Contact ID Codes With Explanation
Contact ID Codes With Explanation
380 Sensor trouble Zone The specified sensor has reported a trouble condition
381 Loss of supervision - RF The specified zone has failed to report in during its designated
Zone
supervision period
382 Loss of supervision - RPM An Remote Polled Module assigned to the specified zone has failed
Zone
supervision
383 Sensor tamper Zone The tamper switch on the specified sensor has been faulted
384 RF low battery The specified battery powered RF zone has reported a low battery
Zone
condition
385 Smoke detector Hi sensitivity Zone A smoke detector's sensitivity level has drifted to the upper limit
386 Smoke detector Low sensitivity Zone A smoke detector's sensitivity level has drifted to the lower limit
387 Intrusion detector Hi sensitivity Zone An intrusion detector's sensitivity level has drifted to the upper limit
388 Intrusion detector Low sensitivity Zone An intrusion detector's sensitivity level has drifted to the lower limit
389 Sensor self-test failure Zone The specified sensor has failed a self-test
391 Sensor Watch trouble A motion sensor has not been triggered within a pre-defined time
Zone
interval
392 Drift Compensation Error Zone A smoke detector cannot automatically adjust its sensitivity
393 Maintenance Alert Zone The specified zone requires maintenance
394 CO Detector needs replacement Zone The specified Carbon Monoxide detector has reached end-of-life
400 Open/Close User The specified user has disarmed/armed the system
401 O/C by user User The specified user has disarmed/armed the system
402 Group O/C User A group of zones has been armed or disarmed
403 Automatic O/C User A partition has been automatically armed or disarmed
404 Late to O/C (Note: use 453 or 454
User
instead )
405 Deferred O/C (Obsolete- do not
User
use )
406 Cancel The specified user has cancelled the previously reported alarm
User
condition
407 Remote arm/disarm The specified user has armed or disarmed the system from off-
User
premises
408 Quick arm User The specified user has quick-armed the system
409 Keyswitch O/C The specified user has armed or disarmed the system using a
User
keyswitch
411 Callback request made User A remote site (central station) has requested the panel call it back
412 Successful download/access The configuration data of the system has been successfully
User
downloaded
413 Unsuccessful access A number of failed attempts have been made to remotely access the
User
system
414 System shutdown command A central station has sent a system shutdown command to the panel
User
received
415 Dialer shutdown command A central station has sent a dialer shutdown command to the panel
User
received
416 Successful Upload The configuration data of the system has been successfully uploaded
Zone
418 Remote Cancel The specified user has remotely cancelled the previously reported
User
alarm condition
419 Remote Verify The specified user has remotely verified the previously reported alarm
User
condition
421 Access denied User The access control system has denied access to the specified user
422 Access report by user User
423 Forced Access Zone The specified access control door has been forced open
424 Egress Denied User The access control system has denied egress to the specified user
425 Egress Granted The access control system has granted egress for the specified user
User
426 Access Door propped open Zone The specified access control door has been held open
427 Access point Door Status Monitor The specified Access Point's Door Status Monitor has reported a
Zone
trouble trouble condition to the panel
428 Access point Request To Exit The specified Access Point's Request To Exit zone has reported a
Zone
trouble trouble condition to the panel
429 Access program mode entry User The access control system has been put into program mode
430 Access program mode exit User The access control system has exited program mode
431 Access threat level change User The access control system's threat level has been changed
432 Access relay/trigger fail The specified access control output device has failed to operate
Zone
properly
433 Access RTE shunt The specified Request To Exit zone has been shunted and will no
Zone
longer report activity
434 Access DSM shunt The specified Door Status Monitor zone has been shunted and will no
Zone
longer report activity
435 Second Person Access A second person has accessed an access point conforming to Two-
User
Man-Rule requirements
436 Irregular Access User
441 Armed STAY User The specified user has armed the system in STAY mode
442 Keyswitch Armed STAY The specified user has armed the system in STAY mode using a
User
keyswitch
443 Armed with System Trouble The specified user has armed the system while overriding a trouble
User
Override condition
450 Exception O/C The system has been armed or disarmed outside of the configured
