VFD 101 For Water: Lesson 1
VFD 101 For Water: Lesson 1
Outline:
Functions of a VFD in pumping
1. Start/Stop
2. Change Speed
3. Constant Speed
4. Limits
5. Ramping
6. Forward/Reverse
7. Save Energy
Note: There are other names for a VFD such as Adjustable Frequency Drive
(AFD); Variable Speed Drive; Adjustable Speed Drive; Inverter and
Frequency Converter. The name VFD is consistently used through out this
lesson.
The pump system in the picture above must maintain a certain pressure
perhaps 70psi (480kPa). Looking at this example, see if you can identify
some of the functions that must be performed by the VFD, AC motor and
pump? In other words, what must the pump do? Take a couple of minutes
to think about its functions.
_________________ ______________________
_________________ ______________________
STOP
In the picture above, the same switch is used to stop the pump. If there
is only 1 switch to start/stop the VFD it is known as a 2-wire Start/Stop. If
there are 2 separate momentary (push button) switches, one to Start and
one to Stop, this arrangement is known as a 3-wire Start/Stop.
On the next page 2-wire and 3-wire start/stop arrangements are explained in
more detail.
2-wire
The picture on the left shows a 2-wire start/stop. The remote switch is a
continuous single-pole-double-throw (SPDT) switch. In stays in the ON or
OFF position. If the VFD is started with only 1 switch it is a 2-wire.
3-wire
The picture on the right shows the 3-wire start/stop. This is considered as a
standard motor starter configuration. Two momentary or push-button
switches are used to start and stop the VFD. A normally-open (NO) push-
button switch is used to start the VFD. A normally-closed (NC) push-button
switch is used to stop it. If the VFD is started with one switch and stopped
with another, it is a 3-wire.
Function #4 – Limits
August 04
Function #4 Limits
It is important that limits be placed on a VFD. Speed limits can be
placed in the program of the VFD so an operator can not go beyond a
maximum speed or less than a minimum speed. The maximum speed of the
pump should not exceed 60Hz in North America (50Hz in the rest of the
world), due to excessive power consumption. For lubrication purposes the
pump should have a minimum speed of at least 18Hz. Because of the
possibility of overheating, fans and blowers should not be run less than 6Hz.
For the same reason as the pump, fans should not be run more than 60/50
Hz.
If the pump gets stuck, there are torque limits that the VFD monitors
stopping the motor if they are exceeded. Current limits are also important for
protection of the drive and motor. In the picture above the maximum
reference is set to 60/ 50 Hz. Notice that in the diagram there is a minimum
reference of 18Hz.
Function #5 – Ramping
Function #5 Ramping
The VFD also ramps the pump up and ramps it down. When the pump
starts, acceleration, it is important that there is no sudden jump to the
reference speed, or water hammer occurs. Older pipes have great difficulty
with rapid pressure changes and can break. In the example above, a ramp-
up slowly increases the speed from stopped or 0Hz up to the reference,
34Hz, over a certain amount of time perhaps 10 seconds. If this ramp up is
too short, the drive can trip on an over current alarm or torque limit. If the
VFD is tripped, the pump stops and it might require an operator to manually
reset the VFD. Many VFDs have an automatic reset setting from 1 restart or
reset per alarm, up to an infinite number of resets per alarm.
Many submersible pumps require 2 startup ramps. One very quick
initial start up ramp (say 1 second) for pump lubrication, up to its minimum
speed, say 20Hz. Then a much slower ramp up (say 20 seconds) from the
minimum speed up to the operating speed of 45Hz.
Function #5 – Ramping
Function #6 – Forward/Reverse
• Change of Direction
• Forward to fill the tank
August 04
Function #6 – Forward/Reverse
REVERSE
If something is stuck in the impeller of the pump, and it is allowed by
the pump manufacturer, it might be of advantage to turn the pump slowly
backwards. From the last page power going to the motor must be changed
between 2 terminals of the motor to move the pump backwards (or Reverse).
When a Reverse command is given to the VFD, it automatically swaps 2 of
the 3 leads of the 3-phase motor to change directions, going backwards.
August 04