3 RPIIDesignGuideandShielding PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 112

RPII 09/01

Radiological Protection Institute of Ireland The Design of Diagnostic Medical Facilities where Ionising Radiation is used
The Design of Diagnostic Medical Facilities
where Ionising Radiation is used

A Code of Practice issued by the


Radiological Protection Institute of Ireland

Contact Details June 2009


Radiological Protection Institute of Ireland
3 Clonskeagh Square
Dublin 14

Telephone: +353 1 269 7766


Fax: +353 1 269 7437
Web: www.rpii.ie
The Design of Diagnostic Medical Facilities
where Ionising Radiation is used

A Code of Practice issued by the


Radiological Protection Institute of Ireland

June 2009
Foreword

The original Code of Practice on The Design of Diagnostic Medical Facilities Using Ionising Radiation was first
published by the Nuclear Energy Board in 1988. In the intervening years the ‘Blue Book’ as it became known
has served the medical community well as the sector has expanded and modernised and the late Dr Noel
Nowlan, then Chief Executive of the Nuclear Energy Board, deserves much credit for initiating this pioneering
contribution to radiation safety in Ireland. There have been significant developments since its publication in
terms of the underlying radiation protection legislation, regulatory practice as well as developments in new
technologies that have given rise to the need for a revision of the Code. This revised Code is based on a
comprehensive draft document produced by the Haughton Institute under contract to the RPII and was
finalised following extensive consultations with the relevant stakeholders.

The revised Code includes a brief review of the current legislative framework and its specific impact on the
management of building projects (Chapters 1 and 2), a presentation of the main types of radiological
(Chapter 3) and nuclear medicine (Chapter 4) facilities, a treatment of the technical aspects of shielding
calculations (Chapter 5) and a discussion of the practical aspects of implementing shielding solutions in a
building context (Chapter 6).

The primary purpose of the Code is to assist in the design of diagnostic facilities to the highest radiation
protection standards in order to ensure the safety of workers and members of the public and the delivery of
a safe service to patients. Diagnostic radiology is a dynamic environment and the Code is intended to be used
in consultation with the current literature, an experienced Radiation Protection Adviser and a multidisciplinary
project team.
Contents

Foreword

1. Legal and administrative framework 6


1.1 Background 6
1.2 The Radiological Protection Act, 1991 (Ionising Radiation) Order, 2000 (S.I. No. 125 of 2000) 6
1.3 European Communities (Medical Ionising Radiation Protection) Regulations, 2002 & 2007
(S.I. No. 478 of 2002 and S.I. No. 303 of 2007) 7
1.4 RPII licensing system and requirements 7

2. Radiation protection, project management and building projects 9


2.1 Radiation Safety Committee 9
2.2 Radiation Protection Adviser (RPA) 9
2.3 Project teams, new building design cycle, refitting buildings 10
2.4 Dose limits and dose constraints 12
2.5 Risk assessment 13

3. Design and layout of radiology facilities 15


3.1 Radiology room types 15
3.1.1 Radiographic equipment 15
3.1.2 Fluoroscopy 15
3.1.3 Computed Tomography (CT) 16
3.1.4 Shared function rooms 16
3.2 Some general comments on shielding 16
3.3 Radiography rooms 20
3.3.1 General X‑ray room 20
3.3.2 Dedicated chest room 21
3.3.3 Mammography room 22
3.3.4 Dual energy X‑ray absorptiometry (DXA) room 23
3.3.5 Facilities for dental radiography (intra-oral and panoramic) 24
3.4. Fluoroscopy rooms 27
3.4.1 Fluoroscopy room (general) 27
3.4.2 Fluoroscopy (special & interventional radiology and cardiology) 28
3.5 Computed Tomography (CT) room 29
3.6 Shared function rooms 30
3.6.1 Accident and Emergency departments (A&E) 30
3.6.2 ERCP, cardiac pacing rooms and lithotripsy 31
3.6.3 Operating theatres and recovery areas 32
3.6.4 ICU/CCU, high dependency units/neonatal units and general wards 32
3.7 Equipment in trailers 33

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 


4. Nuclear medicine 35
4.1 Introduction 35
4.1.1 Location and access 35
4.1.2 Overview of facilities and layout 36
4.2 Nuclear medicine facilities 37
4.2.1 Scanning room 37
4.2.2 Patient injection room 38
4.2.3 Waiting area (pre & post administration) 39
4.2.4 WC facilities 39
4.2.5 Reception/office/reporting and consultation facilities 39
4.3 Radiopharmacy facilities 39
4.3.1 General requirements for the radiopharmacy suite 39
4.3.2 The lobby/changing area 41
4.3.3 Hot lab/radiopharmacy 41
4.3.4 Radionuclide storage area 42
4.4 Special considerations/areas 42
4.4.1 Radionuclides in the operating theatre 43
4.4.2 Therapeutic use of unsealed radionuclides 43
4.4.3 Uptake assessment area 43
4.4.4 In-vitro measurement area 44
4.4.5 Other areas 44
4.5 Hospital laboratories using radionuclides 44
4.6 Special considerations for PET 45
4.6.1 General and facilities required 45
4.6.2 Location, layout and access 45
4.6.3 Patient facilities 46
4.6.4 Dispensing and other facilities 48
4.7 Waste management facilities 48
4.8 Ventilation requirements 49

5. Shielding calculations 50
5.1 General and design goals 50
5.2 Variables affecting shielding design calculations 51
5.2.1 Distance 51
5.2.2 Workload in radiology 52
5.2.3 Occupancy factor 54
5.2.4 Primary radiation 56
5.2.5 Secondary radiation – scatter & leakage 58
5.2.6 Combination of primary and secondary radiation 59
5.2.7 Maximum transmission and specification of shielding material 59

 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


5.2.8 Shielding calculations in nuclear medicine 61
5.2.9 Shielding calculations in PET/CT 62
5.3 Examples of shielding calculations 65
5.3.1 Radiology shielding calculation examples 66
5.3.2 Nuclear medicine shielding calculation examples 71

6. Some practical considerations 74


6.1 Building materials, methods and verification 74
6.1.1 Lead sheet and lead fabricated products 74
6.1.2 Concrete and concrete blocks 75
6.1.3 Barium plaster 75
6.1.4 Brick 76
6.1.5 Gypsum wallboard 76
6.1.6 Lead glass 76
6.1.7 Lead acrylic 76
6.2 Materials for fitting and furnishing nuclear medicine departments 76
6.3 Shielding in radiology department 77
6.3.1 Walls 77
6.3.2 Floors and ceilings 78
6.3.3 Doors 80
6.3.4 Windows 81
6.3.5 Staff areas in X‑ray room 82
6.4 Shielding in nuclear medicine 84
6.4.1 General nuclear medicine 84
6.4.2 PET 84
6.5 Services, joints, openings and perforations 85
6.6 Verification 85

References 87

Appendices
Appendix A: Dose limits 90
Appendix B: Risk assessment for design and construction of a new medical facility
where ionising radiation is used 91
Appendix C: Radiation transmission data for various energies and materials 92
Appendix D: Nuclear medicine radionuclide data 97
Appendix E: Schematic diagrams of radiation transmission paths 100
Appendix F: Examples of radiation warning signs and light 103

Acknowledgements 105

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 


1. Legal and administrative framework

1.1 Background
The system of radiation protection used in Ireland is based on the recommendations of the International
Commission for Radiological Protection (ICRP). The conceptual framework adopted by ICRP in its publication
No.103 (ICRP, 2007) builds on the system of dose limitation central to earlier ICRP documents such as ICRP
60 (1991) and ICRP 26 (1977). This system is embodied in various European Directives most notably the Basic
Safety Standards (BSS) (EC, 1996a) and the Medical Exposure Directive (MED) (EC, 1997).

The BSS lays down the requirements for protection of workers and the general public against the dangers of
ionising radiation. It encapsulates the principles of Justification, Optimisation and Dose Limitation articulated
by the ICRP and develops them into a regulatory system that can control the practices involving ionising
radiation.

The MED addresses the protection of individuals against the dangers of ionising radiation in relation to
medical exposure. This Directive is the main legal instrument dealing with the protection of patients
undergoing diagnostic and therapeutic procedures using radiation. It aims to eliminate unnecessary medical
exposures and to this end the principles of Justification and Optimisation are central.

Legislation governing the use of ionising radiation in Ireland gives effect to these European Directives in two
Statutory Instruments:

n The Radiological Protection Act, 1991 (Ionising Radiation) Order, 2000 (S.I. No. 125 of 2000) (Stationery
Office, 2000).

n European Communities (Medical Ionising Radiation Protection) Regulations, 2002 (S.I. No. 478 of 2002) as
amended by the European Communities (Medical Ionising Radiation Protection) (Amendment) Regulations
2007, (S.I. No. 303 of 2007) (Stationery Office, 2002 and 2007).

1.2 The Radiological Protection Act, 1991 (Ionising Radiation) Order, 2000
(S.I. No. 125 of 2000)
S.I. No. 125 of 2000 implements the BSS and some other European Directives on the protection of workers
and the general public against the dangers of ionising radiation in all workplaces. It is issued under the Act
(Stationery Office, 1991) that provides for the establishment of the Radiological Protection Institute of Ireland
(RPII). It encapsulates the principles of Justification, Optimisation and Dose Limitation and develops them into
a regulatory system for the control of the practices involving ionising radiation. For all practices, the requirements
for authorisation (licensing), justification, optimisation and dose limitation (excluding exposures to patients
arising from their treatment) are specified. For the purpose of this publication S.I. No. 125 of 2000 deals with
a number of issues. First it provides the legislative basis for the use of dose constraints and the application of
dose limits for exposed workers, apprentices, students and members of the public (Appendix A). In addition,
it provides the legislative basis for the requirement to carry out radiation risk assessments for new practices
and deals with the classification of work areas and systems of work (Table 1.1).

 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Table 1.1: Definitions of controlled and supervised areas

Controlled Area n An area in which a worker is liable to receive an effective dose of greater than 6
mSv in a period of 12 months or an equivalent dose greater than 3/10 of any
relevant dose limit in Appendix A, or

n An area where any person who enters must follow a specified system of work.

Supervised Area n An area in which a worker is liable to receive an effective dose of greater than 1
mSv in a period of 12 months or an equivalent dose greater than 1/10 of any
relevant dose limit in Appendix A, or

n An area where it is necessary to keep the conditions of the area under review to
determine whether it should be designated as a controlled area.

Finally, it establishes the requirement to appoint and consult with a Radiation Protection Adviser (RPA). Details
of the licensing system operated by the RPII, and requirements to be fulfilled in regard to new radiographic or
nuclear facilities or equipment, are described in Section 1.4.

1.3 European Communities (Medical Ionising Radiation Protection)


Regulations, 2002 & 2007 (S.I. No. 478 of 2002 and S.I. No. 303 of 2007)
S.I. No. 478 of 2002, as amended by S.I. No. 303 of 2007, is based on the MED. Its scope includes the
exposure of patients as part of their medical diagnosis and treatment, occupational health surveillance, health
screening programmes such as mammography, healthy individuals voluntarily participating in medical research,
exposure of individuals as part of medico-legal procedures and finally the exposure of individuals knowingly
and willingly helping in the support and comfort of individuals undergoing medical exposures. The latter
group are now referred to as comforters and carers, and dose constraints for this group have been adopted
by the Medical and Dental Councils (Medical Council, 2005).

S.I. No. 478 of 2002, as amended by S.I. No. 303 of 2007, reiterates and emphasises the principles of
Justification and Optimisation, in a context where dose limits are not applicable to medical procedures.

1.4 RPII licensing system and requirements


The Radiological Protection Institute of Ireland (RPII) is the competent authority to ensure that members of
the public and workers are adequately protected from the harmful effects of exposure to ionising radiation,
within the State. It fulfils this responsibility through a system of regulatory control, inspections and advice to
licensees, the public and Government.

S.I. No. 125 of 2000 requires all practices involving ionising radiation to be licensed by the RPII – typical
practices carried out in the medical sector include custody, transportation, use and disposal. Within this
sector these practices would be associated with irradiating apparatus such as X‑ray equipment, and
radioactive substances and sources. The undertaking (i.e. any natural or legal person who, as a self employed
person or employer as the case may be, carries on or intends to carry on any practice or work activity to
which S.I. No. 125 of 2000 applies) is required to apply to the RPII for a licence not later than 1 month before
the commencement of the proposed practice. However it is recommended that a licence application should

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 


be made as soon as possible. It should be noted that the processing of an application for a large or complex
facility, such as a nuclear medicine department, may take several months from the time of first receipt of the
draft plans to the issue of the licence. A licence must be obtained prior to any irradiating apparatus or
radioactive substance being acquired by the undertaking.

The following steps should be used as a guide for applicants when making an application for a licence for a
new facility:

n For practices involving the use of irradiating apparatus or radioactive sources/materials, the undertaking
should advise the RPII of the proposal to build a new facility, or to modify an existing facility, as early in
the project as possible.

n The undertaking must appoint an approved RPA to the project at the outset to advise on all aspects of
radiation protection; a register of approved RPAs is maintained by the RPII. All communications between
the project design/building team and the RPII on issues relating to radiation protection should be
channelled through the appointed RPA. The role of the RPA is discussed further in Section 2.2.

n In the case of large building projects a copy of the draft plans, as agreed between the RPA and undertaking,
should be forwarded to the RPII for an initial review. The RPII may query or suggest modifications to the
plans at this stage.

n As the installation progresses and nears completion the RPA should assess the shielding in the installation
and identify any discrepancies from the agreed plans which may affect radiation protection.

n Prior to acquiring any source of ionising radiation e.g. irradiating apparatus, sealed or unsealed radioactive
sources, a licence application form or licence amendment form (in the case of an existing licensee) for
the proposed practices shall be obtained from the RPII.

n The undertaking shall make an application for a new licence, or an amendment of an existing licence, by
returning the completed form to the RPII. The application must be supported by both a risk assessment
of potential exposures to workers and members of the public arising from the practice or from foreseeable
accidents and a copy of the Radiation Safety Procedures to be used in the practice.

n Provided that the RPII is satisfied with the application, a licence will be issued authorising the licensee to
take custody of the licensed items. The use of the licensed items will be restricted solely to those tests
necessary to commission the items.

n Upon receipt by the RPII of a satisfactory RPA commissioning report for a new licensed item, the restriction
on the licence relating to that item will be removed and an amended licence issued.

 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


2. Radiation protection, project
management and building projects
2.1 Radiation Safety Committee
The undertaking/licensee has ultimate responsibility for ensuring that a good radiation protection culture
exists in regard to the licensed practices, and that all licence requirements are met. Within the medical and
dental sectors, hospitals and public sector dental practices are required to have, or be party to, a Radiation
Safety Committee (RSC).

In practice the RSC is the body to which policy making for radiation protection is delegated by the undertaking.
It reports to the undertaking, frequently but not always, through the Health and Safety Framework. It is
responsible for recommending radiological protection measures to ensure compliance with regulatory and
licensing conditions.

The membership of such a committee will generally include radiologists, radiographers, Radiation Safety
Officers, the appointed Radiation Protection Adviser (RPA), representatives of senior management, a medical
officer and other users, for example dentists in the case of dental committees. The committees are required
to meet at least once every 6 months. In practice they approve the standards against which new developments
are judged, approve radiation safety procedures and prepare the advice on radiation safety issues. They
operate within the licence arrangements that require the RPA to be closely involved in new developments
and in dealing with unsatisfactory situations. Private sector dentists and medical centres with relatively small
radiation based activities are not required to have a RSC. They rely on the advice and support of the appointed
RPA to attend to their requirements.

2.2 Radiation Protection Adviser


The policies developed by the RSC and local procedures for their implementation are put into effect using the
line management arrangements that prevail in the hospital or practice concerned. Thus, in practice, the Head
of Department will have responsibility to ensure that arrangements are put into effect in his/her Department.
In this he/she is generally advised and assisted by the RPA.

S.I. No. 125 of 2000 requires each undertaking to appoint in writing one or more persons as RPA from the
register of approved RPAs maintained by the RPII. The RPII will approve an RPA once it has determined that
he/she has the knowledge and training needed to carry out physical, technical or radiochemical tests and to
give advice in order to ensure effective protection of individuals and the correct operation of protective
equipment. It is the responsibility of the undertaking to ensure that the appointed RPA has the appropriate
expertise and experience to provide the necessary advice.

S.I. No. 125 of 2000 explicitly requires the undertaking to consult with the appointed RPA on specific matters
including:

n Prior critical examination of plans of installations from the point of view of radiation protection.

n Acceptance into service of new or modified irradiating apparatus/radioactive sources.

n Implementation of the requirements of controlled and supervised areas.

n Implementation of new procedures involving radiation.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 


It should be noted that it is the undertaking, and not the RPA, who has ultimate responsibility for the
implementation of statutory and licensing requirements.

The requirements of the S.I. No. 125 of 2000 are strongly reflected and given more explicit effect in the
conditions attached to the medical and dental licences issued by the RPII. These conditions state that the
following actions may only be carried out after consultation with or approval by the RPA:

n Significant modifications to licensed items.

n Changes to the use of any buildings or adjoining locations where radiation is used.

n Modifications to the shielding offered by any building where radiation is used.

n The construction of new buildings or the modifications to existing buildings designed for the custody and
use of sources of ionising radiation.

n The introduction of new procedures involving licensable items.

Finally, the conditions of licence require that the licensee ensures that the RPA has commissioned equipment
for medical radiological procedures, prior to its being used on patients. All of these requirements have a
significant impact on the management of development projects in radiology and nuclear medicine.

Day to day aspects of agreed radiation protection policies and procedures may be delegated by heads of
departments to locally appointed departmental radiation safety officers.

Public sector based dental practices are required to appoint an RPA and nominate a Radiation Protection
Officer (RPO) in each Local Health Office (LHO). In addition, a principal dental surgeon in each administrative
area must be appointed to act as the regional RPO for that area.

2.3 Project teams, new building design cycle, refitting buildings


A multidisciplinary project team is required to manage the design and construction of new medical
developments, which include radiology and nuclear medicine facilities. The team should include representatives
from a broad range of hospital disciplines e.g. radiography, radiology, medical physics, clinical engineering,
hospital management, hospital Technical Services Departments, the RPA, as well as nursing and medical staff
from each of the clinical specialties envisaged for the new unit. The project team must establish a vision for
the services to be delivered in the new development, and then manage the process translating this vision into
reality. A number of key steps can be identified which ensure best practice in the management of radiation
protection issues during the building design cycle:

1. The project team prepares a brief, and operational policies. On this basis, following due process, architects
are selected and instructed to develop draft plans for the new building. These should include equipment
layout plans for each room.

2. The Project Manager passes these plans and operational policies to the RPA. The RPA should also be
briefed on the projected workloads.

10 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


3. The RPA issues advice to the Project Manager or Project Team, as appropriate, for the shielding
requirements at the boundaries of the areas in which radiological or nuclear medicine activities are
envisaged. Advice may also be offered in connection with design issues and operational policies, either
of which may have building implications. In practice, this process may involve several rounds of meetings
and exchanges.

4. Following review and appropriate consultation, the Project Team/Manager issues revised instructions to
the architects taking due note of the RPA’s advice.

5. Following one or more iterations of the process in (1) to (4), the final plans for the facility should be
signed off by the relevant parties including the RPA.

6. At an appropriate point in the project, the RPA in association with the Project Manager/Team should
provide a copy of the plans, the operational policy, and an initial draft of the risk assessment to the RPII for
information and informal comment. The outcome of this process should be noted by the RPA in formulating
the advice for the final plans.

7. The process of identifying, specifying and seeking tenders for equipment should, where practical, proceed
in a timely way and in parallel with the planning of the building. Representatives of the end users and
the RPA must be involved in this also, particularly with respect to the layout of equipment.

8. When the building is under construction but before the interior finishing and decoration has been
undertaken, the RPA should make one or more site visits to verify that the shielding and overall design
are as specified and suitable for the final equipment installation. This will enable the signing off of the
facility during the licensing process. Photographs and/or written records should be kept.

9. During the site visits the RPA will identify relevant snags. The Project Manager will liaise with the builders,
fitters and architects to ensure that each item on the snag-list is addressed.

10. A radiation protection survey, which may include verification measurements (Section 6.6), of the finished
facility is made by the RPA as part of the commissioning process, and in preparation for the installation,
acceptance testing and commissioning of the new equipment. The results of this survey will be used in
preparing both the risk assessment and the licence application.

11. During the lifetime of the equipment, the shielding should be kept under regular review, particularly
following changes in room usage, building structure, adjacent buildings, equipment and/or patient
throughput.

An assessment of the facility by the RPA at the various points noted above will identify gross breaches of the
shielding recommendations (e.g. unshielded doors). As it is not possible in practice to measure the shielding
at every point of every boundary, projects rely heavily on the professional integrity of the architects, builders,
fitters and engineers involved to ensure that the shielding is as specified. For this reason it is important to
ensure that all parties to the design, construction and fitting out of the facility are reputable and, where
appropriate, hold professional accreditation or certification. It is also important to retain written confirmation
of the shielding installed from the various parties involved.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 11


Records should be kept as they will be required in years to come. Records to be kept include:

n Final approved shielding drawings and the assumptions on which the shielding recommendations were
based.

n Construction or ‘as built’ documents certifying the shielding installed.

n Survey reports.

n Information regarding alterations.

n Subsequent survey reports following changes.

A similar process is required to ensure best practice in radiation protection when an existing building is
refitted to allow for new clinical facilities, which include radiological or nuclear medicine services. This applies
even where the building is presently used for such purposes. Some of the steps may be combined in practice,
and may not be necessary if little change to the existing building structure proves necessary after a risk
assessment; however the RPA must be involved. In practice it will be essential to have detailed information
on the construction and materials in the existing walls, floors, ceilings, etc., in order to determine if additional
shielding is required.

2.4 Dose limits and dose constraints


To protect workers and members of the public from the hazards of exposure to ionising radiation dose limits
for 12 month periods are set down in S.I. No. 125 of 2000. These dose limits are presented in Appendix A
and are enforced by regulatory control. In brief they require that occupationally exposed workers receive less
than 20 mSv per year and that members of the public receive less than 1 mSv per year. These limits can be
taken as the lower boundary for unacceptable risk.

When designing new facilities the design should be to a standard that will keep the doses to workers and
members of the public as low as reasonably achievable (the ALARA principle) taking social and economic
factors into consideration. This means that the facility should be designed to ensure that the radiation
exposure of workers and members of the public are much lower than those of the legal dose limits. To ensure
that optimisation of protection exists, dose constraints are applied to the design of any new facilities.

A dose constraint is defined by S.I. No. 125 of 2000 and S.I. No. 478 of 2002 as “a restriction on the
prospective doses to individuals, which may result from a defined source, for use at the planning stage in
radiation protection whenever optimisation is involved”. They are generally regarded as advisory. Thus the
dose constraint, while not having the legal force of a dose limit, is the value that must be used in planning
the design of a new facility.

There are other situations in which the term dose constraint is used, for example, in dealing with the exposure
of comforters and carers, and these situations should not be confused with the above.

The dose constraints to be used in the design of all new medical facilities are given in Table 2.1. It is also
prudent to use these dose constraints in situations where existing facilities are being upgraded or modified or
when new equipment is being installed in existing facilities.