User
time window
451 Early O/C The system has been disarmed/armed by the specified user before
User
the configured time window has started
452 Late O/C The system has been disarmed/armed by the specified user after the
User
configured time window has ended
453 Failed to Open The system has failed to have been disarmed during the designated
User
time window
454 Failed to Close The system has failed to be armed during the designated time window
User
455 Auto-arm Failed The system has failed to automatically arm itself at the designated
User
time
456 Partial Arm User The system has been only partially armed by the specified user
457 Exit Error (user) The specified user has made an error exiting the premises after
User
arming the system
458 User on Premises User A user has disarmed the system after an alarm has occurred
459 Recent Close User The system had been armed within the last xx minutes
461 Wrong Code Entry Zone
462 Legal Code Entry User
463 Re-arm after Alarm User
464 Auto-arm Time Extended A user has successfully requested that the system delay automatically
User
arming
465 Panic Alarm Reset Zone The specified panic zone has been reset
466 Service On/Off Premises User A service person has entered or left the premises
501 Access reader disable The credential reader on the specified access point has been disabled
Zone
520 Sounder/Relay Disable Zone The specified sounder or relay has been disabled
521 Bell 1 disable Zone The specified output for Bell 1 has been disabled
522 Bell 2 disable Zone The specified output for Bell 2 has been disabled
523 Alarm relay disable Zone The specified alarm relay has been disabled
524 Trouble relay disable Zone The specified trouble relay has been disabled
525 Reversing relay disable Zone The specified reversing relay has been disabled
526 Notification Appliance Ckt. # 3 The specified output for Bell 3 has been disabled
Zone
disable
527 Notification Appliance Ckt. # 4 The specified output for Bell 4 has been disabled
Zone
disable
531 Module Added Zone The specified access control module has been added to the system
532 Module Removed The specified access control module has been removed from the
Zone
system
551 Dialer disabled Zone The specified dialer has been disabled
552 Radio transmitter disabled Zone The specified radio transmitter has been disabled
553 Remote Upload/Download Remote configuration has been enabled
Zone
disabled
570 Zone/Sensor bypass Zone The specified zone or sensor has been bypassed
571 Fire bypass Zone The specified fire zone has been bypassed
572 24 Hour zone bypass Zone The specified 24 hour zone has been bypassed
573 Burg. Bypass Zone The specified burglary zone has been bypassed
574 Group bypass User A group of zones has been bypassed
575 Swinger bypass The specified zone which has reported an excessive number of
Zone
faults/restores in a short period of time has been bypassed
576 Access zone shunt The specified zone in the access control system has been shunted
Zone
and will no longer report activity
577 Access point bypass The specified access point in the access control system has been
Zone
bypassed and will allow the door to open (unsecured)
578 Vault Bypass Zone The specified vault zone has been bypassed
579 Vent Zone Bypass The specified vent zone has been bypassed and will no longer report
Zone
any activity
601 Manual trigger test report Zone A test report has been triggered manually
602 Periodic test report Zone A periodic test report has been triggered
603 Periodic RF transmission Zone A periodic RF path test report has been triggered
604 Fire test User The specified user has initiated a test of the fire alarm zones
605 Status report to follow Zone
606 Listen-in to follow Zone The system is about to activate a 2-way audio session
607 Walk test mode The specified user has placed the system into the walk-test mode for
User
testing purposes
608 Periodic test - System Trouble A periodic test has been triggered but the fire system has a trouble
Zone
Present condition present
609 Video Xmitter active Zone A video look-in session is about to begin
611 Point tested OK Zone The specified point tested successfully
612 Point not tested Zone The specified point has not been tested
613 Intrusion Zone Walk Tested Zone The specified intrusion zone has been successfully walk-tested
614 Fire Zone Walk Tested Zone The specified fire zone has been successfully walk-tested
615 Panic Zone Walk Tested Zone The specified panic zone has been successfully walk-tested
616 Service Request Zone A request has been made for system servicing
621 Event Log reset The event log has been reset and all stored events have been
Zone
discarded
622 Event Log 50% full Zone The event log is 50% full
623 Event Log 90% full Zone The event log is 90% full
624 Event Log overflow Zone The event log has overflowed and events have been lost
