Lecture 6 Design and Detailing of Specia PDF
Lecture 6 Design and Detailing of Specia PDF
Design and Detailing of Special By: Kerrin Burgess
MSc, MIStructE, CEng
Reinforced Concrete Walls
Agenda
Kerrin Burgess (APESL & IStructE Workshop) 1
25/04/2018
Definition
Kerrin Burgess (APESL & IStructE Workshop) 2
25/04/2018
F
(h 100 ft)
Kerrin Burgess (APESL & IStructE Workshop) 3
25/04/2018
Dual Systems
Kerrin Burgess (APESL & IStructE Workshop) 4
25/04/2018
Slender walls tend to be have like flexural
cantilevers.
For slender coupled walls the target
mechanism is to have ductile yielding of
the coupling beams over the height plus
ductile flexural yielding at the base of the
walls.
Wall shear failure is to avoided as well as
failure of diaphragms and foundations .
Squat walls tend to resist lateral forces through a
diagonal struct mechanism
They have high inherent flexural strength and thus
are prone to inelastic response in shear rather
than flexural yielding
Squat walls are prone the two types of shear
failures that are to be avoided.
• Shear yielding where the web of the wall web
develops inclined cracks.
• Shear sliding tends to occur at construction
joints including the wall‐foundation interfaces
Kerrin Burgess (APESL & IStructE Workshop) 5
25/04/2018
Story Drift
Walls must be proportioned to satisfy the strength and story drift requirements of ASCE7.
Wall Positioning
• Walls should be well distributed within the
building plan, with multiple walls providing
resistance to story shears in each principle
direction
• Long diaphragm spans are to be avoided
Kerrin Burgess (APESL & IStructE Workshop) 6
25/04/2018
Vertical Irregularities
Irregularities can lead to stress concentrations and
localised drift that may be difficult to accommodate
in design. The following design is recommended
• Weak stories should be avoided
Wall
Foundations
• Spread footings may be adequate
for long walls supporting sufficient
gravity loads, as overturning
moments may be low
• For higher overturning demand,
piled foundations are recommend
• Outriggers can be used to spread
overturning demand over
foundations
• Foundations and their
connections are to remain elastic
and consideration of capacity of
vertical elements framing into the
foundation should be made
Kerrin Burgess (APESL & IStructE Workshop) 7
25/04/2018
Wall Configurations
Wall Segments
• Vertical wall segments are bounded horizontally by two openings or
by and opening and an edge
• Horizontal wall segments is bounded vertically by two openings or by
an opening and an edge
Kerrin Burgess (APESL & IStructE Workshop) 8
25/04/2018
Wall Piers – ACI 318 Definition
A wall pier as defined by ACI 318 is a vertical wall segment having ⁄ 6 and ⁄ 2
NB. ACI 318 requires special design provisions for wall piers
Modelling Considerations
1. Fixed base restraints are recommended for the determination of seismic forces
2. Cracked Section Stiffness – Wall are to be analysed using cracked and uncracked stiffnesses of
segments. e.g yielded segments can be modelled as cracked and non-yielded segments
uncracked
Kerrin Burgess (APESL & IStructE Workshop) 9
25/04/2018
Wall Reinforcement
Web Reinforcement
• Web reinforcement ratios (vertical reinforcement) and (horizontal reinforcement) must be at least
0.0025
• and are permitted to be reduced if shear force
• Reinforcing spacing in each direction is not to exceed 18 inches
• At least two curtains (layers) of reinforcement are required if 2
• If ⁄ 2 then is not to be less than the provided .
Kerrin Burgess (APESL & IStructE Workshop) 10
25/04/2018
Shear failure of slender walls can lead to rapid strength lost at drifts below anticipated design levels. This is
especially so for walls resisting high shear forces.
It is for these reasons a capacity approach is recommended in designing for shear resistance, where shear failure
is avoided altogether.
Kerrin Burgess (APESL & IStructE Workshop) 11
25/04/2018
Kerrin Burgess (APESL & IStructE Workshop) 12
25/04/2018
use 0.75
use 0.6
The nominal shear capacity of a vertical segment of a structural wall is given by:
Where:
The maximum allowable shear strength of all vertical segments resisting a common lateral force:
8
For an individual vertical segment: 10
Kerrin Burgess (APESL & IStructE Workshop) 13
25/04/2018
Shear friction capacity is applicable where shear is transferred across an interface of two concrete
volumes cast at different times, e.g. connection of wall to foundation.
The maximum permitted value of nominal shear friction strength is defined as follows:
Kerrin Burgess (APESL & IStructE Workshop) 14
25/04/2018
Design for Flexural and Axial Load involves the following steps
1. Preliminary Proportioning
4. Iterations to optimise the layout considering boundary element vertical and horizontal
reinforcement and section strength.
Where:
- tributary dead load and self weight
- location of center of gravity
- tension capacity of web reinforcement
(NB. You can initially assume As1 = 0.0025Acv)
- tension capacity of boundary reinforcement
0.4 - lever arm of web reinforcement
0.8 - lever arm of boundary reinforcement
Kerrin Burgess (APESL & IStructE Workshop) 15
25/04/2018
See example
attached
Boundary Elements
Where combined seismic and gravity loading results in
high compressive demands on the wall edge, ACI 318
requires special boundary elements
, 400
,
Kerrin Burgess (APESL & IStructE Workshop) 16
25/04/2018
Boundary Elements
u ACI 318 provides two methods for determining whether special
boundary elements are required. The preferred method applies to
walls or wall segments that are effectively continuous from the
base of the structure to the top of wall segment
Procedure:
3. If ⁄
a boundary element is required
Boundary Elements
PLACEMENT
Kerrin Burgess (APESL & IStructE Workshop) 17
25/04/2018
Boundary Elements
AT FOUNDATIONS
Boundary Elements
ALTERNATIVE METHOD FOR DETERMINING BOUNDARY ELEMENTS
The second method recommended by ACI 318 for boundary elements is
based on nominal compressive stress. It is preferred use for irregular or
discontinuous walls.
Procedure:
• For wall cross‐section determine nominal stress
⁄ ⁄ ⁄
• Special boundary elements are required if the nominal stress exceeds
0.2 .
• Once the stress falls below 0.2 An ordinary boundary element is
continued until the stress falls below 0.15 .
Kerrin Burgess (APESL & IStructE Workshop) 18
25/04/2018
Boundary Elements
CONFINEMENT REINFORCEMENT
Special boundary elements shall be provided with confinement
reinforcement (hoops and ties) meeting the following :
1. Area provided 0.9 ⁄
Where
s = spacing of transverse reinforcement
bc = dimension of confined core of the boundary element
measured out‐to‐out of the transverse reinforcement
Boundary Elements
CONFINEMENT REINFORCEMENT
Special boundary elements shall be provided with confinement
reinforcement (hoops and ties) meeting the following :
2. The spacing provided shall be the minimum of b/3; 6db; 4
in; 6 inches
3. The Horizontal web reinforcement shall extend to within 6
inches of the wall end and shall be anchored within the
confined core of the boundary element to develop the full
tensile strength of the reinforcement
Kerrin Burgess (APESL & IStructE Workshop) 19
25/04/2018
Wall Piers
Kerrin Burgess (APESL & IStructE Workshop) 20
25/04/2018
Wall Piers
Wall Piers
Kerrin Burgess (APESL & IStructE Workshop) 21
25/04/2018
Wall Piers
Coupling Beams
,
2. Coupling beams with ⁄ 2 and 4 -
these are required to be reinforced with two
intersecting groiuips of diagonally placed bars
symmetrically about the midspan.
Kerrin Burgess (APESL & IStructE Workshop) 22
25/04/2018
Kerrin Burgess (APESL & IStructE Workshop) 23
25/04/2018
Kerrin Burgess (APESL & IStructE Workshop) 24
25/04/2018
2 10
Where:
- Shear force determined from analysis
0.85
• Full-height confinement is required for the column over all stories beneath the discontinuous walls, if
axial force related to earthquake effects exceed ⁄10
• The confinement must extend upward into the discontinuous wall at least the development of the
longitudinal reinforcement
• If column terminates into a wall the confinement reinforcement must extend the same distance
downward into the wall below
• If it terminates into a footing or mat, extension 12 inches into the footing or mat is required,
• unless it terminates within one-half the footing depth from the edge of the footing, in which case it
must extend at least ld (calculated for fy) of the largest column reinforcement
Kerrin Burgess (APESL & IStructE Workshop) 25
25/04/2018
Other Requirements
• The specified compressive strength of the concrete fc’ shall not be less than 3000 psi (21 MPa) cylinder
strength
• Where high-strength concrete is used is restricted to an upper-bound of 100 psi (8.3 MPa) for any
calculation of shear strength or anchorage/development. This does not apply to beam-column joints
however.
• Deformed reinforcement resisting earthquake-induced flexural and axial forces in frame members must
confirm to specification ASTM A706.
• Alternatively ASTM A615 Grades 40 and 60 are permitted if
i. actual yield strength based on mill test does not exceed fy by more than 18000 psi (120 MPa)
ii. the ratio of actual tensile strength to actual yield strength is not less tan 1.25
iii. Minimum elongation in 8 inches is at least 14% for bar sizes No3 – No6, at least 12% for bar sizes
No7 to No11, and at least 10% for bar sizes No 14 and No 18.
Conclusion – Topic 6
Question
Kerrin Burgess (APESL & IStructE Workshop) 26