager.
FactoryTalk Diagnostics FactoryTalk Diagnostics collects and provides access to activity, status, warning,
and error messages generated throughout a FactoryTalk system.
FactoryTalk Administration Console FactoryTalk Administration Console is a standalone tool that enables you to
configure and manage FactoryTalk-enabled applications and FactoryTalk Linx
configurations. A communications tab in the FactoryTalk Administration
Console also permits configuring network drivers, browsing, and viewing the
available devices that are discovered on the configured networks.
FactoryTalk Security
FactoryTalk Security offers centralized security services that provide the ability to
control access to your automation system. For more information on configuring
FactoryTalk Security, refer to the topic titled About FactoryTalk Security in the
FactoryTalk Linx Help.
Local applications versus An application organizes project information, including elements such as data
servers, HMI servers, and alarm and event servers. The application makes project
Network applications
information available to all FactoryTalk-enabled products participating in a
FactoryTalk system.
Design-time versus runtime FactoryTalk Linx is comprised of design-time and runtime components. The
design-time components provide the user interface that enables you to set up
devices, drivers, and shortcuts that are ultimately used by the runtime
components. Based on this configuration data, the runtime components execute
read or write requests received during runtime operation.
Installation and Use the following checklist to guide you through the installation and
configuration process.
configuration checklist
3. Verify your personal computer meets the minimum "Minimum system requirements" on
hardware and software requirements. page 19
4. Install FactoryTalk Services Platform and "Install FactoryTalk Linx" on page 21
FactoryTalk Linx.
5. Configure FactoryTalk Security. "Secure a FactoryTalk system" in the
FactoryTalk Services Platform Help.
6. Configure a FactoryTalk Administration Console application "Manage applications" in FactoryTalk
Services Platform Help.
7. Add a FactoryTalk Linx server. "Add FactoryTalk Linx to the FactoryTalk
application" on page 26
10. Optionally, set up options for device-based alarms. "Set up FactoryTalk Linx to support
FactoryTalk Alarms and Events
(optional)" on page 33
11. Add drivers and devices. "Add a driver" on page 35
12. Create shortcuts that point to your target devices. "Create shortcuts" on page 37
13. Test the system using FactoryTalk Live Data Test Client "Test FactoryTalk communications" in
FactoryTalk Services Platform Help.
The automated installation with command line syntax reduces user interaction
and provides command line parameters to install FactoryTalk Linx. See Install
FactoryTalk Linx with command line syntax on page 73.
System requirements To use FactoryTalk Linx, your personal computer must meet the following
minimum hardware and software requirements:
Software requirements FactoryTalk Linx runs on either the 32-bit or 64-bit versions of the following
Windows operating systems:
Windows 8 Enterprise
Windows 8 Professional
Windows 8.1
Windows 8.1 Enterprise
Windows 8.1 Professional
Windows 10 Enterprise*
Windows 10 Professional*
Windows 10 IoT Enterprise 2016 Long Term Servicing Branch (LTSB)
Embedded**
Windows Server 2008 R2 Enterprise Edition with Service Pack 1
Windows Server 2008 R2 Standard Edition with Service Pack 1
Windows Server 2012 Standard
Windows Server 2012 Datacenter
Windows Server 2012 R2 Standard
Windows Server 2012 R2 Datacenter
Windows Server 2016 Standard
Windows Server 2016 Datacenter
Software compatibility FactoryTalk Linx version 6.00.00 has been tested with, and is compatible with, the
following Rockwell Automation products:
Rockwell Software
Prerequisite Software
Install FactoryTalk Linx You can install one or more Rockwell Software products to a single personal
computer.
Important: The user installing or configuring FactoryTalk Linx must have administrative rights in Windows on the
computers where the software is being installed or configured. The Windows domain Administrator
account has these rights, for example.
Click Start, and then click Run. The Run dialog box appears.
In the Open control, type x:\setup, where x is the letter of the drive
containing the FactoryTalk Services DVD-ROM, and then click OK.
Click Install Now to start the software installation with the default
settings.
Click Customize to select the products which you want to install, or
specify a different drive where you want to install the software, and
then click Install.
(optional) If you are running out of storage, clear the Register EDS
Files check box. However, clearing this check box turns off the EDS
Parameter shortcut function.
7. On the That's it! dialog box, click Close to exit the installation. Meanwhile,
you can also:
Update an existing RSLinx Enterprise re-brands to FactoryTalk Linx version 6.00.00 in this release.
Note the following before upgrading FactoryTalk Linx:
installation
You must have administrative rights in Windows on the computers where
FactoryTalk Linx is being installed. For example, the Windows domain
Administrator account has these rights.
Be sure that you install FactoryTalk Linx with the compatible Rockwell
Automation products.
Perform the following steps to upgrade from a previous version of the software:
2. Insert the FactoryTalk Services product DVD into the DVD-ROM drive.
Perform the installation steps in the order presented on the screen. You can
refer to Install FactoryTalk Linx on page 21 for the installation steps.
Important: The old version of RSLinx Enterprise that exists on your computer is automatically
uninstalled when you install a newer version of FactoryTalk Linx 6.00.00 or later.
Important: You must restart your computer after installing Rockwell Automation products. If you are
installing multiple products, you must restart your computer after all of the products are
installed.
Update a system that already If you are installing FactoryTalk Linx on a Windows platform, on which other
FactoryTalk-enabled products are currently installed, you must first verify that all
has a FactoryTalk-enabled
products are of the same CPR number. You can do this from Start > Control
product installed Panel > Programs and Features (view by small icons).
The CPR number is shown with the product. If any products are of a previous
release, you must uninstall the products (following the sequence: uninstall
FactoryTalk Activation Manager > uninstall FactoryTalk Services Platform >
uninstall FactoryTalk Diagnostics last), restart your computer, and then use the
installation DVD to install the correct release version.
1. Select Start > Control Panel > Programs and Features (view by small
icons).
Start FactoryTalk FactoryTalk Linx is launched from within FactoryTalk Administration Console.
Administration Console To start FactoryTalk Administration Console, use the following procedure:
1. From the Start menu, select Programs > Rockwell Software >
FactoryTalk Administration Console.
Important: Depending on the security settings, you may be required to enter a User name and Password
to open an application. Refer to the FactoryTalk Help for more information.
FactoryTalk Administration FactoryTalk Administration Console is made up of the following basic user
interface components:
Console user interface
components
Item Description
1 The Explorer pane contains the Application tab and the Communications tab.
2 The Application tab shows your applications in tree format as you create them. With the Application tab,
you can view and manage your applications. You use FactoryTalk Administration Console to add references
to data servers, such as FactoryTalk Linx, within FactoryTalk applications.
For more information about creating applications in the FactoryTalk Administration Console, refer to the
FactoryTalk Administration Console Help.
3 The Communications tab provides a view from the computer you are currently using. With the
Communications tab, you can browse for devices your computer can access on the network (similar to
RSWho in RSLinx Classic) and shows them in tree format. The tree is composed of networks, chassis, devices,
and services. The status bar on this tab indicates whether the computer is online or offline, and whether it is
browsing or not browsing.
4 The workspace is an empty pane when you start FactoryTalk Administration Console. When you launch
FactoryTalk Linx from the Explorer pane, the Communication Setup editor opens in the workspace.
Add FactoryTalk Linx to the To begin using FactoryTalk Linx after you install it, you must first add it to a
FactoryTalk Linx application, which is created in the FactoryTalk Directory.
FactoryTalk application Use the following procedure to add FactoryTalk Linx to an application.