12 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Table 2.1: Annual dose constraints for exposed workers and all others

Category of personnel Dose constraint (mSv/year)

1. Exposed worker 1.0

2. All others 0.3

The dose constraints referred to in the table should be regarded as a Time Averaged Dose Rate (TADR)
modified to take account of occupancy. This is the Instantaneous Dose Rate (IDR) multiplied by the expected
daily beam on time averaged over an eight-hour day (RPII, 2001). Given the definition of TADR, an upper
bound on the instantaneous dose rate (IDR) is warranted. As it is not practical to specify one figure for each
facility, each situation must be assessed on a case-by-case basis in order to demonstrate compliance with the
above dose constraint. In general, for areas that are occupied by workers or to which they have access, the
IDR shall be limited to a few tens of microSieverts per hour. If the IDR is above this general value it may not
be appropriate to apply to the TADR. In these cases access to the area may need to be prohibited or additional
shielding may be required. Notwithstanding the above provision, it is recognised that the IDR may not be
meaningfully applied to all situations involving diagnostic radiography.

In situations where there is a potential for exposure by more than one source, it is likely that one source will
be dominant in regard to the exposures to the representative person, making it possible to treat the sources
independently when considering protective actions. Thus in situations where there is a potential of exposure
from more than one source, the design dose constraint should be applied to the predominant source in
conjunction with a risk assessment being performed of all the sources combined. A flexible approach to such
situations should be taken.

When there are two equal sources, rather than a predominant source, e.g. a shared operator’s console or
work area located between two X‑ray rooms, it may be more prudent to split the dose constraint to take
account of both sources. If access to such a shared operator’s console is restricted to designated workers, the
dose constraint of 1 mSv per year, or 0.5 mSv per room per year, can be used. If the area is one in which
non-designated staff will regularly be in attendance, which is often the case with CT and interventional
suites, the dose constraint for a member of the public of 0.3 mSv per year must be used. Dividing this dose
constraint between the two rooms will result in dose constraints of 0.15 mSv per room per year. Achieving
the level of shielding required to meet this dose constraint is a notable design challenge.

2.5 Risk assessment


S.I. No. 125 of 2000 requires that a risk assessment be provided when applying for a licence or an amendment
to an existing licence. This risk assessment is aimed at identifying protective measures needed to restrict
exposures to ionising radiation arising from routine operation of the practice and from reasonably foreseeable
accidents resulting from the practice. The RPII has issued a guidance note (RPII, 2004) for carrying out a risk
assessment which is available from its website. The assessment process is divided into five steps:

1. Identify all possible radiation hazards, both from routine operation/maintenance and from potential
accidents involving radiation sources.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 13


2. Identify the persons (staff and general public) at risk from these hazards.

3. Evaluate the protective measures in place, and identify areas where improvements may be made.

4. Document the findings in steps (1) – (3).

5. Review the assessment and amend if necessary.

The above risk assessment is based on the final build which will be designed using the required dose
constraints (Section 2.4). Some hospitals have developed their own template for use when performing a
radiation risk assessment for X‑ray and nuclear medicine departments/facilities.

An example of some issues to be considered during a risk assessment for the design and construction of new
medical facilities is presented in Appendix B.

14 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


3. Design and layout of radiology facilities

3.1 Radiology room types


The location, structural design and equipment layout of X‑ray rooms must be carefully considered from a
radiation protection perspective. This is easier when X‑ray facilities are not designed as stand-alone rooms
and are planned as part of an integrated radiology/imaging department with its supporting areas and
services. Planning the room layouts should start as early as possible in the design process and be based on
inputs from a team including architects, engineers, hospital management, radiologists, radiographers, the
RPA, other consultant medical staff such as cardiologists or vascular surgeons where relevant, and once
identified, the equipment supplier(s).

The practical requirements for radiation protection depend on the clinical functions the room is designed for
as well as the workload and adjacent occupancy. For simplicity, at this point, rooms will be divided into four
broad categories:
1) Radiography (e.g. general, chest, dental, mammography, etc.).
2) Fluoroscopy (e.g. general or interventional applications).
3) Computed Tomography (CT).
4) Shared function rooms (e.g. operating theatres or emergency departments where mobile or fixed X‑ray
equipment may be used).

X‑ray rooms should be of a size that allows unimpeded access and ease of movement around the equipment,
the patient table and the operator’s console. The size of the room will vary greatly depending on the modality
and the cost of space. There are no absolute norms, but it may be helpful to bear in mind some examples
from the UK National Health Service which recommends that general rooms, complex interventional suites
and mammography rooms be 33, 50 and 15 m2 respectively (NHS, 2001).

General X‑ray rooms with ceiling-mounted X‑ray tubes must have a minimum height of 3.1 m between the
floor level and the underside of the ceiling support grid (normally concealed by a suspended ceiling). A
conventional ceiling height of 2.4 m should be adequate for dental and dual energy X-ray absorptiometry
(DXA) rooms (NHS, 2001, NHS, 2002).

3.1.1 Radiographic equipment


Radiography equipment provides a single two-dimensional ‘snap-shot’ image, which is, essentially, a partially
penetrated projected shadow. Staff are not normally required to be in the vicinity of the patient during the
procedure. These rooms generally include a fixed screen to protect the operator console area. It is necessary
to be able to see and communicate with the patient from this area. In addition, the rooms should be sufficiently
large to reduce radiation intensity at the operator’s screen and boundaries (Section 3.2 and 3.3).

3.1.2 Fluoroscopy
Fluoroscopy allows for continuous real-time imaging and tends to be used in complex investigations and
treatments requiring some staff to be in close contact with the patient during all or part of the procedure.
Others who do not need to be in the vicinity of the patient e.g. the radiographer, take up position behind a
console as described above. The procedures may be long and can involve high doses in the vicinity of the
patient. Thus additional protective measures at the table are generally provided (Section 3.2 and 3.3).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 15


3.1.3 Computed Tomography (CT)
CT allows cross sectional imaging which was traditionally of the single ‘snap-shot’ form of the head or body.
Modern CT systems produce multiple slices, enable faster three-dimensional imaging, and allow for real-time
tracking of events as in fluoroscopy. These systems have greatly enhanced the clinical value of CT and also
allow for much more rapid patient scanning. For both reasons the workload in CT rooms has increased and
the radiation levels in the vicinity of a CT scanner are possibly higher than for any other imaging modality.
Staff are not generally expected to be in the vicinity of the patient during procedures, so the mechanisms of
radiation protection include the operator screen and the room size approaches already mentioned. However,
the functions accommodated in the operator area are greatly expanded and often include direction and
analysis of the examination by the radiologist as it happens, and observation of the results by the referring
clinical team. Thus the operator’s cubicle in effect acquires a consultation, reporting and analysis function
and occupies a considerable area. There is normally a panoramic window and a door from this area to the
CT room.

3.1.4 Shared function rooms


There are an increasing number of situations involving rooms with shared functions, one of which has a
radiological component. At the extreme upper level of this range are operating theatres for vascular
procedures which also have full permanent fixed radiological equipment installed. However, more commonly,
these applications involve low-dose fluoroscopy for short time periods – e.g. during or following orthopaedic
procedures. By comparison with conventional radiological practice, a large number of staff may be present
in the room at the time. Because of the relatively low doses, radiation protection requirements are generally
less demanding than in the other facilities described above. However the large number of staff, not all of
whom will be trained in radiation protection, presents special problems. In practice a combination of mobile
shields, staff withdrawing from the immediate area and limited structural shielding can usually provide a
good solution. However, the design of these areas is generally approached on a case by case basis. In
addition, the number and type of these areas is increasing, and now routinely includes the Intensive Care,
High Dependency, Theatre, and Emergency Medicine environments (Section 3.6).

3.2 Some general comments on shielding


From the point of view of providing shielding at the room boundaries, it is important to weigh up whether
it is more economical to maximise space or install more structural shielding. For example, it may be possible
to designate a relatively large space for an X‑ray room, and as a result of the increased distances to the
occupants of nearby areas the shielding requirements can be significantly reduced. The cost and practical
implications of distance versus shielding should be considered in optimising the design solution. This will be
considered further in Chapter 5 and may be particularly important with some newer techniques with very
demanding shielding requirements. From the point of view of providing for those who must work within the
controlled or supervised areas that coincide with the room boundaries, there are three approaches to
providing protection that impact on room design or equipment specification. These are:

n Fixed screen: This is a screen which attenuates radiation and behind which the operator console and any
other necessary operator control systems (e.g. emergency stop switch) are located. Where the design
allows, the screen should be positioned so that it protects the staff entry door and staff can enter and

16 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


leave the room without risk to themselves or persons in the corridor outside. Normally the screen is
composed of lead and lead glass. It extends to at least 2 m in height and is of sufficient length to provide
full body protection for the operator(s) from scattered radiation. The screen should allow the operator
a panoramic view of the room to include the patient table, the chest stand (if present) and all doors
(Photo 3.1). See Chapter 6 for more details.

Photo 3.1: Fixed operator’s screen

(Photograph courtesy of St. James’s Hospital, Dublin)

n Room size and equipment positioning: Where possible the imaging equipment should be placed in the room
so as to maximise the distance to the more critical boundaries. A room which has considerable space around
the imaging equipment reduces radiation risks by allowing staff to stand well back from the patient except
when they are specifically required to be near. In addition a large room generally increases the distance
between the operator screen and the patient table thereby reducing the radiation intensity in the operator
console area.

n Partial body shielding: This is used to protect staff who are required to be near the patient during X‑ray
exposures. The shielding may be broadly divided into two types: that used to protect the upper body and
that for the lower body. Upper body shielding is common in interventional rooms; the focus is on head
and neck protection, and particularly on eye shielding. This is normally made of lead glass or lead acrylic
and mounted on the ceiling at the end of a moveable arm. In the case of general fluoroscopy rooms and
some interventional rooms using undercouch tube systems, upper body shielding is provided in the form
of a lead skirt that hangs from the image detector down to the table. Lower body shielding is often
provided for undercouch fluoroscopy tubes; this is achieved by means of a lead skirt hanging from the
table (the norm for interventional systems), or lead panels below the screen (Photo 3.2).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 17


Photo 3.2: Interventional X‑ray room with partial body shielding devices

(Photograph courtesy of St. James’s Hospital, Dublin)

Examples of typical radiology room layouts are shown in Fig. 3.1 to 3.8. Many are based on the classic dual-
corridor design for radiology departments in which the equipment rooms are sandwiched between two
corridors, one being used for staff movements and the other for patients. In addition, many rooms will in
practice have toilet facilities and changing cubicles associated with them. If these are to be used while
another patient examination is in progress in the room, they must be shielded as though the common wall
or door between them and the X‑ray room is a room boundary.

Some general recommendations for the design of radiology rooms are given in Table 3.1. Further detail may
be found on the design of individual rooms in Section 3.3 and Chapter 6.

18 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Table 3.1: Some general recommendations for the design of a radiology room

General recommendations for the design of a radiology room

n The equipment should be positioned so that the primary radiation beam is not directed at the operator’s
console, windows or doors.

n Particular attention must be paid to the shielding of areas where the primary beam will be directed, for
example the wall behind the vertical cassette holder.

n The floor of the X‑ray room must be shielded for the primary radiation beam if there is occupancy in
the room below and the beam is not otherwise attenuated.

n The operator’s console area should be located so that: it is adjacent to the staff entrance door; the
operator has a clear panoramic view of the patient and the access doors to the room; and radiation is
scattered at least twice before entering the protective area.

n The protective screen should be at least 2 m in height and of sufficient width to allow at least two
people stand behind the screen during an exposure.

n Personal protective equipment (lead aprons, thyroid shields, gonad shields) should be available and
reinforced hangers should be used for the storage of lead aprons.

n Multilingual pregnancy signs should be displayed in the waiting room and patient cubicles, advising
female patients to declare their known or suspected pregnancy prior to undergoing a radiological
examination.

n Radiation warning lights should be positioned at all access doors to the room and preferably at eye
level. The light should illuminate during the preparation period (if applicable) and continue for the
duration of the exposure.

n Radiation warning lights may not be required if the operator can prevent inadvertent access to the
room during exposures (for example if there is only one appropriately positioned door).

n Appropriately worded radiation warning signs must be posted on access doors to the room.

n The room layout and shielding design must be reviewed by the RPA each time the equipment or
technology changes.

n An X‑ray room should not be used for more than one radiological procedure at a time, unless specifically
designed for this purpose.

n The X‑ray room should not be a throughway to another room.

n The design of ancillary facilities such as changing cubicles, toilets and preparation rooms should be
considered.

n A pragmatic approach to radiation shielding should be considered; it may be more prudent and possibly
more cost effective to specify a consistent level of shielding in all boundaries in the room rather than
specifying different levels of shielding in each boundary.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 19


3.3 Radiography rooms
3.3.1 General X‑ray room
Figure 3.1: General X‑ray room with chest stand

Chest stand
Staff entrance and beam blocker

Patient table

Operator’s X
console area
Radiation barrier
(protective viewing screen)
X-ray
tube

Patient entrance

A good layout for a radiographic room based on the two-corridor design is shown in Fig. 3.1. The room is
designed for general X‑ray radiography with the facility to use either the patient table or the chest stand/
vertical bucky. An area of 33 m2 has been suggested for general X‑ray systems (BIR, 2000).

The boundaries to all occupied areas (walls, doors, doorframes, floor, ceiling, windows, window frames and
the protective viewing screen) must be shielded appropriately. Generally this requirement will be met by 2
mm of lead, or its equivalent with other material (see Chapters 5 and 6). As noted in Section 6.1.1, in
practice it is preferable to specify the actual British Standard Code of lead sheet required, to avoid errors
arising from inappropriate rounding up or down later. In this case, Code 5 lead sheet (2.24 mm thickness)
would be appropriate. Workload, distances and occupancy in adjoining areas may serve to reduce this
requirement. However, a policy of shielding to the 2.24 mm (Code 5) level may reduce problems that may
arise with future change of use and occupancy in the areas adjacent to the room. Notwithstanding this it is
important to assess each room on an individual basis in consultation with an RPA. Also, as discussed in
Section 6.2, walls should be marked with the lead equivalent thickness for future reference.

The 2.24 mm (Code 5) shielding is adequate to deal with secondary or scattered radiation and assumes the
boundaries will not normally be exposed to the primary beam. Where this may happen additional shielding
is required, for example an additional lead beam blocker may be required behind a chest stand or vertical
Bucky. This additional shielding should extend over the range of possible tube movements when it is directed
towards the wall.

20 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


The room has been designed with a number of features in mind. There is good access through the patient doors,
to allow patients on trolleys to be brought into the room and ensure ease of access to the table. The staff
entrance is placed so that the door to the corridor is behind the protective barrier. This protects both staff
entering this area and the corridor if the door is inadvertently opened. The protective barrier is composed of a
lead-ply or equivalent lower section and a lead glass upper section which allows a panoramic view of the room.
A protective screen length of 2-2.5 m with a 0.6-1.0 m wing is normally adequate. However, how this fits with
the general room design must be considered. The chest stand, in this example, has been positioned to minimise
the amount of scattered radiation that can enter the operator’s console area.

Patient changing facilities must be provided and should be close to a general X‑ray room. Cubicles may be
designed as individual changing rooms, which open directly into the X‑ray room. This will allow for changing
arrangements consistent with good radiation protection practice, greater privacy, security and perhaps faster
patient throughput. The main alternative is to group the cubicles together close to the X‑ray room but not
adjoining it, and allow for a sub-waiting area from which the changed patients are escorted to the X‑ray room
(NHS, 2001). The advantage of this design is that there are less access points into the X‑ray room.

Cubicle doors leading into the X‑ray room must provide adequate radiation protection and the lock should
be controlled from the X‑ray room to prevent inadvertent access. These considerations on cubicles apply to
many of the other room types dealt with in this section.

General X‑ray rooms are occasionally designed with two tables, for example, IVP rooms. Protective
arrangements between the tables are necessary and the RPA must advise on this and on the specification of
the equipment to avoid inadvertent exposures. (Section 3.6.1).

3.3.2 Dedicated chest room


A layout for a dedicated chest room is shown in Fig. 3.2. Chest X‑rays are one of the most common
examinations and hence rooms for this purpose must facilitate a rapid throughput. The room has many
features in common with the general radiographic room shown in Fig. 3.1. However, it can be smaller in size
as there is no patient table. The provision of changing cubicles and arrangements that facilitate throughput
are particularly important. The chest stand has again been positioned to minimise the amount of scattered
radiation that can enter the operator’s console, and an additional lead primary beam attenuator may be
required behind the chest stand (Chapter 5).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 21


Figure 3.2: Dedicated chest room

Chest stand
Staff entrance and beam blocker

X-ray

X
Operator’s tube
console area

Radiation barrier
(protective viewing screen)

Patient entrance

3.3.3 Mammography room


A layout for a Mammography room is shown in Fig. 3.3. Mammography rooms may be smaller in size
than other X‑ray rooms, and the shielding requirements are less due to the low X‑ray energy used.
Because of this, normal building materials such as gypsum wallboard may provide sufficient attenuation
(Section 6.1.5). However, if this approach is used, it is important to remember that in the event of a change
of use of the room to some other radiological purpose complete re-shielding may be required.

When assessing shielding requirements, only scattered radiation needs to be considered as mammography
equipment is generally designed so that all of the primary beam will be intercepted by the image receptor.
When laying out the room, a practical shielding solution may be to position the equipment so that the door
to the room will be in the wall behind the patient, as virtually all of the radiation will be absorbed by the
patient (BIR, 2000). This arrangement also facilitates privacy.

22 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Figure 3.3: Mammography X-ray room

Mammography unit
(tube and detector)

Patient entrance

Radiation barrier
(protective viewing screen)

Operator’s
console area

Staff entrance

3.3.4 Dual energy X-ray absorptiometry (DXA) room


DXA (or DEXA) rooms are often located outside of the radiology department, e.g. in the outpatient
or medicine for the elderly facilities of a hospital, in a G.P. surgery or sports medicine clinic. A room size of
15-20 m2 may be required, depending on the design of the equipment. If limited space is available, 10 m2
may suffice for a compact pencil beam DXA system. (NHS, 2002). An example of a DXA room layout is
shown in Fig. 3.4. The patient table is normally located close to a wall to maximise the functional space in
the room. When this is so, the wall closest to the table may need to be shielded, and the RPA should advise
on this. A protective shield for the operator’s console may be required, depending on design of scanner,
room size and workload, but the protective shield need not be as heavily attenuating as that in a general
X‑ray room.

Where more space is available, the table should be placed so as to maximise distance to the important
boundaries from a shielding point of view. Where the walls are 2 m or more from the DXA scanner (1 m will
suffice for pencil beam scanners), shielding is unlikely to be required for workloads of up to 100 cases per
week, however the RPA should always be consulted. Shielding requirements for ceilings and floors depends
on the factors mentioned above and whether the system uses an over or under-couch X‑ray tube.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 23


Figure 3.4: DXA room

Operator’s
computer /
Patient table
DXA control
area

Radiation barrier

X
(mobile viewing screen)

X-ray tube
& detector

Entrance door

3.3.5 Facilities for dental radiography (intra-oral and panoramic)


Intra-oral X-ray equipment

Intra-oral dental X‑ray equipment may be installed in a dedicated X‑ray room or in a surgery. In the latter
situation the surgery may not be used for other purposes, or as a passageway, while a radiograph is in
progress. The surgery accommodating the equipment must be designed in consultation with the RPA to
provide a safe environment.

A surgery containing an intra-oral X‑ray unit is shown in Fig. 3.5a. The primary beam in intra-oral radiography
should always be intercepted by the patient. The equipment should be installed and used so that the useful
beam is not directed towards wooden floors, unshielded doors or windows if the space immediately beyond
them is occupied (RPII, 1996).

The unit must be provided with a long cable for the exposure hand-switch or a separately located hand switch
to allow the operator to stand at a distance greater than 2 m from the patient’s head/X‑ray tube. During a
dental exposure, the area defined by all points within 2 m of the patient’s head is referred to as the controlled
area. This is illustrated in Fig. 3.5a. The RPA should check that all boundaries (doors, windows, walls, etc.)
within 2 m of the patient’s head during an X‑ray examination provide adequate shielding to meet with the
design dose constraints (see Section 2.4). The RPA’s shielding assessment should take account of the projected
workloads, distances to boundaries, beam directions, boundary materials and occupancy of adjoining areas,
including above and below the surgery. No structural shielding is required in the surgery if the workload is 20
films per week or less and the distance between the patient and the wall or other boundary is at least 2 m
(BIR, 2000).

24 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Where possible the operator exposure controls should be within the surgery but outside the controlled area.
Where the operator exposure controls are located outside the room in a public area, they should be installed
in a lockable box to prevent unintended exposures being made by an unauthorised person.

Figure 3.5a: An intra-oral dental unit installed in a surgery

Window

Surgery

Controlled
area

Office Dental Mains


chair isolator switch
Intra-oral
Exposure
X-ray equipment handswitch

Surgery
entrance

Extra-oral X-ray equipment and combined equipment suites

For new build, extra-oral X‑ray equipment must be located in a dedicated X‑ray room. An indicative area of
12 m2 has been suggested for panoramic/orthopantomographic (OPG) units. A slightly larger area will
comfortably accommodate the widely used combination of panoramic and intra-oral equipment (Fig 3.5b).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 25


Figure 3.5b: A dental radiography suite with several items of equipment

Window
Radiation Mains isolator switch
warning light Exposure handswitch

Room Radiation barrier


entrance (protective
viewing screen)

Patient
chair Dental
Intra-oral
X-ray equipment chair

Panoramic X-ray Surgery


equipment Surgery
entrance

A shielded operator’s console shown in Fig. 3.5b may be required depending on the workload. It is preferable
that it is located within the room, especially if young children and special needs patients are involved.

Due to the restricted size of many dental facilities, it may not be practical to install a protective operator
screen. An alternative solution is to locate the exposure hand switch(es) outside the X‑ray room door and
install a shielded lead glass viewing panel in the door. The hand switch(es) should be installed in a lockable
box for security reasons and each switch clearly labelled to indicate the unit it operates. It is advisable not to
have two or more control panels located close to one another. A screen of 1 mm lead equivalence will often
suffice (NHS, 2002). However, this and the overall level of shielding must be determined in consultation with
the RPA and will depend on the workload, room geometry and use/occupancy of adjoining areas.

26 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


3.4. Fluoroscopy rooms
3.4.1 Fluoroscopy room (general)
Figure 3.6: Fluoroscopy room used for general screening purposes

Staff entrance
Ceiling-suspended Patient table
TV display monitor

Operator’s
console area X-ray tube
& image
Radiation barrier receptor
(protective viewing screen)

Patient entrance

A layout for a general-purpose fluoroscopy room based on the two-corridor design is shown in Fig. 3.6. The
room has similar features to the general radiographic room described above in Section 3.3.1. However, the
operator’s protective screen is longer as there may be more staff in the room for these procedures; a screen
length of 2.5-3 m with a 1 m wing is typical, but this is dependent on the room size and use.

Fluoroscopy systems may have overcouch or undercouch X‑ray tubes. Overcouch tubes will have higher levels
of scattered radiation and are generally operated by remote control from behind the protective screen, and
make heavy demands on this area. Fluoroscopy remote control units may require a larger control area and a
smaller examination room area (NHS, 2001). Undercouch tube systems have lower levels of effective dose to
staff from scatter, and are generally associated with more staff working in the room. There is generally an
exposure control foot switch at the tableside – which should be guarded. There should be clear audible and
visual indicators when the X‑ray beam is on, so as to avoid inadvertent staff or patient exposure.

A ceiling-mounted TV display is normally located in the controlled area so that the operator can view live
X‑ray images when working close to the patient. A combination of mobile shielding (e.g. ceiling mounted
mobile lead screens, table mounted lead skirts) should be installed as part of the building or equipping
project as appropriate. Suitable storage for personal protective equipment (lead aprons and thyroid collars,
etc.) should be provided and easily accessed in the controlled area.

