Product Data Sheet: RS485 Interface 2 Wires ACE949-2 For Sepam 20, 40, 60, 80
Product Data Sheet: RS485 Interface 2 Wires ACE949-2 For Sepam 20, 40, 60, 80
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Sepam series 60
Sepam series 80
Sepam series 40
Sepam series 20
Sepam series 48
Sepam series 80 NPP
Device short name ACE949-2
Complementary
Communication port protocol Modbus RTU network: E-LAN interface: RS485 - 2-wire
Modbus RTU network: S-LAN interface: RS485 - 2-wire
Local signalling LED for link activity (front face)
[Us] rated supply voltage 12 V DC tolerance: +/- 10 %
24 V DC tolerance: +/- 10 %
Maximum supply current 16 mA: receiving mode
40 mA: maximum in sending mode
Mounting mode Fixed
Mounting support Symmetrical DIN rail
Height 88 mm
Width 72 mm
Depth 30 mm
Net weight 0.1 kg
Mechanical robustness Earthquakes in operation (level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
Earthquakes in operation (level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
Jolts de-energized (level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
Shocks de-energized (level: 2) : 27 Gn/11 ms conforming to IEC 60255-21-2
Shocks in operation (level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
Vibrations de-energized (level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
Vibrations in operation (level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
Vibrations in operation (level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6
Maximum cable distance between 10 Devices <180 m at 12 V DC
devices 10 Devices <750 m at 24 V DC
20 Devices <160 m at 12 V DC
Apr 14, 2020
1
20 Devices <450 m at 24 V DC
25 Devices <125 m at 12 V DC
25 Devices <375 m at 24 V DC
5 Devices <1000 m at 24 V DC
5 Devices <320 m at 12 V DC
Auxiliary connection terminal Earthing terminal: screw-type connectorcable 2.5…50 mm² <0.2 m
Earthing terminal: screw-type connectortinned copper braid 6…100 mm²
Tightening torque Earthing terminal: 2.2 N.m
Environment
Electromagnetic compatibility 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 1 kV DM,
conforming to IEC 60255-22-1
1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 2.5 kV DM,
conforming to ANSI C37.90.1
100 kHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 1 kV DM,
conforming to IEC 61000-4-12
Conducted disturbance emission: (emission tests), conforming to IEC 60255-25
Conducted disturbance emission: (emission tests), A, conforming to EN 55022
Disturbing field emission: (emission tests), conforming to IEC 60255-25
Disturbing field emission: (emission tests), A, conforming to EN 55022
Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 4 kV contact, conforming to
ANSI C37.90.3
Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 6 kV contact, conforming to
IEC 60255-22-2
Fast transient bursts: (immunity tests-conducted disturbances), 4kV, 2.5 kHz, conforming to ANSI
C37.90.1
Fast transient bursts: (immunity tests-conducted disturbances), A and B, 4kV, 2.5 kHz/2 kV, 5 kHz,
conforming to IEC 60255-22-4
Fast transient bursts: (immunity tests-conducted disturbances), IV, 4kV, 2.5 kHz, conforming to IEC
61000-4-4
Immunity to conducted RF disturbances: (immunity tests-conducted disturbances), III, 10 V,
conforming to IEC 60255-22-6
Immunity to magnetic fields at network frequency: (immunity tests-radiated disturbances), IV, 30 A/m
(continuous)-300 A/m (1-3 s), conforming to IEC 61000-4-8
Immunity to radiated fields: (immunity tests-radiated disturbances), 10 V/m, 80 MHz...1 GHz,
conforming to IEC 60255-22-3
Immunity to radiated fields: (immunity tests-radiated disturbances), 35 V/m, 25 MHz...1 GHz,
conforming to ANSI C37.90.2
Immunity to radiated fields: (immunity tests-radiated disturbances), III, 10 V/m, 80 MHz...2 GHz,
conforming to IEC 61000-4-3
Surges: (immunity tests-conducted disturbances), III, 2 kV CM, 1 kV DM, conforming to IEC
61000-4-5
Voltage interruptions: (immunity tests-conducted disturbances), 100 % during 100 ms, conforming to
IEC 60255-11
Climatic withstand Influence of corrosion/gaz test 2 (in operation) : 21 days, 75 % RH, 25 °C, 0.5 ppm H2S, 1 ppm S02
conforming to IEC 60068-2-60
Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm
S02, 0.2 ppm NO2, 0.01 ppm CI2 conforming to IEC 60068-2-60
Continuous exposure to damp heat (in operation) : Cab: 10 days, 93 % RH, 40 °C conforming to IEC
60068-2-78
Continuous exposure to damp heat (in storage) : Cab: 56 days, 93 % RH, 40 °C conforming to IEC
60068-2-78
Continuous exposure to damp heat (in storage) : Db: 6 days, 95 % RH, 55 °C conforming to IEC
60068-2-30
Exposure to cold (in operation) : Ad: - 25 °C conforming to IEC 60068-2-1
Exposure to cold (in storage) : Ab: - 25 °C conforming to IEC 60068-2-1
Exposure to dry heat (in operation) : Bd: 70 °C conforming to IEC 60068-2-2
Exposure to dry heat (in storage) : Bb: 70 °C conforming to IEC 60068-2-2
Salt mist (in operation) : Kb/2: 6 days conforming to IEC 60068-2-52
Temperature variation with specified variation rate (in storage) : Nb: - 25 °C to 70 °C, 5 °C/min
conforming to IEC 60068-2-14
Ambient air temperature for operation -25…70 °C
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
2
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile