4010 Applications Manual Rev A
4010 Applications Manual Rev A
Applications Manual
574-908
Rev. A
• Same as UL above.
Local Approvals
• CSFM
• MEA
Chapter 1. Overview
Overview................................................................................................... 1-1
Related Documentation............................................................................. 1-1
In this Chapter........................................................................................... 1-1
Selective Signaling by Fire Floor, Floor Above, and Floor Below............. 2-12
Overview................................................................................................. 2-12
Step 1. Define NAC’s Device Types / Point Types / Custom Label...... 2-12
Step 2. Define Device Types, Point Types, and Custom Labels for
Initiating Devices ...................................................................... 2-13
Step 3. Add Appropriate NACs to List L6 (Off On Silence) ................. 2-13
Step 4: Add Appropriate NACs to List L7 (Off On Reset).................... 2-14
Step 5. Add Each Floor’s Initiating Devices to a User-Defined List .... 2-14
Step 6. Add NACs to User-Defined Lists ............................................. 2-14
Step 7. Add Custom Control Equations ................................................. 2-14
viii
Related Documentation Additional information related to 4010 Version 2.x can be found in the
following documents:
In this Chapter Refer to the following page for specific information on a topic.
1-1
Introduction The 4010 is best used in small to medium size buildings up to 6 stories. Some
of the best uses for the 4010 are:
• K - 12 educational facilities
• Nursing homes and small hospitals
• Board and care facilities
• Inns, motels and small hotels
• Assisted living
• Apartments and condominiums
• Office buildings
• Strip malls
Understand the Details of the Judging whether the 4010 can meet the application requirements of a job
Intended Application requires a detailed understanding of the facilities’ devices (both fire and utility),
as well as an understanding of exactly how the customer and the AHJ expect the
system to function.
In general, the following guidelines can help you determine whether the 4010
can handle the application-specific needs of a facility.
Understand the Built-in The 4010 System Options, Point Types, and Modes provide default fire alarm
Functionality Provided by system operation for common fire alarm system applications without the need
System Options and Point for writing more complex Custom Control programming equations. Whenever
Types possible System Options, Point Types, and Modes should be used in lieu of
Custom Control to provide the required operation. Custom Control
programming is available to provide additional flexibility and to meet job-
specific requirements.
1-2
Overview The term QuickAlert with SmartSync operation refers to a family of Simplex
A/V and VO notification appliances that allow both horns and the synchronized
strobes to work independently on a two-wire notification appliance circuit. The
strobes operate in an “On until Reset” mode and the horns operate in an “On
until Silence” mode. All references to QuickAlert in this document are in
regards to QuickAlert with SmartSync operation.
Class A QuickAlert Class A QuickAlert with SmartSync operation depends on the following:
• All strobes must be Simplex synchronized VO, not free run. All A/Vs,
must be QuickAlert SmartSync compatible. Other manufacturer’s
appliances are not compatible on a SmartSync, two-wire circuit.
• For a General Alarm operation, the “loading” NAC must use a point
type of RSIGNAL (Off on Reset) while the “Horn Control” NAC must
use a point type of SSIGNAL (Off on Silence).
1-3
Class B QuickAlert Class B QuickAlert with SmartSync operation depends on the following factors:
• All strobes must be Simplex synchronized VO, not free run. All
A/V’s, must be QuickAlert SmartSync compatible. Other
manufacturer’s appliances are not compatible on a QuickAlert
SmartSync two-wire circuit.
Blank Page
1-4
Overview Selective signaling replaces the system’s general alarm NAC operation – which
activates all NACs in response to any alarm condition – with selective NAC
control. This type of control allows you to program the system so that only
specific NACs respond to specific initiating devices.
In this Chapter Refer to the following page for specific information on a topic.
2-1
Overview Selective Signaling by Floor limits the activation of NACs to the floor on which
an activated initiating device(s) is located. When activated, audible NAC
appliances sound a temporal code until Alarm Silence, and visible NAC
appliances flash until System Reset.
In Figure 2-1, for example, an activated initiating device on Floor 2 triggers only
the NACs located on Floor 2.
Step 1. Define NAC’s Device The NACs used with the Selective Signaling by Floor application can be either
Type, Point Type, and Custom the NACs located on the panel’s SFIO board or NACs located on a 4009 IDNet
Label NAC Extender.
Use the PC Programmer to program the NACs with the device types and point
types listed in Table 2-1. When defining custom labels make sure to use
descriptive labels, such as “Floor1-Visual-Circuit.”
2-2
Step 2. Assign Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels to Initiating Devices Programmer Installation and Programming Instructions, for information on
programming an initiating device’s device type and point type. Refer to “Point
Types” in Appendix A of this manual for detailed descriptions of the initiating
device point types.
Step 3. Add Appropriate Skip this step if you are using Class B QuickAlert NACs. Use the PC
NACs to List L6 (Off On Programmer’s List Tab to add the following to List L6 (Control Points, Off on
Silence) Silence). Members of this list automatically turn off when an Alarm Silence is
performed.
2-3
Step 4: Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off on Reset) Points Off on Reset). Members of this list automatically turn off when a System
Reset is performed.
Step 5. Add Floor’s Initiating Adding each floor’s initiating devices to a separate user-defined list limits the
Devices to a User-Defined List number of Custom Control equations that must be written to perform Selective
Signaling by Floor. To add these devices to a list, use the PC Programmer’s List
Tab, adding each floor’s initiating devices to one of the available user-defined
lists (L26 through L50).
Step 6. Add Custom Control This section describes programming the Selective Signaling by Floor application
Equations using either standard NAC appliances or Class A/Class B QuickAlert NAC
applicances. Refer to the applicable section below for specific information.
• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Floor 1.
The first output statement programs the floor’s audible NACs to emit a
temporal signal when any point within list L26 enters an ALARM
condition. Because the audible NACs were added to the Control Points –
Off on Silence list, they stop sounding when an Alarm Silence occurs.
The second output statement programs the floor’s visible NACs to activate
when any point within list L26 enters an ALARM condition. Because the
visible NACs were added to the Control Points – Off on Reset list (L7),
they stop flashing when a System Reset occurs.
• Equation 2. The input side of this equation monitors the FIRE DETECT
state of list L27, which is a user-defined list containing all initiating devices
for Floor 2.
The first output statement programs the floor’s audible NACs to emit a
temporal signal when any point within list L27 enters an ALARM
condition. Because the audible NACs were added to the Control Points –
Off on Silence list, they stop sounding when an Alarm Silence occurs.
The second output statement programs the floor’s visible NACs to activate
when any point within list L27 enters an ALARM condition. Because the
visible NACs were added to the Control Points – Off on Reset list (L7),
they stop flashing when a System Reset occurs.
