0% found this document useful (0 votes)
78 views85 pages

4010 Applications Manual Rev A

SIMPLEX

Uploaded by

Robel MT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views85 pages

4010 Applications Manual Rev A

SIMPLEX

Uploaded by

Robel MT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 85

4010 Fire Alarm

Applications Manual

574-908
Rev. A

Technical Manuals Online! - http://www.tech-man.com


Copyright and Trademarks Copyright  Simplex Time Recorder Co., 1999. All rights reserved.
Printed in the United States of America.
Information in this document is subject to change without notice. No part of this
document may be reproduced or transmitted in any form or by any means,
electronic or mechanical, for any purpose, without the express written consent of
Simplex Time Recorder Company.
Walk Test is protected by US Patent No. 4,725,818.
MAPNET addressable communications is protected by US Patent No.4,796,025.
IDNet is patent pending.
TrueAlarm Analog Detection is protected by US Patent No. 5,155,468.
TrueAlarm Detector Base is protected by US Patent No. 5,173, 683.

Cautions and Warnings SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To


ensure proper system operation, this product must be tested in accordance with
NFPA72-1996, Chapter 7 after any programming operation or change in site-
specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification, repair or adjustment
to system hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified.
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in the
installation, operating and programming manuals. These instructions must be
followed to avoid damage to the control panel and associated equipment. Fire
Alarm Control Panel (FACP) operation and reliability depend upon proper
installation.

DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS


DAMAGED. Upon unpacking your Simplex product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.

ELECTRICAL HAZARD - Disconnect electrical power when making any


internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.

RADIO FREQUENCY ENERGY - This equipment generates, uses, and can


radiate radio frequency energy and if not installed and used in accordance with
the instruction manual, may cause interference to radio communications. It has
been tested and found to comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference when operated in a commercial
environment. Operation of this equipment in a residential area may cause
interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.

Technical Manuals Online! - http://www.tech-man.com


Codes and Standards The 4010 is listed for the following.

UL 864 Listings for Type of System:

• UL 864 Power-Limited Fire Alarm Control Unit.

• Local (formerly NFPA 72A).


Requires the sounding of an alarm via listed notification appliance(s).

• Auxiliary (formerly NFPA 72B).


Requires 4010-9809 City Circuit Module.

• Remote Station - protected premise (formerly NFPA 72C).


Requires 4010-9809 City Circuit Module or the 4010-9810 or -9816 DACT.

• Proprietary - protected premise (formerly NFPA 72D).


Requires 4010-9817 (with 4010-9818 or 4010-9819) or 4010-9821 Network
Interface Modules.

• Central Station - protected premise (formerly NFPA 71).


Requires 4010-9810 or -9816 DACT.

• Suppression Releasing Service


Requires 4010-9814 Suppression Kit.

UL 864 Listings for Type of Service:

• Automatic, Manual, Waterflow, and Sprinkler Supervisory.

UL 864 Listings for Type of Signaling:

• Coded, Non-Coded, March-Time and DACT.


DACT requires the 4010-9810 or -9816.

Factory Mutual Approved

• Same as UL above.

Local Approvals

• CSFM
• MEA

Continued on next page

Technical Manuals Online! - http://www.tech-man.com


Codes and Standards The installer should be familiar with the relevant codes listed below as well as
(continued) any other applicable local codes and standards, when installing a fire alarm
system.

• NFPA 72 National Fire Alarm Code


• NFPA 11 Standard for Low-Expansion Foam and Combined Agent
Systems
• NFPA 11A Standard for Medium- and High-Expansion Foam Systems
• NFPA 12 Standard on Carbon Dioxide Extinguishing Systems
• NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems
• NFPA 13 Standard for the Installation of Sprinkler Systems
• NFPA 14 Standard for the Installation of Standpipe and Hose Systems
• NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection
• NFPA 16 Standard for the Installation of Deluge Foam-Water Sprinkler
and Foam-Water Spray Systems
• NFPA 16A Standard for the Installation of Closed-Head Foam-Water
Sprinkler Systems
• NFPA 17 Standard for Dry Chemical Extinguishing Systems
• NFPA 17A Standard for Wet Chemical Extinguishing Systems
• NFPA 25 Standard for Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems
• NFPA 70 National Electrical Code
• NFPA 80 Standard for Fire Doors and Fire Windows
• NFPA 90A Standard for the Installation of Air Conditioning and
Ventilation Systems
• NFPA 90B Standard for the Installation of Warm Air Heating and Air
Conditioning Systems
• NFPA 92A Recommended Practice for Smoke-Control Systems
• NFPA 92B Guide for Smoke Management Systems in Malls, Atria, and
Large Areas
• NFPA 101 Life Safety Code
• NFPA 170 Standard for Fire Safety Symbols
• NFPA 231C Standard for Rack Storage of Materials
• NFPA 1221 Standard on the Installation, Maintenance, and Use of Public
Fire Service Communication Systems

Technical Manuals Online! - http://www.tech-man.com


Table of Contents

Chapter 1. Overview
Overview................................................................................................... 1-1
Related Documentation............................................................................. 1-1
In this Chapter........................................................................................... 1-1

Before You Begin ......................................................................................... 1-2


Introduction............................................................................................... 1-2
Custom Control Capacities ....................................................................... 1-2
Understand the Details of the Intended Application ................................. 1-2
Understand the Built-in Functionality Provided by System Options and
Point Types ............................................................................................... 1-2

QuickAlert Class A / Class B Guidelines ..................................................... 1-3


Overview................................................................................................... 1-3
Class A QuickAlert ................................................................................... 1-3
Class B QuickAlert ................................................................................... 1-4

Chapter 2. Selective Signaling Applications


Overview................................................................................................... 2-1
In this Chapter........................................................................................... 2-1

Selective Signaling by Floor ......................................................................... 2-2


Overview................................................................................................... 2-2
Step 1. Define NAC’s Device Type, Point Type, and Custom Label ...... 2-2
Step 2. Assign Device Types, Point Types, and Custom Labels to
Initiating Devices ........................................................................ 2-3
Step 3. Add Appropriate NACs to List L6 (Off On Silence) ................... 2-3
Step 4: Add Appropriate NACs to List L7 (Off on Reset)....................... 2-4
Step 5. Add Floor’s Initiating Devices to a User-Defined List ................ 2-4
Step 6. Add Custom Control Equations ................................................... 2-4

Selective Signaling by Area.......................................................................... 2-7


Overview................................................................................................... 2-7
Step 1. Define NAC’s Device Types / Point Types / Custom Labels ...... 2-7
Step 2. Assign Device Types, Point Types, and Custom Labels to
Initiating Devices ........................................................................ 2-8
Step 3. Add Appropriate NACs to List L6 (Off On Silence) ................... 2-8
Step 4: Add Appropriate NACs to List L7 (Off On Reset)...................... 2-9
Step 5. Add Area’s Initiating Devices to a User-Defined List ................. 2-9
Step 6. Add Custom Control Equations ................................................... 2-9

Selective Signaling by Fire Floor, Floor Above, and Floor Below............. 2-12
Overview................................................................................................. 2-12
Step 1. Define NAC’s Device Types / Point Types / Custom Label...... 2-12
Step 2. Define Device Types, Point Types, and Custom Labels for
Initiating Devices ...................................................................... 2-13
Step 3. Add Appropriate NACs to List L6 (Off On Silence) ................. 2-13
Step 4: Add Appropriate NACs to List L7 (Off On Reset).................... 2-14
Step 5. Add Each Floor’s Initiating Devices to a User-Defined List .... 2-14
Step 6. Add NACs to User-Defined Lists ............................................. 2-14
Step 7. Add Custom Control Equations ................................................. 2-14

Selective Bypass of NAC/Relay Circuits.................................................... 2-17


Overview................................................................................................. 2-17
Step 1. Define Switch Attributes............................................................ 2-17
v

Technical Manuals Online! - http://www.tech-man.com


Step 2. Define Digital Pseudo Point Attributes...................................... 2-18
Step 3. Add the Floor’s Initiating Devices to a List............................... 2-18
Step 4. Change the Point Type of NACs and Door Relays.................... 2-18
Step 5. Add the NACs and Door Relays to a List .................................. 2-18
Step 6. Add Appropriate NACs to List L6 (Off On Silence) ................. 2-18
Step 7. Add Appropriate NACs to List L7 (Off On Reset) .................... 2-19
Step 8. Add Custom Control Equations ................................................. 2-19

Selective Activation of Single Station Devices........................................... 2-21


Introduction............................................................................................. 2-21
Step 1. Define Device Types, Point Types, and Mode for Single Station
Devices ...................................................................................... 2-21
Step 2. Add Area’s Pull Stations to a User-Defined List ....................... 2-21
Step 3. Add Custom Control Equations ................................................. 2-21

Chapter 3. Suppression Release


Overview................................................................................................... 3-1
In this Chapter........................................................................................... 3-1

Default Suppression Release Applications ................................................... 3-2


Suppression Release Triggered by Single Pull Station or Automatic
Initiating Device .......................................................................... 3-2
Suppression Release Triggered by Dual Automatic Initiating Devices .... 3-2
Programming Default Applications .......................................................... 3-3

Dual Detector, Pre-Signal, and Abort Switch with No Delay....................... 3-5


Introduction............................................................................................... 3-5
Programming System Options, Point Types, and Lists............................. 3-6
Programming Custom Control .................................................................. 3-7

Dual Detector, Pre-Signal, and Abort Switch with Delay............................. 3-8


Introduction............................................................................................... 3-8
Define Lists, Digital Pseudos, and Analog Pseudos ................................. 3-9
Program Custom Control Equations ....................................................... 3-10

Chapter 4. Additional Applications


Overview................................................................................................... 4-1
In this Chapter........................................................................................... 4-1

Pre-Signal Operation..................................................................................... 4-2


Overview................................................................................................... 4-2
Step 1. Define NAC’s Device Type, Point Type, and Custom Label ...... 4-2
Step 2. Define Device Types, Point Types, and Custom Labels for
Initiating Devices ........................................................................ 4-3
Step 3. Add Initiating Devices and NACs to User-Defined Lists ............ 4-3
Step 4. Add Appropriate NACs to List L6 (Off On Silence) ................... 4-3
Step 5. Add Appropriate NACs to List L7 (Off On Reset) ...................... 4-3
Step 6. Add Custom Control Equations ................................................... 4-4

Programming a Utility Monitoring Point...................................................... 4-6


Overview................................................................................................... 4-6
Step 1. Change the Heat Detector’s Point Type and Custom Label......... 4-6
Step 2. Change the AUX Relay Point’s Point Type and Custom Label... 4-6
Step 3. Define a Supervisory Digital Pseudo Point.................................. 4-6
Step 4. Program Custom Control Equations ............................................ 4-6

Day / Night Programming............................................................................. 4-8


Overview................................................................................................... 4-8
Step 1. Program the Monitor Device’s Point Type, Device Type, and
Custom Label .............................................................................. 4-8
vi

Technical Manuals Online! - http://www.tech-man.com


Step 2. Program Custom Control Equations ............................................ 4-8

AHJ City Reset ........................................................................................... 4-11


Overview................................................................................................. 4-11
Program Custom Control Equations ....................................................... 4-11

Elevator Recall............................................................................................ 4-12


Overview................................................................................................. 4-12
Step 1. Add Primary Floor Initiating Devices to a User-Defined List ... 4-12
Step 2. Add Alternate Floor Initiating Devices to a User-Defined List 4-12
Step 3. Add Custom Labels to AUX Relays .......................................... 4-12
Step 4. Add Custom Control Equations ................................................. 4-12

Selective City Circuit Activation ................................................................ 4-14


Overview................................................................................................. 4-14
Step 1. Create a User-Defined List of City Circuit Alarm Points .......... 4-14
Step 2. Create Custom Control Equations.............................................. 4-14

General Alarm Shutdown for Fans and Dampers ....................................... 4-15


Overview................................................................................................. 4-15
Example: Fan / Damper Shutdown for a Four Story Building............... 4-15
Step 1. Program Point Type and Custom Labels for Fan Relays ........... 4-15
Step 2. Program Point Types and Custom Labels for Damper Monitor
Switches and Relays .................................................................. 4-15
Step 3. Custom Control Equations ......................................................... 4-16

Appendix A. System Options and Point Types


Introduction.............................................................................................. A-1
In this Chapter.......................................................................................... A-1

System Options ............................................................................................ A-2


System Options ........................................................................................ A-2

Point Types .................................................................................................. A-4


Introduction.............................................................................................. A-4
AHUF ...................................................................................................... A-4
AHUO...................................................................................................... A-4
AHUR ...................................................................................................... A-5
ALTERN.................................................................................................. A-5
BSIGNAL ................................................................................................ A-5
DHOLDER .............................................................................................. A-6
PRIMARY ............................................................................................... A-6
QALERT.................................................................................................. A-6
SQALERT ............................................................................................... A-6
RELAY .................................................................................................... A-6
RSIGNAL ................................................................................................ A-7
RVISUAL ................................................................................................ A-7
RWATER................................................................................................. A-7
SIGNAL................................................................................................... A-8
SSIGNAL................................................................................................. A-8
SUPREL................................................................................................... A-8
SUPV ....................................................................................................... A-8
SVISUAL................................................................................................. A-9
SWATER ................................................................................................. A-9
TSIGNAL ................................................................................................ A-9
BRELAY ............................................................................................... A-10
RRELAY ............................................................................................... A-10
FIRE....................................................................................................... A-10
WATER ................................................................................................. A-10
DUCT .................................................................................................... A-11
HEAT..................................................................................................... A-11
vii

Technical Manuals Online! - http://www.tech-man.com


FLAME.................................................................................................. A-11
PULL ..................................................................................................... A-11
SMOKE ................................................................................................. A-11
EMERG ................................................................................................. A-12
SFIRE .................................................................................................... A-12
VFIRE.................................................................................................... A-12
SPULL ................................................................................................... A-12
VSPULL ................................................................................................ A-12
GENMON.............................................................................................. A-13
SGENMON............................................................................................ A-13
FPUMP .................................................................................................. A-13
SFPUMP ................................................................................................ A-13
S2STAGE .............................................................................................. A-13
SO .......................................................................................................... A-14
WSO ...................................................................................................... A-14
SUPDET ................................................................................................ A-14
SUPABRT ............................................................................................. A-14
SUPDUMP ............................................................................................ A-14
SUPPRES .............................................................................................. A-15
SUPV ..................................................................................................... A-15
UTIL ...................................................................................................... A-15
TROUBLE ............................................................................................. A-15
VSMOKE............................................................................................... A-15
GVMON ................................................................................................ A-16
LATSUPV ............................................................................................. A-16
STYLEC ................................................................................................ A-16
SDUCT .................................................................................................. A-16
ABORT.................................................................................................. A-16
DAMPER............................................................................................... A-16
4009A .................................................................................................... A-17
USWITCH ............................................................................................. A-17
OSWITCH ............................................................................................. A-17
SSWITCH.............................................................................................. A-17
TSWITCH.............................................................................................. A-17

Index ........................................................................................................... IN-1

viii

Technical Manuals Online! - http://www.tech-man.com


Chapter 1
Overview

Overview This document addresses the following:

• It provides programming examples for common 4010 system applications.