There should be a direct access toilet for patients following examinations, particularly for rooms used for
barium procedures. It is recommended that changing facilities are grouped close together.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 27


Radiation shielding calculations for fluoroscopy systems need only take account of scattered radiation as the
primary beam is generally completely intercepted by the image receptor in modern equipment. However,
fluoroscopy rooms often have an additional overcouch general tube installed, which may be used, for
example, to take lateral radiographic views in barium studies. In such cases, the room must also be considered
as a general room and primary radiation shielding will need to be considered.

3.4.2 Fluoroscopy (special & interventional radiology and cardiology)


The layout for an interventional fluoroscopy room is shown in Fig. 3.7. This is generally part of a suite with
preparation, recovery and other areas as appropriate. Suites of this type are now commonly used in Radiology,
Cardiology, Vascular Surgery and other disciplines. The suites that support interventional procedures should
be designed, as far as possible, to meet operating theatre standards, in terms of hygiene and suite design.

Most of these rooms use complex ceiling suspended X‑ray equipment, often having a C-arm configuration.
Sometimes two such installations are incorporated in a room providing “biplane” X‑ray imaging facilities.
Dual-table cardiac “swing-labs” may also be designed, which may require additional protection between
tables, often in the form of vertical lead blinds (see Section 3.6.1). In addition large numbers of staff are
frequently involved and need to access the room, the patient or the console area. The console area also often
doubles as a teaching/consultation area. This involves considered application of dose constraints (Section
6.3.5). Thus room size should be large and a range spanning 38 to 50 m2 has been recommended (BIR, 2000,
NHS, 2001).

The console area normally occupies the length of one wall with lead glass shielding providing a panoramic
view. A combination of mobile shielding (e.g. ceiling mounted mobile lead screens, table mounted lead
skirts) should be installed as part of the building or equipping project as appropriate. This is absolutely
essential in this type of facility, and it must be fitted in a fashion well adapted to the procedures envisaged
for the room. Suitable storage for personal protective equipment (lead aprons and thyroid collars, etc.)
should be provided and easily accessed in the controlled area.

28 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Figure 3.7: Fluoroscopy room (designed for special and interventional radiology procedures)

X-ray tube
Staff & image receptor
entrance Patient entrance
(C-arm configuration)

Radiation barrier
(wall with protective
viewing screen)
X
Operator’s
console Patient table
room

Ceiling-suspended
TV display monitor

An interventional room will require direct access to patient preparation/anaesthetic/recovery area(s). Many
interventional examinations will require sedation and some will involve general anaesthetic hence the need
for a recovery room/ward and more space in the X‑ray room for ancillary patient monitoring equipment. Staff
changing facilities, patient changing cubicles and toilet facilities should be provided nearby.

The scattered radiation is normally exceptionally high in interventional rooms due to the long fluoroscopy
times, long fluorography acquisitions and high patient doses. Shielding requirements may exceed Code 5
(2.24 mm) lead in some cases. Thus individual shielding assessments are essential for these facilities and
should be undertaken in consultation with the RPA.

3.5 Computed Tomography (CT) room


A CT room layout based on the two-corridor model is shown in Fig. 3.8. It is easy to adapt to a single corridor
approach by switching the staff entrance to the opposite wall. CT rooms are generally part of a suite with
patient waiting, changing cubicles, and toilets.

As with interventional rooms, large numbers of staff are frequently involved and need access to the room, the
patient and the console area. The console area also often serves as image processing/reporting/teaching and
consultation areas and again this must be borne in mind when selecting the dose constraints to be used
(Section 6.3.5). It normally occupies the length of one wall with lead glass shielding providing a panoramic
view. In addition, it may be expanded to serve two CT rooms, or a CT and MRI room, one each side of the
operator area. An intercom must be used for communication with the patient as the door between the CT and
console area must remain closed during exposures.

Within the CT room, the oblique alignment of the scanner allows observation of the patient from the
operator’s area for the duration of the examination. It also facilitates easy movement of patients, wheelchairs,
trolleys and staff in the room. Facilities suitable for storage of personal protective equipment (lead aprons,
etc.) should be provided and easily accessed.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 29


There are large variations in the shielding requirements for different CT systems. The increased patient
throughput facilitated by modern multi-slice and spiral CT systems can result in very high levels of scattered
radiation in the room and therefore greater levels of shielding are required.

Figure 3.8: Computed Tomography (CT) room

Radiation barrier
Staff
(wall with protective
entrance
viewing screen)

Operator’s
console
room Gantry including X-ray
Patient table tube & detector assembly

Patient entrance

Unlike interventional rooms the distribution of scattered radiation in the CT room is well defined and fixed,
as the position of the gantry is fixed and the X‑ray tube follows the same rotation path for each exposure.
Isodose curves for each scanner are normally available from the manufacturer and these should be used to
determine shielding requirements taking due account of local technique. As a general guide, the shielding
requirements for new multi-slice CT systems are between 3-4 mm lead (NHS, 2001). However, individual
shielding assessments based on actual workloads, room dimensions and occupancy of adjoining areas are
essential for these facilities and should be undertaken by the RPA.

3.6 Shared function rooms


3.6.1 Accident and Emergency departments (A&E)
Many A&E departments have dedicated X‑ray facilities (e.g. general, OPG, CT) and some have a dedicated
X‑ray room located immediately adjoining the resuscitation room. The shielding of dedicated X‑ray rooms in
this area should be based on advice from the RPA, but will generally be similar to that applying elsewhere.

As an alternative to a dedicated X‑ray room, some A&E departments have a ceiling suspended X‑ray tube
located in the resuscitation room, for use in several dedicated areas or bays (Photo 3.3). The external
boundaries of the resuscitation room may be fully or partially shielded, depending on the workload and
occupancy and on the RPA’s advice.

30 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Photo 3.3: Resuscitation room in an A&E department

(Photograph courtesy of Connolly Hospital, Blanchardstown)

In such an area, consideration should be given to including a fixed operator’s protective screen which allows
good visibility of all the bays. Protective half-length partitioned walls, fixed screens, blinds or curtains are
generally required between bays. Lead partitions and fixed screens are robust but may restrict the workflow
and visibility within the room. Lead curtains or blinds have the advantage that they may be retracted when
not in use, but may have a limited lead equivalence and may become damaged over time. The dimensions
and lead equivalence of the protective barrier between bays will vary with the workload and the distance
from the bed to the barrier. The dimensions must be sufficient to contain the primary beam for lateral
examinations. Unless the lead protection is adjacent to the patient trolley, it is recommended that the screen
extends by at least 0.5 m beyond both the head and the foot of the bed, if the workload includes lateral skull
examinations for example.

Alternatively, a mobile X‑ray unit may be used in A&E departments. In this case the shielding requirements
for all boundaries within the A&E department must be determined by the RPA on the basis of the workload,
occupancy of adjacent areas, etc. A secure place must be provided for storage of the mobile unit.

3.6.2 ERCP, cardiac pacing rooms and lithotripsy


Endoscopic retrograde cholangiopancreatography (ERCP) facilities are normally associated with endoscopy
suites and use a mobile C-arm or a fixed fluoroscopic system. Cardiac pacing rooms are frequently situated
near the CCU, and these procedures generally require a mobile C-arm. Fixed fluoroscopic systems for
lithotripsy applications may be sited in the Urology department. The boundary shielding of these rooms must

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 31


be assessed by the RPA as part of the room design. If a fixed fluoroscopic system is provided, the room must
contain a shielded operator console.

3.6.3 Operating theatres and recovery areas


Some surgical procedures, particularly in orthopaedic and vascular surgery, require mobile C-arm and/or
mobile X‑ray exposures. The theatre must be large enough to allow staff to stand well back from the X‑ray
tube and the patient; theatre areas of 40 m2 (BIR, 2000) and 55 m2 (NHS, 2001) have been recommended.
The boundaries will require shielding to a level advised by the RPA, and this would normally be Code 3 lead
equivalent, but may be greater for interventional procedures or less for low workloads or for applications
such as intra-operative dental work. It may be feasible to install X‑ray warning lights outside the theatre door.
When building a suite of theatres, it may be pragmatic to shield them all to the same level of shielding as
their usage may change over time.

Dedicated theatres used for interventional X‑ray procedures will require significant protection as these
generally involve fixed equipment with higher power output. The boundaries will generally need to be
shielded as for an X‑ray room. A shielded operating console should be included, and X‑ray warning lights
must be installed outside the door.

The use of mobile X‑ray units is often required in the recovery area. Examinations will often involve chest
X‑rays, and thus the considerations listed below for ICU/CCU/HDU apply, and special consideration must be
given to the need for shielding the floor and the boundary behind the head of the trolley.

Lateral X‑rays are often required after orthopaedic surgery, and thus a shielded trolley bay may be required.
This situation is similar to that discussed previously for multi-bay resuscitation room in A&E. The Theatre area
also needs to include a secure storage place for mobile X‑ray units and mobile C-arms.

3.6.4 ICU/CCU, high dependency units/neonatal units and general wards


In situations where it is not possible or advisable to move patients to the X‑ray department, mobile X‑ray
equipment is required. This occurs in neonatal units, intensive or coronary care units, and high dependency
units. Shielding will often be required to contain the primary beam. Since the majority of exposures involve
chest X‑rays with the patient lying supine, semi-supine or sitting upright, shielding is often required for the
floor and at the back of the bed.

The RPA must assess the shielding requirements. Consideration should be given to the location of the bed.
In new developments, beds are often positioned in front of windows, where shielding may be required.
Generally, Code 3 lead equivalence is sufficient in these situations. Figures 3.9(a) and 3.9(b) illustrate the
issues involved. If the bed backs onto a solid concrete wall, additional lead shielding is not normally required.
However the need for shielding of the floor area must be assessed.

Occasionally mobile X‑rays will be required in general wards, and the above considerations will also apply. A
risk assessment must be carried out to determine if structural shielding is required, but more often than not,
the assessment shows that, because of the low workload, no additional shielding is required.

32 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Figure .9(a): Window shielding not required, as primary X‑ray beam does not impact on window

X-ray tube

Window

Floor

Figure .9(b): Window shielding may be required depending on occupancy outside window

X-ray tube

Window

Floor

. Equipment in trailers


Trailers containing interventional radiology equipment, CT scanners, PET scanners, or mammography
equipment, are now regularly used by Irish hospitals. There are many reasons for this including replacing a
service while an existing facility is being renovated or re‑equipped, or providing a service pending the
development and building of a new facility.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 


The trailer must be sited in an area which can withstand the load involved, where there is easy access to the
hospital and to an adequate power supply. Prior to the trailer being sited a risk assessment must be
undertaken. This must take due account of the use and occupancy of adjacent areas and buildings. It must
also consider if there is sufficient boundary shielding in the trailer. Consultation with the RPA at an early stage
is essential with regard to the development of the risk assessment.

In addition, special attention must be given to the arrangements for PET or PET/CT in trailers. Particular
attention must be given to the floor and the roof of trailers, which in practice may not be shielded. Thus
attention is required to buildings above or below the trailer and within range of the radiation emerging from
it. Furthermore, the restricted space inside the trailer may result in the need for a higher level of shielding
than normal for internal boundaries, for example, in the operator’s console.

As is the case for fixed PET or PET/CT installations (Section 4.6), consideration must also be given to the
provision of designated toilet facilities for injected patients in addition to having appropriately shielded waste
storage facilities put in place. Consideration may be given to locating the trailer within close proximity to the
nuclear medicine department where similar radiation protection issues will be of concern. The RPA should be
consulted with regard to the appropriateness of using existing nuclear medicine facilities for PET patients as
the higher energy radiation (Section 4.6.1) may interfere with the operation of standard nuclear medicine
imaging equipment.

34 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


4. Nuclear medicine

4.1 Introduction
Diagnostic nuclear medicine uses chemical or pharmaceutical compounds labelled with a radioactive
substance and administered to a patient via ingestion, inhalation or intravenous injection. The distribution of
the radiopharmaceutical in the patient is later imaged either with a gamma camera, or another imaging or
measurement device. The radioactive isotope used to label the pharmaceutical is, in the majority of cases,
Tc, and in Ireland the labelling generally takes place on site. This requires appropriate facilities to be
99m

provided. Therapeutic uses of radionuclides also occur in general hospitals, but less frequently and involving
lower patient numbers.

The design of a nuclear medicine department should take account of several issues including radiation
protection, air quality and infection control. It is important to consult with the RPA, the radiopharmacist,
medical physicist, the infections control officer and the radiologist or nuclear medicine physician throughout
the design phase (NHS, 2001). Where no radiopharmacist is available, the advice of a pharmacist should be
sought. A nuclear medicine facility must deal with all the problems of receiving, storing, handling, injecting,
measuring and imaging, and waste disposal for radioactive materials in a hospital setting.

4.1.1 Location and access


The nuclear medicine department has close functional and operational relationships with the radiology/
imaging service, with which it is frequently combined. However, many of its functions need to be self
contained. Close proximity with general paediatric or obstetric imaging facilities should be avoided (this is
particularly important for PET). Shielding and layout should be such that activities in adjoining areas, such as
film storage or low level counting, are not affected by the presence or use of radioactive material.

Access for both ambulatory and trolley patients is required. Some areas within nuclear medicine will be
designated as controlled areas with access restricted to nuclear medicine staff. Entrance to controlled areas
should be marked with a warning notice (at eye level) stating that the area is controlled. Other areas within
the department may be designated as supervised areas and access to these will be regulated by appropriate
signage and systems of work.

In determining location, ease of access for delivery of radioactive material and removal of waste must be
considered. These activities may take place out of hours, so design and operational considerations are
involved. Direct egress for patients without going through the busy public areas of the hospital is desirable,
but not always possible. The requirements for appropriate access for cleaning staff should also be considered
at the design stage.

Ideally all the hospital’s activities involving radioactive material should be centralised into one location to
avoid transport of radioactive materials between units. Exceptions to this include some laboratories within
the Pathology Service and some research laboratories (Section 4.5). Some clinical areas such as Endocrinology
or Haematology may also use radioactive materials but, as far as possible, the handling of larger amounts of
radioactivity should be centralised.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 35


It is recognised worldwide that the security of radioactive materials is very important and that the design of
facilities where these sources are used and stored must cater for the implementation of good security
measures. Although the quantities used in diagnostic nuclear medicine are for the most part relatively low,
the perceived threat that might arise should they be lost, damaged or stolen is more problematic than the
hazard they present. Therefore, security of sealed and unsealed materials and radioactive waste must be
assured. To achieve this, the department should be designed with restricted access to all controlled areas
using the system of access restriction employed by the hospital. These areas also require an appropriate level
of fire and intruder alarms. Where appropriate, the design team should consider obtaining professional
advice on these security issues.

Figure 4.1: A possible layout of a nuclear medicine department


Operator console
Patient

Patient
toilet

toilet

In-vitro

Staff toilet
counting Gamma Gamma Data
& uptake camera camera processing
room room

Corridor
Step-over barrier

Waste
Lobby
Cardiac stress

store
Waiting
test room

Hatch

area
Injection Radiopharmacy
room /hot lab Radionuclide
Hatch

Storage
storage area
area

4.1.2 Overview of facilities and layout


Within the nuclear medicine department, the following facilities must be provided: a radionuclide reception
and storage area, a radiopharmacy, patient waiting area, injection area, gamma camera (scanning) room(s),
patients WC and waste store. Other facilities that should be considered are a reception area, office/reporting
facilities, cardiac stress, uptake assessment, in vitro sample counting and therapy administration areas.
Storage areas for general consumables and collimators will also be required. Premises should preferably be
laid out in such a way as to facilitate workflow. Areas should be connected in the sequence of the operations
and patient flow, and to allow the required level of cleanliness. Separating patient and staff areas will assist
in creating a suitable environment for patients as well as helping reduce contamination hazards. Ensuring
areas are adequately sized will not only provide a pleasant environment for both staff and patients, but will
also contribute to dose reduction strategies and may reduce the need for shielding. A possible layout is
illustrated in Fig. 4.1.

36 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Within nuclear medicine, clear demarcation between areas is required to confine the use and storage of
radioactive material to certain areas within the department. The need for transport of materials within the
department should be minimised by the use of hatches, where appropriate, and the design and layout of the
department should be such that the movement of unsealed isotopes is minimised. Access for delivery of
isotopes to a secure storage area within or adjacent to the radiopharmacy should be provided. In addition, it
may be necessary to receive and store radioactive waste from other areas within the hospital (e.g. theatre,
laboratory, ward areas) and the route by which this will be achieved should be considered.

The appropriate designation of areas such as the scanning room, injection room, patient WC, waiting area
and the radiopharmacy (as controlled or supervised) should be determined by risk assessment and in
consultation with the RPA.

4.2 Nuclear medicine facilities


This section provides a review of the facilities required for diagnostic nuclear medicine. It does not include
those required for therapy or PET related activities, which are treated in Sections 4.4 and 4.6. In the areas
frequented by patients, surfaces should generally be non-porous and easily cleaned and decontaminated as
described in Section 6.2.

4.2.1 Scanning room


A nuclear medicine imaging unit will have one or more scanning rooms. The scanning room will house the
gamma camera and the operator console. The size of the room should be sufficient to accommodate the
particular type of scanner envisaged and allow for patient trolley access and collimator exchange (typically
35-40 m2). Scanners with removable tables will need additional space for this facility. The room should be of
a size that will accommodate the equipment in the preferred orientation, as illustrated in Fig 4.2.

Figure 4.2: A possible layout of equipment in a gamma camera room

Collimator
carts
Acquisition & HIS/RIS
workstations

Mobile lead Display


screen monitor
a
er
m
ca

Wash-hand
a
m

basin
am
G

Patient entrance

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 37


The operator console should be located at a sufficient distance from the patient table so that the patient can
be observed while minimising direct exposure to staff. The console area must have enough space for the
gamma camera acquisition terminal, and any other required equipment, terminals or workstations. If the
gamma camera has an associated CT scanner, then a separate shielded operator console area will be required.
As with interventional radiology and CT, a single operator room may be shared by a number of adjacent
scanning rooms (see Fig 4.1). Where this is done, due regard must be given to the dose constraint used in
planning the area (Section 6.3.5). It should not be necessary to pass through the scanning room to enter a
shared operator room.

Shielding requirements for the room must be assessed by the RPA but 1-2 mm lead is likely to be sufficient.
The radiation involved is generally more penetrating than that used in the radiology department, but the
intensity is lower. Shielding of walls, floor, ceiling, windows and doors must be considered. The walls and
doors should be clearly marked to indicate the level of shielding provided. Consideration should be given to
the exclusion of windows where meeting a dose constraint may present a problem now or in the future. The
location and shielding of the room must ensure that radiation from sources external to the room, such as the
operation of another scanning room close-by, is reduced to a level which will not affect the performance of
the gamma camera. If the gamma camera has an associated CT scanner, the use of the CT scanner must be
taken into account in designing the room layout, shielding and operator area. (See Section 6.3.5).

The load bearing capacity of the building must be sufficient to take the weight of all equipment and shielding.
Modern gamma cameras are used with a range of collimators; the storage, load bearing, and ergonomic
requirements are considerable and must be taken into account during design.

Radiopharmaceuticals are sometimes administered by inhalation involving radioactive gases or aerosols.


Adequate air extraction is required to minimize contamination risks. Ventilation systems should not re-
circulate air and should be vented externally. Grills should be sited away from the gamma camera head(s).
Temperature control should be provided so that conditions are suitable both for patient and staff comfort but
also to ensure extremes that might be detrimental to system performance are avoided. Shielded sharps and
waste containers, and a wash-hand basin with elbow or sensor operated taps, plumbed directly to the main
drain, are required. Ceiling mounted services may offer advantages in terms of ergonomic design.

4.2.2 Patient injection room


The patient injection area should be adjacent to the radiopharmacy and should be sized to accommodate
one or two bays for ambulatory patients. At least one of the bays should be able to accommodate wheelchair
or trolley patients. Within the room, space should be provided for storage of consumables, shielded sharps
and general waste bins, and an instrument trolley; a wash hand basin with elbow or sensor operated taps is
also required. Some level of shielding is likely to be required in this area. The RPA must advise accordingly but
1 mm lead is often adequate. The walls should be clearly marked to indicate the level of shielding provided.
Access to the area should be via a signed and shielded door.

The injection area and the radiopharmacy should be connected by a shielded, airlocked pass through hatch
through which prepared radiopharmaceuticals can be transferred (DH, 2007). An air extraction system must
be provided if ventilation of patients is to take place in this room.

38 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


4.2.3 Waiting area (pre & post administration)
Patient waiting areas are required within the nuclear medicine department. Some departments segregate
patients pre- and post-administration of radioactive materials. Advice should be sought from the RPA as to
whether this is required. If a significant paediatric workload is envisaged, consideration should be given to a
separate waiting area for children. Shielding requirements for the waiting area will depend on location and
must be determined by the RPA. Typically, 1-2 mm lead equivalence is normally adequate. This also applies
to any external windows included in the area.

Seating in the waiting area should have non-absorbent, wipe clean finishes to minimise contamination risks.
Fixed seating is preferred with a separation of 0.8 m centre to centre (NHS, 2001). A separate area for trolley
patients (1 - 2 trolleys) and accompanying staff will facilitate privacy and will help minimise exposure. Provision
of good quality drinking water for patients is essential to assist clearance of unbound radionuclides.

The area should be signed and access restricted to nuclear medicine patients, accompanying persons and
staff. Consideration should be given to the installation of CCTV for supervision and observation of patients.

4.2.4 WC facilities
WCs for use by nuclear medicine patients only should be provided within the department close to the
waiting area. The shielding requirements (if any) for this toilet area must be determined by the RPA. Signs
limiting access to other persons should be prominently placed on the doors, as these toilets are likely to be
contaminated. The waste pipes should be plumbed directly to the external drain. The waste pipes from these
toilets must be clearly marked indicating the presence of radioactive material. All surfaces should be non
porous and easy to clean and decontaminate. Wheelchair access should be provided. It may be desirable to
include a sluice to deal with bedpans from trolley patients. Consideration should be given to the provision of
WC facilities for accompanying persons and staff either within the department or close by.

4.2.5 Reception/office/reporting and consultation facilities


Office, reception, reporting or consultation facilities provided within the nuclear medicine department must
comply with the design dose constraint of 0.3 mSv per year. This may be achieved by a combination of size,
shielding and location.

4.3 Radiopharmacy facilities


4.3.1 General requirements for the radiopharmacy suite
The radiopharmacy suite is an integral part of a nuclear medicine facility when on-site labelling and
preparation takes place. A typical suite will consist of a lobby or changing area, a hot lab, and a number of
other rooms. A possible layout and design is illustrated in Fig. 4.3. In practice an individual development may
not require all of these facilities. Utilisation of therapeutic isotopes may alter the design and shielding
requirements. Facilities using pre‑labelled radiopharmaceuticals will not have such extensive requirements.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 39


Figure 4.3: A possible layout for a radiopharmacy/hot lab & related areas

Shelf

Step-over barrier
Clean area
Lobby
Wash-hand

Hatch
basin

Injection
room

Laminar airflow
cabinet/isolator
Trolley

Trolley

Fridge

Hatch
Hot lab/ Radionuclide
radiopharmacy storage area

Curtain

Shielded
Laminar airflow safe
Shielded Shielded cabinet/isolator Worktop
bin bin

There are no comprehensive statutory guidelines dealing with all of the issues in the previous paragraph. This
Code will become the definitive guide on radiation protection issues for radiopharmacy design.

The location of the radiopharmacy should facilitate easy delivery of radioisotopes by suppliers and allow a
practical route for waste disposal. It should be adjacent to the injection rooms. The location should not
create a new hazard to existing areas or personnel. It is also important that it is not immediately adjacent to
areas where low level counting or imaging equipment is installed.