Equation 1
Equation 2
• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Floor 1. The output side of Equation 1 programs the floor’s QuickAlert
NACs to operate when any point within list L26 enters an ALARM
condition.
• Equation 2. The input side of this equation monitors the FIRE DETECT
state of list L27, which is a user-defined list containing all initiating devices
for Floor 2. The output side of Equation 2 programs the floor’s QuickAlert
NACs to operate when any point within list L27 enters an ALARM
condition.
Important Notes:
2-5
Equation 3
2-6
Overview Selective Signaling by Area limits the activation of NACs to the area in which
the activated initiating device (smoke detector, pull station, etc.) is located. In
the following figure, for example, the initiating devices in Area 1 trigger only
the NACs located in Area 1, the initiating devices in Area 2 activate only the
NACs located in Area 2, etc.
AREA 1 AREA 2
AREA 3 AREA 4
Step 1. Define NAC’s Device The NACs used with the Selective Signaling by Area application can be either
Types / Point Types / Custom the NACs located on the panel’s SFIO board or the NACs located on a 4009
Labels IDNet NAC extender.
Use the PC Programmer to program the NACs with the following device types
and point types. When defining custom labels, make sure to use descriptive
labels, such as “AREA1-VISUAL-CIRCUIT.”
2-7
Step 2. Assign Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels to Initiating Devices Programmer Installation and Programming Instructions, for information on
programming an initiating device’s device type and point type. Refer to “Point
Types” in Appendix A of this manual for detailed descriptions of the initiating
device point types.
Step 3. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.
2-8
Step 4: Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.
Step 5. Add Area’s Initiating Adding the area’s initiating devices to a list limits the number of Custom
Devices to a User-Defined List Control equations that must be written to perform Selective Signaling by Area.
To add these devices to a list, use the PC Programmer’s List Tab, adding each of
the area’s initiating device to one of the available user-defined lists (L26 through
L50). Naming a list (AREA1-INITIATING DEVICES, for example) is done via
the Card Tab and cannot be done through the List Tab.
Step 6. Add Custom Control This section describes programming the Selective Signaling by Area application
Equations using either standard NAC appliances or Class A/Class B QuickAlert NAC
applicances. Refer to the applicable section below for specific information.
• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Area 1.
The first output statement in Equation 1 programs Area 1’s audible NACs
to sound a temporal signal when any point within list L26 enters an
ALARM condition. Because the audible NACs were added to the Control
Points – Off on Silence list, they stop sounding when an Alarm Silence
occurs.
• Equation 2. The input side of this equation monitors the FIRE DETECT
state of list L27, which is a user-defined list containing all initiating devices
for Area 2.
The first output statement in Equation 2 programs Area 2’s audible NACs
to sound a temporal signal when any point within list L27 enters an
ALARM condition. Because the audible NACs were added to the Control
Points – Off on Silence (Step 3 above), they stop sounding when an Alarm
Silence occurs.
2-9
Step 6. Add Custom Control The second output statement in Equation 2 programs the visible NACs to flash
Equations (continued) when any point within L27 enters an ALARM condition. Because the visible
NACs were added to the Control Points – Off on Reset list (Step 4 above), they
stop flashing when a System Reset occurs.
Equation 1
Equation 2
• Equation 1. The input side of this equation monitors the FIRE DETECT
state of list L26, which is a user-defined list containing all initiating devices
for Area 1.
The first output statement in this equation turns the QuickAlert horns OFF
(using the Horn OFF opcode) when P26 is ON (i.e., following an Alarm
Silence).
The second output statement in this equation resets the P26 pseudo point to
its OFF state.
2-10
Note: Use
HOLD
Equation 1 TEMPORAL
for Class B.
Use HOLD
ON for
Class A
Equation 2
2-11
Overview This application limits the activation of NACs to the floor on which the
activated initiating device is located, referred to as the fire floor, and the floors
immediately above and below the fire floor.
Step 1. Define NAC’s Device The NACs used with this application can be either the NACs located on the
Types / Point Types / Custom panel’s SFIO board or the NACs located on a 4009 IDNet NAC extender.
Label
Use the PC Programmer to program the NACs with the following device types
and point types. When defining custom labels, make sure to use descriptive
labels, such as “FLOOR-1 AUDIBLE NACS.”
2-12
Step 1. Define NAC’s Device Table 2-3. NAC Device Types and Point Types
Types / Point Types / Custom
Label (continued) Option Explanation
Use for standard (non-QuickAlert)
Class A NAC. This type of NAC contains
multiple signal paths, allowing circuit
operation to continue if a single open
SIGA circuit occurs. This device type requires
installation of a Class A NAC adapter
NAC card. Important Note: Do not use this
Device device type for Class A QuickAlert
Type applications.
Use for the following:
- Standard (non-QuickAlert) Class B
SIGB NAC.
- QuickAlert Class B NAC.
- QuickAlert Class A NAC.
Step 2. Define Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels for Initiating Devices Programmer Installation and Programming Instructions, for information on
programming an initiating device’s device type and point type. Refer to “Point
Types” in Appendix A of this manual for detailed descriptions of the initiating
device point types.
Step 3. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.
2-13
Step 4: Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.
Step 5. Add Each Floor’s Adding each floor’s initiating devices to a separate list limits the number of
Initiating Devices to a Custom Control equations required to implement this application. To add a
User-Defined List floor’s initiating devices to a list, use the PC Programmer’s List Tab, adding
each floor’s initiating device to a separate user-defined list (L26 through L50).
Step 6. Add NACs to For a multi-story facility containing a large number of NAC circuits, add each
User-Defined Lists floor’s NACs to a separate user-defined list. Doing this limits the number of
Custom Control equations required to implement this application. To add a
floor’s NACs to a list, use the PC Programmer’s List Tab, adding each floor’s
NACs to a separate user-defined list (L26 through L50).
Step 7. Add Custom Control This section describes programming the Selective Signaling by Fire Floor
Equations application using either standard NAC appliances or Class A/Class B
QuickAlert NAC applicances. Refer to the applicable section below for specific
information.
Each of the four equations functions in the same manner. The input side
monitors a list of initiating devices for the floor. If any point within the list goes
into ALARM, the output side activates the NACs for the appropriate set of
floors.
2-14
Equation 1
Equation 2
Equation 3
Equation 4
Figure 2-7. Fire Floor, Floor Above, and Below with Standard NACs
2-15
Step 7. Add Custom Control QuickAlert Class A / Class B NAC Example. The following example,
Equations (continued) shown in Figure 2-8, illustrates how to implement this application for a four-
story building that uses QuickAlert NAC appliances.
