Adequacy Check For Existing Footings

The document summarizes the design of an isolated footing, including input parameters, calculations to check bearing pressure, punching shear, reinforcement requirements, and one-way shear. Key parameters of the footing include dimensions of 3.5m x 2m x 0.6m and maximum loads of 1455.812 kN and 2183.718 kN. Calculations confirm the design is acceptable for bearing pressure, punching shear, reinforcement needs, and one-way shear.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
129 views3 pages

Adequacy Check For Existing Footings

The document summarizes the design of an isolated footing, including input parameters, calculations to check bearing pressure, punching shear, reinforcement requirements, and one-way shear. Key parameters of the footing include dimensions of 3.5m x 2m x 0.6m and maximum loads of 1455.812 kN and 2183.718 kN. Calculations confirm the design is acceptable for bearing pressure, punching shear, reinforcement needs, and one-way shear.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Sankhe Associates ISOLATED FOOTING DESIGN

Designer N.P.
LOGO DESIGN OF ISOLATED FOOTING Checker
Component: Date #########

Input Params:
Length of Footing: 3.5 m
Width of Footing: 2 m
Depth of Footing: 0.6 m
Maximum Axial Load at SLS: 1455.812 kN
Maximum Axial Load at ULS: 2183.718 kN
Column Length: 1.6 m
Column Width: 0.7 m
Soil Bearing Capacity: 250 kPa
Grade of Concrete 25 Mpa
Grade of Steel 500 Mpa
cover to rebars 40 mm

Calculations:
Bearing pressure under footing 207.9731 kPa
O.K. IN BEARING …………1)

Punching Check
Effective Depth 0.56 βc 0.4375
Control Perimeter 6.84 m ks 0.9375
Stress at Contr. P 0.570102 Mpa
Concrete Cap. 1.171875 Mpa
O.K. IN PUNCHING
Reinforcement Calculation
Along Length Along Width

Moment at face of column(kN): 140.7718 Moment at face of column(kN): 65.90149


Status: OK Status: OK
Area of Steel Required mm2/m: 2
720 Area of Steel Required mm /m:: 720
ρst 0.13% ρst 0.13%
Oneway Shear Check
Along Length Along Width
Shear at distance d from face 121.6643 Shear at distance d from face 28.07637
vc 0.28 Mpa vc 0.28 Mpa
Fcap 156.8 kN Fcap 156.8 kN
OK IN ONE WAY SHEAR OK IN ONE WAY SHEAR

Structural Calculations. 1
Sankhe Associates ISOLATED FOOTING DESIGN

Structural Calculations. 2
Sankhe Associates ISOLATED FOOTING DESIGN

SHEAR TABLE
One-way shear strength

Bearing pressure ULS 311.9597 kPA

Structural Calculations. 3