FXS1800 Commissioning Tool

Operating Manual

A6V10239594_c_en Smart Infrastructure


2019-05-26
1 INTRODUCTION....................................................................................................................................... 2
2 INSTALLATION ........................................................................................................................................ 2
2.1 SOFT/HARDWARE REQUIREMENTS ................................................................................................................ 2
2.2 INSTALLATION PROCESS ................................................................................................................................... 2
2.3 USB DRIVE ............................................................................................................................................................ 4
2.4 UNINSTALLATION ............................................................................................................................................... 6
3 START/EXIT ............................................................................................................................................. 8
3.1 START ......................................................................................................................................................................8
3.2 EXIT .........................................................................................................................................................................9
4 OPERATION ........................................................................................................................................... 10
4.1 HOW TO CREATE A NEW SYSTEM...................................................................................................................10
4.2 HOW TO ADD A CONTROLLER.........................................................................................................................12
4.3 HOW TO ADD A LINE ..........................................................................................................................................14
4.4 HOW TO ADD A FIELD DEVICE ........................................................................................................................16
4.5 HOW TO EDIT PARAMETERS ............................................................................................................................18
4.6 HOW TO DELETE A CONTROLLER/LINE/FIELD DEVICE/GROUP .............................................................19
4.7 HOW TO COPY CONTROLLER/LINE/FIELD DEVICE ....................................................................................20
4.8 HOW TO CREATE A LOGIC EXPRESSION .......................................................................................................21
4.9 HOW TO VIEW A LOGIC EXPRESSION ............................................................................................................23
4.10 HOW TO EDIT A LOGIC EXPRESSION .............................................................................................................24
4.11 HOW TO DELETE A LOGIC EXPRESSION .......................................................................................................25
4.12 HOW TO DOWNLOAD/UPLOAD CONFIGURATION FILES ..........................................................................26
4.14 HOW TO CHOOSE LANGUAGE .........................................................................................................................29
4.15 HOW TO VIEW THE VERSION OF FXS1800 ....................................................................................................30
4.16 HOW TO DOWNLOAD SYSTEM FILES ............................................................................................................30
4.17 HOW TO EXPORT/IMPORT FILES TO/FROM EXCEL FILE ...........................................................................32
4.18 HOW TO EXPORT FIELD DEVICE LIST TO EXCEL .......................................................................................36
4.19 HOW TO UPLOAD HISTORY RECORDS ..........................................................................................................38
4.20 HOW TO VIEW HISTORY EVENT......................................................................................................................39
4.21 HOW TO ASSIGN A FIELD DEVICE TO GROUPS/FRT ...................................................................................40
4.22 HOW TO DELETE FIELD DEVICE FROM A GROUP/FRT ..............................................................................42
4.23 HOW TO ADD/DELETE A GROUP .....................................................................................................................43
4.24 HOW TO CHANGE PASSWORD .........................................................................................................................45
4.25 HOW TO FIND FIELD DEVICE ..........................................................................................................................46
4.26 HOW TO CHECK SAME ID OF FIELD DEVICE ...............................................................................................47
4.27 HOW TO ADD/DELETE A SLAVE ......................................................................................................................49
4.28 WINDOW CASCADE/TILE..................................................................................................................................51
4.29 MAIN PROGRAM WINDOW MINIMIZATION/RESUME ................................................................................53
APPENDIX 1 EDITABLE PARAMETER LIST ................................................................................................ 54
APPENDIX 2 EQUIPMENT GROUPING TABLE ........................................................................................... 57
APPENDIX 3 RULES FOR EDITING AN INTERLOCK .................................................................................. 58
APPENDIX 4 SHORTCUT KEY LIST.............................................................................................................. 60

1
Smart Infrastructure A6V10239594_c_en
2019-05-26
1 INTRODUCTION

FXS1800 software is mainly used for the engineering commissioning and maintenance of FS18 fire alarm
system.

2 INSTALLATION

2.1 SOFT/HARDWARE REQUIREMENTS

- Operation system: Microsoft Windows XP, Windows 2000, Vista


- Application software: Microsoft Excel 2003, Microsoft IE5
- CD-ROM
- USB port
- CPU: PIII 1.0GHZ
- Memory: 512M
- Hard disk: 10G
- Display resolution: 1024*768

2.2 INSTALLATION PROCESS

Step 1: Insert the disc installed with FXS1800 softwares in to CD-ROM


Step 2: Click on "Start" in the taskbar.
Step 3: Click on "run"
Step 4: Input document directory and document name E:\setup.exe
(Make corresponding modification if E: is not the CD-ROM)

2
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 5: Click on "Next".