The first four equations monitor the state of each floor’s initiating devices. The
output side of each equation activates the appropriate list of NACs as required.
Important Note: Use HOLD ON for Class A QuickAlert devices; use HOLD
TEMPORAL for Class B QuickAlert devices.
The last equation monitors the state of P26, the Alarm Silence Activated pseudo
point. If this point is ON (i.e., following an Alarm Silence), the output executes,
issuing the HORN OFF command to silence all audible QuickAlert NAC
appliances. HORN OFF opcode is only required for Class B QuickAlert NAC
applications. This equation is not required for Class A QuickAlert NAC
applications. Important Note: You cannot associate a list containing NACs
with the Horn OFF command, you must associate specific NACs with the
command.
The last output statement at the bottom of the sample screen resets the P26
pseudo point to its OFF state. Note: Resetting P26 is very important.
Note: Use
HOLD
TEMPORAL
for Class B.
Use HOLD
ON for Class
A
Figure 2-8. Fire Floor, Floor Above, and Below with QuickAlert
NACs
2-16
Overview The Selective Bypass of NAC/Relay Circuits application allows a 24 Point I/O
switch to override the automatic operation of NACs and door holder relays (i.e.,
horns/strobes do not automatically turn ON and doors do not close when an
alarm condition occurs). This application also causes a Trouble to appear at the
panel to indicate that the bypass switch is active.
Step 1. Define Switch Use the PC Programmer application to program the following switch attributes.
Attributes
• Device Type. Select the GRAPHIN device type, which indicates that the
device being programmed is a 24 Point I/O switch.
• Point Type. Any of the following switch point types can be used.
- OSWITCH. Specifies a two-position switch, supervised for open
circuits. Requires an EOL resistor.
- SSWITCH. Specifies a two-position switch, supervised for open and
short circuits. Requires EOL and current limited (up leg) resistors.
- TSWITCH. Three position (SPDT) switch, supervised for open
circuits. Requires EOL and current limited resistors.
- USWITCH. Two-position switch, unsupervised. Assumes that no
EOL or current limited resistor is used.
• Mode. Select the ONOFF mode. This mode allows one position of the
switch to represent the ON state and another position to represent the OFF
state. Refer to Table 2-4 for information on which switch position is
equivalent to ON or OFF.
• Reference Address. Select a user-defined digital pseudo point. A
Custom Control equation will monitor this point to determine if the signals
should be bypassed or not.
* When the I/O point’s status is viewed from the LCD panel (using
Control/View Points menu selection), this is the state that appears when the
switch is in the ON or OFF position.
2-17
Step 2. Define Digital Pseudo Define the attributes of the digital pseudo point used as the Reference Address
Point Attributes in Step 1 above as follows:
• Point Type. Define the point type of the digital pseudo point as
TROUBLE. This programs the system to display a system trouble if the
switch is active (ON).
Step 3. Add the Floor’s Add the initiating devices for the floor or area that you want to bypass to a list.
Initiating Devices to a List Doing this limits the number of Custom Control equations required. To add a
floor’s initiating devices to a list, use the PC Programmer’s List Tab.
Step 4. Change the Point Use the PC Programmer to program the NACs and Door Holder relays with the
Type of NACs and Door following point types. (Do not program the door holders with a door holder
Relays point type such as DHOLDER. Door holder point types are used to specify the
automatic operation of the relay, not its custom operation.) When defining
custom labels, make sure to use descriptive labels, such as “FLR-1 AUDIBLE-
NAC.”
Step 5. Add the NACs and Add the NACs and Door Relays that you want to bypass to a list. Doing this
Door Relays to a List allows the Custom Control equation to refer to the floor’s entire set of NACs
and Relays as a single point. This limits the number of equations required to
implement the bypass function.
Step 6. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.
2-18
Step 7. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.
Step 8. Add Custom Control This section illustrates how to implement Selective Bypass of NAC/Relay
Equations Circuits for a facility that uses either standard NACs or Class A and Class B
QuickAlert NACs. Refer to the appropriate section below.
Standard NACs. The first two input statements, separated by the AND
operator, check whether there is an activated initiating device and whether the
bypass switch (monitored by pseudo P76) is active. The NACs activate when
the following conditions are both true, and do not activate if either is false.
QuickAlert NACs. Figure 2-10 shows how to implement the selective bypass
application with Class A or Class B QuickAlert NACs. As with the Standard
NACs example, the first two input statements check whether there is an
activated initiating device and whether the bypass switch (monitored by pseudo
P76) is active.
The NACs activate when the following conditions are both true, and do not
activate if either is false. Use HOLD TEMPORAL for Class B QuickAlert
NACs; use HOLD ON for Class A QuickAlert NACs.
2-19
Step 8. Add Custom Control The second equation checks the ON/CODING state of P26, which is ON when
Equations (continued) Alarm Silence is active. If P26 is ON (i.e., an Alarm Silence has occurred), the
HORN OFF command executes, turning off the QuickAlert Horns. Be aware
that you cannot associate a list with the HORN OFF command; you must
specify the specific NAC points (for example, SIG1, etc.).
The last output qualifier resets the state of P26. Note: Resetting P26 is
very important. Do not leave this step out.
Use Hold
ON for
Class A
Use Hold
Temporal
for Class B
2-20
Introduction Single station smoke detectors -- typically used in hotel rooms, dormitories, and
hospital rooms -- contain their own sounder. When activated, only the sounder
on the activated device signals the presence of an alarm condition. This
application describes programming the 4010 so that when a manual pull station
activates, all single station devices in the area also activate.
Step 1. Define Device Types, Use the PC Programmer’s Point tab to program each Single Station Device with
Point Types, and Mode for the following attributes:
Single Station Devices
• Device Type. A single station device can use any one of the following
device types:
• Point Type. Any of the standard point types may be used, including
DUCT, GVMON, SDUCT, SMOKE, UTIL, VSMOKE. Refer to Appendix
A of this manual for the function of these point types.
• Mode. The default mode setting for a TrueAlarm device equipped with
sounder is SSTATION (Single Station), which is required to support single
station operation.
Step 2. Add Area’s Pull Adding each area’s pull stations to a separate list limits the number of Custom
Stations to a User-Defined Control equations required to implement this application. To add an area’s pull
List stations to a list, use the PC Programmer’s List Tab.
Step 3. Add Custom Control Programming selective activation of single station devices requires two
Equations equations, as shown in Figure 2-11.
2-21
Step 3. Add Custom Control Equation 1. This equation uses a single input qualifier to monitor List L26,
Equations (continued) which contains all of Floor 1’s pull stations. If any pull station within this list
activates, this equation’s output qualifiers execute. The first output qualifier
programs the tone used by the single station sounders when they activate. The
second output qualifier turns on the sounders in the area of the activated pull
station.
