Technical Specification For 220kV SF6 Gas


Insulated Metal Enclosed Switchgear (GIS)
Home / Download Center / Electrical Engineering Books and Technical Guides / Power
substation guides / Technical Specification For 220kV SF6 Gas Insulated Metal Enclosed
Switchgear (GIS)

SF6 GIS
The SF6 gas insulated metal enclosed switchgear shall be totally safe against inadvertent
touch of any of its live constituent parts. It should be designed for indoor application with
meteorological conditions at site (winter 3°C to 14° C and summer 31° C to 46° C,
seismic zone: IV) .

https://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/220kv-gis-technical-specification 1/5
9/22/2019 General Technical Specification For 220kV SF6 GIS

General Technical Specification For 220kV SF6 Gas Insulated Metal Enclosed
Switchgear (on photo: ABB Gas-insulated switchgear for the Ras laffan power
plant, Qatar)

All parts of the switchgear should be three phase enclosed for 220kV GIS.

The arrangement of gas sections or compartments shall be such as to facilitate future


expansion of incomer bay with any make on either end without any drilling, cutting or
welding on the existing equipment. To add equipment, it shall not be necessary to move
or dislocate the existing switchgear bays.

The design should be such that all parts subjected to wear and tear are easily
accessible for maintenance purposes. The equipment offered shall be protected
against all types of voltage surges and any equipment necessary to satisfy this
requirement shall be deemed to be included.

The required overall parameters of GIS are as follows:

https://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/220kv-gis-technical-specification 2/5
9/22/2019 General Technical Specification For 220kV SF6 GIS

No. Technical Particulars 220kV System


1. Rated Voltage 245 kV (rms)
2. Rated frequency 50 HZ
Effectively
3. Grounding
earthed
4. Rated Power frequency withstand Voltage (1 min) line to earth 460 kV (rms)
5. Impulse withstands BIL 1.2/50/mic. Sec) Line to earth ±1050 kVp
6. Switching impulse voltage (250/2500 mic-sec) –
7. Rated short time withstand current (1 sec) 40 kA (rms)
8. Rated peak withstand current 100 kA (peak)
Guaranteed maximum gas losses or complete installation as well As per IEC-
9.
as for all individual sections in %. 62271-203
Zone-IV, as
per
10. Seismic level
IS-1893,Year-
2002

The metal-enclosed gas insulated switchgear, including the operating devices,


accessories and auxiliary equipment forming integral part thereof, shall be designed,
manufactured, assembled and tested in accordance with the IEC- 62271-203/IEC-62271-
200 publications including their parts and supplements as amended or revised to date.

Reference Standards
The metal-enclosed gas-insulated switchgear, including the operating devices,
accessories and auxiliary equipment forming integral part thereof, shall be designed,
manufactured, assembled and tested in accordance with the following International
Electro-technical Commission (IEC) standards including their parts and supplements
as amended or revised till date:

IEC 62271-203 – Gas Insulated metal-enclosed switchgear for rated voltages above
52KV.
IEC 60376 – New sulphur hexafluoride
IEC 62271- 100 – High voltage alternating current Circuit breakers

https://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/220kv-gis-technical-specification 3/5
9/22/2019 General Technical Specification For 220kV SF6 GIS

IEC 60694 – Common clauses for high voltage Switchgear and control-gear
standards
IEC 62271-102 – Alternating current disconnectors (isolators) and earthing switches.
IEC 61128 – Alternating current disconnectors. Bus-transfer current switching by
disconnectors.
IEC 61129 – Alternating current earthing switches. Induced current switching
IEC 66044-1 – Current transformers
IEC 66044-2 – Voltage transformers
IEC 60137 – Bushings for alternating voltages above 1000 V
IEC 60859 – Cable connections for gas-insulated switchgear
IEC 60480 – Guide to checking of sulphur hexafluoride taken from electrical
equipment
IEC 60099-1/4 – Non-linear resistor type arresters for AC systems
IEC 60439 – Factory-built assemblies of low-voltage switchgear and control gear.
IEC 60427 – Report on synthetic testing of high-voltage alternating current circuit
breaker.
IEEE 80 (2000) – IEEE Guide for Safety in AC Substation grounding.
CIGRE-44 – Earthing of GIS application guide. (Electra no.151, Dec’93)

The components and devices which are not covered by the above standards shall
conform to, and comply with, the latest applicable standards, rules, codes and
regulations of the internationally recognized standardizing bodies and professional
societies as may be approved by the Purchaser.

The manufacturer shall list all applicable standards; codes etc. and provide copies
thereof for necessary approval.

In case the requirements laid down herein differ from those given in above standard in
any aspect the switchgear shall comply with the requirements indicated herein in regard
thereto.

General Tender Technical Specification For SF6 Gas Insulated Metal


Title:
Enclosed Switchgear (GIS)
Format: PDF
Size: 672 KB
Pages: 40
Download: Right here | Get Download Updates | Get Premium Membership

https://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/220kv-gis-technical-specification 4/5
9/22/2019 General Technical Specification For 220kV SF6 GIS

Technical Specification For 220kV SF6 Gas Insulated


Metal Enclosed Switchgear (GIS)

https://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/220kv-gis-technical-specification 5/5

You might also like