2. Right-click the area or application, select Add New Server > Rockwell
Automation Device Server (FactoryTalk Linx).
3. In the FactoryTalk Linx Server Properties tabs, set the server properties.
These tabs are described in Define FactoryTalk Linx server properties on
page 31.
Explore the FactoryTalk Use the Communication Setup editor to add drivers, add devices, set up driver
and device properties, and set up device shortcuts in your FactoryTalk Linx
Linx Communication Setup configurations.
editor
To open the Communication Setup editor, perform the following steps:
Important: Modifying this data at run time could cause unexpected results. See "Making run-time changes in
FactoryTalk applications" in the FactoryTalk Linx Help.
Item Description
1 In the Device Shortcuts area, you can add, remove, and modify shortcuts and apply the shortcut
properties to the selected shortcut name. A shortcut is a name that stands for the device you want to
connect to, and the data that device contains. The shortcut is associated with a communication path to
tell the application where to find that data.
2 Tab(s) contain a communication tree control, representing the communication topology. Depending on
your product, you will see the following tabs:
FactoryTalk View SE (Site Edition) Local: Primary tab
FactoryTalk View SE Network: Primary tab and, if server redundancy is selected, Secondary tab.
Use the tabs to add, remove, and modify devices and drivers.
Menu options are shown by right-clicking the various nodes within the communication tree.
7 Status shows messages that assist you as you configure your shortcuts.
OK Saves any changes and closes the Communication Setup editor.
Cancel Closes the Communication Setup editor without saving the current changes.
Verify Shows a summary of the shortcuts you created, and their associated status messages.
Help Opens Help.
Start browsing the network. Left-click a network on the communication tree. The Browse
status (4) will indicate Browsing.
or
Right-click a network. Select Start Browsing from the
context menu.
Stop browsing the network. Right-click a network. Select Stop Browsing from the
context menu.
View or edit a property screen. Right-click the device or network. Select Properties from
the context menu.
View a context menu. Right-click.
Important: To open the property screen for a device, do not left-click the device to select it before
right-clicking to open the property screen. The left-click action selects a shortcut target, which
may or may not be the intended target for the highlighted shortcut.
appears next to the component where the edit can be made. Hovering the mouse
cursor over the icon shows the following message:
"Modifying this data at run time could cause unexpected results. See Making
run-time changes in FactoryTalk applications in the Help."
If the edit is made through a menu item, the message opens when you click the
menu item.
Define General server Both Local and Network applications require you to specify server properties on
the General tab of the FactoryTalk Linx Server Properties dialog box.
properties
The server name is FactoryTalk Linx and cannot be changed after the server
has been created.
Use the Description area to describe a component’s location, to identify a
contact person or number in the event of failure, or to keep track of changes
or version information.
For Local applications, the computer hosting the FactoryTalk Linx server
defaults to localhost and cannot be changed. For Network applications,
identify the computer where the FactoryTalk Linx server resides by either
clicking Browse or typing the computer name.
If you are going to set up a redundant server, click the Redundancy tab.
Otherwise, click Apply to save the server information, and then click OK to close
the dialog box.
On the Redundancy tab of the FactoryTalk Linx Server Properties dialog box,
you can set up a secondary (redundant) server that will take over in the event that
there is service loss of the primary FactoryTalk Linx server.
The secondary server cannot be hosted on the same computer as the primary
server. You can set up a redundant data server for a network (distributed)
application only. Refer to the FactoryTalk Linx Help for more information about
redundant servers.
2. Type the name of the computer that the secondary server will run on,
or click Browse to locate and select a computer.
If you are going to set up FactoryTalk Alarms and Events support, click the
Alarms and Events tab. Otherwise, click Apply to save the server information,
and then click OK to close the dialog box.
Setup FactoryTalk Linx to On the Alarms and Events tab of the FactoryTalk Linx Server Properties dialog
box, you can configure the selected server for FactoryTalk Alarms and Events
support FactoryTalk Alarms device-based alarm monitoring. Refer to the FactoryTalk Linx Help, or click Help
and Events (optional) on the property page before attempting to set up FactoryTalk Alarms and Events
support.
Create a configuration
Add a driver
Add a device
Create shortcuts
To begin working with FactoryTalk Linx, you must add a FactoryTalk Linx data
server to the FactoryTalk Directory. Once you have added FactoryTalk Linx and
configured its properties, use the Communication Setup editor to add drivers, set
up driver and device properties, and set up device shortcuts.
Add a driver A driver is software that interacts with a network interface (such as the interface
that connects your computer to the Ethernet network) and manages the exchange
of communication packets over the network, to which the interface is attached.
Refer to the FactoryTalk Linx Help for information about the drivers that are
supported.
If you are running on an If you are running on an Ethernet network, right-click the network shown (for
example, Ethernet), and select Start Browsing to populate the driver with devices
Ethernet network
to add a driver.
Important: Some Ethernet devices may not support the browse protocol used by FactoryTalk Linx on
Ethernet. If the devices you expect to appear during the browse do not appear, manually add
the devices to the workstation's Ethernet network by right-clicking on the network and
selecting Add Device.
If you are running on any If you are running on any network other than Ethernet, right-click the device
shown at this workstation, and select Add Driver to add a driver.
network other than Ethernet
Add a device You can add devices by browsing the network, or you can manually add devices.
Automatically add a device by The list of potential device targets for FactoryTalk Linx can be gathered during
online browsing. During a browse cycle, FactoryTalk Linx scans the network
browsing
addresses, determines the present devices, and shows them in tree format. The
display shows the set of devices discovered during the most recent browse cycle.
If a device is not found during a browse, it does not appear on the display,
regardless of whether or not that device was previously discovered.
If you are running on an Ethernet network, right-click the network shown (for
example, Ethernet) to start browsing. The network is automatically populated
with devices.
Browse the virtual backplane When you select the virtual backplane on the user interface, FactoryTalk Linx
may not automatically discover devices that reside in it. If you have added the
device with a separate software package, such as the SoftLogix Chassis Monitor or
RSLinx Classic, this is most likely to happen.
If you think you have devices resident in your virtual backplane that are not
showing up on the FactoryTalk Linx user interface, you can right-click the virtual
backplane and select Start Browsing, or Show All Devices to see those devices. If
the devices do not appear, saved configuration data is not lost.
Manually add a device You can manually add the devices to the workstation's network using the
following procedure:
A list of Available Devices that applies only to the network you selected
opens.
2. Select the device you wish to add, and click OK. The device is added below
the driver or network on the communication tree. Unless your application
requires a specific device version, you should select the most recent revision
of that device.
For information on device revisions in the device list, see the drivers, device, and
shortcuts section of "Frequently asked question" in the FactoryTalk Linx Help.
The Help also provides information about how to add and configure drives and
devices.
Create shortcuts Your application uses a configuration file to communicate with devices on the
network. This file contains at least one shortcut, which is a name that stands for
the device you want to connect to and the data that device contains. The
communication path associated with the shortcut tells the application where to
find that data.
A shortcut needs to be configured for each device that the application needs
to access. The connected device must be capable of providing data to the
application.
Shortcuts are stored on a per-FactoryTalk application basis instead of being
associated with the FactoryTalk Linx server itself.
Shortcuts are added, deleted, or modified using the Shortcut Editor in the
Device Shortcuts area of the Communication Setup editor.
2. If you wish to change the name of the shortcut, you can enter the new name
at this point.
Use the name of the controller, in which the data (tags) resides.
Ensure that the name is unique within this FactoryTalk View
application.
Do not use any of the following characters: . (period), ], [, %, or /.
Keep shortcut names as short as possible. The name must be less than
255 characters.