The equipment selection and premises design should minimise the risk of errors, permit effective cleaning
and maintenance, minimise the risk of cross-contamination, build up of dust and facilitate preparation of
quality products. Lighting, temperature, humidity and ventilation should be appropriate and such that they
do not adversely affect, directly or indirectly, either the medicinal products during their manufacture and
storage, or the accurate functioning of equipment (EC, 2003). Consideration must be given to the load
bearing requirements of the workstations, where large quantities of lead shielding are required to protect the
operator.

Surfaces should be similar to those described for other areas in nuclear medicine (Section 4.2). They should be
non-absorbent, with the skirting overlapping the edges of the wall and every effort should be made to
minimise fissures in the finish of the suite. Stainless steel finishes should not be used, as they absorb some
types of radioisotopes and are difficult to decontaminate (NHS, 2001). The ceiling should be continuous and
imperforate; the use of de-mountable tiles is not appropriate as it permits collection of dust and the associated
infection risks within an essentially aseptic room (NHS, 2001). The walls should be easy to wash down in case

 A consensus has not yet been reached within the nuclear medicine community on the most appropriate design from an air quality/
infection control perspective. However, radiation protection design issues are relatively clear. The advice contained in this Code is
based on international guidelines including the recommendations of the European Association of Nuclear Medicine (EANM, 2007),
those detailed in the NHS Estates Health Building Notes (NHS, 2001) and in the Department of Health, Health Building Note 14-01
(DH, 2007). Consideration has also been given to the Eudralex Guidelines (European Commission, 2003).

40 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


of contamination or infection risks. Finishes may include specialist paints, as used in operating theatres and
elsewhere, or possibly laminate/plastic faced panelling systems with sealed joints (NHS, 2001).

Calculation of the shielding required, which may be considerable, must be undertaken by the RPA. The
approach frequently adopted is that of poured dense concrete or solid blocks to which additional shielding
can be applied as required (NHS, 2001).

The venting from the laminar airflow cabinets or isolators should be fire resistant, non-absorbent and easily
dismountable in sections (NHS, 2001). Each cabinet/isolator should have its own individual exhaust system
incorporating effective precautions against blow-back and providing safe dispersal to atmosphere (DH, 2007).

4.3.2 The lobby/changing area


A separate gowning/lobby leading to the hot lab/radiopharmacy is required (EANM, 2007). The lobby will be
used by staff to change into aseptic clothing, and will therefore need appropriate signage and an indication
of when it is occupied. Access should be controlled by the system used by the hospital for secure areas (e.g.
magnetic swipe or keypad). The finishes in the lobby should be similar to those described in Section 4.3.1.
Shelving is required to store the appropriate aseptic clothing and a shielded bin should be available for used,
and possibly contaminated, clothing. A permanent barrier/demarcation must clearly identify the entrance to
the “clean” area.

4.3.3 Hot lab/radiopharmacy


The hot lab accommodates the production functions of the radiopharmacy area and for a single workstation
should not be less than 10 m2 in area. A hot lab of approximately 20 m2 should comfortably facilitate two
cabinets or isolators. The work space must ensure a safe and comfortable operational environment to prevent
errors and cross-contamination of products. This is a controlled area and must be delineated by both signage
and access arrangements. The shielding requirements for all the facilities in this area must be determined by
the RPA.

As described in Section 4.2.2, the link to the injection room should be via an airlocked pass through hatch
(DH, 2007). For security purposes, it should only be possible to lock the hatch from the radiopharmacy side.

The installation of bench top workspace should be kept to a minimum in the hot lab to prevent the
accumulation of dust, but some may be required for operational purposes. In these circumstances, all surfaces
should be designed in accordance with those detailed in Section 4.2. Sinks should not be present in the
production area (EANM, 2007).

The preparation of radiopharmaceuticals generally takes place in a workstation such as a laminar airflow
cabinet with HEPA-filtered Grade A air or a total containment workstation. The workstations should be in an
environment conforming to at least Grade D. The requirements for the production of sterile materials are
provided in the European Association of Nuclear Medicine Guidelines (EANM, 2007) and the European
Commission Guidelines (EC, 2003).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 41


The workstation should be adequately shielded and incorporate lead glass windows for the protection of the
operator. A minimum of 5 mm lead equivalent shielding should be present in the window. The 99mTc generator,
which is usually integrated into the workstation, should be suitably shielded. Dose calibrator(s) integrated into
the workstation should be also shielded from ambient activity, and to protect the staff using them.

4.3.4 Radionuclide storage area


A storage area is required for sealed and unsealed radioactive materials that will be used in the radiopharmacy
and should be located adjacent to it. It may also serve as a central store for much, but not all, of the
radioactive material used in the hospital. Typical dimensions for the storage room might be of the order of
10 m2. Its location and access arrangements should facilitate delivery of radioactive materials by suppliers,
transport to the radiopharmacy and elsewhere in the hospital, and removal of radioactive and non-radioactive
materials for waste disposal. Consideration must be given to the requirement for security and the hazards
that may arise in the event of a fire or flood. An appropriately worded warning sign should be prominently
displayed on the door, and provision for control of access should be made. The shielding requirements for
this area must be determined by the RPA and will depend on the level of the local shielding of each source
or subgroup of sources. The suitability of the storeroom, and sub-storage arrangements must be subjected
to a risk assessment prior to approving the design.

The storage or sub-storage areas should be compartmentalised to allow segregation of high and low activity
stock and also sealed and unsealed stock. Each compartment should be marked to permit easy identification.
Gaseous or volatile radioactive materials or those which produce gaseous daughters should be stored in a
facility which is vented directly to the outside or to the fume hood stack. Giga-Becquerel levels of radioactive
materials may require more elaborate arrangements, which must be determined in consultation with the
RPA. Storage areas must be designed to ensure ease of decontamination in the event of spillage. A
temperature-controlled and monitored refrigerator(s) for the storage of pharmaceuticals should be provided.
Preparations that are stable at 2-8ºC should be stored in a refrigerator until required. There may be a
requirement for shielding refrigerators (DH, 2007).

A wash hand basin with elbow or sensor operated taps should be located in close proximity to the storage
area to allow staff wash their hands after handling radioactive substances. An additional sink or sluice for
disposal of radioactive liquids should be installed in this area and should be marked appropriately. Both sinks
should be plumbed directly to the outside drains as specified for the patient toilets (Section 4.2.4). The
finishes should be similar to those described for the radiopharmacy (NHS, 2001).

Over and above the requirements for radionuclides, adequate general storage and security should be
provided for all the materials required for the operation of the radiopharmacy, and for quality control
equipment (EC, 2003).

4.4 Special considerations/areas


Some departments will require additional facilities to those described in the preceding sections. This will be
determined by the operational brief of the service to be provided. Provision or otherwise for these should be
decided at the design stage, following consultation with the RPA and all other relevant parties.

42 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


4.4.1 Radionuclides in the operating theatre
Radionuclides are increasingly being used in the operating theatres as part of planned procedures. They may
also be present in patients who are scheduled for surgery or who arrive in the theatre as a result of an
emergency having recently undergone a diagnostic nuclear medicine scan. Thus some thought needs to be
given to the radiation protection issues involved. In at least one way, theatre design is compatible with the
presence of radionuclides, as the surfaces and finishes used are designed with ease of decontamination in
mind. The main issues that give rise to concern are storage and removal of waste generated during the
procedures and decontamination of the theatre in the event of a spill.

Additional structural shielding is not generally required, and standard operating theatre procedures should
protect the staff from contamination (MDGN, 2002). Waste generated during the procedures will have to be
segregated from non-radioactive waste. Provision must be made for storage of contaminated waste until it
decays to background levels, or can be moved to a central waste storage facility within the operational
guidelines. Finally, consideration must be given to the management of patients in the recovery area who
have been administered radionuclides.

4.4.2 Therapeutic use of unsealed radionuclides


Therapeutic administration of unsealed radionuclides often takes place in nuclear medicine departments,
provided it can be managed on an out-patient basis. Radionuclide therapy, such as thyroid ablation using 131I,
requiring in-patient isolation arrangements is beyond the scope of this publication.

The requirements depend on whether the isotope is administered as a capsule or liquid. Preparation and
administration is generally possible with equipment and facilities used for diagnostic examinations.
Administration should be carried out in a quiet, designated area and this may be either a separate small room
or an area of the diagnostic department temporarily reserved for that purpose (for example the uptake
room). However it should be such that, if there is a spill or the patient is incontinent or vomits, the impact of
the contamination will not compromise the other functions of the department.

The design of areas for radionuclide therapy should conform to the requirements for diagnostic nuclear
medicine areas. Floors and other surfaces should be covered with smooth, continuous and non-absorbent
surfaces that can easily be cleaned and decontaminated. Floor coverings should be coved against walls and
removable if necessary. Walls should be finished with good hard gloss paint.

The RPA must be consulted on the appropriate designation of the area in which therapy administrations take
place. It is likely that it will be considered as a controlled area. The additional shielding requirements, if any,
will also be specified by the RPA. Separate facilities will be required for patients post administration if
procedures do not require that they leave the hospital promptly.

4.4.3 Uptake assessment area


A separate area for assessing quantitative uptake of radionuclides, as opposed to imaging, may be required
within the nuclear medicine department. These measurements generally employ a dedicated uptake detector
and stand (e.g. thyroid uptake). The area should be able to accommodate a patient chair and/or couch, the

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 43


uptake probe and associated equipment. This room should be located away from high activity areas and/or
it should be adequately shielded as the activities measured in it are generally low. A wash-hand basin with
elbow or sensor operated taps should be provided.

4.4.4 In-vitro measurement area


Several tests in nuclear medicine involve assessment of relatively low activity in vitro samples. These include, for
example, patient samples complementary to scanning, and radiopharmacy quality control materials. It may be
possible to integrate this work into the uptake assessment area if both have relatively low workloads, although
the possibility of contamination must be borne in mind. If the workload is large, additional facilities may be
needed. The room should be located away from high activity areas and/or it should be adequately shielded.
Laboratory bench areas will be essential for equipment, sample handling and record keeping. Surfaces should be
non porous and easily cleaned and decontaminated. A dedicated sink connected direct to external drain for
disposal of liquids, and a wash-hand basin with elbow or sensor operated taps should be provided.

4.4.5 Other areas


There are a number of other areas where radionuclides may be used, both within the nuclear medicine unit
and elsewhere throughout the hospital for example a cardiac stress test area. However, these areas are not
considered in this Code as their design features do not draw heavily on radiation protection issues.

4.5 Hospital laboratories using radionuclides


Many hospitals will have laboratories that use radionuclides within the pathology service and/or research
units. In these laboratories the radioactive material is generally more contained than in the nuclear medicine
department and hence the design issues are more straightforward.

The design of a laboratory for the use of unsealed radioactive substances depends on the radionuclides and
activities to be handled, as well as the complexity of procedures being undertaken. Most hospital laboratories
such as haematology or pathology use sources of low activity. However, it is important that the RPA and the
laboratory end user are involved in the design.

A radiation risk assessment will normally show that the structural shielding in good modern laboratory facilities
need little or no upgrading to conform to the requirements for low-level radioactive work. A specific designated
work-area within the laboratory may be required for the preparation and counting of radioactive samples. Surfaces
should be easy to clean and decontaminate, be free of joints and sharp corners should be avoided.

A lockable storage facility, shielded if necessary, must be provided for the safe storage of radionuclides. This
should be situated in proximity to the workbench. Radiation warning signs must be placed on the door of
the storage facility, the designated work area, any sink designated for the disposal of low-level liquid waste
and containers for solid waste.

Local storage for short and medium term waste will be required within the laboratory. However, depending
on space and operational policies, longer term waste storage may be available in the hospital radioactive
waste management facilities (Section 4.7).

44 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


For work involving volatile radioactive materials (such as iodination), the active laboratory should include a
workstation which may be a microbiological safety cabinet, an isolator, or a fume cupboard. Provision must
be made for the safe discharge of all gases. Adequate shielding above and around the workstation should
also be provided.

4.6 Special considerations for PET


4.6.1 General and facilities required
Positron Emission Tomography (PET and PET/CT) is a diagnostic imaging procedure that provides both
functional and anatomical information. PET imaging is similar to radionuclide imaging but differs significantly
in both the technology and the radiation protection issues to be addressed. This is partly because it uses
relatively high activities of radionuclides that emit radiation with an energy of 511 keV, almost four times as
high as the most common energy used in nuclear medicine. This presents unprecedented radiation protection
challenges in nuclear medicine and must be taken into account when constructing new facilities or adapting
existing ones. The addition of CT to PET brings additional radiation protection and equipment issues.
However, most facilities designed with shielding adequate for PET will require little modification for PET/CT.

A PET imaging service will require the following facilities:

n Patient waiting area.

n PET scanning room.

n Control room/console area.

n Uptake/injection areas.

n Patient changing area.

n Patient WC.

n Isotope dispensing area.

n Waste storage area.

In addition an office area, reporting room, and consultation area may be required. Many of the requirements
are similar in principle to those for general nuclear medicine, with important variations. In what follows the
general approach outlined in Section 4.2 is assumed and the emphasis is on the variations from it.

4.6.2 Location, layout and access


Access to the department for both ambulatory and trolley patients is required. Some areas within the
department will be designated as controlled areas with access restricted to authorised staff. Other areas
within the department may be designated as supervised areas and access to these will be controlled by the
use of appropriate signage and warning lights. Access to ‘staff only’ areas should be possible without passing
through areas of high radioactivity. Patients should be able to enter and leave the department without
passing through ‘staff only’ areas.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 45


The layout of the department should be such that it facilitates patient movement through the various steps
involved. The exit route for patients post scanning should be planned so that they leave the hospital promptly
after their examination without passing through other departments or busy public areas, because of their
residual radioactivity.

If the PET scanner is to be located in or close to the nuclear medicine department, care must be taken to
prevent radiation from PET patients after radionuclide administration interfering with other imaging
equipment in the department. Care must also be taken to ensure that radiation from patients leaving the
department following their scan does not interfere with sensitive equipment, including gamma cameras. An
example of good layout is shown in Fig. 4.4. Grouping patient areas together reduces the need for shielding
and reduces staff doses.

Figure 4.4: A possible layout for a PET/CT facility

Uptake room 1 Patient WC Uptake room 3


Radionuclide
Waiting Staff Concrete nib Concrete nib delivery
area & WC latch
Concrete nib Concrete nib
reception Corridor Radionuclide
dispensing
Uptake room 2 Uptake room 4 area

Clean
Entrance
utility
Corridor room

Dirty
Concrete nib
Patient utility
Patient
change back room
exit
Nurse/ Control Server
consultation room Waste
Store
room storage
PET/CT
hold
scanner

4.6.3 Patient facilities


Interview room/office
Thorough patient preparation is an important element of successful PET imaging. An interview room or
office where this can be done prior to attendance for scanning is required. This should be located such that
patients attending should not have to pass through high activity areas.

Waiting rooms
The waiting area requirements for a PET facility are relatively modest because of the pattern of workflow. The
waiting area is for patients and any accompanying persons prior to administration of the radiopharmaceutical
and so special shielding is not required. Access to a patient WC should be provided in this area.

46 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Uptake rooms
The number of injection/uptake rooms required per scanner is in the range 4-6. Because of the high exposure
rate from the patient post injection, these areas will require high levels of shielding. Each room should
accommodate a reclining patient chair, instrument trolley and shielded waste and sharps bins. The patient
may also change into a hospital gown in this area. At least one of the uptake rooms should be able to
accommodate a patient trolley.

A hand-wash basin with elbow or sensor operated taps should be provided. Surfaces should be non-porous
and easily cleaned and decontaminated. Privacy curtains, subdued lighting, and noise control should be
provided (Anderson, 2004). Reliable climate control is essential both for patient comfort and to ensure
optimal conditions for uptake. CCTV may be required for remote patient monitoring.

The shielding requirements for uptake rooms are considerable and must be determined by the RPA. Use of
concrete nibs (see Fig. 4.4 and Photo 4.1) can be effective in reducing the shielding requirements for the
doors. A toilet dedicated for patient use should be provided nearby, so that the patient does not have to walk
through the department to empty his/her bladder prior to scanning.

Photo 4.1(a): Entrance to uptake room – nib on right Photo 4.1(b): Uptake area behind nib

(Photographs courtesy of Mater Private Hospital, Dublin)

Scanning rooms
The minimum requirements for space in the scanning rooms should be obtained from the equipment vendor’s
site planning documentation (Anderson, 2002). Typical dimensions are of the order of 30‑35 m2 with an
additional 10-15 m2 for the control room/console area. Extra space provided within the scanning room may
reduce shielding requirements due to the decreased exposure at the boundaries. Means of observing the
patient and maintaining aural communication with them must be provided. Provision for an automatic
injector may be required for PET/CT examinations. There are strict requirements for environmental control in
the scanning rooms because of the sensitivity of the PET scanner to temperature variation.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 47


The control/console room should provide direct access to the scanning room as illustrated in Fig. 4.4 and be
close to the dispensing and uptake rooms. The shielding of the control/console room must be specified by
the RPA and will depend on whether the dose constraint to be applied is that for the public or designated
radiation workers. If access to the console area is limited to radiation workers, then the design dose constraint
is 1 mSv per year. Where access cannot be restricted solely to radiation workers the design dose constraint
of 0.3 mSv/year must be adhered to. In practice this will present design challenges particularly in cases where
direct patient observation by the operator is required.

Post scan patient changing room


For PET/CT the patient will be scanned in a suitable gown. Changing facilities pre-scanning can be incorporated
into the uptake rooms but after scanning it is convenient to have a changing area elsewhere so that maximum
usage of the uptake rooms can be achieved. A single changing room should be adequate, as only one
patient at a time will require it. This should be sited close to the scanning room in order to minimize movement
of the patient through the facility.

4.6.4 Dispensing and other facilities


Dispensing area
The dispensing area should be suitable for the handling of PET radiopharmaceuticals. It has few special
requirements over and above those already mentioned for nuclear medicine. However the shielding
requirements for 511 keV are substantial and must be specified by the RPA. Benches must be solidly built to
cope with the weight of local shielding in the immediate vicinity of sources (Anderson, 2002). Good use of
local shielding is helpful in reducing exposure rates within the area and at boundaries. Floor level storage
must be provided for the carriers in which isotopes are delivered which are both heavy and bulky.

Space for foot and hand monitors for staff should be provided at the exit from this and other high activity
areas.

Utility rooms
Scanners provided by some vendors require additional rooms or space for ventilation, cooling, heat exchange,
or air conditioning systems. A separate room for the cabinets associated with the CT may also be required.

4.7 Waste management facilities


Dedicated and secure storage facilities for radioactive waste will be required within the nuclear medicine
department. Access to this area should be strictly controlled and limited to designated personnel. The store
should be located adjacent to the radiopharmacy and injection areas. Access should not be through the
clean area, offices, or scanning rooms, and should be such that disruption to services in the event of an
accident in transit will be minimised. A warning sign should be placed on the door.

The waste store included in Figures 4.1 and 4.4 should be of solid, non-combustible construction and should
offer adequate protection from heat, cold, humidity, mechanical damage, vermin, fire and flood. Protective
shielding (possibly up to 4 mm lead equivalent) will be required. This must be specified by the RPA so that
protection is provided for all those outside the store and those who must transfer material to it or process

48 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


materials within it. A shielded safe should be provided for small volumes of radioactive liquids which have
high activity, and sources of small physical size, that must be kept secure for long periods.

The ceiling, wall and floor finishes should be non porous and easy to clean and decontaminate. The store
should be well lit and have sufficient space for the materials to be stored. Corrosive or explosive waste should
not be stored in this facility. Waste stores should be adequately ventilated by mechanical means when
radioactive gas, dust or vapour is liable to be present. Ventilation should be vented externally and at a height
that ensures adequate dispersal. Filters are not usually required for the quantities used in hospitals.

The type of waste likely to be stored will include spent generators, unused radionuclides (liquid and capsule),
contaminated needles, swabs, syringes, etc. Adequate space and shelving to allow segregation of waste
should be provided. High specification shelving or a large floor area is required to store large numbers of self
shielded items (e.g. spent generators which are heavy due to their protective shields). Low-level radioactive
liquids may be disposed to drain via designated (and clearly marked) sinks in accordance with disposal limits
specified in the licence conditions. These sinks must be connected directly to the main outside drain and
labelled to indicate their use for the disposal of radioactive material. The waste store should have a wash
hand basin with elbow or sensor operated taps and fire and intruder alarms.

For waste that cannot be otherwise disposed of there may be a requirement for a second, remote long-term
storage facility. Design requirements are similar to those given above with access even more rigorously
controlled, as it may not be under day-to-day surveillance. The signage may, on the advice of the RPA, be
placed within the store immediately adjacent to the entrance instead of on the outside of the door.

4.8 Ventilation requirements


The specific ventilation requirements from a microbiological perspective detailing the pattern of airflow
within the nuclear medicine department are beyond the scope of this publication but the design will have to
take account of the potentially conflicting requirements for containment of radioactive material and
protection of the product from environmental contamination. The ventilation system in the nuclear medicine
department should be separated from other systems used by the hospital, and the exhaust duct should not
be placed near windows or entrances. Air extracted from areas where radioactive products are handled must
not be re-circulated (NHS, 2001, EC, 2003, DH, 2007).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 49


5. Shielding calculations

5.1 General and design goals


As is evident from Chapters 3 and 4, a key part of the design of most X‑ray and nuclear medicine installations
is calculating the shielding required. The dose constraints that must be applied to the design and planning
of facilities were introduced and detailed in Chapter 2 and are also noted in Table 5.1. These dose constraints
must be employed as design goals to protect both exposed radiation workers and members of the public,
and are used in the example calculations below.

Several methodologies are available for performing shielding calculations. The most notable are those
published by the British Institute of Radiology in the UK, the National Council on Radiation Protection in the
USA and an older document published by the World Health Organisation is also useful (BIR, 2000, NCRP,
2004, WHO, 1975). The NCRP and BIR reports are more recent publications and both are useful sources of
information with practical examples.

The BIR and NCRP approaches have important differences from each other, particularly regarding design goals, but
also in methodology. There are also limitations to the applicability of both methodologies. Attention is drawn to
these here as they pull much of the available primary literature together in a relatively accessible and useable way.
However, they must be used critically and with an awareness of the specific requirements of the Irish regulatory and
licensing systems. Table 5.1 highlights the main differences between the BIR and NCRP methodologies and compares
them with the requirements set out in this Code.

Table 5.1: Comparison of main differences between BIR, NCRP and Irish approaches to shielding
requirements (BIR, 2000 and NCRP, 2004)

Shielding concept BIR NCRP This Code

Classification of Controlled Controlled Controlled


Areas
Not specified Uncontrolled Public area and all
others*

Design Limits Dose Constraint Shielding Design Goal Dose Constraint


Terminology

Design Limits Not specified 5 mSv/year (Controlled) 1 mSv/year


Employed (Exposed workers)

0.3 mSv/year 1 mSv/year 0.3 mSv/year


(Public and non- (Uncontrolled) (All others)*
radiation staff)

Weekly Workload Entrance Surface Dose mA min Either or both,


(Primary) (ESD) or Film Dose depending on
circumstances

Weekly Workload Dose-Area Product mA min Either or both,


(Secondary) (DAP) depending on
circumstances

Occupancy Percentage of time Fraction of time Either or both,


depending on
circumstances.
* A conservative approach requires use of a dose constraint of 0.3 mSv/year for supervised areas, as there can be exposed workers,
non-exposed workers and members of the public present in these areas.

50 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


The two published methodologies differ in respect of the shielding design goal (NCRP) or dose constraint (BIR)
to be employed. These terms refer to the level of air kerma (mGy) or effective dose (mSv) that is employed in a
shielding calculation to ensure that the annual dose limit to the surrounding area is not exceeded. Dose limits
are typically given in terms of effective dose, however both reports take the view that it is not practical to use
effective dose when calculating shielding requirements and therefore use air kerma (mGy).