• It describes the specifications, limitations, and capacities of the 4010’s


Custom Control system. Although the 4010 will meet a wide range of
project requirements, 4020 or 4100 systems are best used in more complex
situations where the listed capacities of the 4010 are approached.

• It provides reference information concerning the 4010’s system options and


point types. In many cases, the built-in application programming provided
by these system components can be used in place of Custom Control.

Related Documentation Additional information related to 4010 Version 2.x can be found in the
following documents:

574-052 ....... 4010 Installation, Operation, and Front Panel Programming


Instructions
574-779 ....... 4010 SFIO Programmed IC Installation Instructions
574-499 ....... 4010 SFIO Board Installation Instructions
574-181 ....... 4009 IDNet NAC Extender Installation Instructions
574-182 ....... 4009 Fiber Optic Link Option Installation Instructions
574-325 ....... 4009-9807 NAC Option Card Installation Instructions
574-326 ....... 4009-9808 NAC Class A Adapter Option Card Installation
Instructions

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Before You Begin 1-2
QuickAlert Class A / Class B Guidelines 1-3

1-1

Technical Manuals Online! - http://www.tech-man.com


Before You Begin

Introduction The 4010 is best used in small to medium size buildings up to 6 stories. Some
of the best uses for the 4010 are:

• K - 12 educational facilities
• Nursing homes and small hospitals
• Board and care facilities
• Inns, motels and small hotels
• Assisted living
• Apartments and condominiums
• Office buildings
• Strip malls

Even in these situations, however, job-specific details (a large number of fan


dampers, for example) combined with complex, job-specific application needs
may push the 4010 beyond its practical limits. Before beginning, therefore, it is
important to know the 4010’s Custom Control capacities, understand the
installation details of the facility, and understand the role of the 4010’s point
types and system options.

Custom Control Capacities The 4010 programming capacities are as follows:

• Up to 75 User Pseudo Points (P76 – P150)


• Up to 25 User List Points (L26 – L50)
• Up to 60 Custom Control Equations (Phase 2 systems)
• Up to 40 Custom Control Equations (Phase 1 systems)

Understand the Details of the Judging whether the 4010 can meet the application requirements of a job
Intended Application requires a detailed understanding of the facilities’ devices (both fire and utility),
as well as an understanding of exactly how the customer and the AHJ expect the
system to function.

In general, the following guidelines can help you determine whether the 4010
can handle the application-specific needs of a facility.

• Situations requiring extensive fan/damper control (i.e., multiple smoke


chambers and a very large number of dampers) are not good candidates for
the 4010.

Understand the Built-in The 4010 System Options, Point Types, and Modes provide default fire alarm
Functionality Provided by system operation for common fire alarm system applications without the need
System Options and Point for writing more complex Custom Control programming equations. Whenever
Types possible System Options, Point Types, and Modes should be used in lieu of
Custom Control to provide the required operation. Custom Control
programming is available to provide additional flexibility and to meet job-
specific requirements.

Refer to Appendix A for a summary of system options and point types.

1-2

Technical Manuals Online! - http://www.tech-man.com


QuickAlert Class A / Class B Guidelines

Overview The term QuickAlert with SmartSync operation refers to a family of Simplex
A/V and VO notification appliances that allow both horns and the synchronized
strobes to work independently on a two-wire notification appliance circuit. The
strobes operate in an “On until Reset” mode and the horns operate in an “On
until Silence” mode. All references to QuickAlert in this document are in
regards to QuickAlert with SmartSync operation.

When programming QuickAlert with SmartSync operation, you must be aware


of the following requirements and differences between Class A and Class B
applications.

Class A QuickAlert Class A QuickAlert with SmartSync operation depends on the following:

• All strobes must be Simplex synchronized VO, not free run. All A/Vs,
must be QuickAlert SmartSync compatible. Other manufacturer’s
appliances are not compatible on a SmartSync, two-wire circuit.

• A 4905-9938 SmartSync Control Module (SCM) is required for all


Class A QuickAlert Applications. The SCM must be mounted within
20 feet of the control panel and all wiring must be in metal conduit.
Refer to 4010 Field Wiring Drawings (841-058) and the 4905-9938
QuickAlert Sync Control Module Installation Instructions (574-719)
for specific installation instructions. (Note: 4010-9806 Class A
Adapter module is not required for Class A QuickAlert.)

• Each SCM requires a Notification Appliance Circuit designated as the


loading circuit. This circuit handles all power consumption of the VO
and A/V appliances connected to the NAC output of the SCM.

• For Multi-sync operation, one Notification Appliance Circuit must also


be designated as the Horn Control Notification Appliance Circuit. This
allows for the interconnection of multiple SCM’s configured in a
Master/Slave configuration to synchronize the QuickAlert devices.

• In the 4010 panel, for QuickAlert with Multi-sync applications, there


would only be three circuits available for the “loading” Notification
Appliance Circuits and one available for the “Horn Control”
Notification Appliance Circuit. (4009 IDNet can be added if
additional signals are required.)

• For a General Alarm operation, the “loading” NAC must use a point
type of RSIGNAL (Off on Reset) while the “Horn Control” NAC must
use a point type of SSIGNAL (Off on Silence).

• QuickAlert Horn operation (Slow March Time, Steady or Temporal) is


set by a dip switch on the SCM.

Continued on next page

1-3

Technical Manuals Online! - http://www.tech-man.com


QuickAlert Class A / Class B Guidelines, Continued

Class B QuickAlert Class B QuickAlert with SmartSync operation depends on the following factors:

• All strobes must be Simplex synchronized VO, not free run. All
A/V’s, must be QuickAlert SmartSync compatible. Other
manufacturer’s appliances are not compatible on a QuickAlert
SmartSync two-wire circuit.

• The QuickAlert with SmartSync notification appliance circuits connect


directly to the 4010 notification appliance circuits terminals. The
4905-9938 SmartSync Control Module is not required.

• For General Alarm operation, the point type SQALERT must be


utilized, which will provide the QuickAlert Horns to be controlled “Off
on Silence” and the Visuals to be controlled “Off on Reset.” For any
selective signal operation, the point type QALERT (no default
operation) must be utilized and all operations must programmed in
Custom Control.

• QuickAlert Horn operation (Slow March Time, Steady or Temporal) is


selected in the System Options, Signal Operation, under QuickAlert
Horn.

Blank Page

1-4

Technical Manuals Online! - http://www.tech-man.com


Chapter 2
Selective Signaling Applications

Overview Selective signaling replaces the system’s general alarm NAC operation – which
activates all NACs in response to any alarm condition – with selective NAC
control. This type of control allows you to program the system so that only
specific NACs respond to specific initiating devices.

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #

Selective Signaling by Floor 2-2


Selective Signaling by Area 2-7
Selective Signaling by Fire Floor, Floor Above, and 2-12
Floor Below
Selective Bypass of NAC/Relay Circuits 2-17
Selective Activation of Single Station Devices 2-21

2-1

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Floor

Overview Selective Signaling by Floor limits the activation of NACs to the floor on which
an activated initiating device(s) is located. When activated, audible NAC
appliances sound a temporal code until Alarm Silence, and visible NAC
appliances flash until System Reset.

In Figure 2-1, for example, an activated initiating device on Floor 2 triggers only
the NACs located on Floor 2.

Figure 2-1. Selective Signaling by Floor

Step 1. Define NAC’s Device The NACs used with the Selective Signaling by Floor application can be either
Type, Point Type, and Custom the NACs located on the panel’s SFIO board or NACs located on a 4009 IDNet
Label NAC Extender.

Use the PC Programmer to program the NACs with the device types and point
types listed in Table 2-1. When defining custom labels make sure to use
descriptive labels, such as “Floor1-Visual-Circuit.”

If necessary, refer to Chapter 7, Programming Points, of the 4010 PC


Programmer Installation and Programming Instructions (574-187) for
information on using the PC Programmer to edit a point’s device type, point
type, and custom label.

For QuickAlert applications, refer to “QuickAlert Class A / Class B Guidelines”


in Chapter 1.

Continued on next page

2-2

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Floor, Continued

Step 1. Define NAC’s Device


Type, Point Type, and Custom Table 2-1. NAC Device Types and Point Types
Label (continued)
Option Explanation
Use for standard (non-QuickAlert)
Class A NAC. This type of NAC contains
multiple signal paths, allowing circuit
operation to continue if a single open
SIGA circuit occurs. This device type requires
installation of a Class A NAC adapter
NAC card. Important Note: Do not use this
Device device type for Class A QuickAlert
Type applications.
Use for the following:
- Standard (non-QuickAlert) Class B
SIGB NAC.
- QuickAlert Class B NAC.
- QuickAlert Class A NAC.

Use only for Class B QuickAlert NACs.


This point type allows you to control
QALERT
Class B QuickAlert appliances with
Custom Control (selective signaling).
NAC Use for either of the following:
Point
Type - Standard, non-QuickAlert (Class A or
B) NAC appliances requiring Custom
SIGNAL
Control (selective signaling).
- Class A QuickAlert devices requiring
Custom Control (selective signaling).

Step 2. Assign Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels to Initiating Devices Programmer Installation and Programming Instructions, for information on
programming an initiating device’s device type and point type. Refer to “Point
Types” in Appendix A of this manual for detailed descriptions of the initiating
device point types.

Step 3. Add Appropriate Skip this step if you are using Class B QuickAlert NACs. Use the PC
NACs to List L6 (Off On Programmer’s List Tab to add the following to List L6 (Control Points, Off on
Silence) Silence). Members of this list automatically turn off when an Alarm Silence is
performed.

• Standard (non-QuickAlert) Audible NACs.


• NAC used for horn control input to SCM (Class A QuickAlert applications
only).

Continued on next page

2-3

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Floor, Continued

Step 4: Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off on Reset) Points Off on Reset). Members of this list automatically turn off when a System
Reset is performed.

• Standard (non-QuickAlert) Visible NACs.


• Class B QuickAlert NACs.
• The Class A QuickAlert NACs wired to the “NAC IN” input of the SCM.
Note: Assign the Class A QuickAlert Horn Control NAC to List L6, as
described in “Step 3. Add Appropriate NACs to List L6 (Off on Silence)”
above.

Step 5. Add Floor’s Initiating Adding each floor’s initiating devices to a separate user-defined list limits the
Devices to a User-Defined List number of Custom Control equations that must be written to perform Selective
Signaling by Floor. To add these devices to a list, use the PC Programmer’s List
Tab, adding each floor’s initiating devices to one of the available user-defined
lists (L26 through L50).

Step 6. Add Custom Control This section describes programming the Selective Signaling by Floor application
Equations using either standard NAC appliances or Class A/Class B QuickAlert NAC
applicances. Refer to the applicable section below for specific information.

Standard NAC Example. The following example, shown in Figure 2-2,


illustrates how to implement Selective Signaling by Floor using standard NAC
appliances.

• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Floor 1.

The first output statement programs the floor’s audible NACs to emit a
temporal signal when any point within list L26 enters an ALARM
condition. Because the audible NACs were added to the Control Points –
Off on Silence list, they stop sounding when an Alarm Silence occurs.

The second output statement programs the floor’s visible NACs to activate
when any point within list L26 enters an ALARM condition. Because the
visible NACs were added to the Control Points – Off on Reset list (L7),
they stop flashing when a System Reset occurs.

• Equation 2. The input side of this equation monitors the FIRE DETECT
state of list L27, which is a user-defined list containing all initiating devices
for Floor 2.

The first output statement programs the floor’s audible NACs to emit a
temporal signal when any point within list L27 enters an ALARM
condition. Because the audible NACs were added to the Control Points –
Off on Silence list, they stop sounding when an Alarm Silence occurs.

The second output statement programs the floor’s visible NACs to activate
when any point within list L27 enters an ALARM condition. Because the
visible NACs were added to the Control Points – Off on Reset list (L7),
they stop flashing when a System Reset occurs.

Continued on next page


2-4

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Floor, Continued

Step 6. Add Custom Control


Equations (continued)

Equation 1

Equation 2

Figure 2-2. Selective Signaling by Floor, Standard NACs

QuickAlert Class A / Class B NAC Example. The following example,


shown in Figure 2-3, illustrates how to implement Selective Signaling by Floor
using Class A or Class B QuickAlert NAC appliances.

• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Floor 1. The output side of Equation 1 programs the floor’s QuickAlert
NACs to operate when any point within list L26 enters an ALARM
condition.

Important Note: Use HOLD ON for Class A QuickAlert applications;


use HOLD TEMPORAL for Class B QuickAlert applications.

• Equation 2. The input side of this equation monitors the FIRE DETECT
state of list L27, which is a user-defined list containing all initiating devices
for Floor 2. The output side of Equation 2 programs the floor’s QuickAlert
NACs to operate when any point within list L27 enters an ALARM
condition.

Important Note: Use HOLD ON for Class A QuickAlert devices; use


HOLD TEMPORAL for Class B QuickAlert devices.

• Equation 3. The input side of Equation 3 monitors the ON state of P26,


which is the Alarm Silence Activated system pseudo point. The first output
statement in this equation turns the QuickAlert horns OFF (using the Horn
OFF opcode) when P26 is ON (i.e., following an Alarm Silence). The
second output statement in this equation resets P26 to its OFF state.

Important Notes:

- The HORN OFF opcode is used for Class B QuickAlert applications.


This equation is not required for Class A QuickAlert applications.
- Resetting P26 is very important; do not leave this out.

Continued on next page

2-5

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Floor, Continued

Step 6. Add Custom Control


Equations (continued)

Equation 1 Note: Use


HOLD
TEMPORAL
for Class B.