Note: You cannot put single station devices in a list; each device must be
separately listed in the Custom Control program, as shown in Figure 2-11.
Equation 2. The input qualifier used in this equation monitors the state of P26,
which is ON if an Alarm Silence has been performed. The output qualifiers
only execute when P26 is ON (i.e., following Alarm Silence). The first output
qualifier, Device Code OFF, turns off the sounders on the single station devices.
The second output qualifier resets the state of P26.
Note: Resetting P26 is very important. Do not leave this step out.
Equation 1
Equation 2
2-22
Overview This chapter describes the 4010 programming required for common
suppression-release applications.
Before continuing, make sure that you have the following information:
In this Chapter Refer to the following page for specific information on a topic.
3-1
Suppression Release The application described in this section is used in situations that require the
Triggered by Single Pull release of the suppression agent immediately (or slightly delayed by a timer)
Station or Automatic Initiating after alarm activation. A typical use is for a fueling station equipped with a
Device manual release station and flame detectors. An important point to note with this
application is that it does not use either an abort switch or a NAC pre-signal that
indicates imminent release of the agent.
ALARM ACTIVATION
Timer
0-30 for Pull
0-60 for Auto.
DISCHARGE SIGNALS
SOLENOID ACTIVATION
Suppression Release Some situations require additional verification of an alarm condition (i.e., two
Triggered by Dual Automatic automatic initiating devices must activate) before the release of the suppression
Initiating Devices agent can occur.
3-2
Suppression Release
Triggered by Dual Automatic
Initiating Devices (continued)
1ST AUTOMATIC INITIATING
DEVICE
RELEASE TIMER
DISCHARGE
SIGNALS
SOLENOID ACTIVATION
Programming Default Programming the suppression component of either default application is done
Applications with the system’s built-in suppression release options, suppression point types,
and suppression lists.
2. Use the PC Programmer’s Point Tab to assign suppression points with the
point types listed below. Refer to Appendix A for specific details on these
point types.
3-3
Programming Default 3. Use the PC Programmer’s List Tab to add the initiating devices and output
Applications (continued) points to the appropriate lists, as follows:
3-4
Introduction The application described in this section provides the following suppression
operation.
• At any time prior to the actual release of the agent, an operator can prevent
the release of the suppression agent by pressing an abort switch. Release of
the suppression agent is prevented for the duration of time this switch is
held. Release of the suppression agent occurs immediately after release of
the abort switch, assuming the timers discussed in the previous bullet have
expired. Operators should be made aware that if the alarm is false, clearing
the alarm condition and resetting the system prior to releasing the switch
prevents agent discharge.
Figure 3-3 shows a timeline for this application. First stage signals activate
following the first stage alarm condition (which is always an automatic initiating
device). Second stage signals activate following the activation of either a
second automatic initiating device or following activation of a manual release
station. The second alarm condition (or the manual pull station) also triggers the
optional release timer, if used. This timer ranges from 0-30 seconds for a
manual release station and 0-60 seconds for an automatic initiating device.
Suppression is delayed until the release timer expires or the abort switch is
released, at which time the signals convert to a discharge tone and the solenoid
activates.
3-5
Introduction (continued)
1St STAGE ALARM
CONDITION
RELEASE TIMER
2ND STAGE
DISCHARGE SIGNALS
SOLENOID
ACTIVATION
Automatic System
Initiating Reset
Device
Activated
Programming System Programming the suppression component of either default application is done
Options, Point Types, and with a combination of Custom Control and the system’s built-in suppression
Lists release options, suppression point types, and suppression lists.
2. Use the PC Programmer’s Point Tab to assign suppression points with the
point types listed below. Refer to Appendix A for specific details on these
point types.
3-6
Programming System 3. Use the PC Programmer’s list tab to add the initiating devices and output
Options, Point Types, and points to the appropriate lists, as follows:
Lists (continued)
List Add These Points
L9 Automatic Suppression Release Points. Add all automatic
initiating devices whose activation should result in the release
of the suppression agent.
L10 Suppression Manual Release Points. Add all manual
suppression release points whose activation should result in
the release of the suppression agent.
L11 Suppression Release Abort Points. Add all abort switch
points to this list.
L12 Suppression Release Output Points. Add the NACs that
control the suppression release solenoids.
Programming Custom Control The following example, shown in Figure 3-4, illustrates how to implement this
application.
• Equation 1. The input side of this equation monitors the FIRE state of list
L9, which is a system list containing all suppression-related automatic
initiating devices. The output side of Equation 1 programs the NAC
appliances to sound in SLOW MARCH TIME when any point within list
L9 enters an ALARM condition.
3-7
Introduction The application described in this section operates in the following way.
Figure 3-5 shows a timeline for this application.
RELEASE TIMER
2ND STAGE
DISCHARGE
SIGNALS
SOLENOID
ACTIVATION
Figure 3-5. Dual Detector, Pre-Signal, and Abort Switch with Delay
3-8
Define Lists, Digital Pseudos, The dual detector, pre-signal, and abort switch with delay application requires
and Analog Pseudos the following components to be defined prior to programming the Custom
Control equations.
1. Use the PC Programmer’s Point Tab to assign suppression points with the
point types listed below. Refer to Appendix A for specific details on these
point types.
2. Use the PC Programmer’s list tab to add four lists similar to the ones shown
below. Do not use the system’s suppression release lists – L9, L10, L11, or
L12.
4. Analog Pseudo Points. Define three analog pseudo points, similar to the
following. These will be used as the running timers in the example.
3-9
Program Custom Control The eight Custom Control equations required to program this application are
Equations shown in Figure 3-7. These equations have the following functions.
Equation 1. This equation contains two input qualifiers and a single output
qualifier. The first input qualifier in this equation monitors the state of list L26.
If two detectors within this list are in the FIRE state, the remainder of the
equation executes. The second input qualifier, which executes only if the first
input qualifier is true (i.e., two detectors are activated), starts a running timer of
30 seconds. The output qualifier at the bottom of the first equation, which also
executes only if the first input qualifier is true, turns P80 on.
Equation 2. The first input qualifier monitors the state of List L28, which
contains all manual release stations (pull stations) in the suppression release
area. The second input qualifier and the output qualifier at the bottom of
Equation 2 execute only if the first input qualifier is true. The second input
qualifier starts a running timer of five seconds. The output qualifier at the
bottom of the equation turns P81on.