For the design of new facilities, the NCRP recommends that the shielding design goal for radiation workers
should be based on a fraction of the annual dose limit, and a value of 5 mSv per year (which corresponds
with an annual air kerma value of 5 mGy) is recommended for controlled/supervised areas. The BIR states
that areas in which exposure can be greater than 6 mSv per year should be controlled.

Based on the ICRP recommendations for the annual limit of effective dose to a member of the public, the
NCRP recommend a shielding design goal of 1 mSv per year for uncontrolled areas. However, the BIR note
that a design limit based on the annual dose limit for members of the public (1 mSv) does not represent a
solution which is As Low As Reasonably Achievable (ALARA). It also refers to guidance on optimisation from
the NRPB (NRPB, 1993). It concludes that a dose constraint would have to be based on the dose limit of 1
mSv per year and, taking account of the principle of optimisation, decided on a value of 0.3 mSv per year.
The Irish dose constraint is also set at 0.3 mSv per year. Although there is a difference in the design goals set,
it is important to be aware that both approaches may still be used for calculations provided the appropriate
value of dose constraint is substituted.

5.2 Variables affecting shielding design calculations


Performing shielding calculations at or near a boundary requires knowledge of the distance from the source
of radiation to the nearest occupants; the maximum expected workload; the levels of occupancy in nearby
areas and the type of radiation involved (energy, primary beam, or secondary/scattered radiation, or both); and
the particular approaches used in nuclear medicine. All of these are discussed in more detail below.

5.2.1 Distance
Radiation intensity will be reduced with distance, therefore it is important to maximise the distance from the
source where possible. This concept should influence equipment layout. It is important to weigh up whether
it is more appropriate in a particular project to reduce radiation levels by maximizing distances and hence
space allocated, or by installing more structural shielding.

Realistic distances to the occupants in adjoining areas beyond the room walls must be used when performing
shielding assessments. The distance to occupants in the rooms above and below must take into account the
heights involved. The measurements should be taken as the distance from the source of radiation to the
organs of interest of the occupant nearest to the boundary in question. In radiology, the source of primary
radiation is the X‑ray tube and the main source of scatter is the patient. In nuclear medicine, the patient or
the radiopharmaceutical can be the source. The following minimum distances from the boundaries (Table 5.2
and Fig. 5.1) are recommended; however realistic measurements of the room involved are worthwhile (NCRP,
2004, AAPM, 2006).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 51


Table 5.2: Suggested minimum distances to the vital organs of an occupant in an adjoining area

Boundary Minimum distance to occupant in adjoining area

Walls 0.3 m

Ceilings 0.5 m from floor above

Floors 1.7 m from floor below


Based on NCRP, 2004.

Figure 5.1: Suggested minimum distances to the vital organs of an occupant in adjoining area

Room above
0.5m

X-ray tube
(source of primary radiation)

Patient
(source of scattered radiation)

0.3m
Patient
table

Room below

1.7m

Adapted from NCRP, 2004

5.2.2 Workload in radiology


An essential factor in a shielding calculation is realistic knowledge of the workload for the X‑ray room in
question. The BIR recommend that the workload should be based on Entrance Surface Doses (ESD) and
Dose-Area Product (DAP) values (BIR, 2000). Most modern X‑ray systems are now fitted with DAP meters,
making it relatively easy to obtain DAP values for the clinical workload in a particular X‑ray room.

For new examinations, or where no local workload data is available, published values should be consulted for
guidance. However, much of the published guidance is from UK studies and caution should be exercised as it
may not always be representative of doses in Irish hospitals. In addition, published values will not necessarily
reflect the current or new technology being installed. Local values should be used where possible.

The workload in many rooms is increasing for reasons that include increased working hours, faster patient
throughput with some digital imaging systems, and the increases in the number and complexity of procedures.
The most satisfactory workload data used for shielding design is based on a realistic audit of current practice,
projected for any envisaged increases in the future. It is better to generously provide for this at the beginning
of the project, as retrofitting additional shielding at a later stage will be expensive. Consideration should also

52 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


be given to exposures made during quality assurance (QA) testing as this may add significantly to the
workload (BIR, 2000).

Many studies which are helpful in determining workload are available, and a few are cited here. For example,
ESD values are available from NRPB reports and the European Guidelines on Quality Criteria for Diagnostic
Radiographic Images. Ranges of dental DAP and ESD values have been published and doses from CT
examinations are also available (EC, 1996b, BIR, 2000, NRPB, 2002, NRPB, 2005). Little data is available from
Irish hospitals although limited ESD values for some common projections have been published (Johnson &
Brennan, 2000). DAP values for some common examinations from UK data are reproduced below in Table
5.3 (NRPB, 2002). The DAP values published in BIR (2000) have now been superseded by these.

Table 5.3: DAP values for common X‑ray examinations (based on NRPB 2002)

Examination DAP (Gy cm2)

Mean Max.

Lumbar Spine AP 1.4 3.7

Lumbar Spine Lat 2.3 5.8

Lumbar Spine LSJ 2.4 6.7

Chest PA 0.10 0.24

Abdomen AP 2.5 8.2

Pelvis AP 2.2 7.3

An alternative approach to workload determination is used by the NCRP and is based on tube current and
“beam-on” time. It is the amount of time that the X‑ray beam is producing radiation multiplied by the
current, in units of milliampere minutes (mA.min), or mA.min per week (NCRP, 2004).

A patient may have multiple exposures during an examination and the average workload per patient is given
by Wnorm. The total weekly workload, Wtot, is calculated by multiplying Wnorm by the average number of patients
per week (N). Wnorm values were determined (for several types of X‑ray installation) from a survey of American
institutions and are reproduced in Table 5.4. For a general radiography room, the workload in the case of “all
barriers”, “chest bucky” only and “floor or other barriers” is presented as is the workload for a room
containing both a general radiographic tube and a fluoroscopy tube (R&F room) (NCRP, 2004).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 53


Table 5.4: Workload data from NCRP (based on NCRP, 2004)

Type of installation Total workload Typical number of patients (N)


per patient per 40 hr week
(Wnorm) (mA min
Average Busy
patient-1)

Radiography Room (All barriers) 2.5 120 160

Radiography Room (Chest Bucky) 0.6 120 160

Radiography Room 1.9 120 160


(Floor or other barriers)

Fluoro Tube (R&F room) 13 20 30

Radiographic Tube (R&F room) 1.5 25 40

Chest Room 0.22 200 400

Mammography Room 6.7 80 160

Cardiac Angiography 160 20 30

Peripheral Angiography 64 20 30

With CT, it is common practice to record pre and post contrast medium scans as one patient examination.
This type of examination doubles the number of scans and hence needs to be identified when compiling
workload figures. In addition caution needs to be applied to the use of displayed CT mAs values in shielding
calculations, as they may not accurately represent the scatter air kerma and can be misleading (NCRP,
2004).

The distribution of workload as a function of kVp is important, as the attenuation properties of barriers exhibit
strong kVp dependence. More detailed values of workload distribution over a wide range of diagnostic operating
potentials are also available (NCRP, 2004). Both approaches to workload determination are useful.

5.2.3 Occupancy factor


The occupancy of adjoining areas must be taken into account when assessing shielding requirements.
Realistic assumptions should be used. For example, an office will have a far greater occupancy than an
adjoining stairwell, toilet or attic.

The occupancy factor is not taken as an indication of the time during which the area is occupied by one or
more of a group of people (e.g. many patients serially occupying space in waiting room). Rather, it is taken
as the fraction of the time spent by the individual that spends the most time there. This will most likely be a
member of staff, who may or may not be a designated radiation worker. In practice the occupancy level is
the fraction of an 8-hour working day or 2000-hour working year during which the individual occupies the
area in question. Where X‑ray facilities are in 24-hour use the RPA must advise on appropriate occupancy
factors for adjacent areas. However, in general the occupancy in adjacent rooms can be based on the
assumption that no individual member of staff is likely to be in the vicinity for more than one-third of the
time that the X‑ray set is in use (BIR, 2000).

54 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Published occupancy factors, shown in Table 5.5, are intended to be indicative but provide useful guidance
where other data are not available (BIR, 2000, NCRP, 2004). There are some differences in the levels
recommended by the BIR and the NCRP, but they both follow a broadly similar approach. One exception is
the occupancy for employee lounges (NCRP)/staff rooms (BIR) which is recommended as 1/5 and 100%
respectively. The BIR suggest that the lowest occupancy factor used be 5% (BIR, 2000). An RPA should be
consulted regarding occupancy levels where additional guidance is required.

Particular care must be taken when classifying corridors as low occupancy areas. There may be another room
or office located across the corridor with a much higher occupancy and it must be ensured that such areas
are adequately protected. Likewise a low occupancy space outside a window may give a false sense of
security if there are nearby buildings with high occupancy. Adjacent offices/buildings that are not under the
same administration, or that are owned by a third party, should be assumed to have an occupancy factor of
100%, as they are subject to change without consultation or control (NCRP, 2004).

Finally, in this connection, shielding calculations must be reviewed if the use/occupancy of an adjoining area
changes. This is an issue over which there may be little control and which can inadvertently give rise to
unexpected radiation hazards. It is well to make allowances for this at the design stage as records of the
shielding calculations and specifications may not always be available or accessible in the future.

Table 5.5: Suggested occupancy factors for radiation shielding design (based on BIR, 2000 and NCRP, 2004)

Location BIR NCRP


Adjacent X‑ray room 100% 1
Reception areas 100% 1
Film reading area 100% 1
Offices, shops, living quarters, children’s indoor play areas, 100% 1
occupied space in nearby buildings
X‑ray control room 100% 1
Nurses’ station 100% 1
Staff room 100% 1/5
Patient examination and treatment rooms 50% 1/2
Wards, patient rooms 20% 1/5
Staff rest rooms - 1/5
Corridors 20% 1/5
Corridor doors - 1/8
Toilets or bathrooms 10% 1/20
Outdoor areas with seating 10% 1/20
Storage rooms 5% 1/20
Unattended vending areas 5% 1/20
Patient changing room 5% 1/20
Unattended waiting rooms 5% 1/20
Stairways 5% 1/40
Unattended car parks 5% 1/40

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 55


5.2.4 Primary radiation
A barrier is required to attenuate the primary beam to a level that complies with the dose constraint. Primary
barriers are typically required in general radiographic rooms, dedicated chest rooms and rooms where there
is a combination of radiography and fluoroscopy. For mammography, fluoroscopy, CT and DXA – the entire
primary beam is normally incident on the face of the image detector which acts as a primary beam stop.
Therefore for these types of rooms only secondary radiation needs to be considered.

The use factor (U) is the fraction of the primary beam workload that is directed toward a given barrier (NCRP,
2004). It is used in the NCRP methodology for primary radiation shielding calculations and the value will
depend on the type of installation and the barrier being assessed. Different barriers may have different use
factors. For example, the workload presented for the radiographic room (Chest Bucky) in Table 5.4 is directed
entirely at the wall behind the Bucky, and the use factor, U = 1 for this wall. In addition, this workload only
contributes secondary radiation to the other barriers in the room. However, it should be noted that a more
complex situation can arise with other configurations.

Primary beam use factors published by the NCRP are reproduced in Table 5.6. The ceiling and operator’s
control screen are generally considered to have U = 0. U is also zero for installations where only secondary
radiation needs to be considered such as image intensifier and mammography systems.

Table 5.6: Use factors from NCRP for radiographic room (based on NCRP, 2004)

Barrier Use factor (U) Workload distribution

Floor 0.89 Rad Room (floor or other barriers)

Cross-table wall 0.09 Rad Room (floor or other barriers)

Unspecified wall (other than chest 0.02 Rad Room (floor or other barriers)
bucky wall or cross-table wall)

Chest Bucky wall 1.00 Rad Room (Chest Bucky)

To calculate the shielding required in the primary barrier, the barrier transmission factor must be determined.
This is the ratio of the air kerma behind a barrier of thickness, x, to the air kerma at the same location with
no barrier. In the following sections, an overview of the BIR methodology and equations are presented.
Detailed equations for employing the NCRP methodology are available (NCRP, 2004). A comparison of both
methods is presented in Example 1 in Section 5.3.

BIR methodology for primary radiation

The BIR recommends that one of two methods is used to calculate primary shielding requirements, and the
method used will depend on the clinical situation. The film dose method is used where the X-ray beam is
entirely intercepted by the patient and the entrance surface dose method is used where this is not the case.

56 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


(a) Film dose method
This approach should be used when:

n the X‑ray beam is entirely intercepted by the patient.

n the shielding calculation is based on incident film kerma.

n the incident kerma Kinc (mGy) at the barrier is calculated using the Inverse Square Law.

2
FFD
K inc = n × K film × Bfilm × Equation 5.1
FFD + d

where n = number of films per week

Kfilm = film kerma (mGy)

Bfilm = transmission through the film and cassette

d = distance from the film to the barrier (m)

FFD = focus-film distance (m)

(b) Entrance surface dose (ESD) method


This approach, uses a minor adaptation of the BIR definitions, and should be used when:

n the X-ray beam passes outside the patient, e.g. skull or extremity radiography.

n the incident kerma Kinc (mGy) at the barrier in question is calculated from the Entrance Surface Dose (ESD)
and uses the Inverse Square Law.


FFD − d f Equation 5.2
K inc = n × ESD ×
FFD + d w

where n = number of films per week

ESD = Entrance Surface Dose per film (mGy)

FFD = focus-film distance (m)

df = entrance surface to film distance (m)

dw = distance from film to barrier (or, for practical


purposes, the point of interest in the
adjacent room/area) (m)

It should be noted that in practice, the unit used for film kerma and Entrance Surface Dose is milligray (mGy)
or microgray (μGy). As referred to in Section 5.1, mGy and mSv are taken as being equivalent for shielding
calculations. Care must be taken to ensure that the magnitude of the unit used to denote the resulting value
of Kinc is consistent with that used for the dose constraint which by convention is stated in millisieverts (mSv).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 57


The primary beam will be attenuated by components that it passes through, and this should be estimated
based on the geometry of the exposure. The three clinical radiography geometries which should be considered
are:

1) Table radiography => attenuation in the cassette plus table.

2) Lateral radiography => attenuation in cassette only.

3) Vertical bucky radiography => attenuation in cassette plus vertical bucky.

Data on the transmission of X‑rays through these components has been published by the BIR. The combined
equivalence of the cassette and table assembly is given as 0.8 mm lead or 75 mm concrete (60 – 125 kVp).
The lead equivalence of a film cassette, or cassette plus grid are given as approximately 0.2 mm lead (60 – 125
kVp). This level of attenuation is quite low and the beam may not always be fully collimated to the cassette.
Therefore the attenuation due to the cassette is often ignored for practical purposes (BIR, 2000).

5.2.5 Secondary radiation – scatter & leakage


Secondary radiation is, in practice, the most ubiquitous radiation type for which shielding is provided. It is a
combination of scattered radiation (generally from the patient) and leakage (from the tube housing). The
former is frequently the dominant component. For shielding calculations, the patient may be regarded as the
source of scattered radiation. The amount of scatter increases with the field size and the thickness of the part
of the patient irradiated. It is also dependent on the spectrum of the primary beam and the scattering angle.
The scattered radiation is generally present throughout the room and decreases with the distance from its
source.

The housing of a diagnostic X‑ray tube is lined with lead and is designed so that the leakage radiation in 1
hour is less than 1 mGy at 1 m from the focal spot, averaged over any area of 100 cm2 (IEC 2008). Although
the leakage radiation component is small, it is highly filtered and consequently is much harder and more
penetrating than the primary beam. It has been shown that for energies below 100 kVp, the contribution
from leakage radiation is negligible (BIR, 2000). However, at energies of 100 kVp and above, transmission
curves for secondary radiation rather than primary should be used as they take this into account and assume
greater penetration due to the leakage component.

The maximum scatter kerma is often a strong function of the Dose Area Product (DAP). It will vary with kVp
and the maximum value at a boundary 1 m from the patient can be calculated using the following equation
which gives the maximum scatter factor per unit DAP (BIR, 2000):

Smax = [(0.031 x kVp) + 2.5] μGy (Gy cm2)-1 Equation 5.3

58 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


The incident air kerma Kinc (μGy) for scattered radiation can then be calculated by:

S max × DAP
K inc = Equation 5.4
d2

where Smax = the maximum scatter factor at 1 m (μGy (Gy cm2)-1)

DAP = weekly dose-area-product (DAP) (Gy cm2)

d = distance from patient to the boundary (m)

5.2.6 Combination of primary and secondary radiation


There will be situations where the barrier being assessed will be exposed to both primary and secondary
radiation. In this case, it must be ensured that the sum of the primary and secondary radiation transmissions
through the barrier is less than either 0.3 or 1.0 mGy per annum (as appropriate). It should not be assumed
that the primary radiation component will always dominate.

The BIR have recommended that in such situations the annual dose constraint should be halved and shielding
calculations performed for primary and secondary radiation using this constraint value. The larger of the two
shielding requirements should be used as the final result. This approach is a conservative one, particularly
when one component differs significantly from the other (BIR, 2000).

5.2.7 Maximum transmission and specification of shielding material


Once the incident kerma is calculated using the methods detailed above, the maximum allowable transmission
(B), based on the annual dose constraint, must be determined. This is given by: (BIR, 2000)

Dc Equation 5.5
B=
K inc × T × 52

where Kinc = incident kerma on boundary per week (mGy)

Dc = annual dose constraint (mSv)

T = occupancy factor for adjoining area

As noted previously, care must be taken to ensure that the units used for Kinc and Dc are consistent.

If additional shielding is required, the maximum transmission factor, B, will be less than unity. If B is unity or
greater, then no additional shielding is required. The following equation can be used to calculate the thickness
of material, χ (millimetres), required to provide the desired transmission:

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 59


β
B −γ +
1 α
χ= ln Equation 5.6
αγ β
1+
α

where α, β and γ are the fitting parameters. Values for α, β and γ have been published for a selection of
materials at a range of diagnostic energies. Coefficients for primary transmission of lead and concrete, and
the coefficients for secondary radiation between 100 – 150 kVp are reproduced in Table 5.7 (BIR, 2000). For
calculations involving secondary radiation at energies less than 100 kVp, primary radiation data can be used
as it has been shown that the differences are negligible (BIR, 2000).

Table 5.7: Coefficients for generating primary and secondary transmission curves for lead and
concrete (based on BIR, 2000)

Material kVp α β γ

Lead 30 38.80 178 0.347

50 8.801 27.28 0.296

70 5.369 23.49 0.588

90 3.067 18.83 0.773

100 (primary) 2.500 15.28 0.756

125 (primary) 2.219 7.923 0.539

100 (secondary) 2.507 15.33 0.912

125 (secondary) 2.233 7.89 0.730

150 (secondary) 1.791 5.48 0.568

Concrete 30 0.3173 1.698 0.359

50 0.0903 0.1712 0.232

70 0.0509 0.1696 0.385

90 0.0423 0.1137 0.469

100 (primary) 0.0393 0.0857 0.427

125 (primary) 0.0352 0.0711 0.697

100 (secondary) 0.0395 0.084 0.519

125 (secondary) 0.0351 0.066 0.783

150 (secondary) 0.0324 0.078 1.566

The thickness of material can also be determined by using the limiting half value layer (HVL) for a given
material at a particular kVp. This approach will result in a conservative shielding design as the limiting HVL
model assumes a highly penetrating beam (BIR, 2000).

60 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


When the thickness of material is determined, it should be compared with the existing composition of the
boundary, if applicable, to determine what additional shielding, if any, is required. Transmission properties of
materials under various conditions are available in Appendix C.

5.2.8 Shielding calculations in nuclear medicine


The shielding requirements for a nuclear medicine facility fall into two categories - structural shielding for the
various rooms in the department and local shielding of the radionuclide sources used. Sealed and unsealed
sources must be stored in secure and adequately shielded storage facilities. In addition, devices such as lead
vials, syringe shields, shielded safes and carrier boxes must be used to reduce radiation exposure to staff,
patients and members of the public while using, transferring and administering sources in work areas.
Protecting against radiation emitted from patients who have been administered a radionuclide must be
achieved by structural shielding and department design. Shielding requirements for the scanning area, the
waiting room, patient toilets and other areas will be determined by the number of patients imaged, the
activities administered, the radiopharmaceuticals used, the time each patient remains in each part of the
facility, and the location of the facility and its environs.

The dose rate from the patient per unit activity administered is dependent on the physical and biological
half-lifes and dose rate constant of the radionuclide administered and by attenuation in the patient. An
estimate of the dose rate at 1 m from various radionuclides and the dose rate from a patient per MBq
administered are provided in Appendix D. For example, the dose rate at 1 m from a patient injected with
Tc HDP is 0.0075μSvh-1/MBq, giving a dose rate constant for the patient of 0.0075μSvm2/MBqh (IPSM,
99m

1991). The effective dose equivalent dose rate constants for positron emitters are also summarised in
Appendix D.

In shielding calculations the radiation dose at the point of interest is estimated using the initial dose rate, the
inverse square law correction for distance, the decay corrections for the reduction in activity and the exposure
time. Once the radiation dose at the point of interest is known, the shielding required is calculated using an
approach similar to that used for X‑rays, but employing the attenuation data for radionuclides from Appendix
D. For shielding calculations the decrease in the activity in the patient due to “voiding” is often ignored and
only physical decay of the radionuclide is taken into account. This will somewhat overestimate the shielding
required.

In calculating the shielding requirements for different areas in the department, allowance for the radioactive
decay of the activity administered to the patient can be treated in two components:

a. The decay in activity up to the time the “active” patient enters the area, Fu, is given by:

- 0.693t u
F u = exp

where tu = Time since administration (h)

T½ = Half life (h) for the radionuclide

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 61


b. The reduction in the dose rate from the patient during the period (t) that the patient is in the area, Rt, is
given by:

D(t)
Rt = .
D (0) × t

where D(t) = Total dose (μSv) received in time t


.
D (0) = Dose rate (μSv/h) at 1 m, at the time of administration

t = Time period (h) in the area

Assuming uptake times of 2 hours and scanning times of 30 minutes, the decay factors to use in shielding
calculations for the scanning room, for patients administered Tc, are 0.79 and 0.97 for Fu and Rt,
99m

respectively.

The total dose D(t), in μSv, at a distance d meters from a patient, during a time period t (h), is given by the
equation:

. F Equation 5.7
D(t) = D (0) × t × R t × u2
d

.
where D (0) is the product of the dose rate constant for the patient (μSvm2/MBqh) and the administered
activity A0 (MBq), Rt and Fu are the corrections for decay as previously described. No allowance has been
made for patient voiding.

To calculate the annual dose at a boundary, the calculated dose should be multiplied by the annual workload.
The maximum allowable transmission can then be calculated using the dose constraint and occupancy
factors in a similar manner to that employed in X‑ray shielding calculations.

5.2.9 Shielding calculations in PET/CT


The shielding of PET and PET/CT facilities presents special challenges because of the 511 keV annihilation
photons associated with positron decay. These emissions are much higher in energy than those typical of
radionuclides used in other diagnostic nuclear medicine procedures. As a result, considerable barrier shielding
is required in floors, ceilings and adjacent walls. Once the radiopharmaceutical is administered, the patient
becomes the radioactive source and continues to be one for the duration of their stay in the PET/CT facility.
A detailed report on PET and PET/CT shielding has been produced by the American Association of Physicists
in Medicine (AAPM, 2006). It should be noted however that the dose constraints used in that report differ
from those used in Ireland. Accordingly the dose constraints used in PET/CT shielding calculations should be
those set out in Section 2.4 of this Code.