Equation 2 Use HOLD


ON for
Class A

Equation 3

Figure 2-3. Selective Signaling by Floor, QuickAlert NACs

2-6

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Area

Overview Selective Signaling by Area limits the activation of NACs to the area in which
the activated initiating device (smoke detector, pull station, etc.) is located. In
the following figure, for example, the initiating devices in Area 1 trigger only
the NACs located in Area 1, the initiating devices in Area 2 activate only the
NACs located in Area 2, etc.

AREA 1 AREA 2

AREA 3 AREA 4

Figure 2-4. Selective Signaling by Area

Step 1. Define NAC’s Device The NACs used with the Selective Signaling by Area application can be either
Types / Point Types / Custom the NACs located on the panel’s SFIO board or the NACs located on a 4009
Labels IDNet NAC extender.

Use the PC Programmer to program the NACs with the following device types
and point types. When defining custom labels, make sure to use descriptive
labels, such as “AREA1-VISUAL-CIRCUIT.”

For QuickAlert applications, refer to “QuickAlert Class A / Class B Guidelines”


in Chapter 1.

Continued on next page

2-7

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Area, Continued

Step 1. Define NAC’s Device


Types / Point Types / Custom Table 2-2. NAC Device Types and Point Types
Labels (continued)
Option Explanation
Use for standard (non-QuickAlert)
Class A NAC. This type of NAC contains
multiple signal paths, allowing circuit
operation to continue if a single open
SIGA circuit occurs. This device type requires
installation of a Class A NAC adapter
NAC card. Important Note: Do not use this
Device device type for Class A QuickAlert
Type applications.
Use for the following:
- Standard (non-QuickAlert) Class B
SIGB NAC.
- QuickAlert Class B NAC.
- QuickAlert Class A NAC.

Use only for Class B QuickAlert NACs.


This point type allows you to control
QALERT
Class B QuickAlert appliances with
Custom Control (selective signaling).
NAC Use for either of the following:
Point
Type - Standard, non-QuickAlert (Class A or
B) NAC appliances requiring Custom
SIGNAL
Control (selective signaling).
- Class A QuickAlert devices requiring
Custom Control (selective signaling).

Step 2. Assign Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels to Initiating Devices Programmer Installation and Programming Instructions, for information on
programming an initiating device’s device type and point type. Refer to “Point
Types” in Appendix A of this manual for detailed descriptions of the initiating
device point types.

Step 3. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.

• Standard (non-QuickAlert) Audible NACs.


• NAC used for horn control input to SCM. (Class A QuickAlert applications
only).

Continued on next page

2-8

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Area, Continued

Step 4: Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.

• Standard (non-QuickAlert) Visible NACs.


• Class B QuickAlert NACs.
• The Class A QuickAlert NACs wired to the “NAC IN” input of the SCM.
Note: Assign the Class A QuickAlert Horn Control NAC to List L6, as
described in “Step 3. Add Appropriate NACs to List L6 (Off on Silence)”
above.

Step 5. Add Area’s Initiating Adding the area’s initiating devices to a list limits the number of Custom
Devices to a User-Defined List Control equations that must be written to perform Selective Signaling by Area.
To add these devices to a list, use the PC Programmer’s List Tab, adding each of
the area’s initiating device to one of the available user-defined lists (L26 through
L50). Naming a list (AREA1-INITIATING DEVICES, for example) is done via
the Card Tab and cannot be done through the List Tab.

Step 6. Add Custom Control This section describes programming the Selective Signaling by Area application
Equations using either standard NAC appliances or Class A/Class B QuickAlert NAC
applicances. Refer to the applicable section below for specific information.

Standard NAC Example. The following example, shown in Figure 2-5,


illustrates how to implement Selective Signaling by Area using standard NAC
appliances. The example uses two areas.

• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Area 1.

The first output statement in Equation 1 programs Area 1’s audible NACs
to sound a temporal signal when any point within list L26 enters an
ALARM condition. Because the audible NACs were added to the Control
Points – Off on Silence list, they stop sounding when an Alarm Silence
occurs.

The second output statement in Equation 1 programs the visible NACs to


flash when any point within L26 enters an ALARM condition. Because the
visible NACs were added to the Control Points – Off on Reset list (Step 4
above), they stop flashing when a System Reset is performed.

• Equation 2. The input side of this equation monitors the FIRE DETECT
state of list L27, which is a user-defined list containing all initiating devices
for Area 2.

The first output statement in Equation 2 programs Area 2’s audible NACs
to sound a temporal signal when any point within list L27 enters an
ALARM condition. Because the audible NACs were added to the Control
Points – Off on Silence (Step 3 above), they stop sounding when an Alarm
Silence occurs.

Continued on next page

2-9

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Area, Continued

Step 6. Add Custom Control The second output statement in Equation 2 programs the visible NACs to flash
Equations (continued) when any point within L27 enters an ALARM condition. Because the visible
NACs were added to the Control Points – Off on Reset list (Step 4 above), they
stop flashing when a System Reset occurs.

Equation 1

Equation 2

Figure 2-5. Selective Signaling by Area, Standard NACs

QuickAlert Class A/Class B NAC Example. The following example,


shown in Figure 2-6, illustrates how to implement Selective Signaling by Area
for a building that uses QuickAlert notification appliances. Only a single area is
shown in the example. To program selective NAC control for additional areas,
copy these equations, substituting another area’s initiating devices and NAC
appliances.

• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Area 1.

The output side of Equation 1 programs the Area’s QuickAlert NACs to


operate when any point within list L26 enters an ALARM condition.

Important Note: Use HOLD ON for Class A QuickAlert applications;


use HOLD TEMPORAL for Class B QuickAlert applications.

• Equation 2. The input side of Equation 2 monitors the ON state of P26,


which is the Alarm Silence Activated system pseudo point.

The first output statement in this equation turns the QuickAlert horns OFF
(using the Horn OFF opcode) when P26 is ON (i.e., following an Alarm
Silence).

The second output statement in this equation resets the P26 pseudo point to
its OFF state.

Note: Resetting P26 is very important; do not leave this out.

Continued on next page

2-10

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Area, Continued

Step 6. Add Custom Control


Equations (continued)

Note: Use
HOLD
Equation 1 TEMPORAL
for Class B.

Use HOLD
ON for
Class A

Equation 2

Figure 2-6. Selective Signaling by Area, QuickAlert NACs

2-11

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Fire Floor, Floor Above, and Floor Below

Overview This application limits the activation of NACs to the floor on which the
activated initiating device is located, referred to as the fire floor, and the floors
immediately above and below the fire floor.

In the figure above, an activated smoke detector or pull station on Floor 3


activates the NACs on Floors 2, 3, and 4.

Step 1. Define NAC’s Device The NACs used with this application can be either the NACs located on the
Types / Point Types / Custom panel’s SFIO board or the NACs located on a 4009 IDNet NAC extender.
Label
Use the PC Programmer to program the NACs with the following device types
and point types. When defining custom labels, make sure to use descriptive
labels, such as “FLOOR-1 AUDIBLE NACS.”

For QuickAlert applications, refer to “QuickAlert Class A / Class B Guidelines”


in Chapter 1.

Continued on next page

2-12

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Fire Floor, Floor Above, and Floor Below,
Continued

Step 1. Define NAC’s Device Table 2-3. NAC Device Types and Point Types
Types / Point Types / Custom
Label (continued) Option Explanation
Use for standard (non-QuickAlert)
Class A NAC. This type of NAC contains
multiple signal paths, allowing circuit
operation to continue if a single open
SIGA circuit occurs. This device type requires
installation of a Class A NAC adapter
NAC card. Important Note: Do not use this
Device device type for Class A QuickAlert
Type applications.
Use for the following:
- Standard (non-QuickAlert) Class B
SIGB NAC.
- QuickAlert Class B NAC.
- QuickAlert Class A NAC.

Use only for Class B QuickAlert NACs.


This point type allows you to control
QALERT
Class B QuickAlert appliances with
Custom Control (selective signaling).
NAC Use for either of the following:
Point
Type - Standard, non-QuickAlert (Class A or
B) NAC appliances requiring Custom
SIGNAL
Control (selective signaling).
- Class A QuickAlert devices requiring
Custom Control (selective signaling).

Step 2. Define Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels for Initiating Devices Programmer Installation and Programming Instructions, for information on
programming an initiating device’s device type and point type. Refer to “Point
Types” in Appendix A of this manual for detailed descriptions of the initiating
device point types.

Step 3. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.

• Standard (non-QuickAlert) Audible NACs.


• NAC used for horn control input to SCM. (Class A QuickAlert applications
only).

Continued on next page

2-13

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Fire Floor, Floor Above, and Floor Below,
Continued

Step 4: Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.

• Standard (non-QuickAlert) Visible NACs.


• Class B QuickAlert NACs.
• The Class A QuickAlert NACs wired to the “NAC IN” input of the SCM.
Note: Assign the Class A QuickAlert Horn Control NAC to List L6, as
described in “Step 3. Add Appropriate NACs to List L6 (Off on Silence)”
above.

Step 5. Add Each Floor’s Adding each floor’s initiating devices to a separate list limits the number of
Initiating Devices to a Custom Control equations required to implement this application. To add a
User-Defined List floor’s initiating devices to a list, use the PC Programmer’s List Tab, adding
each floor’s initiating device to a separate user-defined list (L26 through L50).

Step 6. Add NACs to For a multi-story facility containing a large number of NAC circuits, add each
User-Defined Lists floor’s NACs to a separate user-defined list. Doing this limits the number of
Custom Control equations required to implement this application. To add a
floor’s NACs to a list, use the PC Programmer’s List Tab, adding each floor’s
NACs to a separate user-defined list (L26 through L50).

Step 7. Add Custom Control This section describes programming the Selective Signaling by Fire Floor
Equations application using either standard NAC appliances or Class A/Class B
QuickAlert NAC applicances. Refer to the applicable section below for specific
information.

Standard NAC Example. The following example, shown in Figure 2-7,


illustrates how to implement this application for a four-story building that uses
standard NAC appliances.

Each of the four equations functions in the same manner. The input side
monitors a list of initiating devices for the floor. If any point within the list goes
into ALARM, the output side activates the NACs for the appropriate set of
floors.

Continued on next page

2-14

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Fire Floor, Floor Above, and Floor Below,
Continued

Step 7. Add Custom Control


Equations (continued)

Equation 1

Equation 2

Equation 3

Equation 4

Figure 2-7. Fire Floor, Floor Above, and Below with Standard NACs

Continued on next page

2-15

Technical Manuals Online! - http://www.tech-man.com


Selective Signaling by Fire Floor, Floor Above, and Floor Below,
Continued

Step 7. Add Custom Control QuickAlert Class A / Class B NAC Example. The following example,
Equations (continued) shown in Figure 2-8, illustrates how to implement this application for a four-
story building that uses QuickAlert NAC appliances.

The first four equations monitor the state of each floor’s initiating devices. The
output side of each equation activates the appropriate list of NACs as required.
Important Note: Use HOLD ON for Class A QuickAlert devices; use HOLD
TEMPORAL for Class B QuickAlert devices.

The last equation monitors the state of P26, the Alarm Silence Activated pseudo
point. If this point is ON (i.e., following an Alarm Silence), the output executes,
issuing the HORN OFF command to silence all audible QuickAlert NAC
appliances. HORN OFF opcode is only required for Class B QuickAlert NAC
applications. This equation is not required for Class A QuickAlert NAC
applications. Important Note: You cannot associate a list containing NACs
with the Horn OFF command, you must associate specific NACs with the
command.

The last output statement at the bottom of the sample screen resets the P26
pseudo point to its OFF state. Note: Resetting P26 is very important.

Note: Use
HOLD
TEMPORAL
for Class B.

Use HOLD
ON for Class
A

Figure 2-8. Fire Floor, Floor Above, and Below with QuickAlert
NACs

2-16

Technical Manuals Online! - http://www.tech-man.com


Selective Bypass of NAC/Relay Circuits

Overview The Selective Bypass of NAC/Relay Circuits application allows a 24 Point I/O
switch to override the automatic operation of NACs and door holder relays (i.e.,
horns/strobes do not automatically turn ON and doors do not close when an
alarm condition occurs). This application also causes a Trouble to appear at the
panel to indicate that the bypass switch is active.

Step 1. Define Switch Use the PC Programmer application to program the following switch attributes.
Attributes
• Device Type. Select the GRAPHIN device type, which indicates that the
device being programmed is a 24 Point I/O switch.
• Point Type. Any of the following switch point types can be used.
- OSWITCH. Specifies a two-position switch, supervised for open
circuits. Requires an EOL resistor.
- SSWITCH. Specifies a two-position switch, supervised for open and
short circuits. Requires EOL and current limited (up leg) resistors.
- TSWITCH. Three position (SPDT) switch, supervised for open
circuits. Requires EOL and current limited resistors.
- USWITCH. Two-position switch, unsupervised. Assumes that no
EOL or current limited resistor is used.
• Mode. Select the ONOFF mode. This mode allows one position of the
switch to represent the ON state and another position to represent the OFF
state. Refer to Table 2-4 for information on which switch position is
equivalent to ON or OFF.
• Reference Address. Select a user-defined digital pseudo point. A
Custom Control equation will monitor this point to determine if the signals
should be bypassed or not.

Table 2-4. Relationship between Point Status and ON/OFF State

Mode Point Type Point Status and Result


Limited* Turns point ON
USWITCH
ONOFF – Programs the Normal* Turns point OFF
switch to turn the
referenced point ON or Limited* Turns point ON
OSWITCH
OFF. This mode is Normal* Turns point OFF
typically used with a
2-position maintained or Limited* Turns point ON
SSWITCH
a 3-position switch, and Normal* Turns point OFF
is not intended to be
used with a 2-position Normal* Mode OFF
momentary switch. TSWITCH Limited* Turns Point ON
Short Indicates Short

* When the I/O point’s status is viewed from the LCD panel (using
Control/View Points menu selection), this is the state that appears when the
switch is in the ON or OFF position.

Continued on next page

2-17

Technical Manuals Online! - http://www.tech-man.com


Selective Bypass of NAC/Relay Circuits, Continued

Step 2. Define Digital Pseudo Define the attributes of the digital pseudo point used as the Reference Address
Point Attributes in Step 1 above as follows:

• Point Type. Define the point type of the digital pseudo point as
TROUBLE. This programs the system to display a system trouble if the
switch is active (ON).

• Custom Label. Use a descriptive name such as “3RD-FLOOR-DOORS


& SIGNALS BYPASS TROUBLE.”

Step 3. Add the Floor’s Add the initiating devices for the floor or area that you want to bypass to a list.
Initiating Devices to a List Doing this limits the number of Custom Control equations required. To add a
floor’s initiating devices to a list, use the PC Programmer’s List Tab.