Equation 3. The first input qualifier checks to see whether an abort switch is
active. It does this by checking to see whether any point within list L27, which
contains all abort switch points, is in a supervisory state. (Note that these points
must have a point type of SUPABRT for this to occur.) The second input
qualifier, which is linked to the first by an AND logical operator, determines
whether two detectors are in an activated state. Because the first two input
qualifiers are separated by the AND operator, they both must be true (i.e., an
abort switch must be active while two detectors are in an activated state) for the
equation’s two output qualifiers to execute. If the inputs are both true, the first
output qualifier holds pseudo point P82 ON and the second output qualifier
tracks ON P83. (Understanding the function of this last output qualifier is very
important. Because it uses TRACK ON, P83 turns on when both input
qualifiers are true, and turns off when either one of the input qualifiers is false.)
Equation 4. The first input qualifier checks pseudo point P82, which is ON
only if Equation 3’s input qualifiers are both true (i.e., abort switch is active and
two detectors in the suppression area are active at the same time). The second
input qualifier, which is linked to the first input by the logical AND operator,
checks P83. This input is true only if P83 is NOT in its ON/CODING state (i.e.,
switch is not being held in). The third input qualifier starts a running timer of 10
seconds. The output qualifer turns P84 on, which indicates that the timer is
running.
Equation 5. The four input qualifiers in this expression are linked via logical
operators. The output qualifier (which holds on the suppression release circuits)
in this equation executes if the following occurs:
- Two detectors are active (i.e., P80 is ON) AND the abort switch is not
active (P82 cannot be in the ON/CODING state).
3-10
Program Custom Control Equation 6. If one detector in List L26 goes into alarm, SIG1 turns on steady.
Equations (continued) This functions as a pre-signal for system operators.
Equation 7. This equation turns off SIG1 and sounds a slow march tone on
SIG2 if either two detectors activate in list L26 or if a pull station activates.
Equation 8. This equation turns SIG2 on steady if any one of the releasing
circuits (NACs) is ON (i.e., it is discharging).
3-11
3-12
In this Chapter Refer to the following page for specific information on a topic.
4-1
Overview This application monitors initiating devices and does the following:
Note: Always consult the local AHJ to determine whether this type of
operation is allowed or not allowed.
Step 1. Define NAC’s Device The NACs used with the Pre-Signal application can be either the NACs located
Type, Point Type, and Custom on the panel’s SFIO board or the NACs located on a 4009 IDNet NAC extender.
Label Note: Class A QuickAlert cannot be used with pre-signal applications.
Use the PC Programmer to program the NACs with the device types and point
types listed in Table 4-1. When defining custom labels, make sure to use
descriptive labels, such as “FLOOR1-VISUAL-CIRCUIT.”
Option Explanation
Use for Class A NAC. This type of NAC
contains multiple signal paths, allowing
NAC SIGA circuit operation to continue if a single open
Device circuit occurs. This option requires
Type installation of a Class A NAC adapter card.
Use for Class B NAC, which is a NAC
SIGB
containing only a single circuit path.
4-2
Step 2. Define Device Types, Each initiating device must be programmed with a device type and point type.
Point Types, and Custom Refer to “Programming Points,” located in Chapter 7 of the 4010 PC
Labels for Initiating Devices Programmer Installation and Programming Instructions for information on
programming an initiating device’s device type and point type. Refer to
“Monitor Point Types” in Appendix A of the PC Programmer manual for
detailed descriptions of the initiating device point types.
To add devices to a list, use the PC Programmer’s List Tab, adding each of the
devices to one of the available user-defined lists (L26 through L50).
Step 4. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L6 (Control
NACs to List L6 (Off On Points, Off on Silence). Members of this list automatically turn off when an
Silence) Alarm Silence is performed. Note: Skip this step if you are using Class B
QuickAlert NACs.
Step 5. Add Appropriate Use the PC Programmer’s List Tab to add the following to List L7 (Control
NACs to List L7 (Off On Points Off on Reset). Members of this list automatically turn off when a System
Reset) Reset is performed.
4-3
Step 6. Add Custom Control Standard NAC Example. Figure 4-1 shows an example of pre-signal
Equations Custom Control equations for a facility that uses standard NAC devices.
Information on QuickAlert devices is contained in the example at the end of this
section.
• Equation 3. This equation’s input side monitors the Physical Short state
of each device within L27, which is a list containing the floor’s pull
stations. If a device within this list is active (i.e., pulled), the output side of
this equation programs the NACs to activate in a temporal pattern.
Equation 1
Equation 2
Equation 3
4-4
Step 6. Add Custom Control QuickAlert NACs. A pre-signal application that uses QuickAlert NACs is
Equations (continued) programmed in virtually the same manner as the standard NAC example shown
above. The two differences for QuickAlert are that it requires one additional
equation to turn the horns off and you cannot use Class A QuickAlert with a pre-
signal application. (The horn pattern generated by the Sync module is set via a
switch, and it cannot be controlled by Custom Control.) Figure 4-2 shows an
example of a pre-signal application that uses QuickAlert NACs.
4-5
Overview Utility monitoring points differ from standard fire alarm points in that they do
not report a trouble when they activate and they do not latch (i.e., they reset
themselves). A utility monitoring point tracks the state of a monitor device (for
example, a heat sensor), turning a relay or supervisory pseudo point on when the
sensor’s value equals or exceeds an analog value that you specify.
This section uses an example in which a customer wants a water heater to come
on and a supervisory alert to occur when the temperature of a water tank is
between 38 and 50 degrees.
Step 1. Change the Heat Use the PC Programmer to change the heat detector’s point type to Utility. This
Detector’s Point Type and is a generic point type with no default operation, allowing the point to be
Custom Label controlled by Custom Control. Assign a descriptive custom label, such as
“Water Temp Monitor – Tank 2” to the point.
Step 2. Change the AUX The output point is typically a relay (AUX1, for example). Use the PC
Relay Point’s Point Type and Programmer to change its point type to Relay. This is a generic point type that
Custom Label allows the point to be controlled via Custom Control. Change its custom label
to a descriptive text, such as “Water Heater Control Relay Tank 2.”
Step 3. Define a Supervisory Use the PC Programmer to define a user digital pseudo point. Assign it a point
Digital Pseudo Point type of Supervisory, which means it will generate a Supervisory alert to the
panel when activated. Change its custom label to the message that you want to
appear on the panel when the monitor’s threshold point is reached. For
example, “Water Tank Temp Warning.”
Step 4. Program Custom The Custom Control example, shown in Figure 4-3, outlines the equation needed
Control Equations to program the example water tank/heater application. This equation contains
two input qualifiers and two output qualifiers.
1st Input Qualifier. The first input qualifier in the example equation checks
the value of the heat sensor to determine if it is greater than or equal to 38
degrees. To do this, you need to program this input statement’s properties, as
follows:
1. Choose the COMPARE opcode and select COUNTS (constant) for the
qualifier.