Positron emitters

PET shielding calculations generally focus on 18F-Fluorodeoxyglucose (FDG) as it is the most commonly used
PET radiotracer, and is expected to continue to be for the foreseeable future. Because of its relatively long
half-life, compared to other commonly used positron-emitting radionuclides, one can expect that adequate

62 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


shielding for F procedures should be more than adequate for procedures where similar quantities of
18

radioactivity of shorter-lived radionuclides e.g. 11C, 13N, 15O, 82Rb or those with smaller dose rate constants
e.g. 64
Cu, Ga are administered. However, it should be noted that radionuclides that have higher energy
68

gamma emissions, in addition to annihilation radiation, might not be adequately shielded in a facility designed
for 18F (AAPM, 2006).

Radioactivity administration & uptake

The amount of activity administered for 18F FDG studies is determined by the mass of the patient, the length
of the uptake time, and the acquisition mode. Shielding calculations for a facility must therefore take account
of the maximum activity to be administered in the facility.

Factors affecting dose rates from PET/CT patients

Following administration of the radionuclide, the patient is the primary source of radiation. In determining
the radiation dose in areas around the patient, or from an unshielded source, the following points must be
considered:

Dose rate constant

When calculating the shielding requirements for an unshielded 18


F source, a dose rate constant of 0.143
μSvm /MBqh should be used. The dose rate from an unshielded 37 MBq
2 18
F point source is
5.3 μSv/h at 1 m (AAPM, 2006).

Attenuation by patient & scanner

Attenuation by patient
Since the body absorbs some of the annihilation radiation, the dose rate from the patient is reduced by a
significant factor. The AAPM recommends using a dose rate of 0.092 μSvm2/MBqh from the patient
immediately after administration. This corresponds to an effective body absorption factor of 0.36.

Attenuation by scanner
The gantry and detectors can provide shielding which may substantially reduce the dose rate at some of the
walls of the imaging room (AAPM, 2006). This reduction depends on the layout of the room, the shielding
characteristics of the scanner and the type of scanning procedures. Detailed knowledge of these is required
to accurately estimate the dose reduction that can be achieved. The AAPM report estimates an average dose
reduction of 20% which is partially offset by the exposure during the time the patient is being brought into
the room and positioned on the table. They suggest a figure of 15% overall reduction as being more realistic.
The most conservative approach to shielding requirements will ignore this potential dose reduction.

Physical decay

Decay during uptake or imaging


Because PET radionuclides have short half-lives, the total radiation dose received over a time period t, D(t), is
.
less than the product of the initial dose rate and time [D (0) x t]. The reduction factor, Rt is calculated as

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 63



D(t)
Rt = . Equation 5.8
D (0) × t

T½ − 0.693t
= 1.443 × × 1 − exp
t T½

where D(t) = Total dose (μSv) over a time t at 1 m from the patient
.
D (0) = Dose rate (μSv/h) at 1 m at the time of administration,
given by the product of the dose rate constant for the patient
(0.092 μSvm2/MBqh for 18F) and the administered activity A0 (MBq)

t = Time (min) of interest

T½ = Half life (min) of the radionuclide

For 18F, this corresponds to Rt factors of 0.91, 0.83, and 0.76 for t = 30, 60, and 90 min, respectively.

Decay before Imaging


Because of the decay since the administration of the radionuclide (uptake phase), the activity in the patient
at the commencement of imaging is decreased by

- 0.693t u
F u = exp Equation 5.9

where tu is the uptake time (min) and T½ is the half life (min)

Physiological decay

In most cases the patient will void prior to imaging, removing approximately 15% of the administered activity
and thereby decreasing the dose rate by 0.85.

Calculation of exposure at a boundary


Equation 5.7 may be used for the calculation of total exposure at a boundary, a distance d metres, from the
patient.

Uptake room
The total dose (μSv), at a distance d (m), from a patient during the uptake time, tu (min), will be given by

. R
D(tu ) = D (0) × t u × tu Equation 5.10
d2

64 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


.
where D (0) is the product of the dose rate constant for the patient (0.092 μSvm2/MBqh for 18
F) and the
administered activity A0 (MBq) and RtU is the reduction factor for the uptake time.

Imaging room
To calculate the dose from a patient during imaging, the decay during the uptake phase must be taken into
account. In addition the reduction factor of 0.85 as a result of patient voiding should also be taken into
account. The total dose (μSv) at a distance d (m) from the patient is given by

. F
D(t i ) = D (0) × t i × R ti × 0.85 × u2 Equation 5.11
d

.
where D (0) is the product of the dose rate constant for the patient (0.092 μSv m2/MBqh) for 18F and the
administered activity A0 (MBq), Rti is the reduction factor for the imaging time ti and Fu is the decay in the
radionuclide activity since administration.

To calculate the annual dose at a boundary, the calculated dose should be multiplied by the annual workload.
The maximum allowable transmission can then be calculated using the dose constraint and occupancy
factors in a similar manner to that employed in X‑ray.

Shielding factors
A variety of attenuation coefficients has been used to estimate transmission requirements for PET facilities.
In some cases narrow-beam, good geometry attenuation coefficients for lead and concrete have been used.
However, calculations based on these values will not provide sufficient shielding since they neglect scatter
buildup factors. The AAPM recommends using values of broad beam transmission factors for lead, concrete,
and iron that are based on consistent Monte Carlo calculations. Plots of the broad beam transmission at 511
keV are given in Appendix D for lead and concrete. The transmission factors for 18F through lead and concrete
are also given.

5.3 Examples of shielding calculations


Examples of shielding calculations for radiology, nuclear medicine and PET facilities are presented in Sections
5.3.1 and 5.3.2. The aim of the radiology examples is to show how the BIR and NCRP methodologies may be
applied in particular cases using the dose constraints in Table 2.1 and other local data. In practice it may be
prudent in marginal cases to calculate the shielding requirements using both methodologies. The examples are
provided for illustrative purposes only and are not intended to substitute for the RPA’s assessment.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 65


5.3.1 Radiology shielding calculation examples
Example 1: General radiography room ceiling

A general radiographic room has a ceiling height of 3 m. The distance from the patient table to the ceiling
is 2 m. There is an office directly above the room and it is assumed that the distance from the floor above to
the organs of interest of the nearest occupant is 0.5 m (Fig. 5.1). The weekly workload for the room has been
obtained from the Radiology Information System (RIS) and found to be 1000 Gy cm2 for 300 patients, with
average X‑ray beam energy of 100 kVp.

What shielding is required in the ceiling to protect office workers in the room above?

For the ceiling, only scattered radiation needs to be considered. The occupancy above the room is assumed
to be 100%. The shielding calculation is shown below, using the BIR and NCRP methodologies.

a) BIR method

The annual dose constraint, Dc = 0.3 mSv

Occupancy, T, in office above = 100%

Distance, d, from patient on table to occupant in room above = 2.5 m

Average weekly DAP = 1000 Gy cm2

Scatter factor at 1 m, Smax = [(0.031 x kVp) + 2.5] μGy (Gy cm2)-1 (Equation 5.3)

Smax = 5.6 μGy (Gy cm2)-1

The incident kerma, Kinc


S max × DAP (Equation 5.4)
K inc =
d2
Unattenuated Kinc at 2.5m = 896.0 μGy = 0.896 mGy ≡ 0.896 mSv per week

Dc 0.3 mSv
Max. transmission factor, B = = (Equation
(to meet the dose constraint) K inc × T × 52 0.896 mSv × 1 × 525.5)

D 0.3 mSv
= B c =
K inc × T × 52 0.896 mSv × 1 × 52

B = 0.0064

Using equation 5.6 and the coefficients for secondary radiation at 100 kV for lead and concrete (Table
5.7), a ceiling providing an attenuation equivalent to 1.2 mm lead or 80 mm concrete will provide the
required shielding.

66 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


b) NCRP method

The air kerma from unshielded secondary radiation, Ksec(0), at a distance dsec for N patients is given by:

K 1sec N
K sec (0) = 2
dsec

where K1sec = the total unshielded secondary air kerma (mGy) per patient
for leakage plus scatter radiations at 1 m. The values for
various workload distributions, published by the NCRP
(2004), are given in Table 5.4

N = number of patients per week

dsec = distance from source (m)

The ceiling in this case would be described as radiography room (floor or other barriers). For this
workload distribution, the total unshielded secondary air kerma per patient, K1sec at 1 m is given as 2.3
x 10-2 mGy. (NCRP, 2004)

At a distance of 2.5 m, this gives:

Ksec(0) = (2.3 x 10-2 mGy) x 300 patients per week

(2.5)2

Ksec(0) = 1.104 mGy per week

The level of shielding required to meet the weekly design goal (modified by occupancy) can then be
determined as follows:
0.3 mSv
The weekly design goal, P = = 0.006 mGy per week
52

Occupancy factor, T = 1

Design goal modified by occupancy, (P/T) = 0.006 mGy per week

The secondary barrier transmission required to reduce the air kerma to a value less than (P/T) is
therefore:
0.006 mGy per week
Bsec (x barrier ) =
1.104 mGy per week

B sec ( x barrier ) = 5.4 ×10−3

Using the graphs from the NCRP to get barrier thickness, xbarrier, gives a lead equivalence of approx. 1.4
mm for the ceiling or 110 mm concrete, which is similar to but not identical with the conclusion from
the BIR method.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 67


Example 2: Dedicated chest room (BIR method)

There is a wall behind the erect bucky in the chest room with a lead equivalence of 2.24 mm. Behind this
wall is a reception desk. The distance from the wall to the receptionist (nearest occupant) is taken to be
0.3 m. The occupancy of the reception area is assumed to be 100%. The weekly workload for the chest
room is 500 exposures at 120 kVp.

What additional shielding is required for this wall?

It is assumed that the patient and bucky assembly will not attenuate all of the primary radiation. In this case,
the ESD method (Section 5.2.4) is used and attenuation in the bucky is neglected.

The annual dose constraint, Dc = 0.3 mSv

Occupancy, T, in adjoining area = 100%

Focus to film distance, FFD = 1.8 m

Entrance surface to film distance, df = 0.3 m

Film to point of interest, dw = 0.8 m (0.5 m to wall plus 0.3 m from wall to
occupant)

ESD per chest film = 0.1 mGy

Number of films per week, n = 500


2
FFD − df
The incident kerma, Kinc = n × ESD × (Equation 5.2)
FFD + d w

Kinc = 16.64 mGy per week ≡ 16.64 mSv per week

Dc 0.3 mSv
Max. transmission, B = =
K inc × T × 52 16.64 mSv × 1 × 52

B = 0.000347

Using the equation for the transmission of lead identifies the shielding requirement as 2.36 mm lead
(equation 5.6, see also Appendix C, Figs. C1 – C4). The current composition of the wall has a lead
equivalence of Code 5, (2.24 mm). Therefore an additional “beam blocker” behind the Bucky of 1 mm
or 2 mm lead equivalence will provide the additional shielding necessary.

68 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Example 3: X‑ray room window (BIR method)

The general radiographic room is located on the first floor. There is a window in the external wall, which is
at a height much greater than 2 m from the outside ground. The distance from the patient table to the
window is 2 m. An occupant works at the window of an office across the courtyard at a distance of 8 m from
the window of the X-ray room.

The weekly workload for the room has been obtained from the Radiology Information System (RIS) and
found to be 1000 Gy cm2 for 300 examinations, with an average X‑ray beam energy of 100 kVp.

What shielding is required for this window?

There is no vertical bucky in the room and lateral exposures will not be directed towards the window in this
instance, so only scattered radiation needs to be considered.

The annual dose constraint, Dc = 0.3 mSv

Occupancy in office across courtyard, T = 100%

Distance from patient on table to = 10 m


occupant in the office, d

Average weekly DAP = 1000 Gy cm2

Scatter factor at 1 m, Smax = [(0.031 x kVp) + 2.5] μGy (Gy cm2)-1 (Equation 5.3)

= 5.6 μGy (Gy cm2)-1

S max × DAP
The incident kerma, inc =
Kinc (Equation 5.4)
d2

5.6 × 1000
K inc = = 56 μGy = 0.056 mGy ≡ 0.056 mSv
102

Dc 0.3 mSv
Max. transmission, B = = = 0.1030
K inc × T × 52 0.056 mSv × 1 × 52

From equation 5.6 for the transmission through lead and concrete, 0.3 mm lead or 26 mm concrete is
needed to shield the window (see also Appendix C) (neglecting any attenuation in the glass
window).

Window shielding is therefore required in this room even though the window is located at a height of
greater than 2 m from the outside ground. Shielding may be provided as outlined in Section 6.3.4.
Should there be a requirement to direct lateral exposures towards the window then the shielding
requirement will be increased.

If there are two adjacent X‑ray rooms with external windows facing into the courtyard then the
combined effect of both rooms on the office will have to be considered.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 69


Example 4: Dental X‑ray room (BIR method)

An intra-oral dental X‑ray facility may require shielding from both primary and secondary radiation. The
primary beam should be intercepted by the patient, resulting in a transmission no greater than 2 μGy per film
(BIR, 2000). In this facility the distance from the wall to the nearest occupant in the adjoining surgery is 0.3
m, and the distance from the patient’s head/X‑ray tube head to the wall is 0.7 m. The weekly workload for
the X‑ray room is 100 intra-oral exposures.

Assuming 100% occupancy in the adjoining surgery what shielding is required in the common partition
wall?

BIR advise that for intra-oral exposures the weighted average of primary plus scattered radiation dose at 1 m
is 1 μGy per film (BIR, 2000).

The annual dose constraint, Dc = 0.3 mSv

Occupancy, T, in adjoining surgery = 100%

Distance, d, from patient to occupant = 1.0 m

Average scatter dose per film at 1 m = 1 μGy

Weekly scatter based on 100 films = 100 μGy at 1 m

The incident kerma, Kinc = 100 μGy/week

= 0.1 mGy/week ≡ 0.1 mSv/week

Dc 0.3 mSv
Max. transmission, B = =
K inc × T × 52 0.1 mSv × 1 × 52

= 0.0577

From equation 5.6 for the transmission through lead, 0.2 mm lead will provide the shielding needed
at 70 kVp (see also Appendix C). In practice, Code 3 (1.32 mm) lead would provide adequate protection
and allow for increases in workload.

70 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


5.3.2 Nuclear medicine shielding calculation examples
Example 5: Shielding required for gamma camera room

A gamma camera room is adjacent to the reception area. 60 patients per week are scanned using a 99m
Tc
bone scanning agent with an administered activity of 600 MBq. Patients are scanned two hours post
administration and scanning time per patient is 30 minutes. The distance from the patient to a person in the
adjoining office is 3 m.

What shielding is required for the wall between the camera room and the reception?

The dose from a single patient at the point of interest is given by equation 5.7:
. F
D(t) = D (0) × t × R t × u2
d
.
where D(0) is the product of the dose rate constant for the patient, having been administered 99mTc and
the activity administered (MBq), t is the scanning time, and Fu and Rt are the decay factor prior to
scanning and the dose reduction factor during scanning respectively.

For a workload of Nw patients per week, the annual dose at a distance d from the patient is:
. F
D(t a ) = N w × 52× D (0) × t × R t × u2
d

Values for the dose rate constant for the patient administered 99mTc , Rt and Fu are given in Section 5.2.8
as 0.0075 μSv m2/MBqh, 0.97 and 0.79.

Thus:

D(ta) = 60 x 52 x 0.0075 μSv m2/MBqh x 600 MBq x 0.5 h x 0.97 x


0.79
9
= 598 μSv = 0.598 mSv

For an occupancy factor of 1.0, and a dose constraint of 0.3 mSv, the transmission is

0.3 mSv
B= = 0.50
0.598 mSv × 1

To reduce the transmission to 50%, one half value layer of shielding is required. From Appendix D,
0.3 mm of lead will provide adequate shielding.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 71


Example 6: Shielding required for a PET uptake room

In a new building, attention to the layout and use of the area can be a significant factor in reducing the need
for shielding. Grouping patient areas and distancing them from staff areas is generally recommended. In
situations where a scanner is being installed into an existing building, this is not always possible. The following
example illustrates the high level of shielding that will be required if patient areas are located immediately
adjacent to staff areas which have a high level of occupancy.

A PET uptake room is adjacent to the reception area which is staffed by a single staff member. 50 patients
per week are scanned using 18F FDG with an administered activity of 555 MBq/scan. The uptake time per
patient is 1 hour and the distance from the patient to a person in the adjoining office is 4 m.

What shielding is required for the wall between the uptake room and the reception area?

The AAPM task group report 18 (AAPM, 2006) recommends a value of 0.092 μSvm2/MBqh for the
dose rate from a patient administered 18F FDG. This takes patient attenuation into account. The dose
from the patient should be corrected, to take account of the fact that the radionuclide is decaying
during uptake.

The decay factor, Rtu, for 1 hour is 0.83 (Section 5.2.9).

The total dose at a point d metres from the patient is given by equation 5.10:

. R
D(tu ) = D (0) × t u × tu
d2
R tu
= 0.092 μSvm 2 /MBqh × A o (MBq) × t u (h) ×
d 2 (m 2 )

= 0.092× 555×1× 0.83 = 2.65 μSv


16
For 50 patients per week, the total dose, at 4 m, over the course of a year is

= 2.65 μSv x 50 x 52 = 6890 μSv = 6.89 mSv

The transmission factor, B, required to protect non radiation workers (dose constraint, 0.3 mSv) when
the reception area has an occupancy of 100% is:

0.3 mSv
B= = 0.044
6.89 mSv ×1
Using Table D.4 and Figures D.1 and D.2 in Appendix D, 2.2 cm lead or 25 cm concrete is required to
provide the necessary shielding.

72 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Example 7: Shielding required for PET scanning room

A PET facility scans 50 patients per week using 18F FDG. The administered activity per scan is 555 MBq. The
uptake time is 1 hour and the average imaging time is 30 minutes.

What shielding is required for the wall of the control room which is 3 m from the scanning table?

Because of the delay between administration and imaging, the activity in the patient will decrease by
- 0.693t u
Fu = exp
T1 2

where tu is the uptake time(min) and T1/2 the half-life (min). For tu of 60 mins,

- 0.693 × 60
Fu = exp = 0.69
110

In most cases, the patient will void prior to imaging, thereby removing about 15% of the administered
activity and decreasing the dose rate by a factor of 0.85. Because the 18F FDG will decay during imaging,
a further dose reduction factor Rti is applied
D(t) T½ − 0.693t
R ti = . = 1.443 × × 1 − exp Equation 5.8
D (0) × t t T½

For a scanning time t of 30 mins, Rti is equal to 0.91.

The dose D(ti) per imaging time at a distance 3 m from the patient is given by Equation 5.11

Fu
D(ti) = 0.092 μSvm2 /MBqh × A o (MBq) × t i (h) × R ti × 0.85 ×
d (m) 2
2

= 0.092× 555× 0.5 × 0.91× 0.85× 0.69


9
= 1.514 μSv

Scanning 50 patients per week, the annual dose at 3 m from the Table, D, is

D(ta) = 1.514 μSv x 50 x 52 = 3936 μSv = 3.94 mSv

If the shielding characteristics of the scanner are accurately known, then a dose reduction factor at
some of the walls may be incorporated into the calculation (see Section 5.2.9). A more conservative
approach ignores the potential dose reduction afforded by the scanner.

It is assumed that only designated radiation workers will occupy the control room (dose constraint of
1 mSv) and that it has an occupancy factor of 1. The required transmission factor will be given by:

1 mSv
B= = 0.25
3.936 mSv × 1
Using Table D.4 and Figures D.1 and D.2 from Appendix D, 10 mm lead or 13.3 cm concrete is required
to provide the necessary shielding.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 73


6. Some practical considerations

6.1 Building materials, methods and verification


The range of materials which may be used to provide radiation shielding include:

n Lead sheet and lead fabricated products (lead plywood, lead plasterboard).

n Concrete, concrete blocks and concrete products.

n Barium plaster.

n Various types of brick.

n Gypsum wallboard.

n Lead glass.

n Lead acrylic.

n Other materials (e.g. steel and wood for low energy/mammography trailers).

The choice of material depends on several factors, including the level of shielding to be achieved, the cost,
and the practicalities of installation. It should be noted that design and construction professionals often refer
to the dimensions of materials in terms of ‘nominal’ dimensions. Thus, for example, in the US a ‘four inch’
brick is actually 35⁄8 inches (9.2 cm) so the RPA should request the actual dimensions of the building materials
specified or used if he/she is not already familiar with them (NCRP, 2004).

6.1.1 Lead sheet and lead fabricated products


Lead has both high atomic number and high density (11,350 kg/m3) and hence is a very effective shielding
material. The transmission properties of X‑rays through lead are given in Appendix C. Although lead may be
purchased in sheets/rolls, it is malleable and is usually bonded to plywood or plasterboard to provide a stable
panel for installation. Lead fabricated products are also available including lead lined door sets, protective
screens and blinds.

Lead sheet products are available in a standard range of thicknesses, with code numbers as set out in Table 6.1:

Table 6.1: Standard lead sheet codes and equivalent thickness in millimetres (BSI, 2006)

Lead code Lead thickness (mm)

Code 3 1.32

Code 4 1.80

Code 5 2.24

Code 6 2.65

Code 7 3.15

Code 8 3.55

74 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Traditionally, an RPA may specify the lead requirements for an installation, rounded up to the nearest 0.5
mm. In practice, as lead is not available in increments of 0.5 mm, it is preferable to specify the code required,
to avoid errors arising from inappropriate rounding up or down later. Lead sheet is manufactured to BS EN
12588 standard and has a ± 5% tolerance on the thickness (BIR, 2000). Lead products compliant with the
above standard should be utilised.

6.1.2 Concrete and concrete blocks


High-density solid concrete (2350 kg/m3) is a commonly used shielding material. It may take the form of
poured concrete or solid concrete blocks. Its transmission properties at a density of 2350 kg/m3 are given in
Appendix C. The lead equivalence of concrete and other shielding materials is also given in Appendix C for
a range of kVp (BIR, 2000). Solid concrete blocks may have internal voids, so care needs to be taken in their
use. Lightweight concrete blocks are also available (2200 kg/m3) and if used the thickness of concrete will
have to be scaled accordingly. Likewise using concrete of this density, with the transmission curves in
Appendix C, will require an appropriate adjustment in the shielding thickness read from the curves. Concrete
blocks may be used in combination with other materials such as barium plaster. In practice, approximately
69 mm of high density solid concrete is equivalent to 1 mm lead at 70 kVp; similarly at 70-125 kVp 150 mm
concrete is approximately equal to 2 mm lead (WHO, 1975).

Hollow concrete blocks are not generally suitable for shielding except with low energy or low dose applications
(mammography, dental radiology, DXA scanning) or when used in combination with other shielding materials.
They should be used with caution, as attenuation coefficients can be difficult to obtain.

6.1.3 Barium plaster


Barium plaster is a gypsum plaster incorporating barytes aggregates, which may be used in combination with
concrete blocks. Its absorption properties with respect to X‑rays are greatly enhanced by the presence of a K
absorption edge in barium. A thickness of up to 25 mm can be applied to a surface (BIR, 2000). Applying
barium plaster so that it will be well finished to the thickness required, and crack free, requires a plasterer
with the appropriate skill. It must be applied in several coats and takes a considerable period to dry.

The composition and the attenuation properties of barium plaster manufactured by British Gypsum (Thistle
X‑ray) have been altered since the publication of BIR (2000). The net effect has been to reduce its lead
equivalence by between 15% and 30%. Revised values have been published by Williams (2005).