Do not give the same name to FactoryTalk Linx shortcuts and RSLinx
Classic topics. If a shortcut has the same name as a topic, tags will not
be shown for one of them during a tag browse.
3. Select the device on the communication tree by clicking the device that
contains the data you want to access for this shortcut, and click Apply. A
dialog box opens to confirm your changes.
4. (Optional) You may also choose to use an Offline Tag File by entering the
path and name of the file in the Properties Table or by clicking Browse...
and browsing for the file. Click Apply in the Device Shortcuts area. An
offline tag file is a ControlLogix project file (.acd) that contains tag data.
You can use this file to browse for tags when designing your application
when the controller is not online.
Important: The ControlLogix program file (.acd) must be located on the local computer, instead of on
a networked location. The offline file must be located in the specified directory on all
FactoryTalk Linx server machines associated with the shortcut.
5. (Optional) Enable Alarms and Events support for this shortcut by selecting
Yes from the menu in the Shortcut Properties Table. Refer to the
FactoryTalk Linx Help before enabling Alarms and Events support for a
shortcut.
6. In Shortcut Type, select a shortcut option to define a shortcut type for the
selected shortcut. By default, Processor is selected.
7. To see the status messages associated with each shortcut you have
configured, click Verify on the Communication Setup editor.
When you have finished adding shortcuts, click OK to close the Communication
Setup editor. The shortcuts are not saved until you click OK to close this dialog
box. A dialog box opens to confirm your changes.
Shortcut types A shortcut is a name that stands for the device you want to connect to, and the
data that device contains. The communication path associated with the shortcut
tells the application where to find that data. Shortcuts are added, deleted, or
modified using the Shortcut Properties table in the Device Shortcuts area of the
Communication Setup editor.
The following table shows the available shortcut types. Select one shortcut type for
each shortcut.
Symbolic Used for devices that have tags or symbols defined, such as 1426
PowerMonitor™ 5000, Micro800 series (Micro820, Micro830, and
Micro850) controllers, and 193 E1 Plus Solid-State Overload Relays.
Redundant Controller Path Redundant Controller Path is a shortcut type for a single Logix 5000 controller
with redundant paths. Use redundant controller path to connect the data server
to one device with different communication paths. FactoryTalk Linx can switch
the connection from the active path to the redundant path when a
communication failure occurs.
The following example graphic shows one topology for Redundant Controller
Paths.
Note: Interruption of the redundant path has no impact on the active path.
The following table defines the item names for the graphic above.
Item Description
1 FactoryTalk Linx Data Server
2 Path1 to the ControlLogix controller
3 Path2 to the ControlLogix controller
4 ControlLogix controller
5 ControlLogix EtherNet/IP module for Path1
Item Description
6 ControlLogix EtherNet/IP module for Path2
Redundant ControlLogix Controller Redundant ControlLogix Controller is a shortcut type for two redundant
ControlLogix controllers. Use redundancy modules to synchronize the
communication for a pair ControlLogix controllers in a ControlLogix redundancy
configuration. FactoryTalk Linx can detect the switchover initiated by
redundancy modules and shift the data transfer to the new active ControlLogix
controller.
Note: The Logix 5000 controllers must be at revision 31.50 or above to support redundant
controller paths.
The ControlLogix 1756-EN2T Ethernet modules must contain a specific revision released
with ControlLogix Redundancy system revision 31.50 to support setting fixed IP
addresses for each module
Interruption of the redundant path has no impact on the active path
The following example graphic shows one topology for Redundant ControlLogix
Controller.
The following table defines the item names for the graphic above.
Item Description
1 FactoryTalk Linx Data Server
2 Path to the primary ControlLogix controller
3 Path to the redundant ControlLogix controller
4 Primary ControlLogix controller
5 Secondary ControlLogix controller
6 ControlLogix EtherNet/IP module for Primary Controller
7 ControlLogix EtherNet/IP module for Secondary Controller
8 ControlLogix Redundancy module for the primary controller
9 ControlLogix Redundancy module for the redundant controller
Change shortcut types Use the Communication Setup editor to switch between shortcut types in the
Device Shortcuts area.
Tip: When selecting a redundant shortcut, select the root shortcut to turn on the
Shortcut Type list.
Predefined items for redundant The predefined items for redundant shortcuts are configured in FactoryTalk Live
Data Test Client. Use below predefined items to monitor, diagnose, and configure
shortcuts
the redundant shortcuts.
Inhibit Data FactoryTalk Linx enables you to control which shortcuts are active through both
Communication the FactoryTalk Admin Console or from an HMI screen. It provide appropriate
system diagnostic indications that reflect that communications to the targeted
device is intentionally inhibit. By doing this, the system loading time and network
bandwidth needs could be reduced. The system usability could be improved as well
by inhibiting and enabling data communication flexibly.
3. Click OK.
After the device is inhibit, the icon shows on this device icon. If one or more
shortcut is linked to the inhibit device, the icon also shows on the shortcut icon.
Note: If you have set up primary and secondary servers, you need to inhibit data
communication with the device on the Primary and the Secondary tabs respectively.
If you inhibit a device and delete it from the communication tree, the inhibit data
communication status will be removed from the topology. Even if the device can be
re-browsed and added, it will be taken as a new one.
Troubleshooting
What to check first when Does your computer meet the minimum hardware and software
you have problems requirements? Refer to System requirements on page 19 for these requirements.
1. Select Start > Control Panel > Programs and Features (view by small
icons).
Troubleshooting tools for FactoryTalk Linx provides diagnostic tools, with which you can troubleshoot
problems when they occur:
FactoryTalk Linx
FactoryTalk Diagnostics event log
Predefined items
If you encounter a problem, you can review the events in the log that led up to the
problem to assist in determining the cause. Or you can monitor the log to identify
potential problems and take corrective action before a problem occurs.
Predefined items Predefined items are counters or strings that are made available by FactoryTalk
Linx as data items for diagnostic purposes. These predefined items access
information contained in FactoryTalk Linx. Refer to the FactoryTalk Linx Help
for more information about predefined items.
Answers to common The following are some frequently asked questions about FactoryTalk Linx.
questions
Where is the help for From the FactoryTalk Linx, select Help > Contents > FactoryTalk Help >
FactoryTalk Linx Help.
FactoryTalk Linx?
Why don't I see FactoryTalk Linx FactoryTalk Linx uses the FactoryTalk Administration Console to edit all of the
configuration data and does not require a standalone interface. FactoryTalk View
on my Start menu?
Studio can also make changes to FactoryTalk Linx configurations. Therefore, if
you are using FactoryTalk View SE or FactoryTalk View Machine Edition, you do
not have to leave the main user interface.
Why can't I browse for tags? Tag browsing (that is, browsing online for data items) is not supported in the
FactoryTalk Administration Console. To browse for tags and connect them to
components in your system, you must use the FactoryTalk View Studio or the
FactoryTalk Transaction Manager tag browsers.
Why can't I edit my ME Editing HMI servers within applications, namely FactoryTalk View SE
Distributed, SE Local, and ME, is not supported in the FactoryTalk
configuration?
Administration Console. The FactoryTalk Administration Console is intended to
configure and manage your application. To edit SE or ME configurations, you
must use FactoryTalk View Studio.
Can I run FactoryTalk Linx and FactoryTalk Linx and RSLinx Classic can run simultaneously on the same
computer, although there are some considerations that you must be aware of to
RSLinx Classic on the same
avoid resource conflicts between these two applications. Refer to Use FactoryTalk
computer? Linx with RSLinx Classic on page 53 for more information.