2. Enter the threshold value in the Counts box at the bottom right of the panel.
The example shows 38, which represents a temperature value in this
example.
4-6
Step 4. Program Custom 2nd Input Qualifier. The 2nd input qualifier, which is connected to the 1st
Control Equations (continued) input qualifier by an AND (i.e, both qualifiers must be true), checks to see if the
heat sensor is at a temperature of less than or equal to 50 degrees. Its
programming is very similar to the 1st input statement.
2. Specify 50 in the Counts box and select the AND radio button in the top left
corner.
3. Choose the less than or equal to (<=) operator for the 50 count.
1st Output Qualifier. This output tracks the input. That means that a
supervisory message (“Water Tank Temp Warning”) is sent to the panel when
the temperature range is between 38 and 50. This supervisory cannot be cleared
until the temperature is outside of the 38 to 50 degree range.
2nd Output Qualifier. This output tracks the input as well. Its function,
however, is to turn on a relay connected to a water heater while the temperature
range is between 38 and 50. As soon as the temperature is out of this range, the
relay goes off.
Input 1
Input 2
Output 1
Output 2
4-7
Overview The Day / Night programming application allows Custom Control to perform
one set of instructions during daytime hours and another set of instructions at
night.
Step 1. Program the Monitor The monitor device must be capable of accepting a variable operating level (for
Device’s Point Type, Device example, a smoke sensor whose sensitivity can be changed). The following
Type, and Custom Label devices support this functionality:
• TrueAlarm Photo
• TrueAlarm Heat
• TrueAlarm Ion
• TrueAlarm XPHOTO
Step 2. Program Custom Day / Night programming is done by comparing a constant that represents the
Control Equations time at which an action should occur against the value of A11, the current hour
of day analog pseudo point.
Equation 1:
-2
%+6)%8)68,%2 MWEQ
398
7)88,6)7,30(10):)0SFWGYVEXMSR
)2(
Equation 2:
-2
%+6)%8)68,%2 MWTQ
398
7)88,6)7,30(10):)0SFWGYVEXMSR
1. Add an input to a new equation and change its properties as shown in the
figure below.
c. In the Counts box, enter the hour at which the change takes place.
4-8
4-9
4. Add an output to the equation. Set its Opcode and Qualifier to the
following:
• The Opcode must be one of the following: Set Threshold Photo, Set
Threshold Ion, Set Threshold Heat, Set Threshold XPHOTO.
• The Qualifier is the threshold that you want to set. For example,
Smoke Level 2.5.
Equation 1
Equation 2
4-10
Overview Newer versions of the 4010 FACP (Version 2.01 or later) provide the ability to
reset the City Circuit in the following situations.
Always consult the local AHJ before implementing this functionality. Some
jurisdictions may not allow this operation.
Program Custom Control To program AHJ City reset, enter the following equation.
Equations
1. Add a new equation. Program its input statement to monitor the
ON/CODING state of the A4 analog pseudo point, which is the system
startup pseudo.
2. Program the output statement to Hold ON digital pseudo point P16 (AHJ
Reset).
Equation 1
4-11
Overview The Elevator Recall application programs the system to automatically recall the
building elevators following alarm activation. Guidelines to be aware of
include:
• Installation wiring running between the 4010 FACP and the auxiliary relays
used for fire safety control functions (in this case, elevator recall) must be
monitored for integrity (supervised) and the auxiliary relay must be located
within 3 feet of the controlled circuit or device. Reference NFPA 72, 1996,
Section 3-9.2.
Step 1. Add Primary Floor Use the PC Programmer’s List Tab to add all of the building’s initiating devices,
Initiating Devices to a User- with the exception of those located on the alternate floor, to a user-defined list.
Defined List Use the Card Tab to give the list a descriptive name such as “BANK2
PRIMARY ELEVATOR RECALL.”
Step 2. Add Alternate Floor Use the PC Programmer’s List Tab to add the initiating devices located on the
Initiating Devices to a alternate floor to a user-defined list. Use the Card Tab to give the list a
User-Defined List descriptive name such as “BANK2 ALTERNATE ELEVATOR RECALL.”
Step 3. Add Custom Labels The 4010 uses AUX relays, connected to the appropriate contacts on the control
to AUX Relays panel of the elevator, to indicate that a fire condition exists and the elevator
should be returned to either the primary or alternate floor. Use the Point Tab to
assign a descriptive label, such as “BANK2 PRIMARY ELEVATOR” or
“BANK2 ALTERNATE ELEVATOR,” to the appropriate AUX Relay.
Step 4. Add Custom Control The following example, shown in Figure 4-6, illustrates how to implement
Equations Elevator Recall with Custom Control.
• Equation 1. The first two input statements, separated by the AND NOT
operator, check whether there is an activated initiating device (List L26)
and make sure the relay that returns the elevator to the alternate floor is not
activated (i.e., possible fire on primary floor). If both of these are true, the
relay for the primary floor activates.
4-12
Step 4. Add Custom Control • Equation 2. The input side of this equation monitors List L27, which
Equations (continued) contains the initiating devices located on the alternate floor. If one of these
devices contained activates, the output side of this equation executes,
energizing the relay and returning the elevator to the alternate floor.
Equation 1
Equation 2
4-13
Overview By default, the City Circuit activates on all alarm conditions. In some cases,
however, the customer may want to prevent activation of the city circuit for
certain types of alarms (waterflow alarms, for example).
This application describes programming the system to activate the City Circuit
only for a specific set of alarms.
Note: The trouble circuit on the City Circuit card cannot be selectively
controlled.
Step 1. Create a User-Defined Use the PC Programmer’s List Tab to create a user-defined list containing all of
List of City Circuit Alarm the City Circuit alarm points. Exclude points that you want to prevent from
Points activating the City Circuit. Use the Card Tab to assign a descriptive name, such
as “CITY CIRCUIT ALARM ACTIVATION POINTS,” to this list.
Step 2. Create Custom The following example, shown in the figure below, illustrates how to implement
Control Equations selective City Circuit activation.
• Equation 2. The input qualifier monitors the fire state of all devices in
List L41. If any device within this list activates, the output qualifier
executes, turning ON the City Circuit’s alarm connection.
Equation 1
Equation 2
4-14
Overview This application describes using Custom Control to shutdown all fans and close
all dampers during a general alarm condition. A System Reset returns all fans
and dampers to normal operation.
Example: Fan / Damper The following figure illustrates a typical four-story building. Assume that the
Shutdown for a Four Story building includes a supply and exhaust fan, and the relays controlling the
Building dampers are wired to 24 PT I/O outputs.
