Pca - Iom
Pca - Iom
Pca - Iom
PCA- RP • KA
1. Safety precautions
► Before installing the unit, make sure you read all the “Safety precau- After installation work has been completed, explain the “Safety Precautions,” use,
tions”. and maintenance of the unit to the customer according to the information in the
► Please report to your supply authority or obtain their consent before Operation Manual and perform the test run to ensure normal operation. Both the
connecting this equipment to the power supply system. Installation Manual and Operation Manual must be given to the user for keeping.
These manuals must be passed on to subsequent users.
Warning:
:Indicates a part which must be grounded.
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Warning:
Caution: Carefully read the labels affixed to the main unit.
Describes precautions that must be observed to prevent damage to the unit.
Warning:
• Ask a dealer or an authorized technician to install the unit. • Ventilate the room if refrigerant leaks during operation. If refrigerant comes
• For installation work, follow the instructions in the Installation Manual and into contact with a flame, poisonous gases will be released.
use tools and pipe components specifically made for use with refrigerant • All electric work must be performed by a qualified technician according to
specified in the outdoor unit installation manual. local regulations and the instructions given in this manual.
• The unit must be installed according to the instructions in order to mini- • Use only specified cables for wiring.
mize the risk of damage from earthquakes, typhoons, or strong winds. An • The terminal block cover panel of the unit must be firmly attached.
incorrectly installed unit may fall down and cause damage or injuries. • Use only accessories authorized by Mitsubishi Electric and ask a dealer or
• The unit must be securely installed on a structure that can sustain its weight. an authorized technician to install them.
• If the air conditioner is installed in a small room, measures must be taken • The user should never attempt to repair the unit or transfer it to another
to prevent the refrigerant concentration in the room from exceeding the location.
safety limit in the event of refrigerant leakage. Should the refrigerant leak • After installation has been completed, check for refrigerant leaks. If refrig-
and cause the concentration limit to be exceeded, hazards due to lack of erant leaks into the room and comes into contact with the flame of a heater
oxygen in the room may result. or portable cooking range, poisonous gases will be released.
2
2. Installation location
Min.300
(mm) 2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and main-
W
tenance.
Min.270
Models W
RP50 960
RP60,71 1280
RP100 ,125,140 1600
236
Warning:
Mount the indoor unit on a ceiling strong enough to withstand the weight of
Min.500
the unit.
68 Ma
0 x.2
50 2.2. Outline dimensions (Outdoor unit)
Fig. 2-1 Refer to the outdoor unit installation manual.
4 Band 4 pcs
5 Joint socket 1 pc Marked with “UNIT”
7 8 9 6 Socket cover 1 pc
7 Drain tubing cover 1 pc
8 Wired remote controller 1 pc
9 Flare nut 1 pc ø6.35 (RP60 only)
Fig. 3-1
Models A B
320
190
190
138
D Independent piece (Removable) I Rubber plug
E Right drain tubing J with Joint socket 5
In case of the rear pipe arrangement, make sure to remove the shaded portions
from the D independent piece. Then put the D independent piece back in initial
position.
233 (The heat exchanger might be clogged because of dust)
246 C
D
233
246
Fig. 3-2
3
3. Installing the indoor unit
3.2.4. Indoor unit preparation (Fig. 3-4)
Fig. 3-3 1. Install the suspending bolts. (Procure the W3/8 or M10 bolts locally.)
Predetermine the length from the ceiling (1 within 100 mm).
A Ceiling surface B Suspending bolt C Suspending bracket
2. Remove the intake grille.
Slide the intake grille holding knobs (at 2 or 3 locations) backward to open the
intake grille.
3. Remove the side panel.
Remove the side panel holding screws (one in each side, right and left) then slide
the side panel forward for removal.
D Intake grille J Slide the side panel forward.
E Intake grille holding knob K Side panel
F Slide L Remove the side panel holding screws.
G Hinge M Remove the protective vinyl of vane.
H Pushing the hinge, pull out the intake grille.
2 Forcing open the intake grille or opening it to an angle of more than 120° may
damage the hinges.
Fig. 3-4
1. Install the washer 1 (supplied with the unit) and the nuts (to be locally procured).
2. Set (hook) the unit through the suspending bolts.
3. Tighten the nuts.
5 3 Check the unit installing condition.
• Check that the unit is horizontal between the right and left sides.
Fig. 3-5 • Check that the front and the rear of suspending brackets are horizontal.
(To keep drainage,the unit is inclined to the suspending brackets. The unit slopes
continuously downward from the front to the rear is the right installation position.)
2) Installing the suspending bracket first onto the ceiling (Fig. 3-6)
Installing procedures
7~12
1. Remove the suspending brackets and U-shaped washers from the unit.
2. Adjust the suspending bracket holding bolts on the unit.
3. Attach the suspending brackets to the suspending bolts.
4. Check that the suspending brackets are horizontal (front and rear/ right and left).
5. Set (hook) the unit to the suspending brackets.
6. Tighten fixed bolts of the suspending brackets.
w Be sure to install the U-shaped washers.
A Suspending bracket holding bolt
B Unit
C U-shaped washer
D Suspending bolt
E Washer 1 (mm)
F Double nuts G RP50 882-887
RP60,71 1202-1207
RP100 -140 1522-1527
Fig. 3-6
4
4. Installing the refrigerant piping
4.1. Precautions
45 2 For devices that use R410A refrigerant
• Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigera-
tion oil applied to the flared sections.
0.5
A
• Use C1220 copper phosphorus for copper and copper alloy seamless
pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thick-
90
R0 nesses specified in the table below. Make sure the insides of the pipes are
.4~
R0 clean and do not contain any harmful contaminants such as sulfuric com-
.8 pounds, oxidants, debris, or dust.