Advanced topics
About the virtual backplane The virtual backplane is a driver service that provides connectivity between
FactoryTalk Linx and various device drivers and other applications within the
FactoryTalk Linx server. It allows the software modules and communications
resources contained in the server to be configured and visualized in a manner
similar to the devices in a ControlLogix system.
For example, both the PCICS and PKTCS device drivers plug into the virtual
backplane. Packets received by one of these communications interface cards can be
routed across the virtual backplane to (or through) any other interface card whose
driver plugs into the virtual backplane, or to any application that plugs into the
virtual backplane, such as the SoftLogix5xxx controller.
Supported network routes The preferred route for PCCC networks is for the FactoryTalk Linx engine to be
connected to the end device. For example, a PanelView Plus device connected
directly to a PLC-5, or a FactoryTalk Linx data server on a Windows computer
connected directly to a DH+/RIO module in a ControlLogix rack.
FactoryTalk Linx allows you to change the network type used when going across a
route that includes multiple CIP (Control and Information Protocol; for example,
Ethernet or ControlNet) hops.
FactoryTalk Linx does not support offlink routes. Offlink routes are network
paths, in which the underlying network protocol changes. This mean if you
originally start on a PCCC route (for example, DH+/DH485, DH-RIO), you
cannot switch to a CIP route such as ControlNet or Ethernet. The reverse is also
true: you cannot start on a CIP route (for example, Ethernet to ControlLogix to
DH+ to PLC-5), and then switch to a PCCC route.
Move FactoryTalk Linx The following sections provide guidelines for moving your shortcuts from
application to application and for moving your list of selected hardware from
configurations computer to computer. Before moving your files, stop the FactoryTalk Linx
service using the Windows Service Control Panel.
Move your shortcuts You can reuse shortcuts developed in one application for FactoryTalk Linx for
another FactoryTalk Linx application without having to re-enter the shortcuts
using the following procedures. These procedures move only the shortcuts and not
the drivers themselves.
Move shortcuts from one computer 1. Right-click the FactoryTalk Linx server in the application tree and select
to another: same application Properties.
2. Change the computer name in the computer hosting the FactoryTalk Linx
server box to the new location of the FactoryTalk Linx server.
3. A warning message opens to alert you that this procedure changes the
FactoryTalk Linx server reference. You must reapply your shortcuts because
the paths may not be set correctly; only the shortcut name is preserved.
Follow the instructions provided on the dialog box.
Move shortcuts on the same 1. Identify the computer, on which your FactoryTalk Directory Server is
computer: different application located.
3. Move the shortcuts.xml file to the path where your new application is; all
your shortcuts names will be moved there.
For example:
4. For each shortcut, you must reapply the path to the end device.
Move shortcuts from one computer To move shortcuts between computers and between applications, follow the same
to another: different application path on the FactoryTalk Directory server as described in the previous section.
Keep in mind that the FactoryTalk Directory server will have a directory for each
application and for each FactoryTalk Linx server.
Move shortcuts from one computer To move shortcuts between computers, even with different FactoryTalk
to another: different FactoryTalk Directories, follow the same path on the FactoryTalk Directory server as described
Directory in the previous section. Keep in mind that the FactoryTalk Directory server will
have a directory for each application and for each FactoryTalk Linx server, and
you can move from application to application.
It is important to remember that your shortcut names are copied, but not the
associated paths; so you must reapply each shortcut.
Move your physical layout Applications using FactoryTalk Linx data services from the same FactoryTalk
Linx host computer always share the same physical hardware configuration (for
(drivers and devices)
Rockwell Automation Publication LNXENT-GR001R-EN-E - February 2018 49
Chapter 7 Advanced topics
example, drivers and devices). In this case, there is no need to move hardware
configurations from one application to another.
Move from one computer to another Important: Only qualified personnel familiar with FactoryTalk Linx and the consequences associated with
moving the RSLinxNg.xml file should perform the procedure described in this section. These
consequences include:
Driver mismatch (different driver configurations, including addresses)
Communications interfaces mismatch (some cards may get inappropriately reconfigured)
Topology mismatch (including subnets)
Contact Rockwell Automation Technical Support for assistance.
You have nearly identical control systems on similar process lines, and you
want to copy the same hardware configurations to duplicate FactoryTalk
Linx host computers on each line.
or
You can:
1. Stop the FactoryTalk Linx service, using the Windows Service Control
Panel on both the source and the target computers.
Important: If a Rockwell Automation application attempts to use FactoryTalk Linx service, FactoryTalk
Linx will restart. Rockwell Automation applications that use FactoryTalk Linx must be
stopped or shut down before you proceed. This will prevent the service from automatically
starting, while you are moving the configuration file.
Important: Any time you change the FactoryTalk Linx physical configuration (RSLinxNG.xml), you may
break existing application shortcut assignments. Check all shortcut assignments in all
applications that use the FactoryTalk Linx service on the same host workstation to ensure
that the correct devices are assigned.
Manage CIP connections By default, RSLinx Enterprise CPR 9 SR 1 and earlier would open up to five CIP
connections to a Logix controller: Four for read operations and one for write
operations. In some system configurations, the maximum connection resources in
a controller or bridge module could be reached fairly quickly. In this situation, if
the client load changed, problems could result. For example, if an HMI terminal
was introduced into the system, it could cause performance variation among all
terminals in the system, or you might not be able to go online with programming
software.
Logix controllers with a limited The following Logix controllers are assigned from 1 to 4 read connections, as
configured, with the default being 1 read connection and 1 write connection. This
number of connections
is determined at runtime and is based on the actual controller, not the type
specified in the FactoryTalk Linx topology, if it is different.
1769-L23E-QB1
1769-L23-QBFC1
17-69-L23E-QBFC1
CIP bridge modules with a The following communication bridge modules are assigned from 1 to 4 read
limited number of connections connections, as configured, with the default being 1 read connection and 1 write
connection. This is determination is based on the FactoryTalk Linx topology;
only the bridge module closest to the target controller is checked.
1756-DHRIO
1756-DHRIO
1761-NET-ENI
Use predefined items to count To determine how many CIP connections FactoryTalk Linx is using for a
particular path, create a shortcut using that path and then check the value in the
active CIP connections
@ConnectionsActive predefined item. Refer to the FactoryTalk Linx Help for
more information on predefined items.
Use FactoryTalk Diagnostics to The following FactoryTalk Diagnostics messages are used to support this feature:
track and troubleshoot CIP I_CLXDP_STARTED_ON_ROUTE is logged when a CLX data
connections provider is started.
FactoryTalk Diagnostics I_CLXDP_MAX_READ_CONNECTIONS is logged to indicate the
maximum number of read connections that the data provider will attempt
to open.
Refer to the FactoryTalk Services Platform Help for more information about
FactoryTalk Diagnostics.
Change the allocation of CIP Configuration parameters in the registry file or the RSLinxNG.xml file can be
connections used to override the default values. Refer to Rockwell Automation Knowledgebase
Answer ID 39366 for information on manually changing the connection
allocation.
FactoryTalk Linx and RSLinx Classic can run simultaneously on the same
computer. This is a common setup if you need to create or edit a program using
RSLogix 5, RSLogix 500, and RSLogix 5000 software or Logix Designer
application, which require RSLinx Classic, for use in an application, and you must
accomplish this using only one computer.
Important: FactoryTalk Linx and RSLinx Classic cannot support unsolicited messages on the same computer.