Step 4. Change the Point Use the PC Programmer to program the NACs and Door Holder relays with the
Type of NACs and Door following point types. (Do not program the door holders with a door holder
Relays point type such as DHOLDER. Door holder point types are used to specify the
automatic operation of the relay, not its custom operation.) When defining
custom labels, make sure to use descriptive labels, such as “FLR-1 AUDIBLE-
NAC.”

Type of Device Point Type Required


Class B QuickAlert NACS QALERT
Standard NACs or
SIGNAL
Class A QuickAlert NACs
Door Holder Relays RELAY

Step 5. Add the NACs and Add the NACs and Door Relays that you want to bypass to a list. Doing this
Door Relays to a List allows the Custom Control equation to refer to the floor’s entire set of NACs
and Relays as a single point. This limits the number of equations required to
implement the bypass function.

Step 6. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.

• Standard (non-QuickAlert) Audible NACs.


• NAC used for horn control input to SCM. (Class A QuickAlert only.)

Continued on next page

2-18

Technical Manuals Online! - http://www.tech-man.com


Selective Bypass of NAC/Relay Circuits, Continued

Step 7. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.

• Door Holder Relays.


• Standard (non-QuickAlert) Visible NACs.
• Class B QuickAlert NACs.
• Class A QuickAlert NACs wired to the “NAC IN” input of the SCM.
Note: Assign the Class A QuickAlert Horn Control NAC to list L6.

Step 8. Add Custom Control This section illustrates how to implement Selective Bypass of NAC/Relay
Equations Circuits for a facility that uses either standard NACs or Class A and Class B
QuickAlert NACs. Refer to the appropriate section below.

Standard NACs. The first two input statements, separated by the AND
operator, check whether there is an activated initiating device and whether the
bypass switch (monitored by pseudo P76) is active. The NACs activate when
the following conditions are both true, and do not activate if either is false.

• List L26 contains an activated initiating device (i.e., a smoke detector in


alarm).
• P76 is NOT in its ON/CODING state (i.e., the NACs activate if the switch
is not active).

Figure 2-9. Selective Bypass of NACs, Standard NAC Example

QuickAlert NACs. Figure 2-10 shows how to implement the selective bypass
application with Class A or Class B QuickAlert NACs. As with the Standard
NACs example, the first two input statements check whether there is an
activated initiating device and whether the bypass switch (monitored by pseudo
P76) is active.

The NACs activate when the following conditions are both true, and do not
activate if either is false. Use HOLD TEMPORAL for Class B QuickAlert
NACs; use HOLD ON for Class A QuickAlert NACs.

• List L26 contains an activated initiating device (i.e., a smoke detector in


alarm).
• P76 is NOT in its ON/CODING state (i.e., the NACs activate if the switch
is not active).

Continued on next page

2-19

Technical Manuals Online! - http://www.tech-man.com


Selective Bypass of NAC/Relay Circuits, Continued

Step 8. Add Custom Control The second equation checks the ON/CODING state of P26, which is ON when
Equations (continued) Alarm Silence is active. If P26 is ON (i.e., an Alarm Silence has occurred), the
HORN OFF command executes, turning off the QuickAlert Horns. Be aware
that you cannot associate a list with the HORN OFF command; you must
specify the specific NAC points (for example, SIG1, etc.).

The last output qualifier resets the state of P26. Note: Resetting P26 is
very important. Do not leave this step out.

Use Hold
ON for
Class A

Use Hold
Temporal
for Class B

Figure 2-10. Selective Bypass of NACs, QuickAlert NAC Example

2-20

Technical Manuals Online! - http://www.tech-man.com


Selective Activation of Single Station Devices

Introduction Single station smoke detectors -- typically used in hotel rooms, dormitories, and
hospital rooms -- contain their own sounder. When activated, only the sounder
on the activated device signals the presence of an alarm condition. This
application describes programming the 4010 so that when a manual pull station
activates, all single station devices in the area also activate.

Step 1. Define Device Types, Use the PC Programmer’s Point tab to program each Single Station Device with
Point Types, and Mode for the following attributes:
Single Station Devices
• Device Type. A single station device can use any one of the following
device types:

- SPHOTO designates that a photoelectric sensor is attached to a


separate sounder base.
- XSPHOTO indicates that a photoelectric sensor is mounted to a
separate sounder base and that the system is using a more sensitive
smoke-detection algorithm. (.2% sensitivity to smoke not .5%.).
- QSPHOTO is a quick connect photoelectric sensor/sounder base
combination in which the sensor cannot be removed from the base.
- SHEAT is a heat detector attached to a separate sounder base.
- SION indicates that an ionization detector is mounted to a separate
sounder base.
- SOHEAT is a rate of rise heat detector mounted to a separate sounder
base.

• Point Type. Any of the standard point types may be used, including
DUCT, GVMON, SDUCT, SMOKE, UTIL, VSMOKE. Refer to Appendix
A of this manual for the function of these point types.

• Mode. The default mode setting for a TrueAlarm device equipped with
sounder is SSTATION (Single Station), which is required to support single
station operation.

To check whether this mode is enabled, you need to select the PC


Programmer’s Card Tab and view the IDNet card. The Mode field is on the
far right of the device’s point information. (Note: Mode does not appear
in the Point Tab.)

Step 2. Add Area’s Pull Adding each area’s pull stations to a separate list limits the number of Custom
Stations to a User-Defined Control equations required to implement this application. To add an area’s pull
List stations to a list, use the PC Programmer’s List Tab.

Step 3. Add Custom Control Programming selective activation of single station devices requires two
Equations equations, as shown in Figure 2-11.

Continued on next page

2-21

Technical Manuals Online! - http://www.tech-man.com


Selective Activation of Single Station Devices, Continued

Step 3. Add Custom Control Equation 1. This equation uses a single input qualifier to monitor List L26,
Equations (continued) which contains all of Floor 1’s pull stations. If any pull station within this list
activates, this equation’s output qualifiers execute. The first output qualifier
programs the tone used by the single station sounders when they activate. The
second output qualifier turns on the sounders in the area of the activated pull
station.

Note: You cannot put single station devices in a list; each device must be
separately listed in the Custom Control program, as shown in Figure 2-11.

Equation 2. The input qualifier used in this equation monitors the state of P26,
which is ON if an Alarm Silence has been performed. The output qualifiers
only execute when P26 is ON (i.e., following Alarm Silence). The first output
qualifier, Device Code OFF, turns off the sounders on the single station devices.
The second output qualifier resets the state of P26.

Note: Resetting P26 is very important. Do not leave this step out.

Equation 1

Equation 2

Figure 2-11. Selective Activation of Single Station Devices

2-22

Technical Manuals Online! - http://www.tech-man.com


Chapter 3
Suppression Release

Overview This chapter describes the 4010 programming required for common
suppression-release applications.

Basic applications, which do not involve pre-signaling or an abort switch with


delay, can be programmed without Custom Control using a mix of the 4010’s
built-in system options, point types, and lists. More complex applications,
involving pre-signaling or an abort switch with delay, require Custom Control
programming.

Before continuing, make sure that you have the following information:

• Fire Alarm STRM Ref. number SEB-FAS0899-01. This STRM contains


critical information concerning UL, FM, and IRI suppression requirements.
• Field Wiring Diagram 842-058.
• Field Wiring Diagram 842-073.
• Detailed knowledge concerning AHJ requirements .

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #

Default Suppression Release Applications 3-2


Dual Detector, Pre-Signal, and Abort Switch with 3-5
No Delay
Dual Detector, Pre-Signal, and Abort Switch with 3-8
Delay

3-1

Technical Manuals Online! - http://www.tech-man.com


Default Suppression Release Applications

Suppression Release The application described in this section is used in situations that require the
Triggered by Single Pull release of the suppression agent immediately (or slightly delayed by a timer)
Station or Automatic Initiating after alarm activation. A typical use is for a fueling station equipped with a
Device manual release station and flame detectors. An important point to note with this
application is that it does not use either an abort switch or a NAC pre-signal that
indicates imminent release of the agent.

As shown in Figure 3-1, activation of a single initiating device – typically a


manual release station or an automatic initiating device such as a flame detector
– triggers a Suppression Release Delay Timer. This optional delay timer, which
is a system option having a range of zero to 30 seconds for a manual release
station or zero to 60 seconds for an automatic initiating device, delays the
activation of the NAC signals and prevents suppression dump. When the timer
expires, both of these actions – NAC signal activation and suppression dump –
occur. (Important Note: If the delay timer is not selected, both NAC signal
activation and the release of the agent immediately follow alarm activation.)

ALARM ACTIVATION

Timer
0-30 for Pull
0-60 for Auto.

DISCHARGE SIGNALS

SOLENOID ACTIVATION

Pull Timer Alarm System


Station or Expires Silence Reset
Automatic
Initiating
Device
Activated

Figure 3-1. Timeline for Single Device Suppression Release

Suppression Release Some situations require additional verification of an alarm condition (i.e., two
Triggered by Dual Automatic automatic initiating devices must activate) before the release of the suppression
Initiating Devices agent can occur.

As shown in Figure 3-2, activation of the second automatic initiating device


triggers an optional timer, which has a range of 0-60 seconds for an automatic
initiating device. When this timer expires, the discharge signals sound and the
solenoid activates, releasing the suppression agent. As with the previous
application, it is important point to note that this application does not include
either an abort switch or pre-signal.

Continued on next page

3-2

Technical Manuals Online! - http://www.tech-man.com


Default Suppression Release Applications, Continued

Suppression Release
Triggered by Dual Automatic
Initiating Devices (continued)
1ST AUTOMATIC INITIATING
DEVICE

2ND AUTOMATIC INITIATING DEVICE

RELEASE TIMER

DISCHARGE
SIGNALS

SOLENOID ACTIVATION

Pull Timer Alarm System


Station or Expires Silence Reset
Automatic
Initiating
Device
Activated

Figure 3-2. Timeline for Suppression Release Using Dual Automatic


Initiating Devices

Programming Default Programming the suppression component of either default application is done
Applications with the system’s built-in suppression release options, suppression point types,
and suppression lists.

1. Set the Suppression Release System Options, as shown below. These


options are available by first selecting the PC Programmer Card Tab and
then selecting the System Options Radio button.
Select only if two detectors
must activate prior to agent
discharge

Check and enter number of


seconds to delay, if necessary

2. Use the PC Programmer’s Point Tab to assign suppression points with the
point types listed below. Refer to Appendix A for specific details on these
point types.

• SUPDUMP. Use for manual suppression release points.


• SUPREL. Use for suppression (agent discharge) release output points.
• SUPDET. Use for automatic initiating devices

Continued on next page

3-3

Technical Manuals Online! - http://www.tech-man.com


Default Suppression Release Applications, Continued

Programming Default 3. Use the PC Programmer’s List Tab to add the initiating devices and output
Applications (continued) points to the appropriate lists, as follows:

List Add These Points


L9 Automatic Suppression Release Points. Add all automatic
initiating devices whose activation should result in the release
of the suppression agent.
L10 Suppression Manual Release Points. Add all manual
suppression release points whose activation should result in
the release of the suppression agent.
L12 Suppression Release Output Points. Add the NACs that
control the suppression release solenoids.

3-4

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with No Delay

Introduction The application described in this section provides the following suppression
operation.

• Activation of the suppression release system occurs when either two


automatic initiating devices (detectors) or a single manual release point
(pull station) are activated. Release of the suppression agent can be delayed
for up to 60 seconds after the second automatic initiating device activates
and for up to 30 seconds after a pull station activates. These delays are
configurable via system options.

• At any time prior to the actual release of the agent, an operator can prevent
the release of the suppression agent by pressing an abort switch. Release of
the suppression agent is prevented for the duration of time this switch is
held. Release of the suppression agent occurs immediately after release of
the abort switch, assuming the timers discussed in the previous bullet have
expired. Operators should be made aware that if the alarm is false, clearing
the alarm condition and resetting the system prior to releasing the switch
prevents agent discharge.

• NAC appliances operate in a slightly different manner depending on


whether the activated device is an automatic initiating device or a pull
station.

- Automatic Initiating Devices. When the first automatic initiating


device activates, the NACs in the suppression release area sound a
pre-signal (Slow March Time). When a second automatic initiating
device activates, this tone converts to a Fast March Time tone. At the
time of agent discharge, the tones convert to Steady, indicating that the
agent has been released.

- Manual Release Point (pull station). When a manual release point


activates, the NACs in the suppression area sound a Fast March Tone.
At the time of agent discharge, the tone converts to a Steady tone,
indicating that the agent has been released.

Figure 3-3 shows a timeline for this application. First stage signals activate
following the first stage alarm condition (which is always an automatic initiating
device). Second stage signals activate following the activation of either a
second automatic initiating device or following activation of a manual release
station. The second alarm condition (or the manual pull station) also triggers the
optional release timer, if used. This timer ranges from 0-30 seconds for a
manual release station and 0-60 seconds for an automatic initiating device.
Suppression is delayed until the release timer expires or the abort switch is
released, at which time the signals convert to a discharge tone and the solenoid
activates.

Continued on next page

3-5

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with No Delay, Continued

Introduction (continued)
1St STAGE ALARM
CONDITION

2ND STAGE ALARM CONDITION or MANUAL RELEASE STATION

RELEASE TIMER

ABORT STATION ACTIVE

1ST STAGE ALARM SIGNALS

2ND STAGE PRE-DISCHARGE SIGNALS

2ND STAGE
DISCHARGE SIGNALS

SOLENOID
ACTIVATION

Automatic System
Initiating Reset
Device
Activated

Figure 3-3. Pre-Signal with Abort Switch Timeline

Programming System Programming the suppression component of either default application is done
Options, Point Types, and with a combination of Custom Control and the system’s built-in suppression
Lists release options, suppression point types, and suppression lists.

1. Set the Suppression Release System Options, as shown below. These


options are available by first selecting the PC Programmer Card Tab and
then selecting the System Options Radio button.
Select only if two detectors
must activate prior to agent
discharge

Check and enter number of


seconds to delay, if necessary

2. Use the PC Programmer’s Point Tab to assign suppression points with the
point types listed below. Refer to Appendix A for specific details on these
point types.

• SUPABRT. Use for suppression release abort points.