SUPPLY EXHAUST
POSITIVE
NEGATIVE
POSITIVE
Step 1. Program Point Type Use the PC Programmer’s Point Tab to program each fan relay with the RELAY
and Custom Labels for Fan point type. When defining custom labels, make sure to use descriptive labels,
Relays such as “EXHAUST FAN RELAY.”
Step 2. Program Point Types Each damper typically contains two switches for monitoring the position of the
and Custom Labels for damper and a relay for controlling the damper motor. Use the PC Programmer’s
Damper Monitor Switches and Point Tab to program the Point Type and Custom Label for these components,
Relays as follows:
• Fan Relays. Program each relay with the RELAY point type. When
defining custom labels for damper relays, make sure to use descriptive
labels, such as “EXH DAMPER1 RELAY.”
4-15
Step 2. Program Point Types • Damper Monitor Switches. The switches used to monitor the damper
and Custom Labels for position are typically connected to either an IAM or MZAM. Each damper
Damper Monitor Switches and uses two switches, one switch monitors the OPEN position of the damper
Relays (continued) and the other monitors the CLOSED position.
Step 3. Custom Control Use the CC Tab in the PC Programmer to program the Custom Control
Equations equations as shown below. Note that these equations only show a single damper
being controlled. Copy this equation, changing the damper points as required to
account for all of the building’s dampers.
• Equation 1. This equation monitors the General Alarm List (L1). If any
point within this list activates, the Hold ON Output Qualifier executes,
turning off the relays for the supply and exhaust fans.
Equation 1
Equation 2
4-16
• System Options.
• Software Point Types. 4010 point types are grouped into two general
categories:
- Monitor point types are used with monitoring devices, such as smoke
detectors, pull stations, heat detectors, fire pump monitors, etc.
- Control point types are used with signal (notification appliance) and
relay devices.
A-1
System Options Many common applications have been incorporated into the 4010 panel as
system options. Table 1-1 lists these options.
A-2
The Active Status Reminder option allows you to set an interval and duration during
which the 4010 remind operators that a FIRE, SUPV, or TBL condition still exists in the
panel.
Active Status Active Status Reminder consists of two parts:
Reminder
• Reminder Interval. The range can be from 1 to 12 hours, and the default is 8 hours.
• Acknowledge Option. This option sets the duration of the acknowledge signal. The
range can be from 0 to 60 seconds, and the default is 5 seconds.
Audible and Visible ON until Silence Notification Appliance Circuits (NACs) can be set to
the choices shown below. The default setting for the Audible NACs is Temporal; the
default setting for the Visible NACs is Synchronous; and the default setting for
QuickAlert Horns is TEMPORAL.
Signal Operation • Audible NAC Operation – choices are temporal, steady, march time, slow march
time.
• Visible NAC Operation – choices are steady, march time, slow march time,
temporal, synchronous
• QuickAlert Horn Operation – choices are steady, temporal, slow march time.
A-3
Introduction Some application-specific needs can also be met without Custom Control simply
by using the correct point types. A point’s type determines the following:
• The message displayed on the 4010’s LCD when changes occur to the state
of the point’s circuit.
• The way in which the system operates (for example, initiate an Alarm,
Trouble, or Supervisory action) when changes occur to the state of the
point’s circuit.
AHUF AHU off relay – dual relay control. This point type is used with applications
that use two auxiliary relays for AHU control – one relay for ON and one relay
for OFF. Use this point type for the OFF relay. Points assigned with this type
operate on general alarm (that is, when any point within L1 “General Alarm
List” goes into alarm). Point turns OFF on Reset.
Stagger Start functionality for air handler units is provided by the “Stagger
Start” system option.
See AHUO for the ON relay point type. If you have a single relay that performs
both ON and OFF functions, see AHUR.
AHUO AHU on relay – dual relay control. This point type is used with applications that
use two auxiliary relays for AHU control – one relay for ON and one relay for
OFF. Use this point type for the ON relay. Points assigned with this type
operate on general alarm (that is, when any point within L1 “General Alarm
List” goes into alarm). Point turns OFF on Reset.
Stagger Start functionality for air handler units is provided by the “Stagger
Start” system option.
See AHUF for the OFF relay point type. If you have a single relay that
performs both ON and OFF functions, see AHUR.
A-4
AHUR AHU on/off relay – single relay control. This point type is used with
applications in which a single relay performs AHU ON and OFF control. Points
assigned with this type operate on general alarm (that is, when any point within
L1 “General Alarm List” goes into alarm). Point turns OFF on Reset.
ALTERN Elevator capture – alternate. Used for a relay connected to the elevator controls
to provide alternate floor elevator recall. This relay turns ON when any of the
points in L5, Alternate Elevator Recall Zones, goes into alarm. Points with this
type turn OFF when the system is reset.
BSIGNAL Trouble/supervisory “bell” signal. Used when an audible signal should activate
on any supervisory or trouble condition and remain ON until the condition has
been acknowledged or cleared.
A-5
DHOLDER Door holder control (normally off). Used when the auxiliary relay is connected
to door holders. The relay energizes on alarm (any point in L1 General Alarm
List goes into alarm), loss of AC Power, or when programmed.
PRIMARY Elevator capture – primary. Used for any relay connected to the elevator
controls to provide primary floor elevator recall. A relay assigned this point
type turns ON when any point in L4, Primary Elevator Recall, goes into alarm.
Relay turns Off on reset.
QALERT QuickAlert signal. QALERT device type has no automatic operation. All
operations for this type of device type must be programmed with Custom
Control.
SQALERT SQALERT device type automatically turns on the designated circuit on alarm
detect (general alarm), issues the horn silence command upon Alarm Silence,
and turns off the circuit at the completion of System Reset. Any point
programmed with the SQALERT point type is not available for use in Custom
Control programming.
RELAY Generic relay – no default operation. Used for selective relay applications
(Custom Control) not defined by a specific point type. Point must be
programmed to turn ON and OFF.
A-6
RSIGNAL Alarm signal – On until Reset. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).
RVISUAL Used only with visual notification appliances that must be ON until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).
RWATER Waterflow signal – On until Reset. A point with this type turns ON when any
point within L2, the Waterflow Alarm Monitor List, goes into alarm. Points
with this type turn OFF on System Reset.
A-7
SIGNAL Generic Alarm Signal – no default operation. Used for selective control
(Custom Control) of audible or visible notification appliances. Points assigned
with this point type operate on general alarm.
SSIGNAL Alarm signal – On until Silence. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm (that is, when any point
within L1 General Alarm List goes into alarm). Points with this type turn OFF
when an Alarm Silence is performed.
A-8
SVISUAL Visual – on until silence. Points assigned with this point type are ON when any
point within L1, General Alarm List, goes into alarm. Visual Notification
Appliances assigned this point type remain ON until an Alarm Silence is
performed.
SWATER Waterflow signal – on until silence. Points with this point type turn ON when
any point in L2, Waterflow Alarm Monitor List, goes into alarm. Points remain
activated until the Alarm Silence.
TSIGNAL Trouble/Supervisory Signal On until Clear. Points with this point type turn ON
when any trouble or supervisory condition occurs. Points turn OFF when the
trouble or supervisory condition is cleared.
A-9
BRELAY Trouble / Supervisory “Bell Relay.” A relay with this point type turns ON when
any Trouble or Supervisory condition occurs. Relays with this point type turn
OFF when the condition is acknowledged or cleared.
RRELAY Alarm Relay ON until Reset. A relay with this point type turns ON when any
point in L1, General Alarm List, goes into alarm. These relays turn OFF on
System Reset.
FIRE This is a generic fire alarm point type. A typical application for this point type
is a fire alarm zone containing more than one type of device. For example,
when a combination of smoke detectors, pull stations, waterflow monitors, and
heat detectors is connected to an IAM or ZAM, this point type allows alarms to
report as originating from a zone.
WATER Used to define the operation of a waterflow monitor for all possible circuit
states.
A-10
DUCT Used to define the operation of a duct detector for all possible circuit states.
HEAT Defines the operation of a heat detector for all possible circuit states.
A-11
EMERG Use for an emergency monitor zone in which two types of alarm devices – for
example, emergency alarm devices such as Nurse Call and fire alarm devices --
are connected to an IAM or ZAM. Emergency devices require the use of a
current limiting resistor. These devices generate an Emergency Alarm condition
at the panel.
SFIRE Used when smoke detectors and shorting type devices are connected to an IAM
or ZAM.
VFIRE Used to activate the alarm verification software for all smoke detectors
connected to an IAM or ZAM. Shorting type devices cause an immediate alarm.
SPULL Used when smoke detectors and pull stations are connected to an IAM or ZAM.
VSPULL Used when smoke detectors that must be verified and pull stations are connected
to an IAM or ZAM.
A-12
GENMON Used when emergency generator monitoring is required. The shorted condition
of the circuit indicates an abnormal status and is indicated by the Supervisory
Service LED. The current limited condition of the circuit indicates that the
generator is running, and can be tracked with an LED (must be programmed). A
current limiting resistor must be installed for this to happen.
SGENMON Same operation as the GENMON point type, but the generator running condition
automatically displays and requires operator acknowledgment.
FPUMP Used to monitor fire pump conditions. The shorted condition indicates that the
fire pump is abnormal A current limited condition indicates that the fire pump is
running.
SFPUMP Same as the FPUMP point type, except that the fire pump running condition
requires operator acknowledgement.
S2STAGE Used for 2-stage alarms. The current limited operation of any device indicate a
Stage 1 Alarm. A short on the point’s circuit, such as a key switch operation,
causes a Stage 2 Alarm.
A-13
A-14
SUPV Used to monitor any supervisory type device where operator acknowledgment is
required.
UTIL Used to monitor and supervise any condition; operator acknowledgment is not
required. No alarm is generated by this point type.
TROUBLE Used for trouble monitoring only. No alarm is generated by this point type.
VSMOKE Used with smoke detectors whose alarm status must be verified.
A-15
GVMON Used when the abnormal condition of the circuit must be verified.
LATSUPV Supervisory Monitor – latch until reset. Used for generic supervisory alarm.
STYLEC Style-C Fire Alarm Monitor. Used when only current limited devices are
connected to the zone. A short circuit is reported as a Trouble.
A-16
USWITCH 2-position switch, unsupervised. Used for a 2-position switch without an EOL
or current limited resistor.
SSWITCH 2-position switch, supervised for opens and shorts. Requires EOL and current
limited resistors.
TSWITCH 3-position (SPDT) switch, supervised for opens. Requires EOL and series
current limiting resistors (up leg).
A-17
A-18
4 H
4010 HEAT point type, A-11
limitations of Custom Control, 1-1 horn off opcode, 2-16
system options and point types for, 1-2 horns
and QuickAlert, 1-3
A
L
ABORT point type, A-16
active status reminder system option, A-3 LATSUPV point type, A-16
AHU stagger start system option, A-3 list L6 , off on silence, 2-3
AHUF point type, A-4 list L7, off on reset, 2-4
AHUO point type, A-4
AHUR point type, A-5
alarm cutout timer system option, A-2
N
alarm silence inhibit system option, A-2 NACs
ALTERN point type, A-5 device types and point types, 2-3
B O
BRELAY oswitch point type, 2-17
point type, A-10 overview, 1-1
C P
Custom Control point types, 1-2, A-4
capacities of, 1-2 4009A, A-17
limitations of for 4010, 1-1 ABORT, A-16
AHUF, A-4
D AHUO, A-4
AHUR, A-5
day/night programming application, 4-8 ALTERN, A-5
depleted battery system option BRELAY, A-10
depleted battery, A-2 BSIGNAL, A-5
device types DHOLDER, A-6
summary of, A-1 DUCT, A-11
DHOLDER point type, A-6 EMERG, A-12
door drop on AC fail system option, A-3 FIRE, A-10
door drop on alarm system option, A-2 FLAME, A-11
DUCT point type, A-11 FPUMP, A-13
GENMON, A-13
GVMON, A-16
E HEAT, A-11
elevator recall application, 4-11 LATSUPV, A-16
EMERG point type, A-12 OSWITCH, A-17
PRIMARY, A-6
PULL, A-11
F QALERT, A-6
FIRE RELAY, A-6
point type, A-10 RRELAY, A-10
FLAME point type, A-11 RSIGNAL, A-7
FPUMP point type, A-13 RVISUAL, A-7
RWATER, A-7
S2STAGE, A-13
G SDUCT, A-16
SFIRE, A-12
general alarm shutdown for fans and dampers, 4-14
SFPUMP, A-13
GENMON point type, A-13
SGENMON, A-13
GVMON point type, A-16
SIGNAL, A-8
SMOKE, A-11
SO, A-14
IN-1
IN-2
V
VFIRE point type, A-12
VSMOKE point type, A-15
VSPULL point type, A-12
W
WATER
point type, A-10
WSO point type, A-14
IN-3
Rev. A Simplex Time Recorder Co., • Simplex Plaza • Gardner, Massachusetts 01441-0001 U.S.A. 574-908
Simplex International Time Equipment Co., LTD. • Mississauga, Ontario, Canada