To support unsolicited message, FactoryTalk Linx needs to bind the TCP/IP port 44818 to receive
CIP messages. This port is reserved by CIP standard, which means that other CIP products from
third parties (for example, RSLinx Classic and KepServerEx) may also bind this port. To avoid the
port binding conflict issue, do NOT enable the unsolicited message function of FactoryTalk Linx on
the same machine where other CIP products (such as RSLinx Classic and KepServerEx) need to
bind the TCP/IP port 44818.
For Windows Server 2008 When running FactoryTalk Linx and RSLinx Classic on a Windows Server 2008
R2 or Windows 7 operating system, if your FactoryTalk Linx configuration
and Windows 7 operating consists of a:
systems
Dual-channel 1784-PKTX(D) FactoryTalk Linx and RSLinx Classic both install and use the same
1784-PKTX(D) driver. FactoryTalk Linx uses the first channel (assigned by
driver
default and cannot be changed). RSLinx Classic uses the second channel.
See "Configure the 1784-PKTX(D) driver for FactoryTalk Linx and RSLinx
Classic" in the FactoryTalk Linx Help for this procedure.
Important: This applies only to the dual-channel 1784-PKTX(D) driver; the single-channel 1784-PKTX driver
can be configured in only one product (either FactoryTalk Linx or RSLinx Classic) at a time.
For all the supported When running FactoryTalk Linx and RSLinx Classic on any of the supported
operating systems (see software requirements for the full list), if your FactoryTalk
operating systems Linx configuration consists of a:
1784-PKTX driver If your FactoryTalk Linx configuration consists of a 1784-PKTX driver, and you
need RSLinx Classic to communicate using that same driver, then you must share
the driver within FactoryTalk Linx with RSLinx Classic.
See "Sharing a FactoryTalk Linx driver with RSLinx Classic" in the FactoryTalk
Linx Help for this procedure.
Important: You can use this procedure for Windows 7 operating systems; however, the previous procedure
is the preferred method.
Serial-DF1 driver (RS232 DF1 If your FactoryTalk Linx configuration consists of a Serial-DF1 driver (RS232
DF1 devices), and you need RSLinx Classic to communicate using that same
devices)
driver, you must share the driver within FactoryTalk Linx with RSLinx Classic.
See "Sharing a FactoryTalk Linx driver with RSLinx Classic" in the FactoryTalk
Linx Help for this procedure.
1784-PCIC(S) driver If your FactoryTalk Linx configuration consists of a 1784-PCIC(S) driver, you
configure the driver in FactoryTalk Linx, and then add a virtual backplane to
RSLinx Classic. The virtual backplane is a sharable component between RSLinx
Classic and FactoryTalk Linx. Because the 1784-PCIC(S) plugs into the virtual
backplane, it is sharable as well.
See "Sharing the FactoryTalk Linx virtual backplane with RSLinx Classic" in the
FactoryTalk Linx Help for this procedure.
Select RSLinx Edition in Studio 5000 V31 or later supports communication software switch between
RSLinx Classic and FactoryTalk Linx. This allows you to select which
Studio 5000 Logix Designer communication software is used for network topology browsing and online
communications services. Launch the Who Active dialog box and display the
network topology. Studio 5000 Logix Designer defaults to RSLinx Classic.
Tip: Close open projects and multiple sessions of Studio 5000 Logix Designer before
selecting Communication Software.
Select an RSLinx edition in When working with ControlFLASH, you can use either RSLinx Classic or
FactoryTalk Linx (or RSLinx Enterprise v5.90.00) as your communications
ControlFLASH software. FactoryTalk Linx (or RSLinx Enterprise v5.90.00) can be used with
devices supporting USB and EtherNet/IP communications only.
1. Launch ControlFLASH.
The following table shows the RSLinx edition that ControlFlash uses.
The Network Browser The Network Browser creates and modifies device networking configurations. It
shares networking configuration with FactoryTalk Linx in the FactoryTalk
Administration Console.
Note: The device list capability in the Ethernet driver can only be configured within the Network
Browser control.
For more information, click the Help button on the Network Browser.
Configuring drivers in the A driver is the software interface to the computer or workstation hardware that
allows the computer to communicate with a network to detect and communicate
Network Browser with a control system device. If a device is not detected by the Network Browser,
use the browser to add or modify a driver configuration.
Search
Upload and register an EDS file
56 Rockwell Automation Publication LNXENT-GR001R-EN-E - February 2018
Use FactoryTalk Linx with Studio 5000 Logix Designer and ControlFLASH Chapter 9
Bridge configuration
The Ethernet driver is available with FactoryTalk Linx. The Ethernet driver
provides multiple ways for the computer or workstation to discover or detect
devices on EtherNet/IP:
Local Broadcast - Broadcast message to the full subnet that the computer is
connected to (local)
Remote Broadcast - Broadcast message to a full subnet that is different
from the one the computer is connected (remote)
Device List/Range - Directly communicate with a devices that you specify
in a list or range
Note: Ethernet List and Bridge configured is visible in FactoryTalk Administration Console. But
you need to return to the Network Browser to modify the configurations.
You can add a driver for local or remote broadcast, or create a list or range of IP
addresses. Perform the applicable task to add a driver.
Search criteria for a device Use Search to locate a device in the previously viewed or discovered network
topology.
To perform a search:
1. In the Search box, type a keyword and press Enter. Search text can contain
alphanumeric characters and can be full words, compound expressions,
fragments of a word, or a single letter or number.
Device
Online name
Path
Address
Tip: When entering a search filter, type a keyword followed by a colon. For example, to
locate ControlLogix controllers, type Device:
AND to search for two or more keywords. For example, alarm AND
active.
OR to search for several keywords. For example, error OR fault.
Tip: An example of using operators between keywords to refine search results is Device:
1756-L OR Device: 1768-L to locate ControlLogix and CompactLogix controllers.
5. To repeat a previous search, click the down arrow on the right side of the
Search box and click a previous search.
Tip: Click X in the Search bar to cancel the search and return to the normal view.
Search filters
Search filter options for the Search function make it easy to refine search results.
Operators Use operators with the keyword Search function to return a more precise set of
results.
One of several keywords OR (all capital letters) alarm OR active returns a list of tags that include
the string alarm or active.
Exact keywords " " (quotation marks) "M200" returns a list tags that includes the string
M200 in its name or description.
Upload and register an EDS file Upload and register EDS files from devices to allow device communications in the
Network Browser.
For an online device in the network topology tree, if there is an EDS file within
the device's firmware, you can upload the EDS file and register it to the
FactoryTalk Linx data server. Once registered, the device information shows in
the Network Browser, and communications to other information within the
device is possible.
Upload and register an EDS file in the Starting from FactoryTalk Linx v6.00.00, you can upload and register EDS files of
Network Browser devices within the Network Browser.
For an online device in the network topology tree, if there is an EDS file within
the device's firmware, you can upload the EDS file in the Network Browser and
register it to FactoryTalk Linx data server. Once registered, the device information
shows in the Network Browser, and communications to other information
within the device is possible.
3. If the target device has registered an EDS file, the following warning
message shows:
"An EDS is already registered for this device. Are you sure you still want to
upload and register this EDS file?"
Click OK to continue and replace the existing EDS file, or click Cancel to
stop the uploading process and retain the existing EDS file on the current
computer.
A progress circle shows the registration status. Wait while the system registers the
device. if you want to register several EDS files, repeat Step 1 to Step 3.
Automatically upload and register an The automatic EDS upload function enables the Network Browser to
EDS file automatically upload and register EDS files for a selected node and its child nodes.
For an online device whose EDS file is not registered, the system detects whether
there is an EDS file within the device's firmware. If there is an EDS file found, the
system automatically uploads it from the device and registers it on the current
computer. With the automatic EDS upload function, you can register several EDS
files at a time.