There are no published coefficients for secondary transmission through barium plaster. Coefficients for
primary transmission may be used for energies below 100 kVp (BIR 2000). However above this, the attenuation
properties are unknown. Barium plaster is therefore unsatisfactory for shielding high kVp facilities such as CT
and high kVp chest units, and alternatives should be considered until more complete data are available.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 75


6.1.4 Brick
There are many types of brick, with a range of physical properties and densities that may be as low as 1600
kg/m3. If they are to be used it is important to assess their shielding properties thoroughly. It is also important
to be aware that bricks may contain cavities, which should be filled with mortar of at least the same density
if they are to be used. Bricks often provide support for other shielding materials including lead
plasterboard.

6.1.5 Gypsum wallboard


Gypsum wallboard (plasterboard) is a commonly used building product, which is attached to wood or metal
framing using nails or screws. It provides relatively little attenuation at higher beam energies but is effective
at the lower energies used in mammography (BIR, 2000). Gypsum wallboard typically contains voids and
non-uniform areas therefore a greater thickness should be used than the minimum suggested by
calculation.

6.1.6 Lead glass


Lead glass has a high lead and barium content and is commonly used for operator’s screens, ceiling suspended
protective devices and viewing windows in X‑ray rooms. It is also used in radiopharmacies and laboratories.
It may be purchased in a range of lead equivalent thicknesses. It is softer than normal glass and can be easily
damaged. It is also susceptible to staining and must be kept dry.

6.1.7 Lead acrylic


Lead acrylic is a transparent protective material, which is manufactured in a range of lead equivalent
thicknesses. It is softer than lead glass and is frequently used for screens or viewing windows in a low kVp
environment (mammography).

6.2 Materials for fitting and furnishing nuclear medicine departments


The selection of finishes and fittings in nuclear medicine should minimise the risk of radioactive contamination,
prevent its spread and facilitate decontamination.

Surfaces within controlled and supervised areas should be smooth, non-absorbent, non porous and easily
cleaned and decontaminated. Non absorbent finishes such as conventional sheet vinyl flooring and skirting
together with walls painted using gloss paint or similar easy to clean wall finishes are appropriate. To minimise
residual contamination arising from spills particular care should be taken to avoid gaps in finishes and fixtures
in which radioactive material could become lodged. All horizontal surfaces including the floor covering must
be continuously sealed and impervious to spillage, and coved against the walls to provide in-situ skirting. The
choice of surface materials should take account of the type of solvents and cleaning materials likely to be
used. Caution should be applied in the selection of surfaces that are reported to be cleanable. This can mean
that they are capable of withstanding common cleaning agents rather than their suitability for decontamination.

76 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Bench surfaces in areas where unsealed radionuclides or body fluids are handled should be coved against the
walls and lipped at the edges to prevent radioactive substances becoming lodged in any cracks between the
wall and bench or spilling onto the floor. It should be noted that the use of coving between walls and bench
tops could mean that hatches at bench level may not be flush with the bench thus necessitating items, which
are sometimes heavy or fragile, to be lifted through the hatch. Caution should be applied to the selection of
laminate finishes which although satisfactory in many respects can be susceptible to damage and may not
provide an optimal long-term solution. Durable materials should be used. Floors and benches must be strong
enough to support the weight of shielding materials.

6.3 Shielding in radiology department


6.3.1 Walls
For general X‑ray rooms, the lead equivalence required for a room of dimensions 6 m x 4 m x 3 m is typically
of the order of 2 mm at 150 kV (WHO, 1975) although a lead equivalence of 3-4 mm or more may be required
for angiography suites and multi-slice CT installations (NHS, 2001). This level of shielding is based on the assumption
that the radiation at the boundaries will be mainly scattered radiation. Additional shielding for the primary
beam is needed in situations where it is frequently directed towards a wall. For example, in the case of chest
radiography, a primary beam absorber (typically an additional 2 mm lead equivalent) is required behind the
chest stand/vertical Bucky (Photo 6.1). In practice the level of shielding required must be determined by the
RPA before construction. The walls of an imaging facility may be constructed from high density solid concrete,
concrete blocks, bricks or other materials provided due account is taken of the issues raised in Section 6.1.

As an alternative to using concrete, wall shielding may be provided using panels of lead plasterboard or lead
plywood. The internal walls of many modern buildings are composed of plasterboard attached to both sides
of metal or wooden framing. Lead plywood or plasterboard may be used on one side of the internal framing
to achieve the required shielding. Ideally it should be used on the side which will require the least perforation
(Appendix E). Lead plasterboard is less robust than lead plywood during handling; however it leaves a smooth
finish for decorating.

The shielding must not be compromised at the joints between panels and where nails, screws and other fixings
are used. Lead lined battens should be used at the joints. These are typically 50 mm wide and provide a secure
base for fixing the panels (BIR, 2000). Their lead thickness should be the same as that in the panels and they
should have a sufficient overlap with each panel to provide protection at the joint and for the nails and screws
(Appendix E). Steel nails and screws however generally attenuate radiation equally or more effectively than the
lead displaced by the nails, therefore steel nails or screws used to secure lead barriers may not need to be covered
with lead discs or supplementary lead. However, where the edges of two lead sheets meet, continuity must be
ensured at the joints with lead battens (NCRP, 2004, WHO, 1974).

Additional shielded battens may be provided in areas where items have to be fixed to the wall. Where service
perforations are required in walls, i.e. electrical socket outlets, light switches, service outlets, ventilation
grilles, installation of sinks, cabinets, light boxes, etc., additional lead shielding is required in place of the
shielding that is displaced. All joints, perforations, ducts, service outlets, etc. must be shielded as outlined in
Section 6.5.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 77


Walls are generally shielded to full height from the floor to the underside of the ceiling slab above (not to the
false ceiling), unless the protection in the ceiling extends well beyond the X‑ray room. This is to protect not
only the room directly above but also the adjoining rooms above, which would otherwise be obliquely
irradiated. The join between the wall and the ceiling must be adequately shielded (Appendix E). If the X‑ray
room is adjacent to a dark room or a storage facility for CR plates, shielding to full height is required to
protect films/CR plates located on high-level shelving (NCRP, 2004).

Photo 6.1: Image of a primary beam absorber behind a vertical bucky

(Photograph courtesy of St. James’s Hospital, Dublin)

Some situations may arise where wall shielding to full height is not required. An example of this may be a
single storey building with no two storey buildings in the vicinity. Other examples include low exposure
applications (e.g. mammography or DXA). In these instances, the height of the wall shielding required must
be determined by the RPA and it may be sufficient to shield to a height of 2 m from the outside ground.
However, care must be taken when walls are not shielded to full height as situations may change and records
of the shielding specifications may not always be available or accessible in the future. Therefore walls should
be permanently labelled with the lead equivalence thickness.

Occasionally where lead lined panelling is used, the wall shielding is specified and installed to a height of 2 m,
where the panelling may extend to 3 m. In such cases it is very important to ensure that the leaded part of
the panelling is installed the correct way up as the other third of the panel is unshielded (NCRP 2004).
Reftrofitting at a later stage can be very expensive and troublesome.

Gypsum plaster or 100 mm medium density concrete blockwork may be sufficient for shielding mammography
rooms. Additional advice on the engineering of walls for diagnostic facilities is available in NHS (2001).

6.3.2 Floors and ceilings


Imaging facilities are frequently located on the ground floor of hospitals. Floor shielding is not necessary if
there are no occupied basements or under floor service corridors, provided that the shielded wall extends the

78 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


full way to the ground and does not end at a false floor level. Walls extending beneath false floors shall be
appropriately shielded to protect the adjacent rooms. If there is occupancy or services beneath the X‑ray
facility or if it is located on an upper level, floor shielding will normally be required. In addition, it is likely that
the floor will be required to provide protection against the primary beam.

Poured concrete is commonly used in floor or ceiling slabs. A thickness of 150 mm is needed for load bearing
and this will provide sufficient protection for many ceilings and floors provided that it is solid throughout
(Section 6.1). Waffle type slabs are widely used for floors and ceilings in buildings as illustrated in Photo 6.2.
They typically have a maximum thickness of 150 mm that reduces to 75 mm at the thinnest part. Thus when
waffle type construction is used in the floor or ceiling of an X‑ray room, additional shielding is generally
necessary. This may be provided by lead plywood to the top or underside. The additional shielding must
provide sufficient overlap with the waffle slab and perforations made during fixing must be protected
(Section 6.5).

Lead panelling may be used in ceilings and, less commonly, on floors; it may be used on the underside of the
ceiling or on the floor of the room above. Care must be taken to avoid damage or perforations by heavy loads
or rough handling. Screed is a building product commonly used in ceilings of buildings, in addition to other
materials. It is not suitable for shielding X‑ray room ceilings due to its low density and inconsistencies in its
density. Thus if screed is present in a ceiling, its shielding properties are usually ignored in shielding calculations
and additional shielding may therefore be required.

The RPA must take account of the shielding required for areas adjacent to rooms where sources of ionising
radiation exist, including where maintenance/service staff may require access e.g. interstitial space above
ceilings or a plant room on the roof. In the case of X-ray rooms located on the top of a building where other
higher level buildings are in the vicinity, the possible need for additional shielding must be taken into
account.

Photo 6.2: Waffle type ceiling

(Photograph courtesy of St James’s Hospital, Dublin)

Finally, conventional floor and ceiling construction generally provides adequate protection in mammography.
Additional advice on the engineering of floors and ceilings for diagnostic facilities is available in NHS (2001).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 79


6.3.3 Doors
As illustrated in Chapter 3, there may be several doors leading to an X‑ray room including the patient door,
the staff door, and doors to changing cubicles or possibly to a patient toilet. The room should be designed
so that the uninterrupted X‑ray beam will not normally be directed towards doors, windows, or the operator’s
console. Even with this provision the door and doorframe must be shielded against scatter. The shielding
must be uninterrupted between double doors, between the door and frame, and between the doorframe
and the adjoining wall. Generally the minimum overlap is 1.5 cm (Appendix E). In the case of a concrete or
brick wall, the shielding should overlap the doorframe and wall by a distance at least equivalent to the
thickness of the concrete or brick in the wall (WHO, 1974). Sliding doors are attractive for saving space but
can become difficult and tiring to move, which results in their not being closed properly. Patient doors should
be wide enough to allow beds and trolleys to pass through. They should open into the controlled area to
provide protection should a person enter the room inadvertently (NHS, 2001).

Doors should be of solid construction with the lead bonded on both sides by wood or a suitable alternate
protective material (Photo 6.3(a)). The shielding must run the entire length and width of the door down to a
few mm from the floor, and continue on the underside (Appendix E). Doors may include lead glass windows.
The shielding in the window, window frame and door must be effectively uninterrupted and sufficiently
overlapped as indicated in Appendix E. Doors in rooms such as shielded operating theatres may contain
ventilation panels. These must also be appropriately protected. Doors and windows should be marked with
their lead equivalent thicknesses.

Hinges, handles and keyholes should not compromise the shielding and should be protected as outlined in
Section 6.5 and Appendix E. For general rooms, the lead equivalence of the door is typically 2 mm at 150 kV
although doors of 3-4 mm lead equivalence at 150 kV or more may be required for angiography suites and
multi-slice CT installations. It is essential that door hinges and sliding tracks are suitable for the weight
involved.

Photo 6.3(a) Lead doors Photo 6.3(b) Radiation warning lights and signs

(Photographs courtesy of St James’s Hospital, Dublin)

Access through doors must be controlled by the use of appropriate lights and signs, unless the entrance is
locked during exposures (as may be the case with doors leading to/from changing cubicles or toilets).
Warning lights should preferably be located beside the door at eye level (MDGN, 2002). They should be two

80 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


stage devices, with a yellow ‘Controlled Area’ warning light illuminating when power is supplied to the unit
and a red ‘Do Not Enter’ warning illuminating on preparing the X‑ray tube for an exposure (Appendix F).
Rooms using a single warning light must also have a sign indicating what action is to be taken when the light
is illuminated. Appropriate radiation warning signage should be put in place on each entrance door including
doors leading from changing cubicles and toilets, stating that the area is controlled (Photo 6.3(b), Appendix
F). The radiation trefoil symbol should be illustrated on the signage. Multilingual pictorial signage, advising
female patients to bring a pregnancy or a suspected pregnancy to the attention of the radiographer before
being X‑rayed, should be positioned in all changing cubicles. Additional information on signage is available
in the UK Medical and Dental Guidance Notes (MDGN, 2002).

Door interlocks, which interrupt X‑ray production, are not desirable since they may disrupt patient procedures
and this can be both dangerous and result in unnecessary repeat examinations.

Dental and DXA rooms may be designed with only one door through which access can be controlled by the
operator when the equipment is in use. While it is desirable to use signage in these circumstances, warning
lights are not essential. Solid wooden doors may be sufficient in mammography rooms, depending on their
location and configuration of the patient and equipment (see Section 3.3.3). Over specifying the shielding in
doors will be unwelcome particularly by staff in screening centres or on trailers. Relatively light lead lined
doors should be used when possible.

Some facilities are designed so that the staff entrance has no door but the doorway is protected by the shielded
operators screen. If such a design is to be considered, it must be approved by the RPA. Care must be taken
to ensure that the dimensions of the protective operator’s screen sufficiently exceed the dimensions of the
staff entrance. In particular, the height of the operator’s screen must exceed the height of the staff entrance.

6.3.4 Windows
Unshielded windows at a height of greater than 2 m from the outside ground were previously considered to
be acceptable. However this is often no longer the case, given the high density of modern developments,
the increased workloads possible with new technology and the present dose constraints. The issue of
shielding of X‑ray room windows must be referred to the RPA as the majority of these windows may require
shielding. For general rooms, the lead equivalence of the window required may be 2 mm at 150 kV depending
on the workload, the occupancy outside, and the distance to the nearest occupied area, although windows
of 3‑4 mm lead equivalence at 150 kV or more may be required for multi-slice CT and angiographic
installations. In all cases the actual amount of shielding required should be based on the RPA’s advice.

If windows are required in X‑ray rooms, they may be shielded by lead glass or lead acrylic. These should be
provided in the form of double-glazing, with plate glass on the outside as lead glass and lead acrylic may be
easily damaged and lead glass must be kept dry. Window frames must also be shielded with sufficient
overlap provided between the window and window frame and between the window frame and wall.
Windows should be marked with the lead equivalent thickness. Alternatively, windows may be shielded by
lead blinds or shutters (photo 6.4). A range of lead blinds is available including electronically operated vertical
blinds. The blinds should also be marked with the lead equivalent thickness. The primary beam should not
be routinely directed towards a window.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 81


Photo 6.4 Lead blinds protecting windows

(Photograph courtesy of Connolly Hospital, Blanchardstown)

6.3.5 Staff areas in X‑ray room


A protective screen, or shielded console area, must be provided for staff at the control panel in an X‑ray room.
Protective screens are typically custom designed and the location, size and shape will involve collaboration
between the equipment manufacturer, the user and the RPA. The final design should be approved by the RPA
before installation. The screen should ideally be located in a position adjoining the staff entrance and should
be angulated so that that primary radiation and first scatter cannot enter directly the area behind it (see
Chapter 3). In addition, there should not be an unprotected direct line of sight from the patient or X‑ray tube
to the operator behind the screen or to a loaded cassette or CR plate inside the control booth.

The exposure hand switch should be located so that the operator must remain behind the screen during
operation. This is generally achieved if the exposure switch is located at a distance of more than 1 m from
the edge of the screen (NCRP, 2004). The screen should be fixed in position and should be of an adequate
size to allow the required number of people work behind it. Mobile screens should not be used in fixed
installations (Health Canada, 1999, WHO 1975) with the possible exception of DXA and dental facilities.
General X‑ray room screens are commonly 2-2.5 m in length with an additional wing of length 0.6-1.0 m for
room sizes of approximately 33 m2 (see Chapter 3). The dimensions and location must be approved by the
RPA, prior to installation. Screens are generally longer in fluoroscopy, interventional and CT rooms than in
general X‑ray rooms. This allows for the increased ancillary equipment and accommodates the larger number
of people who may be in attendance (NHS, 2001).

82 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


For general rooms, the lead equivalence of the screen is typically 2 mm although 3-4 mm or more may be
required for angiography suites and multi-slice CT installations. The minimum height should be 2 m (BIR,
2000). The upper half is generally transparent and made of lead glass or lead acrylic to permit the operator
to have a panoramic view of the room, good visibility of the patient, the X‑ray tube, warning lights on
equipment (where fitted) and the doors. The design must ensure integrity at the joints between the panel
sections, and the panels and lead glass (see Appendix E, Fig. E.7). Joints should be adequately shielded and
the lead glass sheets/panels should be overlapped by 30-40 mm (BIR, 2000) or protected by a shielded joint
(Photo 6.5). The screen should be marked with the lead equivalent thickness. Exceptionally, in some rooms a
mirror may be necessary to enable the operator to view entrance doors, which may be out of direct sight. In
addition to protecting the operator, the console may sometimes be required to protect unused films in
cassettes or CR plates. If this is the case, it must be taken into consideration when specifying the lead
equivalence.

Photo 6.5 Lead plywood on lead lined batons

Lead Lead

(Photographs courtesy of Wardray Premise Ltd)

The control panel/operator’s console effectively becomes a separate room in CT and interventional suites (see
Sections 3.4.2 and 3.5). The operator(s) then view the room through a panoramic window composed of lead
glass or acrylic as described above. The window frames must be shielded and there must be sufficient overlap
of the shielding between the window and window frames and between the window frames and the wall as
described above (see Appendix E, Fig. E.7). There will normally be a door leading from the operator’s room
to the controlled area which must be protected as described in Section 6.3.3.

In designing operator areas or rooms a number of operational aspects have a strong influence on the level
of shielding required. If access to these areas is restricted to occupationally exposed workers the design
constraint of 1 mSv per year can be used. This is likely to be the case in a general radiography room. If, on
the other hand, the area is to be used as a general consultation, teaching, cardiac monitoring and reporting
area, non-designated staff will regularly be in attendance. This will often be the case with CT and interventional
suites. In such cases the design constraint for a member of the public, 0.3 mSv per year must be used (see

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 83


Chapter 2). It is becoming common to share an operators’ area between CT and MRI facilities. In these
circumstances, the operators of the MRI facility cannot be assumed to be exposed workers and hence the
lower constraint must be used. In the past these problems have sometimes been overlooked. A further
problem arises when the same console/control area is shared by two CT or procedure suites. The available
dose constraint must then be divided between the two rooms. This is discussed in Section 2.4.

6.4 Shielding in nuclear medicine


6.4.1 General nuclear medicine
By designing the department so that areas of high activity are grouped together, optimal use of shielding can
be achieved. The provision of generously sized patient areas (in particular the scanning, injection and waiting
areas) can help to reduce exposure rates at boundaries. Likewise, the use of local shielding in the immediate
vicinity of sources is effective in controlling exposure rates and can help reduce overall shielding requirements.
Walls surrounding high activity areas should be constructed from dense concrete with a minimum thickness
of 225 mm. Depending on workload and occupancy of the surrounding areas, additional lead shielding may
be specified by the RPA for walls, ceiling or floor.

Wall and door shielding will differ from that used in conventional X‑ray rooms in that the source of radiation
is the patient and other radioactive sources. The use of mobile shields can be helpful as a method of providing
local additional shielding for particular situations. However, it should be noted that these shields are often
between 0.5 and 1 mm lead equivalent. These will offer limited protection at the energies normally used in
nuclear medicine.

6.4.2 PET
The shielding of PET and PET/CT facilities presents special challenges because of the high energy emissions
involved. Barrier shielding required in ceilings, floors and walls must be specified by the RPA. The patient is
the main source of radiation, and once injected consideration has to be given to their journey through the
facility. Thus the areas in which the patient spends time post-administration, particularly the “uptake”
waiting area and the scanning room, must be shielded. The design of the facility should minimise contact
between staff and patient as far as possible without unduly compromising patient care. Floor markings
indicating patient routes obviating the need for staff escorts can be useful in this regard. The dominant
shielding requirements will be dictated by the PET radionuclides in the case of PET/CT, but the radiation
protection issues related to CT must also be considered.

The use of local shielding should be maximised in areas where radionuclides are stored, dispensed and
injected (e.g. purpose-built dispensing stations, shielded dose calibrators, shielded waste containers, shielded
injection systems). This will reduce room shielding requirements.

The use of concrete nibs can be very effective in reducing shielding requirements particularly for barriers such
as doors. The conflicting requirements of providing high level shielding and smooth mechanical operation in
a heavy door are considerable, so the use of shadow shielding can be effective. The use of automated doors
can reduce the physical demands on staff.

84 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


6.5 Services, joints, openings and perforations
During construction, many perforations will be required in the boundary walls, floors and ceiling of the room
being shielded. These have obvious consequences for the integrity of shielding and measures must be taken
to make good any breaches arising from perforation or other flaws in the shielding. Examples of perforations
include those arising from:

n Nails and screws.

n Air conditioning ducts and ventilation grilles.

n Conduits, pipes and ducting.

n Electrical socket outlets.

n Light switches.

n Service outlets.

n Emergency cut-off and aid buttons.

n Plumbing and the installation of sinks, etc.

n Installation of storage cabinets and shelving, etc.

n Installation of light boxes, apron hangers and other wall mounted devices or fixtures.

n Medical gasses, vacuum and associated services.

n Particular services may be required in operating theatres.

Where possible, these perforations should not be in the primary barrier. The perforations and all other breaches
such as joints and outlets should be backed with additional lead shielding whose lead equivalence is the same
as that of the boundary. The diagrams in Appendix E clearly illustrate effective approaches to this issue.

6.6 Verification
It is sometimes necessary to assess shielding to confirm its integrity, to check that it is as specified, or that it is
properly placed and is free from gaps or voids (BIR 2000, NCRP, 2004). The assessment may be performed
using a radiation detector and a suitable gamma or X‑ray source.

Generally gamma sources offer more flexibility. 241


Am is possibly the most suitably matched to diagnostic
radiology as its main gamma ray energy is 60 keV. Alternatively, 99mTc might be used, however results may be
difficult to interpret due to its higher energy. An 125
I source has an energy well suited to verification of
shielding in mammography facilities. Shielding assessment protocols are available in both BIR (2000) and
NCRP (2004).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 85


Gaps in shielding are more likely to occur where different forms of shielding meet. Typical problems
encountered are:

n There may not be sufficient overlap between walls and shielded doorframes/window frames. Similarly there
may not be sufficient overlap between shielded doors and doorframes or windows and window frames.

n The integrity of the joints between lead sheets may not be sufficient.

n Where sockets, switches, plumbing, or ducting, etc. breach the shielding, these areas may not be
adequately protected.

n Joints between ceilings and walls may not be adequately shielded.

n Panels, where the lead lining does not extend the full length of the panel, may be installed incorrectly
(Section 6.3.1).

These problems can be detected by checking boundary transmission at the appropriate places.

86 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


References

Anderson J., Mathews D., 2002. Site Planning and Radiation Safety in the PET Facility, Paper presented at
44th AAPM Meeting held in Montreal, 2002.

AAPM, 2006. American Association of Physicists in Medicine, AAPM Task Group 108: PET and PET/CT
Shielding Requirements. Med. Phys. 33, 1, 2006.

BIR, 2000. Radiation Shielding for Diagnostic X‑rays, Report of a joint BIR/IPEM working party. Edited by D.G.
Sutton and J.R. Williams. London: British Institute of Radiology.

BSI, 2006. BS EN 12588:2006. Lead and Lead Alloys. Rolled Lead Sheet for Building Purposes. BSI British
Standards.

Delacroix, D., Guerre, J.P., Leblanc, P., Hickman, C., 2002 Radionuclide and Radiation Protection Data
Handbook, 2002, Radiation Protection Dosimetry, 98 (1), 2002.

DH, 2007. Department of Health, UK, Medicines Management : Health Building Note 14-01: Pharmacy and
Radiopharmacy facilities. London: The Stationery Office 2007.