It is suggested not to change fold if it is not necessary.

Step 6: Click on “Next”.

Step 7: Click on “Next” to start the installation. An icon will be created on desktop.

Step 8: Click on “Close”. The computer does not need to restart.

3
Smart Infrastructure A6V10239594_c_en
2019-05-26
2.3 USB DRIVE

Installation process
Insert USB wire. For the first time of insert, the installation program will pop out automatically.

Step 1: Click on "Next".

Step 2: Select "Install from a list or specific location (advanced) (S)" and click on "Next".

4
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: Select the location of FXS1800 software (with drive) and click on "Next".

Step 4: Start copy.

5
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 5: Click on "Finish" and exit the installation process.

2.4 UNINSTALLATION

There are two ways to uninstall the FXS1800 software.


The first way: Find the “Uninstall FXS1800” icon through "Begin" menu and click on it. A confirm window will
pop out. Click on "Yes" to confirm the uninstallation or click on "No" to cancel.

6
Smart Infrastructure A6V10239594_c_en
2019-05-26
The second way: Select “SIEMENS FXS1800 Configuration Tool” through "Add or Remove Programs". Click
on "Change/Remove". A confirm window will pop out. Click on "Yes" to confirm the uninstallation or click on
"No" to cancel.

7
Smart Infrastructure A6V10239594_c_en
2019-05-26
3 START/EXIT

3.1 START

Step 1: There are two ways to start FXS1800 system.

- Click on the icon on the desktop directly.

- Find the FXS1800 icon through the "Start" menu and click on it.

Step 2: Input password (The initial password is 4321 which can be changed by users.)
(See "how to change
the password") and click on "OK" to enter the system.

8
Smart Infrastructure A6V10239594_c_en
2019-05-26
Note: The initial defaulted language of FXS1800 softwares is English which can be changed after the system
is started (See how to choose language). The chosen language will become the defaulted language.

3.2 EXIT

There are two ways to exit FXS1800:

The first way: Select "Exit" from the "File" menu. System will remind users to "save the file" if the document is
changed. Click on "OK" to save it and exit FXS1800.

The second way: Directly click on the “X” on the top right corner of the window. System will remind users to
"save the file" if the document is changed. Click on "OK" to save it and exit FXS1800.

9
Smart Infrastructure A6V10239594_c_en
2019-05-26
4 OPERATION

4.1 HOW TO CREATE A NEW SYSTEM

Step 1: Directly click on the icon “/” in taskbar or select "New" through "File" menu. A "New" window will pop
out.

Step 2: Input engineering name and choose the save path of configuration files, then lick "OK". The new
engineering name will appear in the tree browsing window on the left. Meanwhile a configuration fire named
"engineering name .fxs" is created in "Catalog". The engineering name can be edited in the "Property View"
window on the right.

10
Smart Infrastructure A6V10239594_c_en
2019-05-26
Note:

Peer to peer reset: FALSE (default) / TRUE.

· FALSE: press the Reset button on one controller, the fire alarm on the controller disappears only on
the controller while the fire alarm on the slave controller disappears both on the controller and the
slave controller.
· TRUE: the fire alarm status stays in consistent on all controllers in the same network. The same
network means at least one controller contains all the other controllers as slaves.

Refer to 4.27 to learn how to add/delete a slave.

11
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.2 HOW TO ADD A CONTROLLER

Step 1: Select a system and right click on it, the operable items will be listed. Click on "Insert Node", "Add a
station" window will pop out; or select a system and directly click on the icon “+”, the "Add a station" window
will pop out; or select a system and select "Add" in "Edit" menu, the "Add a station" window will pop out.

Step 2: Input data.

- Address: Distributed by the system automatically, which the eight-figure DIP switch should consist with.
- Type: Choose corresponding type according to the controller type. Available controller types:
FS1820/FS1840/FS1860.
- Walk- test time: 3 min (default). Setting range: 1-60 min.
- Login time: 3 min (default). Setting range: 1-60 min.
- Customer Text: defined by user.

12
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: Click on "OK". The added controller will be displayed in the left window with highlight. The editable
items can be edited through the "node view" on the right. Click "Ok" after the change.