625 Time/Date reset The time and date have been reset to a new value by the specified
User
user
626 Time/Date inaccurate Zone The system time and date is known to be in error
627 Program mode entry Zone The system has been placed into program mode
628 Program mode exit Zone The system has exited program mode
629 32 Hour Event log marker Zone
630 Schedule change Zone The specified fire/burglary schedule has been changed
631 Exception schedule change The time schedule for event reporting by exception has been changed
Zone
632 Access schedule change Zone The specified access control schedule has been changed
641 Senior Watch Trouble Zone A person has not activated a motion sensor in a specified period
642 Latch-key Supervision User A child has disarmed the system (after school)
643 Restricted Door Opened Zone A restricted door has been opened / closed
645 Help Arrived Requested help personnel have arrived on the scene
646 Addition Help Needed Addition help personnel are requested
647 Addition Help Cancel Addition help personnel are no longer required
651 Reserved for Ademco Use Zone
652 Reserved for Ademco Use User
653 Reserved for Ademco Use User
654 System Inactivity Zone System has not been operated for x days
655 User Code X modified by Installer User The Installer has modified the specified User's code
703 Auxiliary #3 Zone
704 Installer Test Zone
750 User Assigned
751 User Assigned
752 User Assigned
753 User Assigned
754 User Assigned
755 User Assigned
756 User Assigned
757 User Assigned
758 User Assigned
759 User Assigned
760 User Assigned
761 User Assigned
762 User Assigned
763 User Assigned
764 User Assigned
765 User Assigned
766 User Assigned
767 User Assigned
768 User Assigned
769 User Assigned
770 User Assigned
771 User Assigned
772 User Assigned
773 User Assigned
774 User Assigned
775 User Assigned
776 User Assigned
777 User Assigned
778 User Assigned
779 User Assigned
780 User Assigned
781 User Assigned
782 User Assigned
783 User Assigned
784 User Assigned
785 User Assigned
786 User Assigned
787 User Assigned
788 User Assigned
789 User Assigned
796 Unable to output signal (Derived
Zone
Channel)
798 STU Controller down (Derived
Zone
Channel)
900 Download Abort Download The specified Downloader ID has aborted a download sequence in
er ID progress
901 Download Start/End Download Downloader has started or ended a download sequence to the panel
er ID
902 Download Interrupted Download A download sequence has been interrupted
er ID
903 Device Flash Update Started/ Device A code update for a devices application firmware has started (E903)
Completed Zone or completed successfully (R903)
904 Device Flash Update Failed Device A code update for a devices application firmware has failed
Zone
910 Auto-close with Bypass An auto-close sequence has been started and the specified zone has
Zone
been bypassed
911 Bypass Closing Zone
912 Fire Alarm Silence Zone The fire alarm has been silenced
913 Supervisory Point test Start/End User A fire supervisory device has been tested
914 Hold-up test Start/End User The specified user has started or ended a hold-up test
915 Burg. Test Print Start/End User The printed progress of a burglary test has been started or ended
916 Supervisory Test Print Start/End The printed progress of a supervisory test has been started or ended
User
917 Burg. Diagnostics Start/End Zone A burglary system diagnostic test has been started or ended
918 Fire Diagnostics Start/End Zone A fire system diagnostic test has been started or ended
919 Untyped diagnostics Zone
920 Trouble Closing (closed with burg.
User
during exit)
921 Access Denied Code Unknown Access has been denied because the system did not recognize the
User
supplied access code as valid
922 Supervisory Point Alarm Zone The specified supervisory point has reported an alarm condition
923 Supervisory Point Bypass Zone The specified supervisory point has been bypassed
924 Supervisory Point Trouble Zone The specified supervisory point has reported a trouble condition
925 Hold-up Point Bypass Zone The specified hold-up point has been bypassed
926 AC Failure for 4 hours Zone There has been a loss of AC power for at least four hours
927 Output Trouble Zone The specified output has reported a trouble condition
928 User code for event This message contains the ID of the user who triggered the previous
User
event
929 Log-off User The specified user has logged-off of the system
961 Rcvr Database Connection The connection to the receiver's database has failed/restored
Zone
Fail/Restore
962 License Expiration Notify Zone The product license has been terminated (7810PC)
999 1 and 1/3 Day No Read Log In the last 31.9 hours (1 and 1/3 days), nothing has been posted to the
event log. There is nothing new to read. Does not send to central
station and only occurs in the Vista-20/SE and FA sister products.