(V-2) Top Slab Design Calculation For Size of With Opening of 3'-0"X2'-2"
The document provides design calculations for a 4'x4' concrete slab with a 3'x2'2" opening. It calculates the ultimate bending moments in the x and y directions as 16.9 kip-ft/ft and 14.8 kip-ft/ft respectively, using finite element analysis software and assuming a concrete strength of 3000 psi, reinforcement strength of 60000 psi, and live load of 16 kips from an HS40 truck. It then checks that the minimum required reinforcement of 0.54 square inches is provided based on the design moment and span dimensions. Additional details are provided for designing the beam portion of the slab.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
167 views3 pages
(V-2) Top Slab Design Calculation For Size of With Opening of 3'-0"X2'-2"
The document provides design calculations for a 4'x4' concrete slab with a 3'x2'2" opening. It calculates the ultimate bending moments in the x and y directions as 16.9 kip-ft/ft and 14.8 kip-ft/ft respectively, using finite element analysis software and assuming a concrete strength of 3000 psi, reinforcement strength of 60000 psi, and live load of 16 kips from an HS40 truck. It then checks that the minimum required reinforcement of 0.54 square inches is provided based on the design moment and span dimensions. Additional details are provided for designing the beam portion of the slab.