IPDS User Manual v1.8
IPDS User Manual v1.8
USER MANUAL
EE PD, 2001-2009
Version 1.8
January, 2009
1. Introduction
IPDS-27
IPDS-38
IPDS-07
IPDS-15
IPDS-05
Figure 1
Do not use IPDS at higher voltage than rated voltage marked on the sensor label!
2
Eaton Electrical Predictive Diagnostics IPDS User Manual V1.8
Figure 2
3
Eaton Electrical Predictive Diagnostics IPDS User Manual V1.8
Note:
1. If end user has requirement exceeding temperatures ratings listed above, rubber boots
and cables with extended ratings should be ordered separately.
2. Jumper cable type and rating have been chosen for mechanical and signal propagation
properties only. Jumper cables are not designated to provide electrical insulation and
proper distances between jumpers, ground and other HV parts should be maintained.
When adequate clearances are not possible it is the user’s responsibility to select a
suitable cable.
IPDS-XX has one 3/8” brass insert on its top and two inserts on its bottom. The top insert
is designated for High Voltage cable connection and two bottom inserts for IPDS mounting
to the bracket or to the ground plane directly. The third central insert at the bottom is for
printed circuit board connection and should not be used for mounting purpose.
Mounting inserts dimensions and spacing are the same for all IPDS sensors (Figures 3).
Figure 3
Printed circuit board with phase reference and protection circuitry is installed in the recess
on the bottom of the IPDS (Figure 4a). This circuitry is preinstalled and should not be
removed from IPDS.
Grounding brass strip is also preinstalled (Figure 4b.) and also should not be removed
from the IPDS.
4
Eaton Electrical Predictive Diagnostics IPDS User Manual V1.8
Reference and
protection
circuitry
Shield
a b
Secure coax cable
with the cable ties
c d
Figure 4
IPDS can be mounted on mounting bracket or directly to the ground surface (Figures 4c,
and 4d).
Secure signal coaxial cable to the bracket and route coax cable secure along ground
potential plane (Figures 4c, d). Do not use self sticking cable clips and mounting
bases to secure the cable if there is a danger of falling signal cable onto HV parts.
Always maintain clearance between signal cable and HV conductors!
Rule of thumb: maintain that distance same as IPDS height for given voltage class.
5
Eaton Electrical Predictive Diagnostics IPDS User Manual V1.8
Two types of mounting brackets used: one size for IPDS-05, 07, 15 and another for IPDS-
27 and IPDS-38 (Figure 5).
A B
IPDS-XX inch (mm) inch (mm)
IPDS-5
IPDS-7 6.65 (169) 5.65 (144)
IPDS-15
IPDS-27
IPDS-38 8.7 (221) 7.7 (196)
Ground connection:
d) Remove paint and clean the mounting surface to ensure good contact of the
mounting bracket or the brass ground strip to the ground
e) If contact of the mounting surface to the ground is of suspect, use additional low
inductance ground wire from IPDS mounting bracket to the ground bus or
grounded frame.
6
Eaton Electrical Predictive Diagnostics IPDS User Manual V1.8
HV connection:
b) The conductors must be routed ensuring proper clearances from the grounded
and HV parts, as required by appropriate standards covering the equipment
where the IPDS to be installed. HV jumpers must not touch ground or other
phase jumpers or conductors even if proper voltage class jumpers are used and
formally can touch each other without safety concerns. Touching jumpers can
create partial discharge that can be attributed to the monitored equipment. As a
rule of thumb the gap between a bare wire jumper and ground or another phase
conductor should be at least equal to the IPDS sensor height. For 27 and 38 kV
IPDS sensor minimum clearance distance is 8” when using supplied installation
kit. Use of appropriate barriers or insulated conductors may allow significant
reduction of such clearances but requires dielectric testing of the equipment
before returning to service.
c) The connections must be free of partial discharge and corona. Avoid sharp
edges on HV connections. If connections need to be taped, proper semi-
conductive and grading tapes should be applied to avoid local concentration of
electric stresses that can cause partial discharge.
Connect RG-58A coaxial cable to the terminals on the IPDS printed circuit board. Connect
central conductor to terminal X3 and shield to X4 (Figures 4a and b). Use ring crimp
terminals for both conductors. Be sure that bare wires of the cable shield are completely
isolated from central wire and from ground in place of installation. Use electrical tape if
necessary.
7
Eaton Electrical Predictive Diagnostics IPDS User Manual V1.8
IPDS-27 sensor on large steam turbine IPDS-15 sensors in the motor feeder
generator bus duct head compartment termination cabinet
a b
Figure 6
8
Eaton Electrical Predictive Diagnostics IPDS User Manual V1.8
IPDS-15 sensors mounted directly to High Voltage and ground bus bars
Figure 7
IPDS sensors connected to the main bus in IPDS sensors connected to the load side of
transition section of the switchgear line-up a breaker in a section of the switchgear line
a b
Figure 8