Among the automation control devices, PanelVisa series is a high function but cost
effective Panel. Besides most basic functions, it supports drivers of most PLCs,
invertors and temperature controllers on the market. It is not only equipped with
standard compact plastic case, but also provides customized key types for users to
design their favorite ones. PanelVisa satisfies many kinds of design, such as
emergency buttons with various buttons. Thus, PV series can concur harsh
environments to meet customers’ needs and welcome by tool machines, specified
function machine designers.
A-2 PanelVisa
PV035 Specifications
A-3
PanelVisa
A-4 PanelVisa
PV057 Specifications
COM1/9pin: RS232/RS422/RS485
Communication Ports COM2/9pin: RS232 .
COM2/Terminal 4Pin : RS422/RS485 .
A-5
PanelVisa
A-6 PanelVisa
PL035/PL037/PL057 Specifications
A-7
PanelVisa
The outlet and cut out dimensions of PV037-LSK are shown as following.
The outlet and cut out dimensions of PL035-TST, PL037LST, PV037-LST/LNT &
PV035-TST/TNT are shown as following.
A-8 PanelVisa
The outlet and cut out dimensions of PV057-LST/BST/TST & PV058-TST/TNT are
shown as following.
The outlet and cut out dimensions of PL057-LST & PL057-TST are shown as following.
cut out
A-9
PanelVisa
Installation
Before setup HMI, please cut a hole according to the cutout dimension.
Please see below pictures for your installation reference.
PL035-TST
118.5mmx92.5mm
PL037-LST
118.5mmx92.5mm
A-10 PanelVisa
PV037-LSK
159.5mmx88.5mm
PV037V-LSK
88.5mmx159.5mm
PL057-LST
PL057-TST
PV057-LST
PV057-BST
PV057-TST
PV058-TST/TNT
174.5mmx132.5mm
GD057-LST
GD058-TST
191.5mmx142.0mm
A-11
PanelVisa
PV037-LSK, a kind of key panel equipped with a 3.7” 160(H) x80(V) resolution LCD
display, a 22 keys membrane, allows users to design various applications. If the touch
panel is not fixed in a right position, set the DIP-SW1, SW2 and SW3 to off to execute
the touch panel adjustment. Please adjust it while needed and do not do the
unnecessary adjustment.
The Key panel PV037-LSK, is equipped with 22 keys on the membrane. Those keys
are some for numeric entry and some for programmable function keys. There are four
function keys, which can be assigned with various functions in any screen from the
software. The other 0-9 ten keys on the membrane provide numerical entering function.
They can also be locked temporarily. Press ESC and ENT at the same time to lock the
ten keys. To unlock, press ESC and ENT again. For double-key’s application, users can
operate to press together ESC and F1~F4 to act as a programmable function keys. The
Panel will automatically judge the data format or up/down settings to complete the data
input.
A-12 PanelVisa
Features
A-13
PanelVisa
SW3 SW4 HMI operation mode (Supports special functions for customized BIOS
version)
OFF OFF Res erved
ON OFF To exec ute HMI Com m unic ation tes ting program (SW 1,2 m us t
s et to Off)
OFF ON To exec ute Key adjus tm ent program or Touc h adjus tm ent
program (SW 1,2 m us t s et to Off)
ON ON To exec ute HMI applic ation program
1 2 3 4 5 6
***The PV037/PV057 has a BIOS password recovery system to prevent damage when
missing password. When you forget the password, which has been set to the HMI, this
HMI can execute RUN AP/Calibrate operation but cannot execute BIOS/Download
AP/Clear SRAM operations. When the users want to download new AP without
password, please set all DIP switches to off (SW1-6=Off), When turns on HMI again,
the HMI will display the clean all AP and old password screen. After proceeding this
procedure, the HMI can be operated normally again.
A-14 PanelVisa
Startup test
When turns on HMI, it will display self-testing screen. After completed, HMI will show
the system menu.
FigureA-1 When there are checksum errors, that could be RTC data missing, battery
failed or AP not being well downloaded.
**When turns on HMI, system will automatically execute hardware testing first to make
sure hardware are normal or not. The result will show on the screen (Figure A-1/A-2). If
there are problems, the HMI will not communicate with P.L.C. normally.
When losing electricity during downloading or the PC breaks off downloading, after
restarting the HMI, it will show Firmware Memory Checksum and Application Memory
Checksum error. It means there is an abnormal downloading. To get a correct self-
testing result, please execute a correct download AP procedure again.