• SUPDUMP. Use for manual suppression release points.
• SUPREL. Use for suppression (agent discharge) release output points.
• SUPDET. Use for automatic initiating devices

Continued on next page

3-6

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with No Delay, Continued

Programming System 3. Use the PC Programmer’s list tab to add the initiating devices and output
Options, Point Types, and points to the appropriate lists, as follows:
Lists (continued)
List Add These Points
L9 Automatic Suppression Release Points. Add all automatic
initiating devices whose activation should result in the release
of the suppression agent.
L10 Suppression Manual Release Points. Add all manual
suppression release points whose activation should result in
the release of the suppression agent.
L11 Suppression Release Abort Points. Add all abort switch
points to this list.
L12 Suppression Release Output Points. Add the NACs that
control the suppression release solenoids.

Programming Custom Control The following example, shown in Figure 3-4, illustrates how to implement this
application.

• Equation 1. The input side of this equation monitors the FIRE state of list
L9, which is a system list containing all suppression-related automatic
initiating devices. The output side of Equation 1 programs the NAC
appliances to sound in SLOW MARCH TIME when any point within list
L9 enters an ALARM condition.

• Equation 2. The input side of Equation 2 monitors L9 (suppression-


related automatic initiating devices) and L10 (suppression-related manual
release points). If there is an activated device in either list, the output side
of the equation executes, activating the NAC appliances in FAST MARCH
TIME.

• Equation 3. The input side of Equation 3 monitors the suppression release


output points contained in system list L12. If any of the points in this list
are ON/CODING, the NACs are held ON, indicating that the suppression
agent has been released.

Figure 3-4. Custom Control for Pre-Signal

3-7

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with Delay

Introduction The application described in this section operates in the following way.
Figure 3-5 shows a timeline for this application.

• Activation of the suppression release system occurs when either two


automatic initiating devices (detectors) or a single manual release point
(pull station) are activated. Release of the suppression agent is delayed for
30 seconds after the second automatic initiating device activates and for five
seconds after a pull station activates.
• At any time prior to the actual release of the suppression agent, an operator
can prevent the release by pressing an abort switch. Agent release is
prevented for the duration of time this switch is held. If the condition that
triggered the alarm is cleared (i.e., the detectors or pull station are reset)
and a System Reset is performed, release of the suppression agent does not
occur. If however, the abort switch is released and the condition that
triggered the alarm is still present, a 10-second Abort Switch timer starts.
After the timer expires, release of the agent occurs.
• NAC appliances operate in a slightly different manner depending on
whether the activated device is an automatic or a pull station.
- Automatic Initiating Devices. When the first automatic initiating
device activates, the NACs in the suppression release area sound a
pre-signal (Slow March Time). When a second automatic initiating
device activates, this tone converts to Fast March Time. At the time of
agent discharge, the tones convert to Steady, indicating that the agent
has been released.
- Manual Release Point (pull station). When a manual release point
activates, the NACs in the suppression area sound a Fast March Tone.
At the time of agent discharge, the tone converts to a Steady tone,
indicating that the agent has been released.

1St STAGE ALARM


CONDITION

2ND STAGE ALARM CONDITION

RELEASE TIMER

ABORT STATION ACTIVE TIMER

1ST STAGE ALARM SIGNALS

2ND STAGE PRE-DISCHARGE SIGNALS

2ND STAGE
DISCHARGE
SIGNALS

SOLENOID
ACTIVATION

Automatic Pull Station or System


Initiating 2nd Auto. Reset
Device Initiating Device
Activated Activates

Figure 3-5. Dual Detector, Pre-Signal, and Abort Switch with Delay

Continued on next page

3-8

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with Delay, Continued

Define Lists, Digital Pseudos, The dual detector, pre-signal, and abort switch with delay application requires
and Analog Pseudos the following components to be defined prior to programming the Custom
Control equations.

1. Use the PC Programmer’s Point Tab to assign suppression points with the
point types listed below. Refer to Appendix A for specific details on these
point types.

• SUPABRT. Use for suppression release abort points. Use 2080-9030


system abort switch. Wire this switch according to FWD 842-073.
• SUPDUMP. Use for manual suppression release points.
• SIGNAL. Use for suppression (agent discharge) release output points.
Note: Do not use the SUPREL point type for this application.
• SUPDET. Use for automatic initiating devices

2. Use the PC Programmer’s list tab to add four lists similar to the ones shown
below. Do not use the system’s suppression release lists – L9, L10, L11, or
L12.

List Add These Points


L26 Add all automatic initiating devices (detectors) whose
activation should result in the release of the suppression
agent.
L27 Add all manual suppression release points (pull stations)
whose activation should result in the release of the
suppression agent.
L28 Add all abort switch points to this list.
L29 Add the NACs that control the suppression release solenoids.

3. Define five Digital Pseudo Points, similar to the following:

• P80. Two detectors in alarm


• P81. Manual release station activated
• P82. Abort switch activated
• P83. Abort switch released
• P84. Delay timer running

4. Analog Pseudo Points. Define three analog pseudo points, similar to the
following. These will be used as the running timers in the example.

• A26. 10 Second Abort Delay


• A27. Detector Delay
• A28. Pull Station Delay

Continued on next page

3-9

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with Delay, Continued

Program Custom Control The eight Custom Control equations required to program this application are
Equations shown in Figure 3-7. These equations have the following functions.

Equation 1. This equation contains two input qualifiers and a single output
qualifier. The first input qualifier in this equation monitors the state of list L26.
If two detectors within this list are in the FIRE state, the remainder of the
equation executes. The second input qualifier, which executes only if the first
input qualifier is true (i.e., two detectors are activated), starts a running timer of
30 seconds. The output qualifier at the bottom of the first equation, which also
executes only if the first input qualifier is true, turns P80 on.

Equation 2. The first input qualifier monitors the state of List L28, which
contains all manual release stations (pull stations) in the suppression release
area. The second input qualifier and the output qualifier at the bottom of
Equation 2 execute only if the first input qualifier is true. The second input
qualifier starts a running timer of five seconds. The output qualifier at the
bottom of the equation turns P81on.

Equation 3. The first input qualifier checks to see whether an abort switch is
active. It does this by checking to see whether any point within list L27, which
contains all abort switch points, is in a supervisory state. (Note that these points
must have a point type of SUPABRT for this to occur.) The second input
qualifier, which is linked to the first by an AND logical operator, determines
whether two detectors are in an activated state. Because the first two input
qualifiers are separated by the AND operator, they both must be true (i.e., an
abort switch must be active while two detectors are in an activated state) for the
equation’s two output qualifiers to execute. If the inputs are both true, the first
output qualifier holds pseudo point P82 ON and the second output qualifier
tracks ON P83. (Understanding the function of this last output qualifier is very
important. Because it uses TRACK ON, P83 turns on when both input
qualifiers are true, and turns off when either one of the input qualifiers is false.)

Equation 4. The first input qualifier checks pseudo point P82, which is ON
only if Equation 3’s input qualifiers are both true (i.e., abort switch is active and
two detectors in the suppression area are active at the same time). The second
input qualifier, which is linked to the first input by the logical AND operator,
checks P83. This input is true only if P83 is NOT in its ON/CODING state (i.e.,
switch is not being held in). The third input qualifier starts a running timer of 10
seconds. The output qualifer turns P84 on, which indicates that the timer is
running.

Equation 5. The four input qualifiers in this expression are linked via logical
operators. The output qualifier (which holds on the suppression release circuits)
in this equation executes if the following occurs:

- Two detectors are active (i.e., P80 is ON) AND the abort switch is not
active (P82 cannot be in the ON/CODING state).

- OR a pull station is active (P81 is ON).

- OR P84 is on (i.e., the abort switch delay timer has expired).

Continued on next page

3-10

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with Delay, Continued

Program Custom Control Equation 6. If one detector in List L26 goes into alarm, SIG1 turns on steady.
Equations (continued) This functions as a pre-signal for system operators.

Equation 7. This equation turns off SIG1 and sounds a slow march tone on
SIG2 if either two detectors activate in list L26 or if a pull station activates.

Equation 8. This equation turns SIG2 on steady if any one of the releasing
circuits (NACs) is ON (i.e., it is discharging).

Figure 3-6. Custom Control (Part One)

Continued on next page

3-11

Technical Manuals Online! - http://www.tech-man.com


Dual Detector, Pre-Signal, and Abort Switch with Delay, Continued

Program Custom Control


Equations (continued)

Figure 3-7. Custom Control (Part Two)

3-12

Technical Manuals Online! - http://www.tech-man.com


Chapter 4
Additional Applications

Overview This chapter describes additional useful applications.

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Pre-Signal Operation 4-2
Programming a Utility Monitoring Point 4-6
Day / Night Programming 4-8
AHJ City Reset 4-10
Elevator Recall 4-11
Selective City Circuit Activation 4-13
General Alarm Shutdown for Fans and Dampers 4-14
General Alarm Timer for Single Station 4-16

4-1

Technical Manuals Online! - http://www.tech-man.com


Pre-Signal Operation

Overview This application monitors initiating devices and does the following:

• Automatic Initiating Device Activation. Sounds a pre-alert, slow


march time tone when an automatic initiating device (for example, a smoke
or heat sensor) activates. This tone lasts for five minutes. After five
minutes, if no Alarm Silence has occurred, the tone converts to a temporal
“general evacuation” tone. The purpose of this is to alert system operators
that an automatic initiating device has triggered and allow them up to five
minutes to investigate the cause of the alarm.

• Pull Station Activation. Sounds a temporal “general evacuation” tone,


for a duration of five minutes, when a pull station activates.

Note: Always consult the local AHJ to determine whether this type of
operation is allowed or not allowed.

Step 1. Define NAC’s Device The NACs used with the Pre-Signal application can be either the NACs located
Type, Point Type, and Custom on the panel’s SFIO board or the NACs located on a 4009 IDNet NAC extender.
Label Note: Class A QuickAlert cannot be used with pre-signal applications.

Use the PC Programmer to program the NACs with the device types and point
types listed in Table 4-1. When defining custom labels, make sure to use
descriptive labels, such as “FLOOR1-VISUAL-CIRCUIT.”

If necessary, refer to Chapter 7, Programming Points, of the 4010 PC


Programmer Installation and Programming Instructions (574-187) for
information on editing a point’s device type, point type, and custom label.

Table 4-1. NAC Device Types and Point Types

Option Explanation
Use for Class A NAC. This type of NAC
contains multiple signal paths, allowing
NAC SIGA circuit operation to continue if a single open
Device circuit occurs. This option requires
Type installation of a Class A NAC adapter card.
Use for Class B NAC, which is a NAC
SIGB
containing only a single circuit path.

Use only for Class B QuickAlert NAC


QALERT appliances requiring Custom Control
NAC (selective signaling).
Point Use for either of the following:
Type - Non-QuickAlert (standard) NAC
SIGNAL
appliances requiring Custom Control
(selective signaling).

Continued on next page

4-2

Technical Manuals Online! - http://www.tech-man.com


Pre-Signal Operation, Continued

Step 2. Define Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels for Initiating Devices Programmer Installation and Programming Instructions for information on
programming an initiating device’s device type and point type. Refer to
“Monitor Point Types” in Appendix A of the PC Programmer manual for
detailed descriptions of the initiating device point types.

Step 3. Add Initiating Devices Create user-defined lists, as follows:


and NACs to User-Defined
Lists • Automatic initiating devices.
• Pull stations.
• NACs (if you are using standard NACs you may need two lists, one for
audible NACs and one for visible NACs).

To add devices to a list, use the PC Programmer’s List Tab, adding each of the
devices to one of the available user-defined lists (L26 through L50).

Step 4. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.

• Standard (non-QuickAlert) Audible NACs

Step 5. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.

• Standard (non-QuickAlert) Visible NACs


• Class B QuickAlert NACs

Continued on next page

4-3

Technical Manuals Online! - http://www.tech-man.com


Pre-Signal Operation, Continued

Step 6. Add Custom Control Standard NAC Example. Figure 4-1 shows an example of pre-signal
Equations Custom Control equations for a facility that uses standard NAC devices.
Information on QuickAlert devices is contained in the example at the end of this
section.

• Equation 1. The input side of this equation monitors the Physical


Abnormal state of each device within list L26, which is a user-defined list
containing the automatic initiating devices (smokes/heats, for example) for
Floor 1. The output side of Equation 1 programs SIG1 to sound (slow
march tone) when any point within list L26 enters a physical abnormal
condition (i.e., when any smoke sensor activates).

• Equation 2. The input side of this equation monitors the Physical


Abnormal state of each device within list L26, which is a user-defined list
containing the automatic initiating devices (smokes/heats, for example) for
Floor 1. If any point within L26 activates and P1 (pseudo point for
unacknowledged alarms) is ON (i.e., no operator acknowledgment has
occurred), a timer starts. This timer runs for five minutes (300 seconds).
When it expires, the NACs convert to a temporal pattern. Note that you
must assign an analog pseudo point (A26 in this example) to the timer.

• Equation 3. This equation’s input side monitors the Physical Short state
of each device within L27, which is a list containing the floor’s pull
stations. If a device within this list is active (i.e., pulled), the output side of
this equation programs the NACs to activate in a temporal pattern.

Equation 1

Equation 2

Equation 3

Figure 4-1. Pre-Signal Custom Control, Standard NACs

Continued on next page

4-4

Technical Manuals Online! - http://www.tech-man.com


Pre-Signal Operation, Continued

Step 6. Add Custom Control QuickAlert NACs. A pre-signal application that uses QuickAlert NACs is
Equations (continued) programmed in virtually the same manner as the standard NAC example shown
above. The two differences for QuickAlert are that it requires one additional
equation to turn the horns off and you cannot use Class A QuickAlert with a pre-
signal application. (The horn pattern generated by the Sync module is set via a
switch, and it cannot be controlled by Custom Control.) Figure 4-2 shows an
example of a pre-signal application that uses QuickAlert NACs.

Figure 4-2. Pre-Signal Custom Control, QuickAlert NACs

4-5

Technical Manuals Online! - http://www.tech-man.com


Programming a Utility Monitoring Point

Overview Utility monitoring points differ from standard fire alarm points in that they do
not report a trouble when they activate and they do not latch (i.e., they reset
themselves). A utility monitoring point tracks the state of a monitor device (for
example, a heat sensor), turning a relay or supervisory pseudo point on when the
sensor’s value equals or exceeds an analog value that you specify.

This section uses an example in which a customer wants a water heater to come
on and a supervisory alert to occur when the temperature of a water tank is
between 38 and 50 degrees.

Step 1. Change the Heat Use the PC Programmer to change the heat detector’s point type to Utility. This
Detector’s Point Type and is a generic point type with no default operation, allowing the point to be
Custom Label controlled by Custom Control. Assign a descriptive custom label, such as
“Water Temp Monitor – Tank 2” to the point.

Step 2. Change the AUX The output point is typically a relay (AUX1, for example). Use the PC
Relay Point’s Point Type and Programmer to change its point type to Relay. This is a generic point type that
Custom Label allows the point to be controlled via Custom Control. Change its custom label
to a descriptive text, such as “Water Heater Control Relay Tank 2.”

Step 3. Define a Supervisory Use the PC Programmer to define a user digital pseudo point. Assign it a point
Digital Pseudo Point type of Supervisory, which means it will generate a Supervisory alert to the
panel when activated. Change its custom label to the message that you want to
appear on the panel when the monitor’s threshold point is reached. For
example, “Water Tank Temp Warning.”

Step 4. Program Custom The Custom Control example, shown in Figure 4-3, outlines the equation needed
Control Equations to program the example water tank/heater application. This equation contains
two input qualifiers and two output qualifiers.

1st Input Qualifier. The first input qualifier in the example equation checks
the value of the heat sensor to determine if it is greater than or equal to 38
degrees. To do this, you need to program this input statement’s properties, as
follows:

1. Choose the COMPARE opcode and select COUNTS (constant) for the
qualifier.

2. Enter the threshold value in the Counts box at the bottom right of the panel.
The example shows 38, which represents a temperature value in this
example.

3. Choose the greater than or equal to (>=) operator.

Continued on next page

4-6

Technical Manuals Online! - http://www.tech-man.com


Programming a Utility Monitoring Point, Continued

Step 4. Program Custom 2nd Input Qualifier. The 2nd input qualifier, which is connected to the 1st
Control Equations (continued) input qualifier by an AND (i.e, both qualifiers must be true), checks to see if the
heat sensor is at a temperature of less than or equal to 50 degrees. Its
programming is very similar to the 1st input statement.

1. Select the COMPARE opcode and the COUNTS (constant) qualifier.

2. Specify 50 in the Counts box and select the AND radio button in the top left
corner.

3. Choose the less than or equal to (<=) operator for the 50 count.

1st Output Qualifier. This output tracks the input. That means that a
supervisory message (“Water Tank Temp Warning”) is sent to the panel when
the temperature range is between 38 and 50. This supervisory cannot be cleared
until the temperature is outside of the 38 to 50 degree range.

2nd Output Qualifier. This output tracks the input as well. Its function,
however, is to turn on a relay connected to a water heater while the temperature
range is between 38 and 50. As soon as the temperature is out of this range, the
relay goes off.

Input 1
Input 2

Output 1
Output 2

Figure 4-3. Example Custom Control Non Latching / Non Alarm

4-7

Technical Manuals Online! - http://www.tech-man.com


Day / Night Programming

Overview The Day / Night programming application allows Custom Control to perform
one set of instructions during daytime hours and another set of instructions at
night.

Step 1. Program the Monitor The monitor device must be capable of accepting a variable operating level (for
Device’s Point Type, Device example, a smoke sensor whose sensitivity can be changed). The following
Type, and Custom Label devices support this functionality:

• TrueAlarm Photo
• TrueAlarm Heat
• TrueAlarm Ion
• TrueAlarm XPHOTO

Use the PC Programmer to program the initial sensitivity of the sensor.

Step 2. Program Custom Day / Night programming is done by comparing a constant that represents the
Control Equations time at which an action should occur against the value of A11, the current hour
of day analog pseudo point.

Example: Suppose M1-1 is a TrueAlarm Photo sensor and a customer wants


normal 2.5% sensitivity during working hours (7am – 6pm) and higher
sensitivity (1.0%) at night. (A11 is current hour analog pseudo point).

To do this, you would need two equations similar to the following:

Equation 1:
-2
%+6)%8)68,%2 MWEQ
398
7)88,6)7,30(10):)0 SFWGYVEXMSR
)2(

Equation 2:
-2
%+6)%8)68,%2 MWTQ
398
7)88,6)7,30(10):)0 SFWGYVEXMSR

Program the first equation, as follows:

1. Add an input to a new equation and change its properties as shown in the
figure below.

2. Select COMPARE as the opcode and COUNTS (constant) as the qualifier.

3. In the Compare panel at the bottom of the screen, do the following:

a. Choose A11 as the Analog Pseudo.

b. Choose the equal sign as the operator.

c. In the Counts box, enter the hour at which the change takes place.

4-8

Technical Manuals Online! - http://www.tech-man.com


Continued on next page

4-9

Technical Manuals Online! - http://www.tech-man.com


Day / Night Programming, Continued

Step 2. Program Custom


Control Equations (continued)

Figure 4-4. Input Properties for Compare Operation

4. Add an output to the equation. Set its Opcode and Qualifier to the
following:

• The Opcode must be one of the following: Set Threshold Photo, Set
Threshold Ion, Set Threshold Heat, Set Threshold XPHOTO.

• The Qualifier is the threshold that you want to set. For example,
Smoke Level 2.5.

As shown in the figure below, the second equation is programmed almost


exactly as the first equation. Its Input Qualifier monitors A11 (current hour) to
determine when it is equal to 18 (6:00 p.m.). At 6:00 p.m., the smoke level is
changed to 1.0.

Equation 1

Equation 2

Figure 4-5. Equations for Example Day/Night Programming

4-10

Technical Manuals Online! - http://www.tech-man.com


AHJ City Reset

Overview Newer versions of the 4010 FACP (Version 2.01 or later) provide the ability to
reset the City Circuit in the following situations.

• If the device(s) in alarm is physically removed. (Remove the faulty sensor


from its base, for example.)
• No other devices are in an alarm state.
• A System Reset is performed.

Always consult the local AHJ before implementing this functionality. Some
jurisdictions may not allow this operation.

Program Custom Control To program AHJ City reset, enter the following equation.
Equations
1. Add a new equation. Program its input statement to monitor the
ON/CODING state of the A4 analog pseudo point, which is the system
startup pseudo.

2. Program the output statement to Hold ON digital pseudo point P16 (AHJ
Reset).

Equation 1

4-11

Technical Manuals Online! - http://www.tech-man.com


Elevator Recall

Overview The Elevator Recall application programs the system to automatically recall the
building elevators following alarm activation. Guidelines to be aware of
include:

• General information on and requirements for Elevator Recall and Fire


Safety Control Functions can be found in NFPA 72, 1996, Chapter 3 for
Protected Premises Fire Alarm Systems, and ANSI/ASME A17.1 Safety
Code for Elevators and Escalators.

• Installation wiring running between the 4010 FACP and the auxiliary relays
used for fire safety control functions (in this case, elevator recall) must be
monitored for integrity (supervised) and the auxiliary relay must be located
within 3 feet of the controlled circuit or device. Reference NFPA 72, 1996,
Section 3-9.2.

• It is recommended that relay IAMs be used as the primary and alternate


elevator recall relays. Other supervised wiring methods, such as a 24 Point
I/O output connected to a supervised relay, may be used in lieu of a relay
IAM.

The remainder of this section describes the Custom Control programming


required to implement this application.

Step 1. Add Primary Floor Use the PC Programmer’s List Tab to add all of the building’s initiating devices,
Initiating Devices to a User- with the exception of those located on the alternate floor, to a user-defined list.
Defined List Use the Card Tab to give the list a descriptive name such as “BANK2
PRIMARY ELEVATOR RECALL.”

Step 2. Add Alternate Floor Use the PC Programmer’s List Tab to add the initiating devices located on the
Initiating Devices to a alternate floor to a user-defined list. Use the Card Tab to give the list a
User-Defined List descriptive name such as “BANK2 ALTERNATE ELEVATOR RECALL.”

Step 3. Add Custom Labels The 4010 uses AUX relays, connected to the appropriate contacts on the control
to AUX Relays panel of the elevator, to indicate that a fire condition exists and the elevator
should be returned to either the primary or alternate floor. Use the Point Tab to
assign a descriptive label, such as “BANK2 PRIMARY ELEVATOR” or
“BANK2 ALTERNATE ELEVATOR,” to the appropriate AUX Relay.

Step 4. Add Custom Control The following example, shown in Figure 4-6, illustrates how to implement
Equations Elevator Recall with Custom Control.

• Equation 1. The first two input statements, separated by the AND NOT
operator, check whether there is an activated initiating device (List L26)
and make sure the relay that returns the elevator to the alternate floor is not
activated (i.e., possible fire on primary floor). If both of these are true, the
relay for the primary floor activates.

Continued on next page

4-12

Technical Manuals Online! - http://www.tech-man.com


Elevator Recall, Continued

Step 4. Add Custom Control • Equation 2. The input side of this equation monitors List L27, which
Equations (continued) contains the initiating devices located on the alternate floor. If one of these
devices contained activates, the output side of this equation executes,
energizing the relay and returning the elevator to the alternate floor.

Equation 1

Equation 2

Figure 4-6. Custom Control Equations for Elevator Recall

4-13

Technical Manuals Online! - http://www.tech-man.com


Selective City Circuit Activation

Overview By default, the City Circuit activates on all alarm conditions. In some cases,
however, the customer may want to prevent activation of the city circuit for
certain types of alarms (waterflow alarms, for example).

This application describes programming the system to activate the City Circuit
only for a specific set of alarms.

Note: The trouble circuit on the City Circuit card cannot be selectively
controlled.

Step 1. Create a User-Defined Use the PC Programmer’s List Tab to create a user-defined list containing all of
List of City Circuit Alarm the City Circuit alarm points. Exclude points that you want to prevent from
Points activating the City Circuit. Use the Card Tab to assign a descriptive name, such
as “CITY CIRCUIT ALARM ACTIVATION POINTS,” to this list.

Step 2. Create Custom The following example, shown in the figure below, illustrates how to implement
Control Equations selective City Circuit activation.

• Equation 1. The input side of this equation monitors system startup


pseudo point, A4, to determine if the system has been restarted. Each time
the system restarts, the output qualifier executes, holding the priority of the
City Circuit Output Control pseudo point at Priority 8,8.

• Equation 2. The input qualifier monitors the fire state of all devices in
List L41. If any device within this list activates, the output qualifier
executes, turning ON the City Circuit’s alarm connection.

Equation 1

Equation 2

4-14

Technical Manuals Online! - http://www.tech-man.com


General Alarm Shutdown for Fans and Dampers

Overview This application describes using Custom Control to shutdown all fans and close
all dampers during a general alarm condition. A System Reset returns all fans
and dampers to normal operation.

Refer to Simplex Technical Support for advice on implementing more complex


fan/damper applications. Situations requiring extensive monitoring and control
of the building’s fans and dampers may be beyond the 60 equation capacity of
the 4010.

Example: Fan / Damper The following figure illustrates a typical four-story building. Assume that the
Shutdown for a Four Story building includes a supply and exhaust fan, and the relays controlling the
Building dampers are wired to 24 PT I/O outputs.

SUPPLY EXHAUST

POSITIVE

NEGATIVE

POSITIVE

Figure 4-7. Fan / Damper Example

Step 1. Program Point Type Use the PC Programmer’s Point Tab to program each fan relay with the RELAY
and Custom Labels for Fan point type. When defining custom labels, make sure to use descriptive labels,
Relays such as “EXHAUST FAN RELAY.”

Step 2. Program Point Types Each damper typically contains two switches for monitoring the position of the
and Custom Labels for damper and a relay for controlling the damper motor. Use the PC Programmer’s
Damper Monitor Switches and Point Tab to program the Point Type and Custom Label for these components,
Relays as follows:

• Fan Relays. Program each relay with the RELAY point type. When
defining custom labels for damper relays, make sure to use descriptive
labels, such as “EXH DAMPER1 RELAY.”

Continued on next page

4-15

Technical Manuals Online! - http://www.tech-man.com


General Alarm Shutdown for Fans and Dampers, Continued

Step 2. Program Point Types • Damper Monitor Switches. The switches used to monitor the damper
and Custom Labels for position are typically connected to either an IAM or MZAM. Each damper
Damper Monitor Switches and uses two switches, one switch monitors the OPEN position of the damper
Relays (continued) and the other monitors the CLOSED position.

Program the appropriate device type (IAM, MAZAM, or MBZAM) and


then assign a point type of DAMPER to each device. When defining
custom labels for damper monitor switches, make sure to use descriptive
labels, such as “EXH DAMPER1 OPEN.”

Step 3. Custom Control Use the CC Tab in the PC Programmer to program the Custom Control
Equations equations as shown below. Note that these equations only show a single damper
being controlled. Copy this equation, changing the damper points as required to
account for all of the building’s dampers.

• Equation 1. This equation monitors the General Alarm List (L1). If any
point within this list activates, the Hold ON Output Qualifier executes,
turning off the relays for the supply and exhaust fans.

• Equation 2. If any point within List L1 (General Alarm List) activates


AND the open damper monitor switch is not ON (i.e., the damper is already
closed), the output executes, turning on the damper motor relay and closing
the damper.

Equation 1

Equation 2

4-16

Technical Manuals Online! - http://www.tech-man.com


This is White Text

Technical Manuals Online! - http://www.tech-man.com


Appendix A
System Options and Point Types

Introduction This appendix lists and explains the following:

• System Options.

• Software Point Types. 4010 point types are grouped into two general
categories:

- Monitor point types are used with monitoring devices, such as smoke
detectors, pull stations, heat detectors, fire pump monitors, etc.

- Control point types are used with signal (notification appliance) and
relay devices.

In this Chapter This appendix discusses the following topics:

Topic See Page #


System Options A-2
Point Types A-4

A-1

Technical Manuals Online! - http://www.tech-man.com


System Options

System Options Many common applications have been incorporated into the 4010 panel as
system options. Table 1-1 lists these options.

Refer to Chapter 5 of the 4010 PC Programmer Installation and Programming


Manual (574-187) for information on programming these options.

Table A-1. System Options

System Option Description


The Time Format option allows you to display system time in 12- or 24-hour format.
That is, time is displayed in either a 12-hour format that uses an AM (morning) or PM
Time Format (afternoon) designation, or in 24-hour (military style) format.
The Time format directly affects how time is displayed on the 4010 LCD display and
within the Historical Logs.
This option selects the mode of operation for the 4010 FACP if an alarm occurs during
an AC power loss while a Depleted Battery trouble exists. The specific operation of this
option differs slightly, depending on whether you have a domestic or Canadian system.
Domestic Operation. The default setting for the option is OFF and the depleted battery
threshold voltage is 19.4 VDC ± 5%. Operation of this option for a domestic system is
as follows:
• If the system is in alarm and a depleted battery condition occurs, any NACs that are
Depleted Battery active remain active.
• If the system is not in alarm and a depleted battery condition occurs, the NACs are
prevented from activating.
Canadian Operation. The default setting for the option is OFF and the depleted battery
threshold voltage is 19.4 VDC ± 5%. Operation of this option for a Canadian system is
as follows:
• When a depleted battery condition occurs, power is turned off to the 4010. AC
power must be restored to re-activate the 4010.
This option prevents an Alarm Silence/System Reset on a 4010 FACP for a set
Alarm Silence
duration. The range for the Silence/Reset Inhibit timer is 0-60 minutes. Zero (no inhibit)
Inhibit
is the default setting.
The Alarm Signal Cut-Out timer allows you to set a duration for how long signals sound
after an alarm. In other words, when an alarm condition exists, the signals sound until
Alarm Cutout silenced. With this option set at two minutes, building signals sound on alarm for two
Timer minutes and then stop sounding. However, the alarm condition remains active in the
panel. The default setting for this option is No Cutout (meaning an Alarm Silence is
required to shut off signals).
The Door Drop on Alarm timer allows the 4010 to hold doors open for a set duration
during an alarm condition. After that duration has expired, the 4010 shuts off the door
Door Drop on holder relays and the doors close. The range for the timer is 0-60 seconds with a
Alarm default setting of zero seconds. To have door holders drop the doors immediately,
leave the timer set to zero seconds. Note: to make a relay a door holder relay, you
must assign it the DHOLDER point type.

Continued on next page

A-2

Technical Manuals Online! - http://www.tech-man.com


System Options, Continued

System Options (continued)


Table 1-1. System Options, continued

System Option Description


The Door Holder - AC Fail Door Drop Timer allows the 4010 to hold doors open for a set
duration during an AC power loss condition. After that duration has expired, the 4010
Door Drop on conserves battery power by shutting off the door holder devices and closing the doors.
AC Fail The range for the timer is 0-60 minutes, with a default setting of 5 minutes. To have
door holders drop the doors immediately upon AC power loss, set the timer to zero
minutes.
This option allows you to set the 4010 to stagger start any Air Handling Units (point
types AHUR, AHUO, and AHUF) in the 4010 FACP. This option protects against power
Air Handling spikes that may cause the circuit breakers to trip when AHUs start simultaneously. The
Units (AHU) range for stagger starting the AHUs is 0-60 seconds. The default setting for this option
Stagger Start is 30 seconds. A setting of zero allows all AHUs to start immediately.
The 4010 FACP displays an AHU Stagger Start message when the sequence starts and
an AHU Stagger Start Complete message when the sequence ends.
The Suppression Release option contains three selections:
• Dual Detector. When enabled, this option requires two points in L9 (Automatic
Suppression Release Points List) to activate before the outputs specified in L12
(Suppression Release Output Points List) activate.
Suppression • Detector Delay. When enabled, this option allows you to specify a delay between
Release the time that a detector activates and the time that a point within the L9 list triggers.
The range is from 0 to 60 seconds (60 is the default).
• Manual Delay. When enabled, this option allows you to specify a delay, ranging
from 0 to 30 seconds, between the time that a manual release point is activated and
the time that the suppression release points in L10 (Suppression Manual Release
Points) trigger.

The Active Status Reminder option allows you to set an interval and duration during
which the 4010 remind operators that a FIRE, SUPV, or TBL condition still exists in the
panel.
Active Status Active Status Reminder consists of two parts:
Reminder
• Reminder Interval. The range can be from 1 to 12 hours, and the default is 8 hours.
• Acknowledge Option. This option sets the duration of the acknowledge signal. The
range can be from 0 to 60 seconds, and the default is 5 seconds.

Audible and Visible ON until Silence Notification Appliance Circuits (NACs) can be set to
the choices shown below. The default setting for the Audible NACs is Temporal; the
default setting for the Visible NACs is Synchronous; and the default setting for
QuickAlert Horns is TEMPORAL.
Signal Operation • Audible NAC Operation – choices are temporal, steady, march time, slow march
time.
• Visible NAC Operation – choices are steady, march time, slow march time,
temporal, synchronous
• QuickAlert Horn Operation – choices are steady, temporal, slow march time.

A-3

Technical Manuals Online! - http://www.tech-man.com


Point Types

Introduction Some application-specific needs can also be met without Custom Control simply
by using the correct point types. A point’s type determines the following:

• The message displayed on the 4010’s LCD when changes occur to the state
of the point’s circuit.

• The way in which the system operates (for example, initiate an Alarm,
Trouble, or Supervisory action) when changes occur to the state of the
point’s circuit.

AHUF AHU off relay – dual relay control. This point type is used with applications
that use two auxiliary relays for AHU control – one relay for ON and one relay
for OFF. Use this point type for the OFF relay. Points assigned with this type
operate on general alarm (that is, when any point within L1 “General Alarm
List” goes into alarm). Point turns OFF on Reset.

Stagger Start functionality for air handler units is provided by the “Stagger
Start” system option.

See AHUO for the ON relay point type. If you have a single relay that performs
both ON and OFF functions, see AHUR.

Circuit Status LCD Display System Status


ON AHU OFF Relay ON
OFF AHU OFF Relay OFF
AHU OFF Relay CODING
Disabled TBL AHU OFF Relay TROUBLE
OFF AUTO TBL AHU OFF Relay TROUBLE

AHUO AHU on relay – dual relay control. This point type is used with applications that
use two auxiliary relays for AHU control – one relay for ON and one relay for
OFF. Use this point type for the ON relay. Points assigned with this type
operate on general alarm (that is, when any point within L1 “General Alarm
List” goes into alarm). Point turns OFF on Reset.

Stagger Start functionality for air handler units is provided by the “Stagger
Start” system option.

See AHUF for the OFF relay point type. If you have a single relay that
performs both ON and OFF functions, see AHUR.

Circuit Status LCD Display System Status


ON AHU ON Relay ON
OFF AHU ON Relay OFF
AHU ON Relay CODING
Disabled TBL AHU ON Relay TROUBLE
OFF AUTO TBL AHU ON Relay TROUBLE

Continued on next page

A-4

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

AHUR AHU on/off relay – single relay control. This point type is used with
applications in which a single relay performs AHU ON and OFF control. Points
assigned with this type operate on general alarm (that is, when any point within
L1 “General Alarm List” goes into alarm). Point turns OFF on Reset.

Circuit Status LCD Display System Status


ON AHU Relay ON
OFF AHU Relay OFF
AHU Relay CODING
Disabled TBL AHU Relay TROUBLE
OFF AUTO TBL AHU Relay TROUBLE

ALTERN Elevator capture – alternate. Used for a relay connected to the elevator controls
to provide alternate floor elevator recall. This relay turns ON when any of the
points in L5, Alternate Elevator Recall Zones, goes into alarm. Points with this
type turn OFF when the system is reset.

Circuit Status LCD Display System Status


ON ALT Elevator Recall ON
OFF ALT Elevator Recall OFF
ALT Elevator Recall CODING
Disabled TBL ALT Elevator Recall TROUBLE
OFF AUTO TBL ALT Elevator Recall TROUBLE

BSIGNAL Trouble/supervisory “bell” signal. Used when an audible signal should activate
on any supervisory or trouble condition and remain ON until the condition has
been acknowledged or cleared.

Circuit Status LCD Display System Status


ON Trouble Signal ON
OFF Trouble Signal OFF
Trouble Signal CODING
Disable TBL Trouble Signal TROUBLE
OFF AUTO TBL Trouble Signal TROUBLE

Continued on next page

A-5

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

DHOLDER Door holder control (normally off). Used when the auxiliary relay is connected
to door holders. The relay energizes on alarm (any point in L1 General Alarm
List goes into alarm), loss of AC Power, or when programmed.

Circuit Status LCD Display System Status


ON Door Holder ON
OFF Door Holder OFF
Door Holder CODING
Disable TBL Door Holder TROUBLE
OFF AUTO TBL Door Holder TROUBLE

PRIMARY Elevator capture – primary. Used for any relay connected to the elevator
controls to provide primary floor elevator recall. A relay assigned this point
type turns ON when any point in L4, Primary Elevator Recall, goes into alarm.
Relay turns Off on reset.

Circuit Status LCD Display System Status


ON Pri Elevator Capture ON
OFF Pri Elevator Capture OFF
Pri Elevator Capture CODING
Disable TBL Pri Elevator Capture TROUBLE
OFF AUTO TBL Pri Elevator Capture TROUBLE

QALERT QuickAlert signal. QALERT device type has no automatic operation. All
operations for this type of device type must be programmed with Custom
Control.

SQALERT SQALERT device type automatically turns on the designated circuit on alarm
detect (general alarm), issues the horn silence command upon Alarm Silence,
and turns off the circuit at the completion of System Reset. Any point
programmed with the SQALERT point type is not available for use in Custom
Control programming.

RELAY Generic relay – no default operation. Used for selective relay applications
(Custom Control) not defined by a specific point type. Point must be
programmed to turn ON and OFF.

Circuit Status LCD Display System Status


ON Auxiliary Relay ON
OFF Auxiliary Relay OFF
Auxiliary Relay CODING
Disable TBL Auxiliary Relay TROUBLE
OFF AUTO TBL Auxiliary Relay TROUBLE

Continued on next page

A-6

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

RSIGNAL Alarm signal – On until Reset. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
OFF AUTO TBLE Signal Circuit TROUBLE

RVISUAL Used only with visual notification appliances that must be ON until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).

Circuit Status LCD Display System Status


ON Visual ON
OFF Visual OFF
Visual CODING
Disable TBL Visual TROUBLE
Off Auto TBL Visual TROUBLE

RWATER Waterflow signal – On until Reset. A point with this type turns ON when any
point within L2, the Waterflow Alarm Monitor List, goes into alarm. Points
with this type turn OFF on System Reset.

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Off Auto TBL Visual TROUBLE

Continued on next page

A-7

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

SIGNAL Generic Alarm Signal – no default operation. Used for selective control
(Custom Control) of audible or visible notification appliances. Points assigned
with this point type operate on general alarm.

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
OFF AUTO TBLE Signal Circuit TROUBLE

SSIGNAL Alarm signal – On until Silence. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm (that is, when any point
within L1 General Alarm List goes into alarm). Points with this type turn OFF
when an Alarm Silence is performed.

Circuit Status LCD Display System Status


Normal Signal Circuit ON
Normal Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
OFF AUTO TBLE Signal Circuit TROUBLE

SUPREL Suppression release (agent discharge) output.

Circuit Status LCD Display System Status


Normal Signal Circuit ON
Normal Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE

SUPV Sprinkler supervisory signal. Turns ON when any point in L3 Sprinkler


Supervisory Monitor Points activates. Turns OFF on ACK or when the
supervisory clears. Example: Have a relay and its point type is SUPV, used to
set off a bell when a tamper is triggered or a gate valve is opened.

Circuit Status LCD Display System Status LED


Normal Signal Circuit ON
Normal Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE

Continued on next page

A-8

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

SVISUAL Visual – on until silence. Points assigned with this point type are ON when any
point within L1, General Alarm List, goes into alarm. Visual Notification
Appliances assigned this point type remain ON until an Alarm Silence is
performed.

Circuit Status LCD Display System Status


Normal Visual ON
Normal Visual OFF
Visual CODING
Disable TBL Visual TROUBLE
OFF AUTO TBL Visual TROUBLE

SWATER Waterflow signal – on until silence. Points with this point type turn ON when
any point in L2, Waterflow Alarm Monitor List, goes into alarm. Points remain
activated until the Alarm Silence.

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Disable TBL Signal Circuit TROUBLE

TSIGNAL Trouble/Supervisory Signal On until Clear. Points with this point type turn ON
when any trouble or supervisory condition occurs. Points turn OFF when the
trouble or supervisory condition is cleared.

Circuit Status LCD Display System Status


ON Signal Circuit ON
ON Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Disable TBL Signal Circuit TROUBLE

Continued on next page

A-9

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

BRELAY Trouble / Supervisory “Bell Relay.” A relay with this point type turns ON when
any Trouble or Supervisory condition occurs. Relays with this point type turn
OFF when the condition is acknowledged or cleared.

Circuit Status LCD Display System Status


ON ON
ON OFF
CODING
Disable TBL TROUBLE
Disable TBL TROUBLE

RRELAY Alarm Relay ON until Reset. A relay with this point type turns ON when any
point in L1, General Alarm List, goes into alarm. These relays turn OFF on
System Reset.

Circuit Status LCD Display System Status


ON ON
ON OFF
CODING
Disable TBL TROUBLE
Disable TBL TROUBLE

FIRE This is a generic fire alarm point type. A typical application for this point type
is a fire alarm zone containing more than one type of device. For example,
when a combination of smoke detectors, pull stations, waterflow monitors, and
heat detectors is connected to an IAM or ZAM, this point type allows alarms to
report as originating from a zone.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Fire Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Fire Alarm

When an Alarm or Trouble condition occurs, press Enter to view specific


information for the Fire Monitor Zone

WATER Used to define the operation of a waterflow monitor for all possible circuit
states.

Circuit Status LCD Text Status


Normal Normal
Limited Waterflow Monitor Fire Alarm
Open Waterflow Monitor Open Trouble
Short Waterflow Monitor Fire Alarm

Continued on next page

A-10

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

DUCT Used to define the operation of a duct detector for all possible circuit states.

Circuit Status LCD Text Status


Normal Normal
Limited Duct Detector Fire Alarm
Open Duct Detector Open Trouble
Short Duct Detector Fire Alarm

HEAT Defines the operation of a heat detector for all possible circuit states.

Circuit Status LCD Text Status


Normal Normal
Limited Heat Detector Fire Alarm
Open Heat Detector Open Trouble
Short Heat Detector Fire Alarm

FLAME Use for flame detectors.

Circuit Status LCD Text Status


Normal Normal
Limited Flame Detector Fire Alarm
Open Flame Detector Open Trouble
Short Flame Detector Fire Alarm

PULL Use with manual pull stations.

Circuit Status LCD Text Status


Normal Normal
Limited Manual Pull Station Fire Alarm
Open Manual Pull Station Open Trouble
Short Manual Pull Station Fire Alarm

SMOKE Use for 2- and 4-wire smoke detectors.

Circuit Status LCD Text Status


Normal Normal
Limited Smoke Detector Fire Alarm
Open Smoke Detector Open Trouble
Short Smoke Detector Fire Alarm

Continued on next page

A-11

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

EMERG Use for an emergency monitor zone in which two types of alarm devices – for
example, emergency alarm devices such as Nurse Call and fire alarm devices --
are connected to an IAM or ZAM. Emergency devices require the use of a
current limiting resistor. These devices generate an Emergency Alarm condition
at the panel.