Note:

- L2/L3 user password: for Level 2/3 users to log on the controller. The passwords for L2 and L3 can’t be
the same.
- Buzzer sound level: 7 (default). Setting range 0~7. System is muted when it's set at 0
- LCD closing time: 5 min (default). Setting range 1~60 min.
- The following functions can be realized through the settings of “Time Base”:
1. When “Only Time Base” is selected, this controller is configured as the time base. The system time of
other controllers in the same network is synchronized when the time base controller starts up and is
synchronized once an hour. Only one time base controller is allowed in a network.
2. When “Only Master” is selected, this controller is configured as the master controller in the same
network, and therefore it realizes the functions of manual/auto switching and resetting in the whole
network.
3. When “Time Base and Master” is selected, this controller is configured as the time base and master at
the same time, which results in system time synchronization, manual/auto switching and resetting for the
whole network.
4. When “None” is selected, this controller is not configured as the time base or master.

13
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.3 HOW TO ADD A LINE

Step 1: Choose the "Physical Tree" under the controller to which you want to add a loop and right click on it.
The operable items will be listed. Click on “Insert Node", the "Add Line" window will pop out; or choose the
"Physical Tree” under the controller to which you want to add a loop and click on the icon “+” in the taskbar
directly, the "Add Line" window will pop out; or choose the "Physical Tree” under the controller to which you
want to add a loop and select "Add" in "Edit" menu, the "Add Line" window will pop out.

Step 2: Input data.

- Address: Distributed by the system automatically


- Type: Choose corresponding type according to the purpose of a loop
- Customer Text: User define

14
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: Click on "OK". The added loop will be displayed in the left window. The editable items can be edited
through the "Property View" on the right. Click "Ok" after the change.

Note:

Normally FC1820/FC1840 loop is defaulted to be full loaded and need no more lines. Only FC1860 can add
new line.

- The defaulted lines of FC1820 controller are: power monitor line, Onboard I/O line, main board port,
detective loop #1, interlocking panel and fire display panel;
- The defaulted lines of FC1840/FC1860 controller are: power monitor line, Onboard I/O line, main board
port, onboard detection line #1, onboard detection line #2, interlocking line, FRT and mimic drivers.

15
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.4 HOW TO ADD A FIELD DEVICE

Step 1:Choose the line to which you want to add an field device and right click on it. The operable items will
be listed. Click on "Insert Node", the "Add a field device" window will pop out; or choose the line to which you
want to add an field device and click on the icon “+” in the taskbar directly, the "Add a field device" window will
pop out; or choose the line to which you want to add an field device and select "Add" in "Edit" menu, the "Add
a field device" window will pop out.

Step 2: Input data.

- ID : the only identification of a field device. It's on the label.


- Type: Choose corresponding type according to the purpose of the field device.
- Customer Text: user defines.

16
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: Click on "OK". The added field device will be displayed in the left window. The editable items can be
edited through the "Property View" on the right. Click "Ok" after the change.

Note:

- Up to 252 field devices (or 252 load factors) can be connected to one line; Up to 32 floor repeater display
panels can be connected to FRT line.
- Connectable field devices of detection line:
No. Type Description
1. FDT181 Heat detector
2. FDO181 Smoke detector
3. FDM181 Manual call point
4. FDHM181 Hydrant manual call point
5. FDCI181-2 Input module
6. FDCIO181-2 Input/output module
7. FDCL181 Line seperator

- Connectable field devices of FRT line:


No. Type Description
1. FT1810 Floor repeater display panels

17
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.5 HOW TO EDIT PARAMETERS

Find the controller/line/field device which parameters need to be edited through the tree or "Find Point"
function ( See 4.24) in the left window (lines and field device are under physical tree and groups are under
logical tree.). After chosen, all its parameters will be displayed in "Property View" in the right window, among
which editable items are white and non-editable items are gray. Select a parameter to edit it. After the change,
click "OK".

Note: To change customer text of a controller/line/field device, you can press "F2" directly with highlight of the
controller/line/field device.

18
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.6 HOW TO DELETE A CONTROLLER/LINE/FIELD DEVICE/GROUP

Find the controller/line/field device which parameters need to be deleted through the tree or "Find Point"
function (See 4.24) in the left window (lines and field device are under physical tree and groups are under
logical tree.). Chose an item and right click on it, the editable items will be listed. Click on "Delete Node", a
confirm window will pop out. Click on "OK" to confirm the delete or click "Cancel"; or find the
controller/line/field device which parameters need to be deleted (lines and field device are under physical tree
and groups are under logical tree.). Directly click on the icon "-" in the taskbar, a confirm window will pop out.
Click on "OK" to confirm the delete or click "Cancel"; or find the controller/line/field device which parameters
need to be deleted (lines and field device are under physical tree and groups are under logical tree.). Select
"Delete" in "Edit" menu, a confirm window will pop out. Click on "OK" to confirm the delete or click "Cancel".