Tip: This enables the automatic upload and registration function. By default, the function is disabled.
The system automatically browses the selected node and its child devices. If an
unregistered online device is found, and it has an EDS file within its firmware, the
system automatically uploads and registers the EDS file on your computer. A
progress circle shows beside the unregistered device indicating the auto EDS
upload status.
Register EDS files using the EDS You can register the EDS files of hardware devices using the EDS Hardware
Hardware Installation Tool Installation Tool.
To register the EDS file of a hardware device, you must have a valid and
complete EDS file of the hardware device. To search and download the EDS
file of a specific hardware device, visit Rockwell Automation Network
Resources.
If an icon file (*.ico) exists for the hardware device, save it with the same
name as the EDS file in the same directory. You can save one or more EDS
files (and the related icon files) in one directory.
1. From Windows Start menu, select All Programs > Rockwell Automation
> RSLinx > Tools > EDS Hardware Installation Tool.
4. In the Registration dialog box, click Browse to select the EDS file (if you
are registering a single file), or the directory of the EDS files (if you are
registering two or more EDS files), and click Next.
5. In the EDS File Installation Test Results dialog box, review the hardware
device list and click Next.
6. In the Change Graphic Image dialog box, review the icon(s) of the
hardware device(s) and click Next.
Tip: Rockwell Automation's EDS Wizard assigns a default icon to each hardware device. You can specify a
different icon for the hardware device(s) by selecting the hardware device and clicking the Change
icon button.
7. In the Final Task summary dialog box, review the hardware device list and
click Next.
9. Click Exit.
Considerations when uploading and To manually or automatically upload and register EDS files in the Network
registering EDS files Browser, consider the following:
This function updates the EDS files on the computer which hosts the
FactoryTalk Linx data server. Once registered, the EDS file is available for
use in clients computers which exchanges data with the FactoryTalk Linx
data server.
To support a new device on computers with different FactoryTalk Linx
data servers, you must register the hardware device's EDS file on each target
computer respectively.
Some hardware devices, such as Data Highway Plus (DH+) devices, do not
have EDS files and therefore do not support upload and registration.
Some hardware devices, such as Micro800 series devices and PanelView Plus
terminals, require a patch or a new release of FactoryTalk Linx that officially
adds support for the new hardware devices. These devices cannot
communicate with FactoryTalk Linx merely by EDS file upload and
registration.
If an EDS file is invalid, or an error occurs during the upload and
registration, the EDS file cannot be registered, and a diagnostics message is
logged into FactoryTalk Diagnostics Viewer. To view the diagnostics
messages:
From Windows Start menu, select All Programs > Rockwell Software
> FactoryTalk Tools > Diagnostics Viewer, or
In FactoryTalk Administration Console, from the Tools menu, select
FactoryTalk Diagnostics > Viewer.
If you upgrade or re-install FactoryTalk Linx, the EDS files that are
previously registered on your computer are lost. You need to register the
EDS files again.
To automatically upload and register EDS files in the Network Browser, consider
the following:
does not upload and register it. To update the new EDS file, right-click the
existing device in the network topology tree and select EDS upload
.
If there are many EDS files being registered, the Network Browser may
respond slowly.
What is EDS Hardware Installation How do I access the EDS Hardware Installation Tool?
Tool
From Windows Start menu, select All programs > Rockwell Software > EDS
Hardware Installation Tool.
The EDS Hardware Installation Tool allows you to change the hardware
description information currently installed on your computer.
Use EDS Hardware Installation Tool to register EDS files for unrecognized
devices.
Bridge across networks Use a bridge to connect two networks and, if necessary, convert communications
from one network protocol to another so that they can communicate. Creating a
bridge in the Network Browser enables the browser to detect devices on another
physical network and enables users to perform diagnostic and configuration
functions on those devices. After adding a bridge, the name given to the bridge
appears in the Network Browser tree topology.
Add a bridge Create a bridge to enable the Network Browser to detect devices on another
network and perform diagnostic and configuration functions on those devices.
To add a bridge:
Tip: You can also add a bridge from Advanced tab in the Advanced Settings dialog
box.
3. From the Add New dialog box, in the Name box, enter a name for the
bridge.
4. Next to the Select Target Bridge Network box, click Browse (...).
5. From the Bridge Path Selection dialog box, select a device for the
Network Browser to detect on another network.
Tip: To add an existing configuration path from another bridge instead of creating a new target bridge path, click the
Copy Setting From list and select a configuration. If there are no existing configuration paths to select, Empty is
displayed in the Copy Setting From list.
6. Click the General tab and configure the browsing discovery options for the
bridge.
7. Click OK to save.
Edit a bridge Edit a bridge to update settings and make changes to the IP addresses for devices
in the bridge configuration.
To edit a bridge:
Tip: You can also edit a bridge from Bridged tab in the Advanced Settings dialog
box.
2. In the Bridge Configuration dialog box, click the Advanced tab and
configure the tuning settings to change how fast the Network Browser
discovers items on the network.
3. Click Apply.
6. To remove an IP address or range from the list, select the check box next to
the address and click Delete.
Delete a bridge Deleting a bridge removes the connection between devices on a bridged network.
If devices on a bridged network are no longer valid, delete the bridge in the
Network Browser.
To delete a bridge:
Tip: You can also delete a bridge from the Bridged tab in the Advanced Settings
dialog box.
Copy and paste items to a list in a To have a list of devices stored in a spreadsheet or a database to manage updates
bridge configuration and maintenance schedules, copy the list from a Device List/Range
configuration. Additionally, if updating the included devices, paste additional
items into the Device List/Range instead of manually entering the device
information.
Tip: To select all the items, select the check box next to the No. list.
5. Paste the copied items into the desired editing tool and make the desired
modifications.
7. In the Bridge Configuration dialog box, select the location in the list to
paste the items and click Paste.
Delete an item in a list in a bridge Delete an item to a list or range of IP addresses for a bridge.
configuration
To delete an item to a list in a bridge configuration:
Tip: To delete all the items in the list at once, select the check box next to the No.
column and then click Delete.
Add New dialog box How do I open the Add New dialog box?
Setting Description
Name Used to create a name for the bridge. Names can include letters, numbers, spaces, and
special characters.
Select Target Bridge Network Used to select a device that has two communication ports for two different networks or a
separate device in the same chassis to connect with a different network.
Copy Setting From Used to copy an existing configuration path into the new bridge. If there is not an
existing configuration path, empty will appear in the list.
Copy a device configuration in a Copy a configuration for a device that is being deleted or replaced with a new
bridge module or moved to a new location. For example, if replacing a module, copy the
configuration from the old module and add it to the new module.
Important: Deleting a module from a bridged network permanently removes the module configuration from the
Network Browser. If removing or replacing a module, be sure to copy the module configuration to a
different module prior to deletion. Once a module is deleted, the corresponding module configuration is
also deleted and cannot be retrieved.
3. Select the device in the applicable bridge configuration and click Add New.
4. In the Add New dialog box, click the Copy setting from list and select the
bridge that contains the desired device.
Bridge Path Selection dialog box How do I open the Bridge Path Selection dialog box?
4. From the Add New dialog box, in Name, enter a name for the bridge.
5. Click Browse (...) next to the Select Target Bridge Network box.
The Bridge Path Selection dialog box includes the devices from the network
topology tree in the Network Browser. In the Bridge Path Selection dialog box,
select the network to connect the current network.
Bridge Configuration dialog box How do I access the Bridge Configuration dialog box?
network.