Fig. 4-1
Warning:
When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig-
Flare cutting dimensions erant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.
Copper pipe O.D. Flare dimensions
(mm) :A dimensions (mm)
:6.35 8.7 - 9.1 RP35, 50 RP60-140
:9.52 12.8 - 13.2 Liquid pipe [ 6.35 thickness 0.8 mm [ 9.52 thickness 0.8 mm
:12.7 16.2 - 16.6 Gas pipe [ 12.7 thickness 0.8 mm [ 15.88 thickness 1.0 mm
:15.88 19.3 - 19.7
:19.05 23.6 - 24.0 • Do not use pipes thinner than those specified above.
5
5. Drainage piping work
• For left side tubing, be sure to insert the rubber plug into the right drain port. (Fig.
5-1)
• Use VP-20 (O.D. ø26 (1”) PVC TUBE) for drain piping and provide 1/100 or more
downward slope.
• After completion of work, check that correct drain is available from the outflow
port of the drain tubing.
A Drain pan
B Plug
C Insert the driver etc.in the plug deeply.
Fig. 5-1
Installing procedures (Fig. 5-2)
1. Attach the joint socket 5 supplied with the unit to the drain port on the unit with a
vinyl chloride adhesive.
2. Fasten the socket cover 6 supplied with the unit to the joint socket 5.
3. Attach the field drain tubing (VP-20) to the joint socket 5 with a vinyl chloride
adhesive.
4. Wrap the drain tubing cover 7 supplied with the unit. (Seam taping)
A Drain pan
B Drain tubing
Fig. 5-2 C Socket cover 6
D Joint socket 5
E Drain tubing cover 7
F Insertion length 37mm
Fig. 5-3
6. Electrical work
Fig. 6-1
6
6. Electrical work
1:1 System
D G
A Outdoor unit power supply
L
A B C N B Earth leakage breaker
C Wiring circuit breaker or isolating switch
S1 S1 D Outdoor unit
S2 S2
E Indoor unit/outdoor unit connecting cables
S3 S3
F Remote controller
E G Indoor unit
1
F 2
* Affix label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
* Affix label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
(mm²)
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 60245 IEC 57)
3. Install an earth longer than other cables.
6.1.2. Separate indoor unit/outdoor unit power supplies (For PUHZ application only)
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
1:1 System
* The indoor power supply terminal kit is required. A Outdoor unit power supply
G B Earth leakage breaker
D
C Wiring circuit breaker or isolating switch
L L
A B C N J B C N H D Outdoor unit
E Indoor unit/outdoor unit connecting cables
S1 S1 F Remote controller
S2 S2
S3
G Indoor unit
S3
E 1
H Option
F 2 J Indoor unit power supply
* Affix label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
7
6. Electrical work
* Affix label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table
below. If the indoor power supply terminal kit is used, change the indoor unit elec-
If the indoor and
trical box wiring refering to the figure in the right and the DIP switch settings of the Connectors (connections of initial setting outdoor units have
outdoor unit control board. are for indoor unit power supplied from separate power
Option
Indoor unit specifications outdoor unit) supplies, change the
connections of the
Indoor power supply terminal kit (option) Required
L connectors as shown
BLUE YELLOW
BLUE YELLOW
Indoor unit electrical box connector connec- Required N in the following
tion change BLACK figure.
CN01
CN01
Label affixed near each wiring diagram for Required
Indoor unit
the indoor and outdoor units S1 control board Option
S2
Outdoor unit DIP switch settings (when us- Connectors
ON 3 S3
ing separate indoor unit/outdoor unit power
OFF 1 2 (SW8) Indoor unit power supplied from outdoor unit
YELLOW BLUE
L
BLUE YELLOW
supplies only) (initial setting) N
Set the SW8-3 to ON. BLACK
CN01
CN01
Indoor unit
* There are 3 types of labels (labels A, B and C). Affix the appropriate labels to the control board
S1
units according to the wiring method. S2
S3
1) Installing procedures
(1) Select an installing position for the remote controller. (Fig. 6-2)
30 30 The temperature sensors are located on both remote controller and indoor unit.
46 ► Procure the following parts locally:
83.5
8
6. Electrical work
9
6. Electrical work
Function table
Select unit number 00
Mode Settings Mode no. Setting no. Initial setting setting
Power failure automatic recovery Not available 1
01
Available w 2 Ο
Indoor temperature detecting Indoor unit operating average 1 Ο
Set by indoor unit’s remote controller 02 2
Remote controller’s internal sensor 3
LOSSNAY connectivity Not Supported 1 Ο
Supported (indoor unit is not equipped with outdoor-air intake) 03 2
Supported (indoor unit is equipped with outdoor-air intake) 3
Power voltage 240 V 1
04
220 V, 230 V 2 Ο
10
6. Electrical work
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode Settings Mode no. Setting no. Initial setting setting
Filter sign 100Hr 1
2500Hr 07 2 Ο
No filter sign indicator 3
Fan speed Silent 1
Standard 08 2 Ο
High ceiling 3
Up/down vane setting No vanes 1
Equipped with vanes (vanes angle setup 1) 11 2 Ο
Equipped with vanes (vanes angle setup 2) 3
w When the power supply returns, the air conditioner will start 3 minutes later.
7. Test run
7.1. Before test run
► After completing installation and the wiring and piping of the indoor and ► Do not carry out this test on the control wiring (low voltage circuit) termi-
outdoor units, check for refrigerant leakage, looseness in the power sup- nals.
ply or control wiring, wrong polarity, and no disconnection of one phase Warning:
in the supply. Do not use the air conditioner if the insulation resistance is less than 1.0 M .
► Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 M .