19
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.7 HOW TO COPY CONTROLLER/LINE/FIELD DEVICE

Step 1: Find the controller/line/field device to copy through the tree or "Find Point" function (See 4.24) in the
left window (lines and field devices are under physical tree). Chose an item and right click on it, the editable
items will be listed. Click on "Copy"; or select the controller/line/field device to copy through the tree or "Find
Point" function ( See 4.24) in the left window (lines and field devices are under physical tree), directly click on
the icon “2”; or select the controller/line/field device to copy through the tree or "Find Point" function ( See
4.24) in the left window (lines and field devices are under physical tree), select "Copy" in the "Edit" menu.

Step 2: Right click on the place you want to paste it, editable item list will pop out. Click "Paste"; or directly
click on the icon “4" in the taskbar; or select "Paste" in the "Edit" menu.

20
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.8 HOW TO CREATE A LOGIC EXPRESSION

Step 1: Choose “Logic Express Container” right click on it. Click “Insert Node” item, “Control View” will be
displayed automatically in the right window. The “Edit logic expression” view is marked with “P “.

Step 2: Input logic expression according to logic expression regulation (see appendix 3), input logic expression
name defined by user, and choose a save place for logic expression from list.

Two ways of input interlock expression:

- Input address of field device manually


- Double clicking on the selected field device from the tree

21
Smart Infrastructure A6V10239594_c_en
2019-05-26
Link

New Compile

Step 3: After finishing input, click on "compile" icon (shown as above). If the input is correct, compile result
window will display "OK!"; otherwise error information will be displayed. After the correction, compile again.

Note:

“New” button: For creating a new logic expression.

“Link” button: Select a field device address in the logic expression input window and click the icon, system will
find the field device in the left tree.

“Compile” button: For compiling logic expression.

“*” button: For inputting “*” in a logical expression.

“=” button: For inputting “=” in a logical expression.

“+” button: For inputting “+” in a logical expression.

22
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.9 HOW TO VIEW A LOGIC EXPRESSION

Step 1: Choose a logic expression to view through the interlock list in logical tree; click on "Control View" on the
right window, the logic expression information will be displayed.

23
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.10 HOW TO EDIT A LOGIC EXPRESSION

Step 1: Choose a logic expression to be edited through the LogicalExpressContainer list in logical tree, then
click on "Control View" on the right window, the logic expression information will be displayed on the right
window.

Compile

Step 2: Click on "edit logic expression" (shown as above), the interlock name domain, edit interlock, input
domain; output domain will turn to white. Now the logic expression can be edited. Data input please refer to
"how to create a logic expression".

Step 3: After finishing input, click on "Compile" icon (shown as above). If the input is correct, compile result
window will display "OK!"; otherwise error information will be displayed. After the correction, compile again.

24
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.11 HOW TO DELETE A LOGIC EXPRESSION

Find the logic expression to be deleted through the logical tree in the left window. Select it and right click on it,
the editable items will be listed. Click on "Delete node", a confirm window will pop out. Click on "OK" to
confirm the delete or click "cancel"; or find the logic expression to be deleted. Select "Delete" in "Edit" menu,
a confirm window will pop out. Click on "OK" to confirm the delete or click "Cancel".

25
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.12 HOW TO DOWNLOAD/UPLOAD CONFIGURATION FILES

Download configuration files

Step 1: When configuration is finished, directly click on the "download configuration files" icon in the taskbar;
or select "Download Config Files" from "Tool" menu; or press Ctrl+W on keyboard.

For downloading
configuration file

Step 2: System attention window is shown as follows. Click on "Yes" to continue the download; otherwise
click on "No".

Step 3: If the download is successful, "Successful download" will be displayed; otherwise "Unsuccessful
download" will be displayed. Controller need to be restarted after a successful download to make the
configuration files downloaded take effect.

26
Smart Infrastructure A6V10239594_c_en
2019-05-26
Upload configuration files:

Step 1: If there are a large amount of configurations to modify, it is suggested to upload them to a PC/laptop
to make the modification. Click on the "Upload configuration files" icon in the taskbar; or select "Upload
Config Files" from "Tool" menu; or press Ctrl+U on keyboard.

Uploading
Configuration files

Step 2: System attention window is shown as follows. Select according to the actual situation and click on
"OK".

27
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: Choose a way of uploading and click on "OK".