Setting Description
Poll interval between discovery cycles The number of milliseconds that occur between each time the Network
(msec) Browser queries the network.
Poll timeout (msec): Specifies the amount of time (in milliseconds) to wait for poll responses.
Maximum concurrent packets to this Used to configure the maximum number of requests that can be waiting for a
network response on this network at any given time as part of the browsing process.
Enable discovery using subnet mask Enables the Network Browser to communicate with each device on the
subnet.
Important: Enabling the discovery command significantly increases the
amount of traffic on a network. Determine the impact on your network prior
to enabling this command.
Reset Used to return the Tuning settings to the default values.
Bridge Configuration dialog box, The General tab on the Bridge Configuration dialog box contains this
General tab settings information:
Setting Description
Name The descriptive name for the bridge. Adding a descriptive name for a bridge
makes it easier to find the bridge in the Network Browser network
topology tree. The name can contain characters, including letters, numbers,
and special characters.
Device Serial Number The unique identification number of the device.
Port Number\IP Address The downstream IP address and port number of the bus node to help identify
a unique bridge configuration.
No. Indicates the number of an item in the list.
Device List/Range A list of items in the applicable range. Select the check box next to an item in
the Device List/Range to edit the item settings.
Pencil Icon Used to modify an IP address.
Add New Used to add a new item to the list.
Delete Used to delete an item from the list.
Copy Used to copy an item(s) in the list.
Paste Used to paste an item(s) in the list.
Advanced Settings dialog box How do I access the Advanced Settings dialog box?
(drivers)
From the Who Browser, click the Advanced Settings icon.
Advanced Settings dialog box, General Use the General tab on the Advanced Settings dialog box to control the
tab settings discovery behavior of the Network Browser.
Setting Description
Enable Automatic Discovery Used to enable the discovery type.
Make Discovery Continuous (Auto browse) Used to turn on continuous browsing of the network.
Show Unrecognized Devices Used to enable unrecognized devices found during network discovery to
be included in the Network Browser topology tree.
Advanced Settings dialog box, Bridged Use the Bridged tab on the Advanced Settings dialog box to configure network
tab settings bridges.
Setting Description
Add New Opens the Add New dialog box where the settings for a new bridge are
specified.
Edit Opens the Bridge Configuration dialog box where the settings for a
bridge can be edited.
Delete Deletes the selected bridge.
Add a driver for Local Broadcast To add a driver to the same subnet that a computer is connected to, configure the
driver for Local Broadcast.
2. In the Add Driver dialog box, select a driver, and click OK. The General
and Advanced tabs display in the Add Driver dialog box.
3. Click the Advanced tab and select the physical port of the computer, and
configure the tuning settings to change how fast the Network Browser
discovers items on the network.
4. Click Apply.
5. Click the General tab, and in the Name box, enter a name for the driver.
Add a driver for Remote To add a driver to a different subnet than the one the computer is connected to,
configure the driver for Remote Broadcast.
Broadcast
To add a driver for Remote Broadcast:
2. In the Add Driver dialog box, select a driver, and click OK. The General
and Advanced tabs display in the Add Driver dialog box.
3. Click the Advanced tab and select the physical port of the computer, and
configure the tuning settings to change how fast the Network Browser
discovers items on the network.
4. Click Apply.
5. Click the General tab, and in the Name box, enter a name for the driver.
Add a driver with a Device When adding a driver, use a list or range of IP addresses to make sure broadcast
messages reach the desired devices.
List/Range
Note: Ethernet List and Bridge configured is visible in FactoryTalk Administration Console. But
you need to return to the Network Browser to modify the configurations.
2. In the Add Driver dialog box, select a driver, and click OK. The General
and Advanced tabs display in the Add Driver dialog box.
3. Click the Advanced tab and select the physical port of the computer, and
configure the tuning settings to change how fast the Network Browser
discovers items on the network.
4. Click Apply.
5. Click the General tab, and in the Discovery Method list, click Device
List/Range.
6. In the box under Device List/Range, enter the desired subnet range.
7. In the Name box, enter a name for the driver and click OK.
FactoryTalk Administration 1. From the Explorer, under the FactoryTalk Linx data server, double-click
Console Communication Setup.
3. In the Add Driver Selection dialog box, the available drivers will appear.
Select the driver you want to add, and click OK.
4. From the applicable driver properties dialog box, enter the settings and click
OK.
5. After you add the driver, right-click on the driver and then click Start
Browsing to populate the driver with devices.
Tip: If you are adding a driver via an Ethernet network, from the Communications
Setup editor, right-click on the network shown, then select Start Browsing
to populate the driver with devices.
Some Ethernet devices may not support the browse protocol used by
FactoryTalk Linx on Ethernet. If the devices you expect to appear during the
browse do not display, right-click the network and click Add Device to
manually add the device to the Ethernet network of the workstation. Before
you add a device manually, you must register it using the EDS Hardware
Installation Tool.
Ethernet list configured in the network browser control is visible in the
FactoryTalk Administration Console but you need to return to the network
browser control to modify the configuration.
Besides the Setup Wizard installation, FactoryTalk Linx also supports automated
installation using command line syntaxes. You can typically use this automated
installation method during large-scale rollouts, when it might be too slow and
costly to have administrators or technicians interactively install the software on
individual computers.
This automated installation method requires you enter a command line at the
beginning of the installation. During the installation process, instead of prompting
you for installation and configuration information interactively, the process
follows the specific command line, without user intervention.
Comparing different FactoryTalk Linx supports setup wizard installation, and installation with
command line syntax (that is, unattended installation and silent installation). The
installation methods following table illustrates the differences among each installation method.
Unattended An automated installation method in RSLinx Enterprise version 5.90.00 Use unattended
installation and later (renamed FactoryTalk Linx with version 6.00.00). It installs all installation on page
the necessary prerequisites software and required components with 74
little (or no) user intervention, and provides multiple parameters that
allow customized installations. It is recommended for large-scale
rollouts.
Tip: Depending on the customized parameters, you can silently install
FactoryTalk Linx, prerequisite software, and required components using
this method. See Example 1 on page 76.
Silent installation for An automated installation method in RSLinx Enterprise version 5.60.00 Use silent
FactoryTalk Linx .msi and later (renamed FactoryTalk Linx with version 6.00.00). It installs the installation for
file FactoryTalk Linx .msi file with little (or no) user intervention. You need FactoryTalk Linx
to manually install the prerequisite software and required components .msi file on page 76
before silent installation.
Use unattended installation Starting with CPR 9 SR 9, FactoryTalk Services support unattended installation.
In the unattended installation, you enter a specified command line syntax with
multiple parameters. You can customize the parameters to meet your needs.
Perform unattended To perform unattended installation, follow the steps below. The steps may vary
slightly. Follow the on-screen instructions that apply to your operating system.
installation
1. Close all open Windows programs.
Tip: The User Account Control dialog box may show after you press Enter, click Yes
to continue.
5. Press Enter. The installation process starts with the parameters you
specified.
6. For detailed description about each parameter, see Parameters on page 74.
You can also type Setup /? in the Command Prompt window, and press
Enter to view the help information of all parameters and examples.
Parameters The parameters and values are not case sensitive. If the value includes spaces, you
need to enclose it in quotation marks (" ").
/Q
Installs the product in the silent mode without any user interface.
/QS
/IAcceptAllLicenseTerms
Required. Specifies that you read and acknowledge all license agreements,
and agree to continue the installation.
/AutoRestart
/SetupLanguage=value
If omitted, the default language is the user or system user interface language.