Circuit Status LCD Text Status


Normal Normal
Limited Monitor Zone Emergency Alarm
Open Monitor Zone Open Trouble
Short Monitor Zone Fire Alarm

SFIRE Used when smoke detectors and shorting type devices are connected to an IAM
or ZAM.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Smoke Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Fire Alarm

VFIRE Used to activate the alarm verification software for all smoke detectors
connected to an IAM or ZAM. Shorting type devices cause an immediate alarm.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Verified Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Fire Alarm

SPULL Used when smoke detectors and pull stations are connected to an IAM or ZAM.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Smoke Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Manual Alarm

VSPULL Used when smoke detectors that must be verified and pull stations are connected
to an IAM or ZAM.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Verified Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Manual Alarm

Continued on next page

A-12

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

GENMON Used when emergency generator monitoring is required. The shorted condition
of the circuit indicates an abnormal status and is indicated by the Supervisory
Service LED. The current limited condition of the circuit indicates that the
generator is running, and can be tracked with an LED (must be programmed). A
current limiting resistor must be installed for this to happen.

Circuit Status LCD Text Status


Normal Normal
Limited Generator Monitor Running
Open Generator Monitor Open Trouble
Short Generator Monitor Abnormal

SGENMON Same operation as the GENMON point type, but the generator running condition
automatically displays and requires operator acknowledgment.

Circuit Status LCD Text Status


Normal Normal
Limited Generator Monitor Running
Open Generator Monitor Open Trouble
Short Generator Monitor Abnormal

FPUMP Used to monitor fire pump conditions. The shorted condition indicates that the
fire pump is abnormal A current limited condition indicates that the fire pump is
running.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Pump Monitor Running
Open Fire Pump Monitor Open Trouble
Short Fire Pump Monitor Abnormal

SFPUMP Same as the FPUMP point type, except that the fire pump running condition
requires operator acknowledgement.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Pump Monitor Running
Open Fire Pump Monitor Open Trouble
Short Fire Pump Monitor Abnormal

S2STAGE Used for 2-stage alarms. The current limited operation of any device indicate a
Stage 1 Alarm. A short on the point’s circuit, such as a key switch operation,
causes a Stage 2 Alarm.

Circuit Status LCD Text Status


Normal Normal
Limited 2 Stage Monitor Stage 1 Alarm
Open 2 Stage Monitor Open Trouble
Short 2 Stage Monitor Stage 2 Alarm

Continued on next page

A-13

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

SO Used to indicate abnormal sprinkler conditions, such as the opening of a PIV or


OS&Y tamper switch. This point type must be used with normally open
contacts only.

Circuit Status LCD Text Status


Normal Normal
Limited Sprinkler Monitor Abnormal
Open Sprinkler Monitor Open Trouble
Short Sprinkler Monitor Abnormal

WSO Combination Waterflow/Sprinkler Monitor (NO). Where permitted by the AHJ,


this circuit operates both waterflow monitors and PIV/OS&Y tampers on the
same circuit. All tamper switches (N.O. contacts) must be connected with a
current limiting resistor. Refer to the 4010 field wiring diagrams. A short
condition indicates waterflow alarms.

Circuit Status LCD Text Status


Normal Normal
Limited Sprinkler Monitor Abnormal
Open Sprinkler Monitor Open Trouble
Short Sprinkler Monitor Waterflow Alarm

SUPDET Suppression (Agent Discharge) Monitor.

Circuit Status LCD Text Status


Normal Normal
Limited Suppression Detector Fire Alarm
Open Suppression Detector Open Trouble
Short Suppression Detector Fire Alarm

SUPABRT Suppression Abort (supervised)

Circuit Status LCD Text Status


Normal Normal
Limited Suppression Abort Activated
Open Suppression Abort Open Trouble
Short Suppression Abort Short Trouble

SUPDUMP Manual suppression agent discharge

Circuit Status LCD Text Status


Normal Normal
Limited Suppression Manual Dump Activated
Open Suppression Manual Dump Open Trouble
Short Suppression Manual Dump Short Trouble

Continued on next page

A-14

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

SUPPRES Suppression agent pressure switch monitor.

Circuit Status LCD Text Status


Normal Normal
Limited Suppression Pressure Discharge
Open Suppression Pressure Open Trouble
Short Suppression Pressure Short Trouble

SUPV Used to monitor any supervisory type device where operator acknowledgment is
required.

Circuit Status LCD Text Status


Normal Normal
Limited Supervisory Monitor Abnormal
Open Supervisory Monitor Open Trouble
Short Supervisory Monitor Abnormal

UTIL Used to monitor and supervise any condition; operator acknowledgment is not
required. No alarm is generated by this point type.

Circuit Status LCD Text Status


Normal Normal
Limited Utility Monitor Abnormal
Open Utility Monitor Open Trouble
Short Utility Monitor Abnormal

TROUBLE Used for trouble monitoring only. No alarm is generated by this point type.

Circuit Status LCD Text Status


Normal Normal
Limited Trouble Monitor Abnormal
Open Trouble Monitor Open Trouble
Short Trouble Monitor Abnormal

VSMOKE Used with smoke detectors whose alarm status must be verified.

Circuit Status LCD Text Status


Normal Normal
Limited Smoke Detector Verified Alarm
Open Smoke Detector Open Trouble
Short Smoke Detector Fire Alarm

Continued on next page

A-15

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

GVMON Used when the abnormal condition of the circuit must be verified.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Verified Alarm
Open Fire Monitor Open Trouble
Short Fire Monitor Fire Alarm

LATSUPV Supervisory Monitor – latch until reset. Used for generic supervisory alarm.

Circuit Status LCD Text Status


Normal Normal
Limited Supervisory Alarm Abnormal
Open Supervisory Alarm Open Trouble
Short Supervisory Alarm Abnormal

STYLEC Style-C Fire Alarm Monitor. Used when only current limited devices are
connected to the zone. A short circuit is reported as a Trouble.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Fire Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Short Trouble

SDUCT Supervisory Duct Detector.

Circuit Status LCD Text Status


Normal Normal
Limited Flame Detector Abnormal
Open Flame Detector Open Trouble
Short Flame Detector Abnormal

ABORT Abort zone.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Alarm Abort Abnormal
Open Fire Alarm Abort Open Trouble
Short Fire Alarm Abort Abnormal

DAMPER Damper Monitor

Circuit Status LCD Text Status


Normal Normal
Limited Damper Monitor Abnormal
Open Damper Monitor Open Trouble
Short Damper Monitor Abnormal

Continued on next page

A-16

Technical Manuals Online! - http://www.tech-man.com


Point Types, Continued

4009A 4009A Point Type.

Circuit Status LCD Text Status


Normal Normal
Limited 4009A Abnormal
Open 4009A Open Trouble
Short 4009A Abnormal

USWITCH 2-position switch, unsupervised. Used for a 2-position switch without an EOL
or current limited resistor.

Circuit Status LCD Text Status


Normal OFF
Limited 2-Position Switch Invalid State TBL
Open 2-Position Switch ON
Disable TBL 2-Position Switch Disable TBL

OSWITCH 2-position switch, supervised for opens. Requires an EOL resistor.

Circuit Status LCD Text Status


Normal OFF
Limited 2-Position Switch Invalid State TBL
Open 2-Position Switch Open CKT TBL
Short 2-Position Switch ON
Disable TBL 2-Position Switch Disable TBL

SSWITCH 2-position switch, supervised for opens and shorts. Requires EOL and current
limited resistors.

Circuit Status LCD Text Status


Normal OFF
Limited 2-Position Switch ON
Open 2-Position Switch Open CKT TBL
Short 2-Position Switch SHORT CKT TBL
Disable TBL 2-Position Switch Disable TBL

TSWITCH 3-position (SPDT) switch, supervised for opens. Requires EOL and series
current limiting resistors (up leg).

Circuit Status LCD Text Status


Normal CENTER
Limited 3-Position Switch UP
Open 3-Position Switch Open CKT TBL
Short 3-Position Switch DOWN
Disable TBL 3-Position Switch Disable TBL

A-17

Technical Manuals Online! - http://www.tech-man.com


This is the Font

A-18

Technical Manuals Online! - http://www.tech-man.com


Index

4 H
4010 HEAT point type, A-11
limitations of Custom Control, 1-1 horn off opcode, 2-16
system options and point types for, 1-2 horns
and QuickAlert, 1-3
A
L
ABORT point type, A-16
active status reminder system option, A-3 LATSUPV point type, A-16
AHU stagger start system option, A-3 list L6 , off on silence, 2-3
AHUF point type, A-4 list L7, off on reset, 2-4
AHUO point type, A-4
AHUR point type, A-5
alarm cutout timer system option, A-2
N
alarm silence inhibit system option, A-2 NACs
ALTERN point type, A-5 device types and point types, 2-3

B O
BRELAY oswitch point type, 2-17
point type, A-10 overview, 1-1

C P
Custom Control point types, 1-2, A-4
capacities of, 1-2 4009A, A-17
limitations of for 4010, 1-1 ABORT, A-16
AHUF, A-4
D AHUO, A-4
AHUR, A-5
day/night programming application, 4-8 ALTERN, A-5
depleted battery system option BRELAY, A-10
depleted battery, A-2 BSIGNAL, A-5
device types DHOLDER, A-6
summary of, A-1 DUCT, A-11
DHOLDER point type, A-6 EMERG, A-12
door drop on AC fail system option, A-3 FIRE, A-10
door drop on alarm system option, A-2 FLAME, A-11
DUCT point type, A-11 FPUMP, A-13
GENMON, A-13
GVMON, A-16
E HEAT, A-11
elevator recall application, 4-11 LATSUPV, A-16
EMERG point type, A-12 OSWITCH, A-17
PRIMARY, A-6
PULL, A-11
F QALERT, A-6
FIRE RELAY, A-6
point type, A-10 RRELAY, A-10
FLAME point type, A-11 RSIGNAL, A-7
FPUMP point type, A-13 RVISUAL, A-7
RWATER, A-7
S2STAGE, A-13
G SDUCT, A-16
SFIRE, A-12
general alarm shutdown for fans and dampers, 4-14
SFPUMP, A-13
GENMON point type, A-13
SGENMON, A-13
GVMON point type, A-16
SIGNAL, A-8
SMOKE, A-11
SO, A-14

IN-1

Technical Manuals Online! - http://www.tech-man.com


SPULL, A-12 SFIRE point type, A-12
SQALERT, A-6 SFPUMP point type, A-13
SSIGNAL, A-8 SGENMON point type, A-13
SSWITCH, A-17 SIGA device type, 2-3
STYLEC, A-16 SIGB device type, 2-3
summary of, A-1 signal operation system option, A-3
SUPABRT, A-14 SIGNAL point type, 2-3, A-8
SUPDET, A-14 single station
SUPDUMP, A-14 custom control equations for, 2-22
SUPPRES, A-15 device types of, 2-21
SUPREL, A-8 selective activation of, 2-21
SUPV, A-8, A-15 SmartSync, 1-3
SVISUAL, A-9 SMOKE point type, A-11
SWATER, A-9 SO point type, A-14
TROUBLE, A-15 SPULL point type, A-12
TSIGNAL, A-9 SQALERT point type, A-6
TSWITCH, A-17 SSIGNAL point type, A-8
USWITCH, A-17 sswitch point type, 2-17
UTIL, A-15 stagger start system option, A-3
VFIRE, A-12 strobes
VSMOKE, A-15 for QuickAlert, 1-3
VSPULL, A-12 STYLEC point type, A-16
WATER, A-10 SUPABRT point type, A-14
WSO, A-14 SUPDET point type, A-14
pre-signal application, 4-2 SUPDUMP point type, A-14
QuickAlert NACs, 4-5 SUPPRES point type, A-14
standard NAC example, 4-4 suppression release, 3-1
PRIMARY point type, A-6 default applications, 3-2
PULL point type, A-11 dual detector, pre-signal, abort switch with delay, 3-8
dual detector, pre-signal, abort switch with no delay, 3-5
field wiring diagrams and STRM, 3-1
Q triggered by dual automatic detectors, 3-2
QALERT point type, 2-3, A-6 triggered by single device, 3-2
QuickAlert, 1-3 suppression release point types, 3-2
class A guidelines, 1-3 suppression release system options, A-3
Class B guidelines, 1-4 SUPREL point type, A-8
QuickAlert Class A, 1-3 SUPRES point type, A-15
QuickAlert Class B, 1-3 SUPV point type, A-8, A-14, A-15
SVISUAL
point types, A- 9
R SWATER
related documentation, 1-1 point types, A-9
related documents, 1-1 system option
RELAY point type, A-6 door drop on alarm, A-2
RRELAY system options, 1-2
point type, A-10 active status reminder, A-3
RSIGNAL point types, A-7 AHU stagger start, A-3
RVISUAL point types, A-7 alarm cutout timer, A-2
RWATER point types, A-7 alarm silence inhibit, A-2
depleted battery, A-2
door drop on AC fail, A-3
S signal operation, A-3
summary of, A-2
S2STAGE point type, A-13
suppression release, A-3
SDUCT point type, A-16
time format, A-2
selective bypass of NAC/Relay circuits, 2-17
QuickAlert NAC example, 2-19
standard NAC example, 2-19 T
selective city circuit activation, 4-13
selective signaling time format system option, A-2
by floor, 2-2 TROUBLE point type, A-15
selective signaling by area, 2-7 TSIGNAL
QuickAlert Class A/Class B example, 2-10 point types, A-9
standard NAC example, 2-9 tswitch point type, 2-17
selective signaling by fire floor, 2-12
selective signaling by floor
QuickAlert Class A/Class B example, 2-5, 2-16
standard NAC example, 2-4, 2-14

IN-2

Technical Manuals Online! - http://www.tech-man.com


U
uswitch point type, 2-17
UTIL point type, A-15
utility monitoring point application, 4-6

V
VFIRE point type, A-12
VSMOKE point type, A-15
VSPULL point type, A-12

W
WATER
point type, A-10
WSO point type, A-14

IN-3

Technical Manuals Online! - http://www.tech-man.com


This is white text

Rev. A Simplex Time Recorder Co., • Simplex Plaza • Gardner, Massachusetts 01441-0001 U.S.A. 574-908
Simplex International Time Equipment Co., LTD. • Mississauga, Ontario, Canada

Technical Manuals Online! - http://www.tech-man.com

You might also like