System attention window is shown as follows. Click on "Yes" to continue the upload; otherwise click on "No".

Step 4: Click on "Start" to upload configuration files. Click on "Cancel" to stop the upload.

28
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.14 HOW TO CHOOSE LANGUAGE

Step 1: If there are no FXS1800 configuration files opened, select "Language" from the "View" menu; if there
are configuration files opened, close them before selecting "Language" from the "View" menu.

Step 2: Select a proper language and click on "OK". FXS1800 software will be restarted and the language
chosen will take effect. When FXS1800 software is re-started, that language becomes the defaulted one.

Note: The initial defaulted language of FXS1800 software is English.

29
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.15 HOW TO VIEW THE VERSION OF FXS1800

Step 1: Select "About FXS1800" from "Help" menu, the version information of FXS1800 will be displayed.

4.16 HOW TO DOWNLOAD SYSTEM FILES

Step 1: Select "download system" from "Tool" menu.

Step 2: "Download system" pops out. Click on "Browse" and select system files, then input CRC validation
code (provided together with the new version system software).

Step 3: Click on "Start", system will remind user to restart the controller.

30
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 4: After restarting the controller, click on "OK" to start the download.

If the download is successful, "successful download" will be displayed; otherwise "unsuccessful download"
will be displayed.

Step 5: Click on "OK", system will remind user to restart the controller.

Step 6: After restarting the controller, click on "OK" to finish the download.

31
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.17 HOW TO EXPORT/IMPORT FILES TO/FROM EXCEL FILE

Export configuration file to Excel:

Step 1: Click on "Export to Excel File" icon in the taskbar; or select "Export to Excel File" from the "Tool"
menu.

Export To Excel File

Step 2: Input file name and click on "Save".

32
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: Choose an export mode and click on "OK".

Step 4: Click on "OK" to finish the export.

Step 5: Configuration file contents including controller, line, group, FRT, logic expression, point & channel are
displayed in different tables of an Excel file.

33
Smart Infrastructure A6V10239594_c_en
2019-05-26
Import configuration files from Excel:

Step 1:Click on "Import From Excel File" icon in the taskbar; or select "Import From Excel File" from the "Tool"
menu.

Import From Excel File

Step 2: Select the configuration files to import to Excel from the file list and click on "Open".

If the file format is not correct, system attention is shown as follows. Click "OK".

34
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: Choose a way to upload and click "OK".

Step 4: Choose a way to import/export and click "OK" to start the import.

Step 5: If the import is successful, system notification is shown as the following figure. Click "OK" to finish the
import.

35
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.18 HOW TO EXPORT FIELD DEVICE LIST TO EXCEL

Step 1: If there is a need to export field device list to Excel, click on the icon shown as follows or select
"Export Commissioning Table to Excel" from the "Tool" menu.

Export commissioning table to Excel

Step 2: The following window pops out. Input project name, location, customer name, contact name and
contact number, click on "print".

36
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: The following window pops out. Input file name and click on "save"

Step 4: Field device list is displayed as the following figure.

37
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.19 HOW TO UPLOAD HISTORY RECORDS

Step 1: Select "Upload History Event" from the "Tool" menu.

Step 2: The "Upload History Event" window pops out. Set the saving path and click "OK".

Step 3: System attention window pops out, Click "Start" to start the upload. The history records uploaded will
be saved as Excel files in the place chosen.

38
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.20 HOW TO VIEW HISTORY EVENT

Step 1: Select "View History Event" from the "Tool" menu.

Step 2: The "View History Event" window pops out. Set the saved path and click "OK".

Step 3: Select the file containing history records and click "OK". The file will be displayed as Excel format.

39
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.21 HOW TO ASSIGN A FIELD DEVICE TO GROUPS/FRT

Step 1: Select a field device to be assigned to a group/FRT from the logic tree. Right click on it to pop out an
operable item list. Select "Add to groups/FRT.

Step 2: "Select group/FRT" window pops out. Select the target group/FRT and click "OK".

40
Smart Infrastructure A6V10239594_c_en
2019-05-26
Step 3: The field device will be displayed in “Children View” of the selected group/FRT".

Besides, group assign can be also realized through the "Assign to group" of "Property View".

41
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.22 HOW TO DELETE FIELD DEVICE FROM A GROUP/FRT

Step 1: Select a field device to be deleted from a group/FRT in the left window and right click on it to pop out
the operable item list. Select "Delete From Group/FRT"

Step 2: Confirm window pops out. Click "Yes" to confirm the delete; otherwise click "No".