EANM, 2007. Guidelines on Current Good Radiopharmacy Practice (cGRPP) in the Preparation of
Radiopharmaceuticals. European Association of Nuclear Medicine, Version 2, March 2007.

EC, 1996a. Council Directive 96/29/Euratom of 13 May laying down basic safety standards for the protection
of the health of workers and the general public against the dangers arising from ionising radiation. Official
Journal of the European Communities, L159, 29/6/1996, p. 1-114.

EC, 1996b. European Guidelines on Quality Criteria for Diagnostic Radiographic Images, EUR 16260.
Luxembourg: European Commission.

EC, 1997. Council Directive 97/43/Euratom on the health protection of individuals against the dangers of
ionising radiation in relation to medical exposures. Official Journal of the European Communities, L180,
09/07/1997, p. 22-27.

EC, 2003. Eudralex Guidelines, Volume 4 – Medicinal Products for Human & Veterinary Use: Good
Manufacturing Practice, Chapter 3 & Annex 3, Luxembourg: European Commission.

Health Canada, 1999. X‑ray Equipment in Medical Diagnosis, Safety Code 20A, revised 1999. Minister of
Public Works and Government Services, Canada.

ICRP, 1977. Recommendations of the International Commission on Radiological Protection, ICRP Publication
26. Annals of the ICRP, 1 (3).

ICRP, 1991. Recommendations of the International Commission on Radiological Protection, ICRP Publication
60. Annals of the ICRP, 21, (1-3).

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 87


ICRP. 2007. Recommendations of the International Commission on Radiological Protection, ICRP Publication
103, Annals of the ICRP, 37, (2-4).

IEC, 2008. Medical Electrical Equipment Part 1-3: General Requirements for Basic Safety and Essential
Performance. Collateral Standard: Radiation Protection in Diagnostic X‑ray Equipment, International
Electrotechnical Commission, IEC: 60601-1-3:2008.

IPSM, 1991. Radiation Protection in Nuclear Medicine and Pathology. Editors: KE Goldstone, PC Jackson, MJ
Myers, AE Simpson. Report No 63, York: Institute of Physical Sciences in Medicine.

Johnson, D.A., Brennan, P.C., 2000. Reference Dose Levels for Patients Undergoing Common Diagnostic
Examinations in Irish Hospitals. Br. J. Radiol. 73, p. 396 – 402.

MDGN, 2002. Medical and Dental Guidance Notes. A Good Practice Guide on All Aspects of Ionising
Radiation Protection in the Clinical Environment, Prepared by the IPEM with the support of the NRPB, HSE,
the Health Departments and the Environment Agencies, UK, 2002.

Medical Council, 2005. Dose Constraints for Helpers – Position Paper, 2004. Circular to CEOs, December
2005.

NCRP, 2004. Structural Shielding Design for Medical X‑ray Imaging Facilities, Report no. 147. Bethesda:
National Council on Radiation Protection.

NHS, 2001. Facilities for Diagnostic Imaging and Interventional Radiology, National Health Service, HBN 6,
NHS Estates, London Stationery Office.

NHS, 2002. Diagnostic Imaging: PACS and Specialist Imaging, HBN 6 Volume 2, NHS Estates, London
Stationery Office.

NRPB, 1993. National Radiological Protection Board Statement on the 1990 Recommendations of ICRP.
Documents of the NRPB, 4 (1). Chilton: NRPB.

NRPB, 2002. Doses to Patients from Medical X‑ray Examinations in the UK – 2000 Review,
Hart D et al., NRPB Report W-14. Chilton: NRPB.

NRPB, 2005. Doses from Computed Tomography (CT) Examinations in the UK – 2003 Review,
P.C. Shrimpton et al., NRPB Report W67. Chilton: NRPB.

RPII, 1996. Code of Practice for Radiological Protection in Dentistry, prepared by the Radiological Protection
Institute of Ireland, in conjunction with the Department of Health and the Dental Council. Dublin: Radiological
Protection Institute of Ireland.

RPII, 2001. Guidance Note on Dose Constraints, Dublin: Radiological Protection Institute of Ireland.

88 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


RPII, 2004, Guidance Notes on Radiation Risk Assessment. Dublin: Radiological Protection Institute of
Ireland.

Saha Gopal, B., 2004, Fundamentals of Nuclear Pharmacy, 5th Ed, Ed. Springer.

Shleien B, Slaback, L.A., Birky, B.K., 1998. The Handbook of Health Physics and Radiological Health, 3rd ed.,
Baltimore: Williams and Wilkins.

Simpkin, D.J., 1995. Transmission Data for Shielding Diagnostic X‑ray Facilities, Health Physics, 68 (5) p. 704-
709.

Stationery Office, 1991. Radiological Protection Act, 1991. No. 9 of 1991. Dublin: Stationery Office.

Stationery Office, 2000. Radiological Protection Act, 1991 (Ionising Radiation) Order, 2000,
S.I. No. 125 of 2000. Dublin: Stationery Office.

Stationery Office, 2002. European Communities (Medical Ionising Radiation Protection) Regulations, 2002,
S.I. No. 478 of 2002. Dublin: Stationery Office.

Stationery Office, 2007. European Communities (Medical Ionising Radiation Protection) (Amendment)
Regulations 2007, S.I. No. 303 of 2007). Dublin: Stationery Office.

WHO, 1974. Manual on Radiation Protection in Hospitals and General Practice. Volume 1, Basic Protection
Requirements. Geneva: World Health Organisation.

WHO, 1975. Manual on Radiation Protection in Hospitals and General Practice, Volume 3, X‑ray Diagnosis.
Geneva: World Health Organisation.

Williams, J., Sutton, D., 2005. Factors for Calculating the Attenuation of Barium Plaster. Br. J. Radiol,
78 (935), p. 1061.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 89


Appendices

Appendix A: Dose limits


The Dose Limits prescribed in Schedule 2 of S.I. No. 125 of 2000 are reproduced in Table A.1 below. Effective
and Equivalent Limits are provided for occupationally exposed workers, pregnant workers, apprentices and
members of the public who are not occupationally exposed. The latter group include, for example, hospital
staff that are not designated as radiation workers. This would include administrative staff and non-radiological
nursing and medical staff.

Table A.1: Dose Limits for categories of workers and all others, reproduced from S.I. No. 125 of 2000

Effective dose limit Equivalent dose limits (in a


period of 12 months)

Exposed Workers1 20 mSv in a period of 12 Lens of the eye: 150 mSv


(including Apprentices and months. Skin (averaged over an area of
Students aged 18 years or over) 1 cm2): 500 mSv
Hands, forearm, feet and
ankles: 500 mSv

Dose to the foetus of a 1 mSv after declaration of


pregnant worker pregnancy.

Apprentices and Students 6 mSv in a period of 12 months. Lens of the eye: 50 mSv
aged 16 years or more but Skin (averaged over an area of
less than 18 years 1 cm2): 150 mSv
Hands, forearm, feet and
ankles: 150 mSv

Members of the Public 1 mSv in a period of 12 months. Lens of the eye: 15 mSv
(Including apprentices and Skin (averaged over an area of
students under the age of 16) 1 cm2): 50 mSv

1
An exposed worker is any person, either self employed or working for an employer, who is liable to receive an exposure resulting in a
dose which exceeds one or more of the dose limits for a member of the public.

90 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Appendix B: Risk assessment for design and construction of a new
medical facility where ionising radiation is used
Table B.1: Risk assessment for design and construction of ionising radiation facilities

Hazard Persons at risk Method of reducing risk from hazard Risk

Target radiation level breached as Patients being Set up interdisciplinary project team to Low
a result of a inadequate boundary treated in adjacent manage radiation protection for new
shielding. In addition to radiation areas. installations.
hazard, this may give rise to:
Members of the Use only qualified, professionally
n Potential litigation costs public frequenting accredited staff to input to all stages of
resulting from radiation risk. adjacent areas. shielding assessment process.
n Loss of professional & Hospital and Keep accurate workload records for each
institutional reputations non-hospital installation/clinical area.
because of radiation risk staff working in
For new or changing technologies ask
posed to patients/staff/public. adjacent areas.
RPA to make quantitative estimation of
n Loss of staff morale due to dose to adjacent areas and required
worry over radiation risks. boundary attenuation.
n Cost of building works Get signed advice from RPA regarding
to retrofit shielding. shielding requirements for each
boundary of installation.
n Interruption to clinical services
during building works. Simplify shielding advice wherever
possible – e.g. 2 mm lead for all
boundaries.
Review standard practise re shielding of
similar installations.
Use only accredited architects, builders,
fitters, etc. to design facility, supply
materials and construct building.
Quality management of building
projects.
Spot checks of boundary shielding when
building works are complete.
Keep accurate records of shielding advice
and boundary construction details.

Boundary shielding higher than No person receives As above plus: High


required (e.g. ICU where 2 mm radiation risk.
lead installed when no shielding
actually required; CT room – 4 Ensure project team has sufficient
mm lead installed when 3 mm knowledge of architectural design and
sufficient) which may result in: building costs for various levels of
shielding.
n Increase in cost of shielding
works.
n Delay in opening rooms.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 91


Appendix C: Radiation transmission data for various energies and materials
Attenuation and thickness values for all materials apart from barium plaster and brick were computed from
data published by Simpkin (1995); for barium plaster and brick, thickness values were computed from data
published by Williams and Sutton (2005) and by BIR (2000) respectively.

Table C.1: Transmission through lead at 75 kVp, and lead equivalent thickness for various materials
Lead Trans- Steel Barium Concrete Brick Plate Gypsum Wood
thickness mission at (mm) plaster (2350kg/m ) (Oxford clay,
3
Glass (mm) (mm)
(mm) 75 kVp (mm) (mm) 1650kg/m3) (mm)
(mm)
1.0 6.9E-4 7 11 88 123 102 263 879
1.32 1.5E-4 10 14 117 157 131 446 1340
(Code 3)
1.8 1.6E-5 13 19 162 207 173 446 1340
(Code 4)
2.0 6.1E-6 15 21 181 228 191 491 1454
2.24 2.0E-6 17 23 205 253 212 545 1591
(Code 5)
2.65 2.9E-7 20 27 244 295 248 638 1824
(Code 6)
3.0 5.8E-8 23 31 278 332 279 717 2024
3.15 2.9E-8 24 32.4 293 344 292 751 2109
(Code 7)
3.55 4.4E-9 27 36.6 332 385 328 841 2336
(Code 8)
4.0 5.4E-10 31 41 375 435 367 943 2592

Table C.1 applies to both primary and secondary radiation.

Table C.2: Transmission through 2 mm lead at different kVp values, and 2 mm lead equivalent
thickness for various materials.
kVp Trans- Steel Barium Concrete Brick Plate Gypsum Wood
mission (mm) plaster (2350kg/m3) (Oxford clay, Glass (mm) (mm)
through 2 (mm) (mm) 1650kg/m3) (mm)
mm lead (mm)
30 1.4E-36 11 - 244 - 254 639 3642
50 2.0E-10 11 42 197 222 208 517 2065
75 6.1E-6 15 21 181 228 191 491 1454
100 5.2E-4 14 21 129 184 149 414 1034
primary
125 8.1E-4 21 31 158 217 168 491 1107
primary
150 9.4E-4 30 35 188 - 189 567 1196
primary

92 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


It should be noted that below 100 kVp, transmission is similar for both primary and secondary radiation.
Table C.3 provides values for secondary radiation transmission through concrete for 100‑150 kVp.

Table C.3: Transmission and lead equivalent thickness of concrete (2350 kg/m3) for secondary
radiation 100–150 kVp.

100 kVp 125 kVp 150 kVp

Lead (mm) Transmission Concrete (mm) Transmission Concrete (mm) Transmission Concrete (mm)

2.0 7.8E-4 128 1.5E-3 142 2.8E-3 157

2.24 4.3E-4 143 8.7E-4 157 1.8E-3 171


(Code 5)

2.65 1.5E-4 168 3.4E-4 192 8.1E-4 186


(Code 6)

3.0 6.3E-5 190 1.6E-4 204 4.2E-4 216

3.15 4.3E-5 199 1.1E-4 213 3.2E-4 224


(Code 7)

3.55 1.6E-5 225 4.6E-5 238 1.5E-4 247


(Code 8)

4.0 5.1E-6 253 1.7E-5 265 6.7E-5 272

Table C.4: Lead equivalent thickness for standard size concrete blocks (density 2350 kg/m3)

Lead thickness (mm)

Concrete thickness (mm) Primary and Secondary Primary Secondary

kVp: 30 50 75 100 125 150 100 125 150

100 0.8 1.0 1.1 1.5 1.2 0.9 1.5 1.3 1.1

215 1.8 2.2 2.3 3.4 2.9 2.4 3.4 3.2 3

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 93


Figure C.1: Transmission of primary radiation through lead

1.00E+00

30 kVp

1.00E-01 50 kVp

70 kVp

75 kVp
1.00E-02
90 kVp

100 kVp
1.00E-03
Transmission

125 kVp

150 kVp
1.00E-04

1.00E-05

1.00E-06

0 1 2 3 4 5 6

Thickness (mm)

(Compiled from Simpkin, 1995)

Figure C.2: Transmission of primary and secondary radiation through lead

1.00E+00
100 kVp (P)

100 kVp (S)


1.00E-01
125 kVp (P)

125 kVp (S)


1.00E-02
150 kVp (P)
Transmission

150 kVp (S)


1.00E-03
(P) - Primary
(S) - Secondary

1.00E-04

1.00E-05

1.00E-06

0 1 2 3 4 5 5.9
Thickness (mm)

(Compiled from Simpkin, 1995)

94 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Figure C.3: Transmission of primary radiation through concrete
1.00E+00

30 kVp

50 kVp
1.00E-01
70 kVp

75 kVp
1.00E-02
90 kVp

100 kVp
Transmission

1.00E-03
125 kVp

150 kVp

1.00E-04

1.00E-05

1.00E-06

0 50 100 150 200 250 300 350 400


Thickness (mm)

(Compiled from Simpkin, 1995)

Figure C.4: Transmission of primary and secondary radiation through concrete


1.00E+00
100 kVp (P)

100 kVp (S)


1.00E-01
125 kVp (P)

125 kVp (S)


1.00E-02
150 kVp (P)

150 kVp (S)


1.00E-03
Transmission

(P) - Primary
(S) - Secondary

1.00E-04

1.00E-05

1.00E-06

0 50 100 150 200 250 300 350 400

Thickness (mm)

(Compiled from Simpkin, 1995)

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 95


Figure C.5: 2 mm lead equivalent thickness at varying kVp
700
gypsum

600 brick

plate glass

500 concrete

ba plaster
Thickness (mm)

400 steel

300

200

100

0
30 50 60 70 80 90 100 110 120 130 140 150

kVp

Compiled from various sources

Figure C.6: Lead equivalence of various materials at 75 kVp


500

450

400

350

300
Thickness (mm)

250
gypsum
200 brick

150 plate glass


concrete
100
steel
50

0
(1.8mm)
(1.32mm)

(2.24mm)

(2.65mm)

(3.15mm)

(3.55mm)
CODE 3

CODE 4

CODE 5

CODE 6

CODE 7

CODE 8

1 2 3 4

Lead Equivalent Thickness (mm)

Compiled from various sources

96 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Appendix D: Nuclear medicine radionuclide data
Table D.1: Half value thickness (mm lead) for radionuclides used in nuclear medicine

Radionuclide Half Value Layer Tenth Value thickness


(mm lead)a (mm lead)b
123
I 1.0c 1.2
133
Xe 0.2 ≤0.7
201
Tl 0.23 ≤0.9
99m
Tc 0.3 0.9

Ga
67
0.66 5.3
131
I 3.0 11
111
In 1.3 2.5
82
Rb 6.0 -
15
O 5.5 17c
11
C 5.5 17c
18
F 5.5 17c
13
N 5.5 17c
125
I - ≈0.06
a In general the use of 10 half-value layers will reduce the intensity to 1,000th of the unshielded value.
b γ attenuation data are derived from tables published by Amersham International plc and are for guidance only; they do not take
account of low energy (<20 keV) X/γ emissions. Values quoted are for the first Tenth Value Layer (TVL) in lead; due to filtration of
lower energy emissions, subsequent TVLs may be greater than the values quoted. The TVL refers to attenuation of dose rate not
absolute γ flux.
c Taken from Delacroix D, et al. (2002). HVL for I-123 is given as 0.4 mm of lead in Saha (2004).

Half Value Layer Thickness and footnote (a) are taken from Table 6.12 of Shleien et al (1998). Tenth Value
Thickness and Footnote (b) are taken from IPSM (1991).

Table D.2: Calculated instantaneous dose rates from radionuclides used for diagnosis (IPSM, 1991)

Radionuclide Half Life Typical Dose rates (μSv h-1/MBq) at 1 m from:

Point Source Patient


67
Ga 78.1 h 0.028 0.011
99m
Tc 6.02 h 0.0195 0.0075
111
In 2.8 d 0.086 0.03
123
I 13 h 0.041 0.015
131
I 8.06 d 0.0575 0.023
133
Xe 5.3 d 0.135 0.006

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 97


Table D.3: Physical properties & effective dose equivalent dose rate constants of PET Radionuclides
(AAPM, 2006)

Nuclide Half life Decay Positron Photon Photons/ Dose rate


mode max energy emission decay constant
(MeV) (keV) (μSvm2/
MBqh)
11
C 20.4 min ß+ 0.96 511 2.00 0.148
13
N 10.0 min ß+ 1.19 511 2.00 0.148
15
O 2.0 min ß +
1.72 511 2.00 0.148
18
F 109.8 min ß , EC
+
0.63 511 1.93 0.143
64
Cu 12.7 h ß ,ß , EC
- +
0.65 511, 1346 0.38, 0.005 0.029
68
Ga 68.3 min ß , EC
+
1.9 511 1.84 0.134
82
Rb 76 s ß , EC
+
3.35 511, 776 1.90, 0.13 0.159
124
I 4.2 d ß+, EC 1.54, 2.17 511, 603, 0.5, 0.62, 0.185
1693 0.3

Table D.4: Broadbeam transmission factors at 511 keV in lead, concrete (Based on AAPM, 2006)

Transmission factors
Thickness Lead Concrete
(mm lead/cm concrete)
0 1.0000 1.0000
1 0.8912 0.9583
2 0.7873 0.9088
3 0.6905 0.8519
4 0.6021 0.7889
5 0.5227 0.7218
6 0.4522 0.6528
7 0.3903 0.5842
8 0.3362 0.5180
9 0.2892 0.4558
10 0.2485 0.3987
12 0.1831 0.3008
14 0.1347 0.2243
16 0.0990 0.1662
18 0.0728 0.1227
20 0.0535 0.0904
25 0.0247 0.0419
30 0.0114 0.0194
40 0.0024 0.0042
50 0.0005 0.0009

98 The Design of Diagnostic Medical Facilities where Ionising Radiation is used


Figure D.1: Broadbeam transmission at 511 keV as a function of lead thickness
Lead
1.0000

0.1000
Transmission

0.0100

0.0010

0.0001
0 10 20 30 40 50
Thickness (mm)

(Reproduced from AAPM, 2006)

Figure D.2: Broadbeam transmission at 511 keV as a function of concrete thickness

Concrete
1.0000

0.1000
Transmission

0.0100

0.0010

0.0001
0 10 20 30 40 50
Thickness (cm)

(Reproduced from AAPM, 2006)

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 99


Appendix E: Schematic diagrams of radiation transmission paths
(Figures E1 – E7 reproduced from WHO, Volume 1, 1974)

Figure E.1: Radiation paths through shielding assemblies

The sum of the radiations through all paths from Space S2 to Space S1 must not exceed the relevant dose
constraints

S1
S1 S2
S1

S2

S2 WHO 40213

a b c
Figure E.2: Overlapping in shielding between lead and concrete

The width of overlapping (b) must be at least as great as the thickness of concrete (t).

b
b

a b WHO 40214

Figure E.3: Protection on recesses in shielding

The width of overlapping (b) must be at least as great as the thickness of concrete (t).

WHO 40215
a b

100 The Design of Diagnostic Medical Facilities where Ionising Radiation is used
Figure E.4: Shielding of perforations

WHO 40216

a b c

Figure E.5: Shielding of doors and doorframes

The protective lead covering the door must overlap that of the doorframe by at least 1.5 cm. The protective
lead covering the doorframe must overlap the concrete in the wall by at least the same amount as the
thickness of concrete (t).

1.5 cm
≥t

Lead-lined door
Wall of
t concrete
or brick WHO 40217
Frame

Lead-lined door
Lead-lined wall

Figure E.6: Shielding beneath doors not exposed to primary radiation

Lead-lined door

max. 1.5 cm

Concrete floor

WHO 40218

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 101
Figure E.7: Shielding around the edge of an observation window

Lead sheets in contact with lead glass must have an overlap of at least 1.5 cm or the thickness of the lead
glass, whichever is greater.

Lead glass
Wall of
concrete WHO 40219
or brick

102 The Design of Diagnostic Medical Facilities where Ionising Radiation is used
Appendix F: Examples of radiation warning signs and light
Figure F. 1: Sample radiation warning sign (based on MDGN, 2002)

Figure F. 2: Sample radiation warning light

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 103
Figure F. 3: Sample radiation warning sign for area containing sealed sources (private communication,
Cork University Hospital, 2008)

104 The Design of Diagnostic Medical Facilities where Ionising Radiation is used
Acknowledgements

This revised Code is based on a comprehensive document supplied under tender from the Haughton Institute.
The Code was drafted by members of the Department of Medical Physics and Bioengineering, St James’s
Hospital, Dublin. The text was reviewed and edited by the RPII in liaison with the principle contributors from
St. James’s Hospital.

Contributors:
St James’s Hospital, Dublin:
Professor Jim Malone (also Trinity College, Dublin), Ms Anita Dowling,
Dr Geraldine O’Reilly, Ms Una O’Connor, Ms Aoife Gallagher and Dr Noirin Sheahan.

Radiological Protection Institute of Ireland:


Dr Stephen Fennell, Mr Dermot Howett, Dr Tom Ryan, Mr Christopher Hone,
Ms Tanya Kenny and Ms Noeleen Cunningham.

The RPII wishes to thank the Radiation Protection Advisers, the Irish Institute of Radiography and Radiation
Therapy, the Association of Physical Scientists in Medicine and the Irish Dental Association for the valuable
comments received on the first draft of this Code. The review by, and comments received from, the members
of the RPII’s Medical Radiation Advisory Committee on the final draft is also gratefully acknowledged.

An appreciation is also extended to the RPII staff who assisted in various ways to the completion of this
project – Mr David Dawson, Ms Catherine McCarron, Ms Marie Kelly, and Ms Clare Mander.

Finally, the RPII is grateful to St James’s Hospital, Mater Private Hospital and Connolly Hospital for allowing
photographs of locations within their hospitals to be used, to Wardray Premise Ltd for providing additional
photographs, and to Cork University Hospital for providing a design for a radiation warning sign.

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 105
Notes

106 The Design of Diagnostic Medical Facilities where Ionising Radiation is used
Notes

The Design of Diagnostic Medical Facilities where Ionising Radiation is used 107
Notes

108 The Design of Diagnostic Medical Facilities where Ionising Radiation is used
RPII 09/01

Radiological Protection Institute of Ireland The Design of Diagnostic Medical Facilities where Ionising Radiation is used
The Design of Diagnostic Medical Facilities
where Ionising Radiation is used

A Code of Practice issued by the


Radiological Protection Institute of Ireland

Contact Details June 2009


Radiological Protection Institute of Ireland
3 Clonskeagh Square
Dublin 14

Telephone: +353 1 269 7766


Fax: +353 1 269 7437
Web: www.rpii.ie

You might also like