/Record
/Playback
/InstallDrive=value
Optional. Specifies the installation drive. If omitted, the default drive and
location are:
/Uninstall
Examples The following examples show how to use the commands during the unattended
installation.
Example 1
Setup.exe /Q /IAcceptAllLicenseTerms
means:
Example 2
means:
Example 3
Setup.exe /Q /Uninstall
means:
Use silent installation for RSLinx Enterprise v5.60.00 (CPR 9 SR 6) (Renamed FactoryTalk Linx with
FactoryTalk Linx .msi file version 6.00.00) and later supports silent installation for .msi file. In the silent
installation, FactoryTalk Linx is installed with default settings, with no (or little)
dialog boxes, messages, or user intervention.
Before you begin Before installing the .msi file of FactoryTalk Linx using the silent installation, you
must manually install the following prerequisite software and required
components, in the following sequences:
Certificates installation
For detailed instructions about how to install it, refer to Install certificates
on page 78.
Rockwell Automation x64 driver Rockwell Automation x64 driver package includes the following drivers:
package
1747-UIC (DH485)
1752-SmartGuard USB
1784-PCIC(S) (ControlNet)
1784-PKTCS (ControlNet)
1784-PKTX (DH485 / DH+ / RIO)
1784-U2DHP (DH+)
Micro800 Remote LCD (208-REMLCD / 820 Remote LCD)
Micro810
Virtual Backplane
USB CIP
Install certificates The following certificates are available in the installation directory \Redist\Cert:
2016-Rockwell-Driver-SHA1.cer
2016-Rockwell-SHA256.cer
DriverCodeSigning2012-1.cer
Drivers-12-06-2016.cer
Logix-11-04-2016.cer
Rockwell_2013.cer
Rockwell_2014.cer
Rockwell_2015.cer
rockwellcert2010.cer
rockwellcert2013.cer
VeriSign Class 3 Public Primary Certification Authority - G5 2036.cer
The steps below take the VeriSign Class 3 Public Primary Certification Authority -
G5 2036.cer certificate as an example.
2. On the General tab of the Certificate dialog box, click Install Certificate.
4. Select Place all certificates in the following store, and click Browse.
5. In the Select Certificate Store dialog box, select the Trusted Root
Certificate Authorities folder, and click OK.
7. Click Finish.
Perform silent installation To perform silent installation, follow the following steps:
Tip: The User Account Control dialog box may show after you press Enter, click Yes
to continue.
The installation process starts silently. For the installation log file, type the
following command line syntax in the Command Prompt window:
Uninstall FactoryTalk Linx To uninstall FactoryTalk Linx software, do any of the following:
Note: Components, such as FactoryTalk Activation Manager, that are shared with other products
will not be uninstalled.
For more information about command-line parameter, see Parameters on page 74.
Area. Areas organize and subdivide a distributed Network application into logical
or physical divisions. For example, separate areas may correspond with separate
manufacturing lines in a facility, separate plants in different geographical locations,
or different manufacturing processes. Areas are not available with Local
applications.
Configuration. A file that contains information about the physical structure you
defined for your system. This file includes all network paths, defined drivers and
devices, data providers, and object protocols.
Data element. An individually addressable item of data. For example, a tag (for
example, OPC or HMI), or an HMI Project Component (for example, a graphic
display, event file, node, channel).
Data Provider. Logic that knows how to speak to a particular class of products.
One of the building blocks of FactoryTalk Linx, a Data Provider acts as a
multiplexor for multiple clients and optimizes what data can be read together for
more efficient handling.
Driver. Software that interacts with a network interface (such as the interface that
connects your computer to the Ethernet network), and manages the exchange of
communication packets over the network, to which the interface is attached.
FactoryTalk Live Data. FactoryTalk Live Data is a service that reads and writes
tag values (OPC items) to or from any OPC-DA (OLE for process Control - Data
Access) or Live Data server on behalf of client software products, such as
FactoryTalk View Site Edition and FactoryTalk Transaction Manager.
Local application. A Local application is accessible only from the local computer
where it resides. Even if the computer is connected to a network or a Network
application resides on the same computer, the Local application remains
self-contained and does not share its data or any of its project elements. Local
applications do not support areas. Also called stand-alone applications.
Offline data item. A data item (tag) whose server is not currently available but
whose name is still available for browsing, selection, and use. Offline data items are
read directly from a controller’s project file.
Offline device. The device that is not in direct communication (for example,
when programming in Logix Designer).
Online data item. A data item (tag) whose server is currently available to supply
data. Online data items are read directly from a controller, just as they are defined
in that controller.
OPC DA. OPC Data Access is a group of client-server standards that provides
specifications for communicating real-time data from data acquisition devices such
as PLCs to display and interface devices like HMI, SCADA, and ERP/MES
systems.
OPC UA. The OPC Unified Architecture (UA), released in 2008, is a platform
independent service-oriented architecture that integrates all the functionality of
the individual OPC Classic specifications into one extensible framework.
Server. A subsystem that provides services for clients, using a set of interfaces.
Shortcut. Represents a device that you want to connect to on the network, and
the data that device contains. The communication path associated with the
shortcut tells the application where to find that data. This symbolic reference to a
physical device is similar to a topic in RSLinx Classic.
Tag. A logical name for a variable in a device or in local memory. For example, a
tag can represent a process variable in a Logix 5000 controller.
A
E
adding a data server 25
adding a device Ethernet network, adding drivers to 33
automatically 34 event log, FactoryTalk Diagnostics 45
manually 34
adding drivers 33 F
Alarms and Events tab 31
applications, about 14 FactoryTalk Administration Console 14
starting 23
user interface components 23, 45
B FactoryTalk Diagnostics 45, 52
browsing FactoryTalk Directory 14
for devices 34 FactoryTalk Linx
tag 46 adding a device 33
virtual backplane 34 adding drivers 33
basic concepts 13
Communication Setup editor 25
C creating a configuration 33
checklist, installation and configuration 15 creating shortcuts 35
CIP (Control and Information Protocol) 47 definition 11
Communication Setup editor, exploring 25 design-time vs runtime 15
configurations features and benefits 12
creating 33 installing 19
moving 48 moving configurations 48
consulting services 9 system requirements 17
contacting troubleshooting 45
Customer Support Center 8 updating an existing installation 21
creating 35 using with RSLinx Classic 53
creating shortcuts 35 FactoryTalk Linx Server properties, General tab 29
Customer Support Center, contacting 8 FactoryTalk Linx Server Properties, Redundancy tab 30
FactoryTalk Live Data 14
FactoryTalk Security 14
D FactoryTalk Services Platform
data server, adding 25 about 13
design-time component 15 FactoryTalk View Machine Edition 46
device shortcuts, creating 35 FactoryTalk View Site Edition 46
devices FactoryTalk View Studio 15, 46
adding 33 FactoryTalk, basic concepts 13
moving 49
drivers
G
adding 33
moving 49 General tab 29
N U
Network applications 14
updating an existing RSLinx Enterprise or FactoryTalk Linx installation 21
network routes, supported 47
V
O
virtual backplane
offline tag file 35
about 47
browsing 34
P
PCCC networks 47
predefined items 46
R
Redundancy tab 30
Release Notes 8
RSLinx 2.x, see RSLinx Classic 53
RSLinx Classic 46
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local
distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone.
Installation assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact
Customer Support for initial help in getting your product up and running.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to
your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
feedback form, publication RA-DU002
Supersedes Publication LNXENT-GR001Q-EN-E Copyright © 2018 Rockwell Automation Technologies, Inc. All Rights Reserved. Printed in the U.S.A.