42
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.23 HOW TO ADD/DELETE A GROUP

Add a group:

Step 1: Select the group type of the group to add from the logic tree and right click on it to pop out the
operable item list. Select "Insert Node"; or directly click the “+” icon in the taskbar to pop out the "Add
Group(s)" window; or select "Add" in the "Edit" menu to pop out "Add Group(s)" window.

Step 2: Input quantity and customer text. Click "OK" to finish adding. The added group will be displayed in the
group type.

43
Smart Infrastructure A6V10239594_c_en
2019-05-26
Delete a group:

Step 1: Select the group to be deleted and right click on it to pop out the operable list. Select "Delete Node".

Step 2: Confirm window pops out. Click "Yes" to confirm the delete; otherwise click "No".

44
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.24 HOW TO CHANGE PASSWORD

Step 1: Start FXS1800 software and input initial password, then select "Change Password" and click "OK".

Step 2: Input new password twice and click "OK".

Step 3: If the input is correct, the system attention is shown as follows. Click "OK" to finish password change.

45
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.25 HOW TO FIND FIELD DEVICE

Step 1: Click on "Find Point" icon in the taskbar.

Find Point

Step 2: Input customer text or device ID number and click "Find". If the field device is found, the cursor in the
left window will locate on it; otherwise the system will display "No Such Point".

46
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.26 HOW TO CHECK SAME ID OF FIELD DEVICE

Step 1: Click the "Check Field device same ID " icon on the tool bar.

Check Field device same ID

Step 2: If there are same ID numbers, a window will pop out displaying all the equipments with repeated ID
numbers and their controller names, line names and field device names. Users can find them according to
this information until all the changes are finished. Click "OK" to close the window; if there no field device with
same ID numbers, system will display "No field device with same ID".

Note: System automatically saves configuration files every 20 minutes. Same ID number will be checked
before the saving. There will be notification if there are repeated ID numbers.

47
Smart Infrastructure A6V10239594_c_en
2019-05-26
48
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.27 HOW TO ADD/DELETE A SLAVE

Add:

Step 1: Select "Station container" from the logical tree of the controller and right click on it to pop out the
operable list. Click "Insert Node" to pop out "Insert" window; or directly click the “+” icon in the tool bar to pop
out the "Insert" window; or select "Add" in the "Edit" menu to pop out the "Insert" window.

Step 2: Select the controller to be set as a slave and click "OK". The selected controller will appear on the
slave list, which means this controller is a slave while its upper level controller is a master.

49
Smart Infrastructure A6V10239594_c_en
2019-05-26
Delete:

Step 1: Select a slave to be deleted from the station container list of the logical tree and right click on it to pop
out the operable item list. Click "Delete Node"; or directly click the “-” icon in the tool bar; or select "Delete"
from the "Edit" menu.

Step 2: Confirm window pops out. Click "Yes" to confirm the delete, the controller will be deleted from the
salve list. Otherwise click "No".

50
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.28 WINDOW CASCADE/TILE

FXS1800 software support operations to more than one configuration files at the same time. Therefore it's
necessary to arrange and shift between different windows. “Window” menu include "Cascade" and "Tile".
When files are opened, file name list will appear on the menu. Click on the file name to shift between the
present file. Click "Cascade", all the files opened will be cascaded. Click "Tile", all the files opened will be
vertically tiled.

51
Smart Infrastructure A6V10239594_c_en
2019-05-26
Stacked windows:

Tiled windows:

52
Smart Infrastructure A6V10239594_c_en
2019-05-26
4.29 MAIN PROGRAM WINDOW MINIMIZATION/RESUME

FXS1800 software can operate independently backstage. Users can minimize the window when it's not being
used and resume it when you need to use it. Minimization operation can be conducted by the "-" icon on the
top right corner of the window. Resume operation can be conducted by clicking on the icon of the program.
FXS1800 software cannot be minimized when it's operating.