If losing electricity during downloading or the PC breaks off downloading when
upgrading OS, it will surely cause download failure. If you restart the HMI, it will not
display normal screens or even cannot be turned on. In that case, please set the DIP
SW2 to OFF, restart the HMI to get a default BIOS version B then execute the
upgrading OS program to get a correct OS version. Set the DIP SW2 to ON then the
HMI can be turned on normally.
A-15
PanelVisa
DIP-SW Model:
If the DIP SW1 set to off, after self-testing the PV037/PV057 will show startup menu as
following figures.
The Startup menu of PV037-LSK is shown as below.
Situation 1: When SW2=OFF, it will show the default BIOS Ver. B.
Situation 2:When SW2=ON, it will show the Panel Setup screen or customized Version
screen.
Situation 2: When SW2=ON, it will show the Panel Setup screen or customized version
screen.
A-16 PanelVisa
No DIP-SW Model:
The Startup mode setting of the “No DIP-SW Models” is shown as below.
Situation 1: When power on, the user press the upper-left position of the touch screen
till the HMI has a beep sound.
Situation 2: It will enter BIOS mode and then you can adjust the startup mode is the
“Panel Setup” or “Run AP” screen.
A-17
PanelVisa
A-18 PanelVisa
Download AP
To download AP to HMI, please make sure the download cable is connected properly.
During the operating or in startup menu the HMI is ready to receive AP data sent by PC
automatically. When download AP the SW2=ON.
2. The HMI will judge the data correctness during downloading AP.
When the PC sends AP data to HMI, the HMI will show download AP screen and
display related information automatically to receive data. The HMI will show ”Incorrect
Model !” when the Model No. is not set correctly in the AP data. Please select a correct
Model No. from the software then download it again. If the HMI shows ”Incorrect User
ID Code !!”, then the hardware and software might not fit each other. Please check the
brand name of the HMI to make sure you purchased a right hardware.
A-19
PanelVisa
Extension Bus Port (It’s an Optional device) this port can link with other extension
modules for advanced functions.
A-20 PanelVisa
LCD adjustment
A-21
PanelVisa
Use DC24V as PV037 power input. The power consumptions are as following table. To
ensure the PV037/PV057 hardware working properly, to avoid outside
electromagnetism noise, please ground the power source properly.
Power grounding caution: The products are all equipped with power terminals and lock
assembling sets. The operating procedure is:
1.Screw off the power terminal.
2.Peel the 24V wiring(1.25mm) for 1 cm then plug in the power terminal.
3.Use line screw driver to screw the power terminal tight.
Package content
We are appreciated for your purchasing our products. Our standard package should be
equipped with 5 items as following. Please check after receiving it. If there’s any
shortage, please refer to the suppliers.
Cautions
If this product is used in a house, radio-wave interference might occur to other devices.
In the case that it does occur, the user is requested to try a variety of remedies to solve
the problem.
A-22 PanelVisa
Power source
PV037/PV057 is equipped with DC24V input power. If the supply power is other than
DC24V, whatever less or excess, it will severely damage the HMI. Therefore, check
the switching power supply supporting the DC power regularly.
To avoid electronic shock, be sure the Power Cable is unplugged from the power
outlet when connecting the cable to the HMI.
Grounding
From the FG terminal at the rear side of HMI, please make sure the grounding is
made exclusively.
When the FG terminal is connect, be sure the wire is grounded. Without grounding,
the operation of HMI may be severely affected by excess external noise levels and
vibrations.
Use a cable at 2 m㎡ (AWG 14) to ground the equipment. Ground resistance must
be less than 100Ω(class3).Note that the ground cable must not be connected to the
same ground point as the power circuit.
Installation
Mount the HMI from the front of a suitable preserved hole.
Attached the brackets behind.
Fasten the screw of the brackets with proper force. Tightening too much may cause
damage to the structure of the unit.
Input and Output signal lines must be separated from the power cables for
operational circuits. Use shielded cables or it may cause unpredictable problems.
Do not allow cut wires, filling, or shavings to fall inside a unit or block when drilling
holes or connecting cables/lines.
Environment
Do not install in areas subject to excessive dust, oily mist, conductive dust, corrosive
gas, or flammable gas.
Do not mount in areas subject to shock or vibration.
Do not mount in areas subject to high temperature, moisture, or rain.
Indicated loss of life, severe personal injury, or substantial property damage will result
if proper precautions are not taken.
A-23