Week 1: 1.1) The symmetrical components are used in the fault analysis because 1 point
Week 2
The number of equations becomes smaller
Week 3
The sequence networks do not have mutual coupling
Week 4
(Contd.)
1
Lecture 52: Xn < (X 1 − X 0 )
3
Symmetrical
components
1
(Contd.) Xn =
3
(X 1 − X 0 )
Lecture 53:
Symmetrical Xn = 0
components
(Contd.) No, the answer is incorrect.
Score: 0
Lecture 54:
Symmetrical Accepted Answers:
components Xn >
1
(X 1 − X 0 )
(Contd.) 3
3) A fault occurring at the terminals of an unloaded synchronous generator operating at its rated 1 point
Lecture 55:
Power system voltage has resulted in the following values of the current and voltages as below
stability
Ia0 = j2.31pu, Ia1 = j3.51pu, Ia2 = −j0.84pu
Quiz : WEEK 11
ASSIGNMENT
https://onlinecourses.nptel.ac.in/noc17_ec08/unit?unit=101&assessment=126 1/4
07/12/2017 Power System Analysis - - Unit 12 - Week 11
1 Va0 = Va1 = Va2 = j2.31pu
WEEK 11
ASSIGNMENT Determine which type of fault has occurred.
SOLUTIONS
LL fault
Week 12 LG fault
SLG fault
LLG fault
4)The voltage at the terminals of a balanced load consisting of three 20 ohm star connected 2 points
resistances are
The ratio of positive sequence power to negative sequence power consumed by 20 ohm resistance is in
between
4.0-5.5
6.0-7.5
0.1-0.3
8.0-9.5
5) A 50 MVA, 11 kV, 3 phase alternator was subjected to different types of faults. The 1 point
magnitude of the fault currents are as below
Three phase fault: 1870 A
Line to line fault: 2590 A
Single line to ground fault: 4130 A
The neutral of the alternator is solidly grounded. What will be the negative sequence reactance of the
alternator? (Neglect the resistance)
1.2-1.6 ohm
0.7-0.9 ohm
3.0-4.0 ohm
0.2-0.4 ohm
6)For the above mentioned problem (Problem 5) find out the zero sequence reactance of the 1 point
alternator
1.2-1.6 ohm
0.7-0.9 ohm
0.2-0.4 ohm
3.0-4.0 ohm
https://onlinecourses.nptel.ac.in/noc17_ec08/unit?unit=101&assessment=126 2/4
07/12/2017 Power System Analysis - - Unit 12 - Week 11
0.2-0.4 ohm
7) A 3 phase generator rated 15 MVA, 13.2 kV has a solidly grounded neutral. Its positive, 1 point
negative and zero sequence reactances are 0.4 pu, 0.3 pu and 0.05 pu respectively. Find the value of
the reactance to be connected in the neutral circuit so that fault current for a single line to ground fault
with zero fault impedance, does not exceed the rated line current
2.25 pu
0.083 pu
0.25 pu
0.75 pu
8) For the previous problem (Problem 7) find the value of the resistance to be added in the 1 point
neutral circuit to serve the same purpose
30-32 ohm
2.2-3.2 ohm
10-12 ohm
0.90-1.10 ohm
9) A 33 kV bus bar has a 3 phase fault level of 1000 MVA. The negative and zero sequence 2 points
source reactances are 2/3 and 1/3 of positive sequence reactance. The zero sequence source
resistance is 60 ohm. A 30 MVA 33kV/132 kV solidly grounded delta/star transformer having a reactance
of 0.1 pu is fed from 33 kV bus. Find fault current at 132 kV bus for double line to ground fault. Phase
sequence is a-b-c and b, c are the faulted phases.
700-800 A
1100-1200 A
100-200 A
900-1000 A
10)For the previous problem (Problem 9) find the fault MVA at 132 kV bus for L-L fault. Phase 2 points
sequence is a-b-c and b,c are the faulted phases.
100-150 MVA
300-350 MVA
400-450 MVA
None of the above