53
Smart Infrastructure A6V10239594_c_en
2019-05-26
APPENDIX 1 EDITABLE PARAMETER LIST
Equipment type Editable item Parameter description
System Text System name
Station Text Controller name
- FC1820 Login time Under 2nd/3rd level, if there is no operation in preset login time,
- FC1840 controller will automatically log out to 1st level. Effective value:
- FC1860 1-60 minutes.
Walk-test time When controller is being tested, it will automatically resume to
normal status after preset mobile test time, without the need of
manual operation. Effective value: 1-60 minutes.
Buzzer sound Setup sound volume of beeper, with effective value of 0-7.When
level the value is 0, it is silence mode.
LCD closing If there is no operation of controller in preset LCD off time, LCD
time will shut off back light. Effective value: 1-60 minutes.
Main board input/output Text Main board input/output (default)
P2 circuit Text P 2 circuit #
Topology type Option 1: Stub
Option 2: Loop(default)
Power supply Text Power supply (default)
Interlocking panel Text Interlocking panel (default)
FDO181 Smoke Text Equipment location description
detector Sensitivity Option 1: Standard (default)
Option 2: Sensitive
FDO181 heat detector Text Equipment location description
Detection Option 1: A2S (constant temperature) (default)
mode Option 2: A2R (Difference/constant temperature)
FDM181 Manual call Text Equipment location description
point
FDHM181 Hydrant Text Equipment location description
manual call point
FDCI181 Input module Text Equipment location/function description
FDCIO181 Input/output Text Equipment location/function description
module
Monitor input Text Equipment location/function description
(FDCI181&FDCIO181) Inversion Option 1: Normal (close of normally open contact is state of start)
(default)
Option 2: Inverting (open of normally open contact is state of
start)
Monitor input Text Equipment location/function description
(Main board input)
Status input Text Equipment location/function description
(FDCI181&FDCIO181)

54
Smart Infrastructure A6V10239594_c_en
2019-05-26
Status input Text Equipment location/function description
(Main board input)
Fire alarm input Text Equipment location/function description
(FDCI181&FDCIO181)
Fire alarm input Text Equipment location/function description
(Main board input)
Output without answer Text Equipment location/function description
(FDCIO181) Inversion Option 1: Normal (When normally open contact NO of relay is
close, it is state of start) (default)
Option 2: Inverting (When normally open contact NC of relay is
open, it is state of start)
Signal Shape Option 1: Level signal (after startup, output status remains start
constantly) (default)
Option 2: Pulse signal (after startup, output status remains start
for a period of time)Time period can be configured through pulse
time)
Failsafe Option 1: Hold (remain the same status as failure happened
position before)
Option 2: Halt (remain off status) (default)
Option 3: Start (remain start status)
Pulse model Option 1: 1s (default)
Option 2: 2s
Option 3: 3s
Option 4: 4s
Option 5: 10s
Option 6: 15s
option 7: 20s
Output style option 1: Active output
option 2: Passive output
Output without answer Text Equipment location/function description
(interlocking panel and
main board output)
Output with answer Text Equipment location/function description
(FDCIO181) Supervision In preset monitor time, if there is no answer signal received,
time system defines it as start without answer. Default value is 10
seconds. Effective value: 1-60 seconds.
Inversion option 1: Normal (When normally open contact NO of relay is
close, it is state of start) (default)
option 2: Inverting (When normally open contact NC of relay is
open, it is state of start)
Signal Shape option 1: Level signal (after startup, output status remains start
constantly) (default)
option 2: Pulse signal (after startup, output status remains start
for a period of time)Time period can be configured through pulse
time)
55
Smart Infrastructure A6V10239594_c_en
2019-05-26
Failsafe option 1: Hold (remain the same status as failure happened
position before)
option 2: Halt (remain off status) (default)
option 3: Start (remain start status)
Pulse model option 1: 1s (default)
option 2: 2s
option 3: 3s
option 4: 4s
option 5: 10s
option 6: 15s
option 7: 20s
Output style option 1: Active output
option 2: Passive output
Output with answer Text Equipment location description
(interlocking panel and Monitor time In preset monitor time, if there is no answer signal received,
main board output) system defines it as start without answer. Default value is 10
seconds. Effective value: 1-600 seconds.
NAC Text Equipment location description
Main power Text Main power (default)
Backup power Text Backup power (default)
Charging circuit Text Charging circuit
Detecting group Text Equipment location description
Control output group Text Equipment location description
Supervision group Text Equipment location description
FRT group Text Equipment location description
Printer Text Equipment location description
FDCL181 Line Text Equipment location description
seperator

56
Smart Infrastructure A6V10239594_c_en
2019-05-26
APPENDIX 2 EQUIPMENT GROUPING TABLE
Fire
Control
Detecting Monitor display
Equipment type output
group group panel
group
group
FDO181 Smoke detector √ √
FDT181 Heat detector √ √
FDM181 Manual call point √ √
FDHM181 Hydrant manual call point √ √
FDCI181 Input module √
FDCIO181 Input/output module √
Main board supervision input √ √
Main board status input √ √
Main board alarm input √ √
Main board output, interlocking panel output (without
√ √
answer)
Main board output, interlocking panel output (with
√ √
answer)
NAC √
Main power √
Backup power √
Charging circuit √
Printer
FDCL181 Line seperator √
FDCI181 Input module/ FDCIO181 Input/output
√ √
module supervision input
FDCI181 Input module/ FDCIO181 Input/output
√ √
module status input
FDCI181 Input module/ FDCIO181 Input/output
√ √
module alarm input
FDCI181 Input module/ FDCIO181 Input/output
√ √
module output (without answer)
FDCI181 Input module/ FDCIO181 Input/output
√ √
module output (with answer)

Note:
- Relations among equipments of control output group is “and” relations. Relations among
equipments of monitor and detection group is “or” relations.
- Alarm and failure information of equipments of fire display panel group can be displayed on
the display panel.
- Equipments must be put into groups to participate interlocking relation program.

57
Smart Infrastructure A6V10239594_c_en
2019-05-26
APPENDIX 3 RULES FOR EDITING AN INTERLOCK
1. Logic expression:
01.0001.07+01.0002.07+01.0003.07=01.0004.10
1 2

Input Output
① Group No.: xx.xxxx First two number express controller No. Last four number express group code.
② Status code:xx express the status in the logic
- 01:Alarm
- 02:Supervision
- 03:Active
- 04:Confirmation
- 05:Output with confirmation
- 06:Output without confirmation
- 07:Trouble
- 08:Disable
- 09:Test
- 10:Active (only suitable for control group to active the output in this group)
- 11:Stop (only suitable for control group to stop the output in this group)
2. Format specification:

● “+”: “or” relation;


Example: 01.0001+01.0002+01.0003=01.0004; indicates that alarm of any group of 01.0001, 01.0002,
01.0003 can activate group 01.0004.
● “*”: “and” relation;
Example: 01.0001*01.0002*01.0003=01.0004; indicates that 01.0001, 01.0002, 01.0003 simultaneously
alarm can activate group 01.0004.
● “!”: “Not” relation;
Example: 01.0001*!01.0002=01.0004;indicates that 01.0001alarm, and 01.0002 no alarm,active 01.0004
group。
● “()”: Priority;
Example: (01.0001+01.0002)*01.0003=01.0004; indicates that any group of 01.0001, 01.0002 and 01.0003
simultaneously alarm can activate group 01.0004.
● “+~+”, “*~*” : Abbreviations, but can not be used in “[ ]N”.
Example: 01.0001+~+01.0015=01.0016; indicates that in No. 01 controller, any group of No. 1 to No. 15
alarm can activate No. 16 group.
01.0001*~*01.0006=01.0007; indicates that in No. 01 controller, No. 1 to No. 6 groups simultaneously alarm
can acvitate No. 7 group.
●“[ ]N”: Total N groups simultaneously alarm; 1≤N≤8 (and N ≤ total groups);
Example: [01.0001, 01.0002, 01.0003]2=01.0004; indicates that any 2 groups of 3 groups alarm can activate
group 01.0004.
[01.0001~01.0003, 01.0005]2=01.0004; indicates that any 2 groups of 4 groups (1 to 3 and 5) alarm can
activate group 01.0004.
58
Smart Infrastructure A6V10239594_c_en
2019-05-26
● “; ”: End of logic expression;
● “@N”: Union alarm in a group, 2≤N≤ total device amount;
Example: 01.0001@2=01.0004; indicates that any 2 devices in group 01.0001 alarm can activate group 01.0004.
Remark : when adding /deleting device in a group, the logic expression need to be verified.
●When a logic expression need to activate more groups (output) simultaneously, use “,” to separate;
Example: (01.0001+01.0002)*01.0003=01.0004, 01.0005; indicates that any group of 01.0001, 01.0002 and
01.0003 simultaneously alarm can activate group 01.0004 and 01.0005.
3. Interlocking across controllers

Just directly input addresses of groups in logic expression;


Example: 01.0001+02.0001=01.0002, 02.0002;

59
Smart Infrastructure A6V10239594_c_en
2019-05-26
APPENDIX 4 SHORTCUT KEY LIST
Shortcut key Function
CTRL+A Insert node
CTRL+D Delete node
CTRL+F Find point
CTRL+N New engineering
CTRL+O Open engineering
CTRL+S Save engineering
CTRL+U Upload configuration files
CTRL+W Download configuration files

60
Smart Infrastructure A6V10239594_c_en
2019-05-26
Beijing Siemens Cerberus Electronics Limited © 2013 Copyright by